Attachment 2 - Updated Bill of Quantities (BOQ)

View the file

Other files for this federal contract opportunity

Other files attached to Renovation of office space, newest first.
File Type Posted
Attachment___4_-_Updated_Drawings.pdf PDF
Amendment___A001.pdf PDF
Letter_to_prospective_offerors.pdf PDF
Solicitation___SIS400-16-Q-5205863_(Renovation_of_the_Healt_Unit_-_Lazarist).doc DOC document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

Renovation of the HEALTH UNIT
Talpiot- Jerusalem
General Services Office-Procurement
No.DescriptionUnitQtyUnit Rate NISTotal NIS
1 - Demolishing Works
1The contractor, shall when pricing the rates of this bill take into consideration all cost occur upon him and allow for the cost and expenses of all requirements stipulated in the special specifications, drawings and general specifications of the contract, according to engineer`s requirements.
1.1All existing equipment should be packed up carefully and adequately to avoid and protect all sensetive medical machines from harm and damage, using bubble nylon wrapping or sponge coverage.

Also all equipment should be labeled with numbers according to the equipment plan, on the item itself and outside the wrapping.

All packed items will be delivered to the Arnona Consular site at start of the works and will be brought back at the end of the works to be put and installed appropriately. The price for this item will include all the above material works, transportation and all other needed works.EA.0
1.2Dismantle the existing Jerusalem stone tiles. Job includes removing fill below the tiles as per engineer's requirements and keeping the tiles in a safe place to reinstall them where specified on the drawing and by engineer. And removing all debris outside the site in a legal manner and all according to engineer's instructionsm2850
1.3Dismantle the existing Terrazzo and Porcelain floor tiles where specified on drawings. The job includes the removal of fill below the tiles. All the debris must be thrown away in a legal manner according to egineer's instructions.m2120
1.4Demolition of existing Ytong block partitions where specified on drawings. The job includes removing all debris outside the site in a legal manner according to engineer's instructions.m2700
1.5Demolition of existing Gypsum partitions where specified on drawings. The job includes removing all debris outside the site in a legal manner accodring to engineer's instructions.m2600
1.6Removal of all false ceiling and mouldings in all the rooms and dumping them in an approved area outside the site.The job includes removing all debris outside the site in a legal manner accodring to engineer's instructions.m280
1.7Removal of existing doors and keeping them in a safe place to be reinstalling after finishing the works.Job10
Total of Bill # 10
17% VAT0
Total of Bill # 1 (Including VAT)0
2- Tiling works
2The contractor, shall when pricing the rates of this bill take into consideration all cost occur upon him and allow for the cost and expenses of all requirements stipulated in the special specifications, preambles, drawings and general specifications of the contractor, and whatever neccessary to accomplish the work according to engineer`s requirement and specifications.
2.1Install the existing Jerusalem stone floor tiles that were dismantled where specified on drawings. Price includes the mortar below the tiles from sand and cement, price includes also the pointing works. All works are done according to instructions given by the engineer.m2650
2.2Supply and install Jerusalem stone floor tiles same to existing .Price includes the mortar below the tiles from sand and cement, price includes also the pointing works. All works are done according to instructions given by the engineer.m2300
2.3Supply and install of non-slip ceramic tiles for the in bathrooms (300x300x8 mm). The price includes the sand and mortar layer under the tiles above the concrete screed. Insulation layer is required, two coats of Sika top seal 107 with its two components liquid and powder or equivalent. The tiling work is done according the drawings and accroding to the supervisor engineer.m250
2.4Supply and Install of Granite Porcelain wall tiles (Spanish or equivalent) in bathroom (200*200*8mm) at height 1200mm. The price includes insulation layer and Grouting with the required color is done between the tiles.m3100
