SEPRL Production Buildings HVAC Replacement.docx
DOCX document 58 KB Posted
- Attached to
- HVAC Parts for Bldgs 13, 15, and 17
- Solicitation number
- 12405B24Q0462
About this file
This document is a Request for Quote (RFQ) for HVAC parts to replace equipment in Buildings 13, 15, and 17 at the U.S. National Poultry Research Center in Athens, Georgia. The USDA Agricultural Research Service is seeking a contractor to provide 6 gas furnaces, 8 swamp coolers, and 6 fan motors to meet the specified technical requirements. The government anticipates awarding a firm-fixed-price contract to the vendor submitting the lowest-priced, technically acceptable proposal. Quotes must be received by August 16, 2024, at 4:00 pm Central Time. The contract will be awarded to a small business under NAICS code 238220. Vendors must be registered in SAM and provide pricing, technical specifications, and past performance information in their responses.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SEPRL Production Buildings HVAC Replacement.docx | DOCX document | |
| Clauses and Provisions.docx | DOCX document | |
| Beta Sam Solicitation 12405B24Q0462.docx | DOCX document | |
| Clauses and Provisions.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
United States Department of Agriculture Agricultural Research Service
Description of Equipment Needed for
SEPRL Building 13, 15, and 17 HVAC Replacement
U.S. National Poultry Research Center 934 College Station Road Athens, Georgia 30605
EQUIPMENT ONLY, No installation required.
The contractor shall provide all materials necessary to complete the replacement of 6 heaters (2 per building) for buildings 13, 15, and 17. We will also be replace eight swamp coolers with four mounted on the roof and four on the ground. We will also replace six fan motors for the motor and fan wheel.
The material needed for this project is as follows:
1. 6 - Gas furnace
a. Must be outdoor rated.
b. Must be a horizontal flow orientation
c. Minimum air flow rate: 1400cfm
d. Maximum air flow rate: 3700cfm
e. Use Sterling Model# QVED150S
2. 8 – Swamp coolers
a. Use Phoenix Manufacturing Model# FS/FD650
b. Side discharge
3. 6 – Fan motors
a. 2.0hp
b. 1740 RPM
c. Use Dayton Model# 36VF53B All processes of this project shall meet or exceed the manufacturers and industry standard requirements.
image1.jpg
File details come from the government source that posted it. Updated .