SALIENT CHARACTERTICS
(3) Hour Fire Rated Roller Curtain Doors with motor/controller/fuselink links Drawings Provided For Form/Fit/Function Requirements
ROLLER CURTAIN DOOR 10’W x 8’6”H, COOKSON MODEL #ERD10 (or equal)
Quantity Two (2) Door Door to confirm to all Cookson Door Model #ERD10 Requirements:
For an opening 10’w x 8’6”h Interior face of wall mounted to steel 2 5/8” flat slat Non-insulated 18 gauge, galvanized steel, gray galvanized steel 3 HR UL & cUL fire label Thru wall fuselink and to include One (1) electric operator model PRO-GHE150 1 ½ horsepower 460/3/60 Micanan logic control operator (OR EQUILAVENT WITH FORM FIT & FUNCTION ) to be wall mounted and includes One (1) NEMA 1 surface mounted 3 button push button station
ROLLER CURTAIN DOOR 13’W x 8’6”H, COOKSON MODEL #ERD10 (or equal)
Quantity Four (4) DOORS Door to confirm to all Cookson Door Model #ERD10 Requirements:
For an opening 13’w x 8’6”h Interior face of wall mounted to steel 2 5/8” flat slat Non-insulated 18 gauge, galvanized steel, gray galvanized steel 3 HR UL & cUL fire label Thru wall fuselink and to include One (1) electric operator model PRO-GHE150 1 ½ horsepower 460/3/60 Micanan logic control operator (OR EQUILAVENT WITH FORM FIT & FUNCTION ) to be wall mounted and includes One (1) NEMA 1 surface mounted 3 button push button station
Doors shall be individually crated, for international shipment (minimum crating requirement for international shipment is ISPM 15 either heat treatment (HT) or methyl Bromide (MB) ISPM 15 Fumigation)