2.5Supply and install 3cm thick stone internal sills of 250*1500 mm of excellent quality from Sourmaeen or an approved eq.,free from cracks. bedded in or backed with white cement
and sand mortar [1:3] .The price shall include grouting with a water resistant grout like Mapei and sand-cement fill under tiles as per engineer instructions (internal edges should be rounded ), price includes removal of existing sills.MR1.50
Total of Bill # 20
17 % VAT0
Total of Bill # 2 (Including VAT)0
3- Gypsum works
3The contractor shall, when pricing the rates of this bill, take into consideration including and allowing for the costs or expenses of all requirements stipulated in the preambles, drawings and technical specification of the tender.
3.1Supply & install100 mm thick gypsum partition consisting of 12 mm thick gypsum boards , two boards from each side with horizontal studs on floors and ceilings and vertical ones every 400mm ,the outside gypsum boards are fire resistant boards (red), while the inner gypsum boards are white, the gap between the gypsum boards to be filled with wool rock 50mm thick and 36kg/m3 density . all according to specifications and to engineer's instructions.m21250
3.2Ditto, but one side is water resistance green gypsum board ( bathroom side) and the corridor side is fire resistance gypsum boardm2150
3.3Supply & install 600x 600mm Ecophone Focus Frost square edge board ceiling tiles with all required hangers, supports and connected with T24 main runners and cross T and L and
Z edges, works include supply and install Moisture resistant gypsum board MR, for false ceilings edges with studs at every 400mm in both directions including decorations, forms, trims with all connections supports, fixing, putty sealer, wire mesh and special angles for edge of boards and all necessary accessories needed for the best completion of works. The price shall include for all opening of air condition grills, light fixture and the like, price shall include also the painting works for the gypsum board margins by applying two coats of putty followed by three coats of Tambour Supercryl 2000 (white colour).m2800
3.4Supply & install galvanized perforated metal strip 30cm wide, panels to be installed on a metal structure which includes L & Z on the parameter wall made of painted aluminum .works include supply and install Moisture resistant gypsum board MR, for false ceilings edges with studs at every 400mm in both directions including decorations, forms, trims with all connections supports, fixing, putty sealer, wire mesh and special angles for edge of boards and all necessary accessories needed for the best completion of works. The price shall include for all opening of air condition grills, light fixture and the like, price shall include also the painting works for the gypsum board margins by applying two coats of putty followed by three coats of Tambour Supercryl 2000 (white colour).M2170
Total of Bill # 30
17% VAT0
Total of Bill # 3 (Including VAT)0
4- Wooden works
4.1Supply and install wooden doors 45mm thick from plywood 5mm thick and covered with veneer oak wood to be specified by the engineer, and solid frame from oak wood, and all as per attached drawings, price shall include fixing ironmongery, three stainless steel hinges per leaf of a door, price includes also supply and install locks, handles, cylinders, kick plate ,louvers and specail bar for handicapped and all have to be approved by the engineer, and all according to engineer's instructions.EA.10
4.2Reinstall the dismantled doors, price to include whatever necessary to accomplish the work.EA.100
Total of Bill # 40
17% VAT0
Total of Bill # 4 (Including VAT)0
5- Aluminum works
Supply and Install of sliding aluminum window from kalil profile 7000, the glass should be double glaze ( 4mm + 6mm voide+ 4mm ) according to specifications required.Price to include all the cevil works needed to install the window.
window size: 1500*1000mmEA.10
Total of Bill # 50
17% VAT0
Total of Bill # 5 (Including VAT)0
6- Painting works
6.1Prepare surface, clean and apply two coats of putty followed by
three coats of Tambour Supercryl 2000 on gypsum board walls. The price shall include all materials and workmanshipM23000
Total of Bill # 60
17% VAT0
Total of Bill # 6 (Including VAT)0
7- Additional Equipment
7Prior to supplying, and approval by supervising engineer, for the below furniture, the contractor shall produce a catalogue of all ready made items with all technical specifications and shall also produce a shop drawing for making any connections needed.

