Siemens_Circuit_Switcher_brochure_201711-13.PDF
PDF 2 MB Posted
- Solicitation number
- ITB#202625
- Issued by
- Miami-Dade County, Florida
About this file
This is a product brochure and specification document for the City of Homestead Power System (HPS) in Florida, detailing materials procurement for the Donnie Avocado 138kV/13.2kV Substation Project. The solicitation seeks bids for supply and delivery of critical long-lead electrical equipment and associated materials, with bids due July 30, 2026. The primary equipment specified is the Siemens Type CPV2 Circuit Switcher, a three-cycle circuit interruption device available in voltage ratings from 72.5kV to 245kV with interrupting capacities of 20kA, 25kA, 31.5kA, and 40kA. The circuit switcher features a vertical interrupter design ideal for space-limited applications, operates with an FA2 spring operator mechanism, and includes optional temperature-compensated SF6 gas density monitoring for EPA compliance. HPS is procuring major substation components directly from qualified manufacturers to ensure timely delivery, maintain compatibility with existing utility infrastructure, and control equipment procurement throughout the project.
Vendors must provide comprehensive pricing, technical information, lead times, and all other requirements identified in the solicitation documents, including the Donnie_Material_Specs.docx attachment. The Siemens CPV2 circuit switcher is available in multiple configurations with continuous current ratings of 1200, 1600, 2000, and 3000 amperes, and can be equipped with various optional accessories including grounding switches, bypass switches, disconnect switches, and external manual trip mechanisms. The device is suitable for transformer protection, cable switching, capacitor bank switching, and reactor applications, with low-temperature operation capability down to -40°F for specified applications. The City of Homestead Power System is an Equal Opportunity Employer that encourages participation from MBE/WBE/DBE businesses in this procurement opportunity.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Power Transmission & Distribution
Circuit Switcher Type CPV2
72.5 - 245kV
Siemens CPV2 Circuit Switchers Siemens Type CPV2 (Circuit Protector Vertical) circuit switchers are ideal for applications that require 3 cycle circuit interruption and requires limited space . The CPV2 model provides space-saving, fast protection at an economical cost.
Operation of the CPV2 is controlled by a FA2 spring operator which is same as the operating mechanism used in the SPS2 SF6 Circuit Breakers worldwide. There are several reasons to specify and install the CPV2 Circuit Switcher: field proven design, robust construction, simple installation, minimal maintenance and low installed cost. The Siemens CPV2 can switch and protect transformers, cables, shunt capacitor banks and shunt reactors. It also provides a low cost, low temperature, high fault interrupting device. It has a consistent and fast operating time of 3 cycles with a high interrupting capability of up to 40kA.
The Siemens type CPV2 Circuit Switcher is ideal for space limited applications. In new or existing substations where sufficient room is not available to install a horizontal circuit switcher or a conventional SF6 dead tank circuit breaker. The vertical type CPV2 is also the preferred model for retrofit installations where a circuit switcher is recommended to replace an existing fault interrupting device.
Gas Monitoring Each pole unit is equipped with a manifold which incorporates a fill valve, a pressure gauge and rupture disc. This manifold is located at the lower end of the pole unit, connected to the cover assembly by a union coupling. The coupling allows the pressure gauge to be rotated by the user to provide the most satisfactory view from the ground.
The pressure gauge has a color coded face for ease of reading from a distance. A label showing a picture of the gauge and an operating pressure range versus ambient temperature is located on the door of the control cabinet.
For specific applications of the Siemens Type CPV2 Circuit Switcher, contact the nearest Siemens sales office.
Siemens exclusive!
As an option, the Siemens CPV2 Circuit Switcher can be equipped with a temperature compensated pressure switch to automatically monitor the SF6 gas status in the pole units. This switch with gauge is located inside the control cabinet and is connected to the pole units by stainless steel tubing. It has two sets of contacts. One set of contacts provides an alarm indication when the gas pressure approaches within 5 psi of the lockout value. The other set prevents operation if gas pressure falls to a level at which current interruption is not assured. The temperature compensating feature of the switch avoids alarms and lockouts due to normal pressure variations associated with local temperature changes.
Type CPV2 Circuit Switchers
Key Features
¥ 72.5 thru 169kV Shipped Assembled.
¥ 245kV Shipped in Sub-Assemblies.
- Factory timed and tested to save installation time and cost.
- Pre-engineered designs facilitate reduced approval times and allow quicker delivery times.
¥ Vertical Interrupter Design.
- Requires minimum installation space. Ideal for retrofit applications.
¥ Increased Interrupting Ratings.
