Salient Characteristics.xlsx
XLSX spreadsheet 21 KB Posted
- Attached to
- 6115--Mobile Diesel Generator
- Solicitation number
- 36C25026Q0918
About this file
This is a salient characteristics specification document for a 500kW mobile diesel generator procurement by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10 under Solicitation Number 36C25026Q0918.
The generator must meet specific technical and operational requirements including 60Hz multipower voltage output capabilities (480/277V, 240/139V, and 208/120V). The equipment must comply with U.S. EPA Tier 4 Final emission standards and obtain CARB certification for non-road mobile applications at all 60Hz ratings, while also meeting ISO 8528-5 transient response standards. The generator must feature a heavy-duty diesel engine with a 100-amp charging alternator, three-phase random wound stator with coastal insulation protection, permanent magnet excitation, and Class H insulation with Class F temperature rise. Additional requirements include single-point access to accessory connections, UL 1446 recognized Class H insulation, sound levels not exceeding 72 dB(A) at seven meters per SAE J1074 measurement procedures at 110% prime load, 110% spill containment capacity for onboard engine fluids, and anti-condensation heaters rated at 120/240V, 1.2kW. Vendors may submit brand-name equipment or approved equal alternatives meeting all specified salient characteristics.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25026Q0918_1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Salient
SALIENT CHARACTERISTICS OF SELECT ITEMS FOR EVALUATION PURPOSES
| COLOR TV 47 IN | Pass/Fail | ||
| Item | Brand/Model Or Equal | Minimum Salient Characteristic(s) | |
| 500kw mobile generator | 500kw | ||
| 60hz | |||
| mutivoltage output 480/277, 240/139,208/120 | |||
| Meets U.S. EPA Tier 4 Final emission standards | |||
| and CARB certified for non-road mobile | |||
| applications at all 60 Hz ratings | |||
| Meets ISO 8528-5 transient response | |||
| Single point access to accessory connections | |||
| UL 1446 recognized Class H insulation | |||
| Sound levels are 72 dB(A) or less at 7 meters | |||
| per SAE J1074 measurement procedure at | |||
| 110% prime load | |||
| 110% spill containment of onboard engine fluids | |||
| heavy-duty diesel engine meets | |||
| Tier 4 Final emission standards | |||
| 100-amp charging alternator | |||
| Three-phase, random wound, coastal insulation | |||
| protection, 0.6667 pitch, permanent magnet | |||
| excited, Class H insulation with Class F | |||
| temperature rise | |||
| anti-condensation heaters (120/240V | |||
| 1.2 kW) | |||
| . | |||
| board (480V) |