This document is a Salient Characteristics specification for the procurement of four (4) ISO-rated shipping containers with dimensions of 20 feet by 8 feet by 8.5 feet (or equal). Project #384-340 specifies minimal required capabilities and features for these containers, which must be insulated with finished interior walls, overhead lighting, 120-volt surface-mounted wall outlets, an HVAC unit, and two steel fire-rated man doors (one on the long side and one on the end). All electrical components must comply with National Electrical Code (NEC) standards.
The specification imposes strict safety and certification requirements, mandating that the HVAC unit be inspected and certified by a Nationally Recognized Testing Laboratory (NRTL) authorized by OSHA to conform to Code of Federal Regulations Title 29, Part 1910, Subparts O and S. Contractors must provide two hard copies of NRTL certification reports for all four containers. The contractor must furnish two hard copies of comprehensive manufacturer operation, maintenance, and repair manuals bound in three-ring binders, including mechanical and electrical schematics suitable for journeymen-level troubleshooting, in English language and imperial units of measure (applicable to the HVAC unit only). A manufacturer's standard commercial warranty of one year commencing from the date of acceptance must be provided in two hard copies, with all warranty work performed by a factory-authorized distributor. The contract terms and conditions take precedence over any conflicting manufacturer warranty terms.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SPMYM226Q7254 ISO CONTAINER.pdf | ||
| SPMYM226Q7254 SF 30.pdf | ||
| Shop Drawing_2.24.26.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Salient Characteristics for Containers (Qty: 4) Project #384-340
26 Jan 2026
1. Scope - Containers (Qty: 4) (W&K Container, 20 ft x 8 ft x 8 ½ ft, or equal). The containers shall include the following minimal capabilities/features/items:
a. ISO rated container
b. 20 ft x 8 ft x 8 ½ ft
c. Insulated
d. Interior wall finished
e. Overhead lighting (the electrical power panel/wiring/components of the lighting system shall meet all NEC, etc. codes
f. Surface mounted wall outlets 120v (the electrical power panel/wiring/components of the wall outlet system shall meet all NEC, etc. codes)
g. HVAC unit (must meet NRTL requirements as outlined in paragraph #2 of this salient characteristics listing
h. Steel fire rated man doors (one located on the long side of the container and one door located on the end).
2. Safety Requirement - The equipment and its component parts shall be in compliance with applicable Code of Federal Regulations (CFR) Title 29, Part 1910. By definition, any equipment will be deemed acceptable and approved by TRF, Bangor, if it meets specific Occupational Safety and Health Administration (OSHA) conditions outlined in CFR Title 29, Part 1910; Subparts "O" and "S". Specifically, equipment will be
"Accepted" by TRF, Bangor, if it has been inspected and found by a Nationally Recognized Testing
Laboratory (NRTL) to conform to specified plans or procedures of applicable codes. The equipment (as a whole system) shall be Nationally Recognized Testing Laboratory (NRTL) inspected and certified (by an
OSHA authorized third party), for the HVAC unit only. Two (2) “hard” copies (for all four containers) of the NRTL certification report shall be provided. If the equipment type/model has already been NRTL inspected and certified, a certification report (two (2) ”hard” copies) or documentation mounted on the equipment, (which acknowledges it is NRTL certified), shall be provided. NOTE: This applies only to the HVAC unit.
3. Operator / Maintenance / Repair Manuals - The equipment shall be furnished with two (2) “hard” copies (for all four containers) of the manufacturer’s standard Product Manual/Operation, Maintenance, and Repair Manual(s), bound in durable three ring binder(s). The manuals shall include all mechanical and electrical schematics showing discrete components/block diagrams/wiring diagrams with inputs and outputs identified/system electrical interface documents and drawings for the specific model of the HVAC unit. The information contained in the manual(s) shall reflect the unit and its components in the “as built” configuration. The information contained in the manual(s) shall be adequate to permit trouble shooting and repair of the equipment by journeymen level personnel. The information contained in the manual(s) shall be in the English language. The information contained in the manual(s) shall be in imperial units of measure. NOTE: This applies only to the HVAC unit only
4. Warranty - Two (2) “hard” copies (for all four containers) of the warranty certificate shall be provided.
Supplies and services furnished shall be covered by warranty from defects in design, materials and workmanship. The warranty shall be the manufacturer’s standard commercial warranty, which shall conform to all the requirements of the contract. Acceptance of the manufacturer’s standard commercial warranty shall not minimize the rights of the government under clauses in the contract, and in any conflict that arises between the terms and conditions of the contract and manufacturer’s warranty, the terms and conditions of the contract shall take precedence. The warranty period shall be for 1 year. The warranty period shall commence from the date of acceptance. All warranty work shall be provided by a factory authorized distributor.