- 20kA, 25kA, 31.5kA, 40kA Primary Fault Ratings Available
- Ratings based on TRV parameters defined in Table 2 of
ANSI C37.06.
¥ Fast 3 CYCLE Interrupting Speed.
- Significantly reduces system disturbances and minimizes damage to key system components.
¥ Full Strength Interrupter Insulation.
- Maintains full BIL insulation across open contacts and permits use of non-disconnect models.
¥ Proven Spring Operator Mechanism.
- FA2 Spring Operator offers simple stored energy mechanism.
- Same operator used on 10,000 SPS2 SF6 Gas Circuit Breakers.
¥ Color-coded PSI Gauge
- Permits easy gas pressure readings for each pole from a distance
¥ Rupture Disk on each Interrupter
- Protection for over-pressure conditions in any pole unit
CPV2 Ratings
¥ Maximum Design Voltages --- 72.5, 121, 145, 169 and 245 kV
¥ BIL of SF6 Interrupter --- 350, 550, 650, 750 and 900KV
¥ Continuous Currents --- 1200, 1600, 2000 and 3000 amperes
¥ Short Circuit Interrupting Capacity --- 20, 25, 31.5 and 40 Kv
¥ Transformer Thru-fault --- 4 KA rms symmetrical
¥ Close and Latch (fault closing, multiple duty) --- 108 KA rms crest
¥ Thru-Fault Withstand (10 cycles Momentary) --- 108 KA rms crest
¥ 3-Second Short Time Current --- 40 KA rms symmetrical
Features and Ratings
Device Description
48VDC
(Amps)
125VDC
(Amps)
Motor Inrush Current
75 33
Motor Running Current
17.4 9.8
Trip Coil Currents
16 12
Anti-Pump Relay Coil
0.2 0.1
Time Delay Relay Coil
0.2 0.1
Motor Fuses Heater Fuses
Operation Current Ratings
Type FA2 Operating Mechanism
The type FA2 operator and necessary control and monitoring equipment are housed in a common cabinet. Large doors located on either side of cabinet are easily lifted from their hinges for unobstructed access to the cabinet interior.
The FA2 operating mechanism stores energy for use in closing the circuit switcher. This energy is stored by compressing a powerful spring. An electrical motor with an integral gear reduction set (called a gearmotor) is used to compress the operator spring. The purpose of storing the motor-supplied energy in the spring is to allow a rapid closing operation of the circuit switcher.
It takes about ten seconds for the gearmotor to
A FA-4 Spring Operator Mechanism B Two Cabinets, Painted ANSI Gray #70 C Close Coil/ Dual Trip Coils D Control Terminal Blocks E Red/Green Indicating Lights F Trip/Close Pushbuttons G Non-Reset Operations Counter H 14-Stage Adjustable Auxiliary Switch
(8 Stages for Customer) I 120 or 240 VAC Heater J Fused Pull-Outs for DC Control and Heater Circuits K Open/Close Position Indicator (Interrupter) L Internal Cabinet Lights (2) with Toggle Switch (1) M Duplex Receptacle (GFI) N 125 VDC Motor
O View Window in Front Door P Local/Remote Selector Switch (Optional) Q Gas Monitor with Lock-Out (Optional) R Control Relay(s) (Optional) S Auxiliary Switch Stages to 28 Max. Ð
24 Stages for Customer (Optional) T Pressure Gauge (Optional with Gas Monitor System) U Gas Fill Port (Optional with Gas Monitor System)
Other Optional Features (Not Shown) Internal Cabinet Light with Door Actuated Switch Fused Knife Switches Molded Case Circuit Breakers 120/240 VAC Cabinet Heater with Thermostat Control 48 VDC Motor compress the spring, but the spring can discharge and close the switcher in less than 0.1 seconds.
With the circuit switcher open, a close operation is initiated by energizing the gearmotor. The closing spring becomes fully compressed, and then discharges, closing the switcher and charging the opening spring.
The gearmotor is automatically de-energized.
The switcher is maintained in the closed position by a latch system in the operator. A trip operation is initiated by energizing a solenoid which releases the trip latch and allows the switcher to open.
Standard and Optional Features (Shown)
SF6 Gas Density Monitor
The circuit switcher can be equipped with a temperature compensated pressure switch to automatically monitor the status of the SF6 gas in the pole units. The pole unit gas systems will then be connected to the density switch, which is located inside the control cabinet. The switch has two contacts, one for an alarm indicating low gas, and the second will prevent operation at a level at which current interruption is not recommended.
The system incorporates a fill port and pressure gauge with easy access located inside the control cabinet. The gauge is located by the cabinet window for ease of viewing, without opening the door.