7.1 supply and install: A digital business hours sign, black and silver with 35.5 x 33 cm. As per drawing #A23. Model No. 4247 from U.S. Stamp & Sign HeadLine Century Series. Or equivelant EA. 1 0

7.2 Supply and install: A Cream Cordless 12 mm blackout Vinyl Roller Shade. As per drawing #A11. Model No. 37-4002-02-62.5-78 from Bali Cut-to-Size Company. Or equivelant. EA. 9 0

Total of Bill # 70
17% VAT0
Total of Bill # 7 (Including VAT)0
8 - Electrical Works
Note: Contractor shall provide samples and shop drawings for all items for approval prior to the

execution of these item.

8General Provisions of Electrical Works
8.APreambles
Rates of electrical installations shall includes for:-
8.A.1Demolition of all existing electrical systems (Lighting, power, cables, outlets, trays, switches, electrical panel, fire alarm, general alarm & all related cabling trunking & conduits) , keeping in good condition delivery to owner with full in coordination with the engineer.
8.A.2Electrical works including all required materials, accessories, labor, all as required according to drawings, specifications and bill of quantities.
8.A.3Cutting, and pining including all making good
8.A.4Forming, or cutting hales, chases, channels etc.in reinforced concrete structure, block works or existing walls.
8.A.5Plugging and screwing
8.A.6Preparation of all required workshop drawings and as built drawings.
8.A.7Testing electrical installations including providing written reports & certificates by authorized inspector /engineer approved by consultant . The report should indicate detailed measurements for electrical installations, electrical panels, cables, outlets, isolators, lighting,... etc., and if it is matching the Israeli electrical code, fire code & ministry of health requirements
8.A.8Preparing working drawings by authorized Fire Alarm Engineer, testing the works during & after completion including providing and personal necessary for testing, providing written reports & certificates by authorized fire alarm & "Taken" inspector approved by consultant .
8.A.9Protection of all electrical works
8.A.10All outlets, switches, cables, wires should be labeled ( numbers & tags)
8.A.11All conduits used should be fire retardant and color coded.
8.A.12providing Operating and Maintenance Manual

Mechanical and Electrical Services including as made drawings hard & electronic copy

