This document is an amendment to a technical specification for a federal contract solicitation. The solicitation is for the supply of GSU transformers for the Old Hickory Power Plant. The amendment revises the specification to change references to "maximum ONAN" losses to "base ONAN" losses. It also updates a proposal content section and a FAR clause to reflect this change. The transformers required have ratings of 161x69 kV and 13.2 kV, with Wye and Delta winding configurations. Additional details such as impedance, BIL levels, taps, losses, sound levels, and weight are provided. Structural design criteria and seismic calculations must also be submitted for the transformers and associated components. The solicitation is issued by the Department of the Army Corps of Engineers Nashville District.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| W912P519R0004-0005.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GSU Transformer Supply Old Hickory Lock W912P519R0004 Old Hickory Tennessee
(1) High-voltage windings: 161 x 69
(2) Low-voltage windings: 13.2
e. Winding connections:
(1) High-voltage windings: Wye
(2) Low-voltage windings: Delta
f. Impedance, at ONAN rated current, subject to IEEE tolerances, percent:
(1) 69 kV: 7.5
(2) 161 kV: minimum 7.5, maximum 12
g. Angular displacement, low-voltage lags high-voltage by, degrees:
h. Basic impulse insulation levels (BIL), kV:
(1) Line ends of the high-voltage windings, not less than: 650
(2) Neutral ends of the high-voltage windings, not less than:
(3) Low-voltage windings, not less than: 110
i. Taps in low voltage windings: None
j. Taps (full capacity) in high voltage winding
(1) Tap A, nominal voltage: 69 kV
(2) Tap B, nominal voltage: 161 kV
(3) Tap 1, percent of high-voltage tap A selection: 105.0
(4) Tap 2, percent of high-voltage tap A selection: 102.5
(5) Tap 3, percent of high-voltage tap A selection: 100.0
(6) Tap 4, percent of high-voltage tap A selection: 97.5
(7) Tap 5, percent of high-voltage tap A selection: 95.0
k. Maximum no-load losses at 69 kV and rated frequency, kW: 90
l. Maximum load losses at base ONAN rated kVA, 69 kV, and 1.0 power factor, kW: 180
m. Maximum average sound level at 69 kV and rated frequency, with all cooling groups in operation, dB: 68
n. Maximum transformer total weight, completely assembled and oil filled with all accessories installed, pounds: N/A
2.1.6 Unusual Service Conditions
The transformers will not be subject to any unusual service conditions, as defined by IEEE C57.12.00 , paragraph 4.3.
2.2 STRUCTURAL DESIGN CRITERIA AND SEISMIC CALCULATIONS
Structural design criteria and seismic calculations shall be provided for the transformers, to include the main tank and all major components such as bushings, cooling equipmentand cabinets.
SECTION 48 19 23.04 26 Page 16