Low Temperature Operation
If specified, the circuit switcher is suitable for operation in temperatures ranging from -40F (-40C) to +104F (40C). The maximum interrupting current is 31.5 kA.
Additional Options
External Manual Trip Additional Auxiliary Switch Contacts (12) Thermostat for the Control Cabinet Heater Control Switch, with pistol grip handle Local remote switch Bypass switch Center Break Disconnect switch Ground switch Seismic Design per IEEE 693
Dimension Data
Structure Height 8’0” (96.0”) 10’0” (120.0”) 12’0” (144.0”)
Nominal kV
Class
Type
Identification Ratings Related Capabilities
Current Values - AmpresCurrentInsulationVoltage
Rated Max kV
Rated Voltage Range Factor
Low Freq.
(kV, rms)
Impulse (kV, crest)
Rated Continuous
Current (Amps. rms)
Inter-rupting
Time Cycles
Maximum Symmetrical Interrupting
Capability
3 sec.
Short Time
Current Carrying
Capability
Closing and
Latching Capability
Rated Short
Circuit Current at Rated Max kV
Dimensional Data
Ratings Chart kV Rating 72.5 121 145 170 245 72.5 121 145 170 245 72.5 121 145 170 245
CPV2-72.5-20 69.0 72.5 1.0 160 350 1200 thru 3000 20,000 3 20,000 40,000 108,000
CPV2-72.5-25 69.0 72.5 1.0 160 350 1200 thru 3000 25,000 3 25,000 40,000 108,000
CPV2-72.5-31.5 69.0 72.5 1.0 160 350 1200 thru 3000 31,500 3 31,500 40,000 108,000
CPV2-72.5-40 69.0 72.5 1.0 160 350 1200 thru 3000 40,000 3 40,000 40,000 108,000
CPV2-121-20 115 121 1.0 260 550 1200 thru 3000 20,000 3 20,000 40,000 108,000
CPV2-121-25 115 121 1.0 260 550 1200 thru 3000 25,000 3 25,000 40,000 108,000
CPV2-121-31.5 115 121 1.0 260 550 1200 thru 3000 31,500 3 31,500 40,000 108,000
CPV2-121-40 115 121 1.0 260 550 1200 thru 3000 40,000 3 40,000 40,000 108,000
CPV2-145-20 138 145 1.0 310 650 1200 thru 3000 20,000 3 20,000 40,000 108,000
CPV2-145-25 138 145 1.0 310 650 1200 thru 3000 25,000 3 25,000 40,000 108,000
CPV2-145-31.5 138 145 1.0 310 650 1200 thru 3000 31,500 3 31,500 40,000 108,000
CPV2-145-40 138 145 1.0 310 650 1200 thru 3000 40,000 3 40,000 40,000 108,000
CPV2-170-20 161 170 1.0 365 750 1200 thru 3000 20,000 3 20,000 40,000 108,000
CPV2-170-25 161 170 1.0 365 750 1200 thru 3000 25,000 3 25,000 40,000 108,000
CPV2-170-31.5 161 170 1.0 365 750 1200 thru 3000 31,500 3 31,500 40,000 108,000
CPV2-170-40 161 170 1.0 365 750 1200 thru 3000 40,000 3 40,000 40,000 108,000
CPV2-245-20 230 245 1.0 425 900 1200 thru 3000 20,000 3 40,000 40,000 108,000
CPV2-245-25 230 245 1.0 425 900 1200 thru 3000 25,000 3 40,000 40,000 108,000
CPV2-245-31.5 230 245 1.0 425 900 1200 thru 3000 31,500 3 40,000 40,000 108,000
CPV2-245-40 230 245 1.0 425 900 1200 thru 3000 40,000 3 40,000 40,000 108,000
Internal kV BIL 350 550 650 750 900 350 550 650 750 900 350 550 650 750 900
Insulator kV 72.5 121 145 170 245 72.5 121 145 170 245 72.5 121 145 170 245
Phase Spacing 48 84 102 110 48 84 102 110 48 84 102 110
84 102 120 -- 84 102 120 -- 84 102 120 --
“A” Dim. (In.) 109.2 130.8 148.5 186 109.2 130.8 148.5 186 109.2 130.8 148.5 186 “B” Dim. (In.) 50.3 71.9 81.8 100 50.3 71.9 81.8 100 50.3 71.9 81.8 100
Net Weight (lbs.) 4450 4750 5100 8800 4550 4850 5200 8900 4650 4950 5300 9000
Siemens has designed the CPV2 With our customers’ needs in mind:
¥ Three-cycle operation
¥ Greater interrupting capabilities of 20, 25, 31.5, and 40kA
¥ Greater continuous current ratings of 1200, 1600, 2000
¥ Continuous gas monitoring for EPA compliance
¥ State-of-the-art arc-assist technology
¥ Anchor bolts and column spacing designed to accommodate existing 12Ó x 12Ó or 20Ó x 20Ó foundations
¥ Two cabinet design for ease of shipping and installation and long-term access and inspection
¥ Optional accessories include grounding switch, by-pass switch and disconnect switch (motorized option)
SteveJohnson
Type CPV2 - 72.5 kV Low Profile
Type CPV2 - 245 kV FG
Type CPV2 - 245 kV FI
Type CPV2 with Switches Center Break Disconnect Switch (left)
By-pass Switch (right)
Application Guide CPV2 Circuit Switcher a Maximum switching/interrupting current (amperes) RMS symmetrical. Tripping of the CPV2 circuit switcher need not be coordinated with source side breakers for short circuit faults up to 40kA RMS symmetrical. Ratings are per ANSI temperature range of -30OC (-22OF) to +40OC (+104OF).