8.1Raceways
Cable Trays, and Ladders
Supply, install, test and commission cable trays, cable ladders, cable truncking and sleeves as per drawings and specifications complete with supports, fixing devices, separators, clamps, end caps, draw wires, elbows, joints, branches, reducers, offsets,...etc.with all accessories needed to complete the work as shown on drawing, as per the preamble, the specifications and supervision engineer's requirements.
8.1.120 cm wiremesh cable trayMR500
8.2Electrical Distribution Panels
Supply, install, connect, test and commission complete approved factory made sub-main distribution boards including digital instruments, signal lamps, (MCCB) circuit breakers bus bars, space for cables, cable clamps/terminals, cable shoes, current transformers, protection equipment, as per drawings, specifications and local electric authority requirements.
8.2.1DB-Health UnitEA.10
8.3Supporting Devices
Power sockets
Supply, install, test and commission the following power sockets/points as shown on drawing, as per the preamble, rate includes conduits, N2XY cables (individual wires not allowed)up to related panels,... the specifications and supervision engineer's requirements.
Biticino, Nisko or Unica/Schneider
8.3.116A power socket outlet normal or water proof ( N2XY 3x2.5 mm2)EA.250
8.3.216A power socket outlet surface mount above false ceiling ( N2XY 3x2.5 mm2)EA.90
8.3.3Double pole switch with indication lampEA.30
8.3.4Nisko 16A 3P+N+E Interlocked Socket with back box IP44 Red 3 Phase + 1 phase socket covered ( N2XY 5x2.5 mm2)EA.10
8.3.5Nisko Office set including 4 sockets 16 A grounded sockets, 4 sockets non grounded,3 data RJ45 cat 6 socket & 1 USP socket including all related cables " Data points measured separately as per item 16-10"EA.50
8.4Lighting
Lighting points
Supply, install, connect, test and commission a complete lighting point including conductors, fire retardant PVC conduits, N2XY cables (individual wires not allowed) ,(3*1.5mm2)/ (5x2.5mm2), switches & push buttons, boxes, ceiling rose, fire retardant silicon flexible connection cables and all other accessories terminated to electrical panel. as per drawings specifications and related standards.
8.4.1Lighting point ( N2XY 3x2.5 mm2 )EA.500
8.5Lighting Fixtures
Supply, install, connect, test and commission complete lighting fixture, including all supports, suspensions, clamps, power supplies, drivers, internal conductors and/or cables, and all other accessories necessary as per drawings, specifications and related standards.
8.5.160x60 cm LED panel as per Nisko LED panel 4200KEA.270
8.5.23W LED Non-Maintained Emergency Down light in Cool White, LED Down light, min. 3 hours, electrozen or Eq.EA.50
8.5.33W LED Non-Maintained Emergency EXIT with self test function, min. 3 hours, electrozen or Eq.EA.20
8.5.4Continuous LED lighting tunnel 10watt/meter opal cover body aluminum body with trim recessed inside ceiling, cool white 4200K complete with power supply & Led driver.Mr.90
8.5.57 watt LED downlight aluminum body complete with driver, celling recessedEA.120
8.5.616 watt LED downlight aluminum body complete with driver, celling recessedEA.10
8.6Grounding
Supply, install, connect, test and commission a complete earthing system for the project including all conductors, termination to PEC ,19 mm dia steel copper rods, cables, clamps, conduits, hand holes with heavy duty cast iron cover, fixing, etc., as per specification, drawings, local electric authority regulations, engineers approval and related codes.
8.6.110 mm2 flex. earthing of all metal parts that includes cable trays, water pipes, cable ladder,ac units, distribution boards bodiesJOB10
8.6.210mm2 earthing of false ceilingEA.200
8.7Fire Alarm System
Fire Alarm Main Controller
Supply, install, connect, test and commission analog addressable fire-alarm system as existing , including all accessories as per drawings, specifications and related codes rate should include fire retardant conduits, 4*0.8mm fire resistance cables and boxes (850c) and all accessories as per drawings, specifications engineers approval and related codes , connecting to existing system testing and operation in addition of providing testing certificates as specified :
8.7.1Fire alarm system point " conduits, boxes & wires for smoke, heat detectors, break glass, siren, horn/strobe, control module.)EA.200
8.7.2Analog Addressable photo smoke detectorEA.120
8.7.3Analog Addressable manual call point (break glass) TPB-800ASR - analog addressable call pointEA.20
8.7.4Addressable Alarm Notification Sounder indoorEA.20
8.8Public Address/Voice Evacuation System
Speakers
Supply , Install , connect and testing public address/ voice alarm system speakers including fire retardant conduits, 2x1.5mm2 audio cables and all related cabling to data room , 850C connection boxes as described in specification & shown on drawing.
8.8.1Ceiling recessed speaker as Toa PC-580RVU with fire dome.EA.40
8.9Data Points (Data, Telephone, intercom,)
Cat6 Cables, RJ45 sockets, data cabinets, patch panels for Data system will be supplied by owner, the contractor shall supply all related conduits, back boxes, covers & he shall also responsible for installation, labeling & termination for all points
8.9.1Install, connect, test, label and commission complete data point including boxes, conduits, covers as drawings, specification and related codes.EA.350
8.9.2Install one network cabinet (as per description in HU data system job description #2)job10
8.9.3Mount three color-coded 48-port 2U RJ45 patch panel(s) and cable management systems in the network cabinet.job10
8.9.4Install 35 each of orange, green, and blue, 30 cm patch cords to connect data

ports to a network switch that the Consulate will provide.

