Salient Characteristics.xlsx

XLSX spreadsheet 21 KB Posted

Attached to
6115--Mobile Diesel Generator
Solicitation number
36C25026Q0918
Issued by

About this file

This is a salient characteristics specification document for a 500kW mobile diesel generator procurement by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10 under Solicitation Number 36C25026Q0918.

The generator must meet specific technical and operational requirements including 60Hz multipower voltage output capabilities (480/277V, 240/139V, and 208/120V). The equipment must comply with U.S. EPA Tier 4 Final emission standards and obtain CARB certification for non-road mobile applications at all 60Hz ratings, while also meeting ISO 8528-5 transient response standards. The generator must feature a heavy-duty diesel engine with a 100-amp charging alternator, three-phase random wound stator with coastal insulation protection, permanent magnet excitation, and Class H insulation with Class F temperature rise. Additional requirements include single-point access to accessory connections, UL 1446 recognized Class H insulation, sound levels not exceeding 72 dB(A) at seven meters per SAE J1074 measurement procedures at 110% prime load, 110% spill containment capacity for onboard engine fluids, and anti-condensation heaters rated at 120/240V, 1.2kW. Vendors may submit brand-name equipment or approved equal alternatives meeting all specified salient characteristics.

View the file

Other files

File Type Posted
36C25026Q0918_1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salient

SALIENT CHARACTERISTICS OF SELECT ITEMS FOR EVALUATION PURPOSES

COLOR TV 47 INPass/Fail
ItemBrand/Model Or EqualMinimum Salient Characteristic(s)
500kw mobile generator500kw
60hz
mutivoltage output 480/277, 240/139,208/120
Meets U.S. EPA Tier 4 Final emission standards
and CARB certified for non-road mobile
applications at all 60 Hz ratings
Meets ISO 8528-5 transient response
Single point access to accessory connections
UL 1446 recognized Class H insulation
Sound levels are 72 dB(A) or less at 7 meters
per SAE J1074 measurement procedure at
110% prime load
110% spill containment of onboard engine fluids
heavy-duty diesel engine meets
Tier 4 Final emission standards
100-amp charging alternator
Three-phase, random wound, coastal insulation
protection, 0.6667 pitch, permanent magnet
excited, Class H insulation with Class F
temperature rise
anti-condensation heaters (120/240V
1.2 kW)
.
board (480V)