b Siemens circuit switchers can close, carry, and interrupt the magnetizing current of the protected transformer.
c Rating is based on transient-recovery-voltage parameters defined in Table 2A of ANSI standard C37.06-1997 for Siemens circuit Switchers rated 72.5kV and Table 3A for 123kV through 245kV.
d Siemens circuit switchers are suitable for transformer-primary applications where the inherent secondary-side of the transformer does not exceed 6000 amperes. The inherent secondary fault current is defined as secondary-side fault current as reflected through to the primary side of the transformer and may be calculated as follows.
I = Inherent Secondary Fault Current KVA = Transformer Self-cooled 3-phase Rating
E = System Voltage kV Z = Impedance Primary-to-Secondary in Percent
For applications where the inherent secondary-fault current exceeds the above limits, but where the maximum expected fault current, Based on transformer impedance plus source impedance is within these limits, refer to your local Siemens sales representative.
e Grounded capacitor banks applied on solidly grounded systems at a maximum line-to-ground voltage of 1.0 x f Ungrounded capacitor banks at a maximum line-to-ground voltage of 1.5 x
Transformer
Application Qualification Maximum Currenta
Line or Cable
Single Shunt Capacitor
Series Reactor
Shunt Reactor Switching
Protection Fault Interrupting Primary Faults 40,000c
Secondary Faults 6,000d
Switching Parallel Switching -- 4,000 Load Droppingb -- 4,000
Protection Fault Interrupting -- 40,000
Switching Load Splitting (parallel or loop switching) -- 4,000 Load Dropping -- 4,000 Line, Cable Dropping (charging current) -- 400
Switching Refer to local Siemens PT&D sales representative
Protection Fault Interrupting -- 40,000c
Switching Bank Current Switching Grounded capacitor 400e banks through 170kV Undergrounded capacitor 400f banks through 123kV
Protection Fault Interrupting -- 40,000
Switching Reactor Current Switching Grounded reactor applied 4,000 (but not on solidly grounded less than 250) systems through 170kV
I= x where100 Ã3
E Ã3
E Ã3
KVA
ExZ
Interrupter Unit Arc-assist interrupter
The durable construction of the SPS2 circuit breaker includes the field proven 3AP arc-assist interrupter. Each interrupter consists of a stationary contact assembly and a moving contact assembly mounted inside a pole unit housing.
During the opening operation, the puffer action in the compression cylinder of the 3AP interrupter is sufficient for low current faults and switching operations. During high current interruptions, heat from the arc causes the pressure to rise in the heating volume chamber. The resulting high pressure gas from the heating volume extinguishes the arc.
This arc-assist technology, coupled with our FA2 up to 170kV, 40kA, FA4 for 50/63kA and all 245kV spring-stored, and FA5 on 550kV energy operator, assures that the components are subjected to less stress which results in optimal operating reliability.
KEY:
1. Aluminum Housing
2. Stationary Contact Support
3. Nozzle
4. Main Contact
5. Arcing Contact
6. Heating Volume
7. Moving Contact Support Base
8. Compression Cylinder
Closed Position
Opening Main contact open
Opening Arcing contact open
Open Position
Live-tank and Dead-tank Circuit Breakers Same technology for every application in two designs
Special technical features of live-tank design
On live-tank circuit breakers, the interrupter chamber is arranged in the insulator, which can be either porcelain or of a composite material, and is at high potential with the voltage level determining the length of the insulators for the interrupter chamber and the insulator column.