job10
8.9.5Install 35 each of orange and green, and blue, three-meter patch cords to connect data ports to workstation equipment.job10
8.9.6Install 6-pair / 12 strand 50 micron multimode plenum-rated fiber optic cable (as per description in HU data system job description #6)job10
8.9.7Install Nlount one 1-U SC-connector fiber optic patch panel (similar to below) in the network cabinet. Patch panel will be provided by the vendor(as per description in HU data system job description #7)job10
8.9.8Terminate the new 6-pair multimode fiber optic cables with SC connecters, and connect to fiber patch panels in existing patch panel in the ISC server room and in each cabinet.job10
8.9.9All ports . jacks, patch panels, and cabinets will be labelled according to the following standards:(as per description in HU data system job description #12)job10
8.10TV/Sat Outlets
8.10.1Satellite socket outlet RG6 cable, 3/4"fire retardant conduit terminated to SAT SW inside data roomEA.50
8.11IP Video Intercom System
Supply, Install, connect, test, label and commission complete IP Video intercom system including software, power suupplies as drawings, specification and related codes.
8.11.1Door Station as aiphone IS-DV series or approved equalEA.10
8.11.2Master Station as aiphone IS-IPMV series or approved equalEA.60
8.11.3Door StrikeEA.10
Total of Bill # 80
17% VAT0
Total of Bill # 8 (Including VAT)0
9- General Provisions of Mechanical Works
Division 1: Drainage System
9.1Supply and install the following HDPE drainage and vent pipes laid exposed, in walls, or under tiles and ground, type Huliot, Wavin, Geberet, or E.A, complete with all accessories and fittings, including connections with the existing pipes, wherever shown in Drawings and to the approval of the Engineer:
Drainage and vent HDPE pipes of the following sizes:
9.1.1100 mm diameter HDPE soil, drain and vent pipe.20Mr.0
9.1.250 mm diameter UPVC soil, drain and vent pipe.20Mr.0
9.2Supply and install 4” floor trap outlets, type Huliot, Wavin, Geberet, or E.A, including casting into concrete, excavating, bedding, surrounding and connections to drainage pipes, complete as specified and as shown on drawing.
100 mm diameter HDPE FT.4EA.0
9.3HDPE floor trap stainless steel cover and strainer of the following sizes:
110 mm diameter HDPE floor trap with stainless steel cover and strainer.4EA.0
9.4HDPE floor clean out with stainless steel cover and strainer of the following sizes:
100 mm diameter HDPE FCO.1EA.0
9.5Supply, install, test and commission Porcelain undercounter Wash Basin, type Ideal Standard, Roca, or E.A, complete with all drain and water fittings and accessories needed to complete the work as per specification and direction of the supervisor engineer.3EA.0
9.6As above but for handicapped including all stainless steel accessories.1EA.0
9.7Supply, install, test and commission Porcelain handicapped Wall Hung W.C., , type Ideal Standard, Roca, or E.A, complete with stainless steel accessories and all drain and water fittings needed to complete the work as per specification and direction of the supervisor engineer.1EA.0
Division 2: Water And Fire Fighting Systems
9.8Supply, install, test and commission copper Pipes for cold and hot water complete with all type of fittings such as elbows 45deg, or 90 deg , reducers , plugs, tees , joint adaptors, rubber expansion - flexible joints ,shut off valve, copper non return valves swing type , Hilti type hangers and supports , shut off valve. The rate shall include connection to existing Pipes and all other accessories needed to complete the work as per dwgs, specification and direction of supervisor engineer.
9.8.13/4"40Mr.0
9.8.21/2"20Mr.0
9.9Supply and install 13mm thick thermal insulation for domestic hot and return water pipes type ANAVID or equivalent. The work includes insulating all fittings, valves, and wrapping with 10cm wide plastic wrap, as follows:

A. The thermal insulation materials shall be made from materials which will not burn. All material finishes shall conform to spread of flame classification class O. B. Insulation shall be rotproof, odourless, non-hyroscopic, shall not sustain vermin and shall not contribute to metal corrosion. C. Thermal insulation materials and their finishes shall be asbestos free and be suitable for continuous use throughout the range of operating temperatures and within the environment indicated. D. All insulating materials and associated products, sealants, tapes, adhesives, securing bands and protective cladding shall be as specified or equal and approved.

