B2 EUS PROCUREMENT
ADDITIONAL CONTROLS TRUNK CABLE
AUGUST 08, 2022
STATEMENT OF WORK
The purpose of this SAT procurement is to obtain a two lengths of trunk cables for additional B2 Facility Controls capability needed for Exploration Upper Stage (EUS) testing. This cable will be used to interface the new B2 Facility Controls hardware on Level 11 inside the soft core to the new Terminal Equipment Box (TEB) on L11 outside. These cables will provide Controls signals to the TEB.
This effort includes procurement of multiple types and lengths of trunk cables and delivery to SSC as follows:
30 TSP 18 AWG Multi-Conductor Cable Spec
Conductor
Number of pairs: 30
AWG Size and Stranding: 18 AWG, 7 strands
Material: Tinned copper
Insulation
Material: Polyvinylchloride (PVC)
Pair color code: Black and White or Black and Red
Pair Assembly
Cable lay: 6 twist/ft minimum
Cable shield: Aluminum/mylar – 100% coverage
Drain wire: 18 AWG 7 strands tinned copper
Inner jacket
Color code: black with white numbers for each pair (1 One thru 30 Thirty)
Outer Jacket
Color: black
Type: Polyvinylchloride (PVC)
Sequential footage mark
Additional info
Maximum operating voltage: 300V
Made in the USA
CMP(UL) or CL3P(UL), ROHS II compliant
REQUIRED 500 FT
60C 16 AWG Multi-Conductor Cable Spec
Conductor
Number of conductors: 60
AWG Size and Stranding: 16 AWG, 7 strands
Material: Tinned copper
Insulation
Color code: white with black numbers (1 ONE thru 60 SIXTY)
Assembly
Overall cable shield: Aluminum/mylar – 100% coverage
Drain wire: 18 AWG 7 strands tinned copper
Jacket
Color: black
Type: Polyvinylchloride (PVC)
Sequential footage mark
Additional info
Maximum operating voltage: 300V
Made in the USA
CMP(UL) or CL3P(UL), ROHS II compliant
1000 Ft put ups +/-10% (continuous length)
REQUIRED 1500 FT