For higher voltage levels, several interrupter chambers series-connected on live-tank circuit breakers and installed on the insulator column.
The current transformers are arranged separately either in front of or behind the live-tank circuit breakers. As in live-tank circuit breakers, no fault currents can occur between the interrupter unit and the housing; only one current transformer per pole assembly is necessary.
A further feature of live-tank circuit breakers are the comparatively small gas compartments. The advantage of the low gas volume is that there is a reduction in the amount of gas maintenance work.
To ensure the safe operation of live-tank circuit breakers in seismic regions, the breakers can be mounted on anti-friction structures, a solution that has been tested up to 800kV and has proved its worth many times.
Special technical features of dead-tank design
The distinguishing feature of dead-tank technology is that the interrupter chamber is accommodated in an earthed metal housing. With this arrangement, the SF6 gas filling insulates the high voltage live parts of the contact assembly from the housing.
The connection to the high voltage is via a SF6 outdoor bushing.
The current transformers are mounted directly on the bushing, which eliminates the fastening devices and cabling required in the case of exterior mounting.
Dead-tank circuit breakers offer particular advantages if the protection design requires the use of several current transformers per pole assembly, such as for a typical American system. The possibility of being able to arrange current transformers in front of and behind the circuit breaker enables protection schemes to be met in a particularly cost-saving manner. Furthermore, it is relatively simple to retrofit the current transformers in the field.
As an additional advantage, dead-tank circuit breakers are particularly resistant to earthquakes due to their compact design and low center of gravity.
Both the live-tank and the dead-tank designs possess their own special features, and each design has its own particular advantages.
CPV2 Specification Longer operating life – Lower maintenance costs
In considering any circuit switcher, todayÕs utilities must be concerned not only with initial price and installation, but also with the ongoing costs of ownership. The Siemens CPV2 wins in every category. Its relatively low price tag, simple installation and easy maintenance will continue to pay dividends decades into the future.
In addition to the reliable performance you can expect from your CPV2 switcher, youÕll also find it can handle a number of special requirements, such as:
¥ Switching capacitors, cables and reactors
¥ Environmentally restricted sites requiring oil sumps
¥ System stability problems requiring three-cycle interrupting
¥ Reclosing duty without derating interrupting capability
¥ High contamination zones that require extra creep and low contamination weather shields
¥ High altitude application up to 10,000 feet without derating
Getting the Best Switcher for your Needs How to Order
When ordering a Type CPV2 switcher, specify the following:
1. Switcher type and rating
2. Trip voltage (see Ratings Section)
3. Close voltage (see Ratings Section)
4. Motor voltage: 120VAC/125VDC, 240VAC/250VDC, 48VDC
5. Heater voltage: 115, 230 VAC
6. Terminals: specify in detail if desired
7. Include customer specifications covering special equipment, accessories, test, etc.
Basic Switcher The Standard basic switcher includes:
1. Three-pole SF6-filled outdoor power circuit switcher with three SF6 interrupters
2. Galvanized base with four galvanized pedestals
3. Light gray standard color
4. Six light gray ANSI #70 SF6-filled porcelains
5. Six relaying accuracy bushing current transformers
6. Trip-free spring operating mechanism
7. Instrumentation to monitor SF6 gas pressure and provide low pressure alarm
8. Twelve stage auxiliary switch; Eight stages for customer use
9. Trip coil and close coil
10. Cabinet heater to prevent condensation
11. Necessary terminal blocks and wiring
12. Operations counter
13. Fused knife switches (3)
14. Grounding pads (3)
15. Mechanical position indicator
16. Provision for travel recorder attachment
17. SF6 gas for initial filling
18. Set of tools required for installation
Operational modifications
1. Capacitor trip
2. Relays for reclosing or non-reclosing switcher application
3. External pull to trip handle
4. Cabinet light and convenience outlet
5. Special heaters and cabinet insulation for operation down to -50OC
6. Two additional 12-pole auxiliary switches
7. Dual trip coils
8. Control switch
9. Local/remote switch
10. Thermostat for cabinet heater www.usa.siemens.com/energy
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness hereof is not guaranteed. Since conditions of use are outside our control, the user should determine the suitability of the product for its intended use and assumes all risk and liability whatsoever in connection herewith.
Siemens Power Transmission and Distribution 444 Hwy. 49 S Richland, MS 39218 USA tel: 601.939.0550 fax: 601.932.9911
© 2006, Siemens Power Transmission & Distribution, Inc.
All rights reserved.
PBBR-1000F
Subject to change without notice.