9.9.13/4"20Mr.0
9.9.21/2"20Mr.0
9.10Supply, install and test Hot and Cold Water Collectors type Tiemme, Giaccomini or E.A. Complete with hangers, end pieces , automatic air vents , shut of valve at each outlet, copper elbows, plugs, reducers, main shut of valve 3/4",1" ,1 1/4" type Tiemme or E.A , and all other fittings and accessories needed to complete the work. The price shall also include 16mm pex pipes with their 25mm conduits including all fittings needed to connections to sanitary fixtures outlets, all as per dwgs, specification and direction of supervisor engineer.
Cold Water Collector of 6 openings and hot water collectors of 4 openings.1L.S0
9.11Supply and install portable fire extinguishers of the ABC type, type Lahavot or equal approved, and shall be supplied complete with the operating charge from the factory. The brackets shall be specifically supplied for the extinguisher type and size concerned, full vision pressure gauge, discharge hose and heavy duty drawn steel cylinder with hard scratch resistant finish.
3KG ABC Powder Fire Extinguisher2EA.0
9.12Supply and install painted Galvanized steel fire pipes to ASTM A53: complete with all Tees. Elbows, flexible connections, valves, etc., and connections to existing pipes, all as specified:
Galvanized steel fire pipe (GSP) of the following size.
9.12.150 mm diameter (GSP).15Mr.0
9.12.240 mm diameter (GSP).10Mr.0
9.12.332 mm diameter (GSP).10Mr.0
9.12.425 mm diameter (GSP).37Mr.0
9.13Supply & install automatic fire nozzle sprinkler, type Global, Viking or E.A, for exposed installation chrome plated, reccaded quick response k=5.6, T=68Cْ U.L/F.M approved including all required fittings, according to the following specifications:

A. Sprinklers shall be installed as shown on drawings and in accordance with the requirements of NFPA 13.

B. All Sprinklers shall be manufactured, tested and approved in accordance with the applicable standards of Underwriter Laboratories and Factory Mutual.

C. Unless otherwise stated on drawings automatic sprinklers shall have a temperature rating of 68 deg C with bulb color red. Orifice diameter shall be 15 mm with NPT thread type.

Sprinkler head - pendent , chrome plated.18EA.0
Division 3: Ventilation and Air Conditioning Systems
9.14Supply, install, and commission indoor ducted fan coil unit, type Carrier, Trane, York or equal approved. The price includes all accessories and fittings needed for installation and commissioning, i.e, 3-way valve, shut-off valves, insulated pipes flexible connections, connection of drain pipe, connections of chilled water pipes, acoustic insulation adapter between the unit and main duct, vibration isolators, duct flexible connection, hangers and supports, high performance washable filters, wall mounted thermostat (three fan speeds – summer/winter changeover – temperature setting module) with its control cable, drain pan, in addition to electrical connection, all according to drawings and engineer’s instructions and as follows:
• 13.5 kW Cooling Capacity & 625 L/s Air Flow1EA.0
9.15Dismantle, re-install, test and commission existing indoor ducted fan coil unit. The price includes supplying and installing all accessories and fittings needed for installation and commissioning, i.e, 3-way valve, shut-off valves, insulated pipes flexible connections, connection of drain pipe, connections of chilled water pipes, acoustic insulation adapter between the unit and main duct, vibration isolators, duct flexible connection, hangers and supports, new high performance washable filters, new wall mounted thermostat (three fan speeds – summer/winter changeover – temperature setting module) with its control cable, drain pan, in addition to electrical connection, all according to drawings and engineer’s instructions and as follows:
• 3.5 kW Cooling Capacity & 180 L/s Air Flow4EA.0
9.16Supply and install ducted in-line mixed flow ducted ventilation air fans, type Dynair, S&P or equal approved. The price includes vibration isolators, flexible connections between the fan and duct, including outdoor gravity grilles with mesh for exhasut fans and outdoor grille with filter for fresh air fan. The price shall also include control and electrical connections, complete as specified and as shown on drawing:
9.16.1In-linel exhaust fan of 50 L\s (EXF - 01).1EA.0
9.16.2Inline exhaust fan of 30 L\s (EXF - 02).1EA.0
9.17DUCTING WORK
Supply and install galvanized metal sheet duct for air conditioning and ventilation system of thickness as per SHRAE Standards. The price includes all joints, fire rated sealant compound, and all necessary accessories, galvanized hangers, hooks, complete as specified and as shown on drawing.
9.17.1G.I. Sheets duct work (with insulation)40M²0
9.18Supply and install thermal insulation material for ductwork according to the following specifications:

A. The material shall be rigid rock wool mineral fibre slab consisting of long fine fibres (free from short and coarse fibres) bonded with a temperature resistant resin. The density shall be a minimum of 48 kg/m3.

B. The thickness of insulation material shall be at least 25mm thick where its declared value of thermal conductivity at the relevant temperature is equal to or less than 0.04 W/m.K or at least 38mm thick where the declared value of thermal conductivity is between 0.04 and 0.06 W/m.K.

D. All ductwork thermal insulation shall be complete with a reinforced aluminium foil applied to one side during the manufacturing process.

9.18.125mm thick insulation material22M²0
9.19Supply and install white anodized Aluminum, supply air diffusers with registers, type Trox, Metal Press or equal approved. The price includes opening in false ceiling, in addition to galvanized duct connection, and flexible duct connection (where needed), as per engineer instructions:
4-Way Supply Ceiling Diffuser (SCD)
9.19.1SCD 230 mm x 230 mm1EA.0
9.19.2SCD 300 mm x 300 mm8EA.0
9.2Supply and install white anodized Aluminum, return air grilles and diffusers, including openings in false ceiling, complete as per specifications:
Return Air Grilles (RAG)
9.20.1RAG 230 mm x 230 mm1700
9.20.2RAG 300 mm x 300 mm1800
9.21Supply and install white anodized Aluminum, exhaust air grilles of two opposed blades with registers, type Trox, Metal Press or equal approved, including openings in false ceiling. The price includes connections to grilles through galvanized duct connection, complete as per specifications:
Exhaust Air Grilles (EAG)
9.21.1EAG 200 mm x 200 mm1EA.0
9.21.2EAG 150 mm x150 mm1EA.0
9.22Supply and install HDPE condensate drain pipes, type Holiut, Wavin, Geberet or equal approved, with all needed fittings including 15 mm insulation as per drawings and/or specifications:
50 mm diameter insulated HDPE condensate drain pipe.15Mr.0
9.23Supply, install, test and commission Black Steel Pipes - Sch 40 with 19 mm thick thermal insulation type ANAVID or E.A. for heating/chilled water pipes net work .The rate shall include wrapping with 10 cm wide aluminum foil tape for outdoor pipes and with nylon wrapping for indoor pipes, and all type of fittings such as elbows 45deg, or 90 deg , reducers , plugs, tees , joint adaptors, air vents, valves ,hangers and supports -Hilti type. Also the rate include any required concrete coring by Hilti machine and using sleeves around the pipes with all accessories needed to complete the work as per dwgs, specification and direction of supervisor engineer.
9.23.13/4"20Mr.0
9.23.211/4"20Mr.0
9.23.311/2"20Mr.0
Total of Bill # 90
17% VAT0
Total of Bill # 9 (Including VAT)0

&P summary

Renovation of the HEALTH UNIT
Talpiot- Jerusalem
General Services Office-Procurement
Summary
SectionWorksTotals/ NIS
1Demolishing works0
2Tiles works0
3Gypsum works0
4wood works0
5Aluminum works0
6Painting works0
7Additional Equipment0
8Electrical works0
9Mechanical works0
TOTAL0
17% VAT0
GRAND TOTAL INCLUDING VAT0