Salient Characteristics.pdf

PDF 137 KB Posted

Attached to
Generator/Parts
Solicitation number
FA469024Q0060
Issued by

About this file

This document is the Salient Characteristics for a 100kW diesel generator (C100D6C) being procured under federal solicitation FA469024Q0060. The generator has a standby power rating, is EPA Tier 3 certified, and includes a sound-attenuated enclosure, dual wall fuel tank, and other features.

The solicitation is for the supply and delivery of the generator and related parts, issued by the 28th Contracting Squadron at Ellsworth AFB, South Dakota. It is a 100% Small Business set-aside under NAICS code 335312, with a size standard of 1,250 employees. Quotes are due by 4 September 2024 and must be valid until 30 September 2024. The award will be based on the criteria in the solicitation. Questions are due by 28 August 2024, with responses posted by 30 August 2024.

View the file

Other files

File Type Posted
Standard Form 1449 - Solicitation - FA469024Q0060.pdf PDF
Brand Name Justification.pdf PDF
Parts List.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salient Characteris cs

C100D6C Diesel Genset, 60Hz, 100kW 1 USD 44648.75

U.S. EPA, Sta onary Emergency Applica on

C100D6C, Diesel Genset, 60Hz, 100kW

Duty Ra ng - Standby Power (ESP)

Emission Cer fica on, EPA, Tier 3, NSPS CI Sta onary Emergency

Lis ng - UL 2200

Warning - Low Coolant Level

NFPA 110 Type 10 Level 1 Capable

Exciter/Reg - Torque Match

Voltage - 120/208, 3 Phase, Wye, 4 Wire

Alternator - 60Hz, 12L, 208/120V, 120C, 40C Ambient

Aluminum Sound A enuated Winter Enclosure, with Exhaust System

Enclosure Color - Green, Aluminum

Enclosure - Wind Load 180 MPH, ASCE7-10

Skidbase - Housing Ready

Fuel Tank - Regional, Dual Wall, Sub Base, 72 Hour Minimum

High Fuel Level Alarm Panel

Fuel Water Separator

High Fuel Level Switch, 90%

Low Fuel Level Switch, 40%

Mechanical Fuel Gauge

5 Gallon Lockable Spill Containment Fuel Fill Box

Switch - Fuel Tank, Rupture Basin

Control Moun ng - Le Facing

Power Command 1.1 Controller

Gauge - Oil Pressure

Analog Meters - AC Output

Stop Switch - Emergency

Control Display Language - English

Load Connec on - Single

Circuit Breaker, Loca on A, 200A - 600A, 3P, LSI, 600 Volts AC, 80%, UL

Circuit Breaker or Terminal Box (Posi on B)-None

Circuit Breaker or Terminal Box (Posi on C)-None

Engine Governor - Electronic, Isochronous

Engine Starter - 12 Volt DC Motor

Engine Exhaust Connec on-None

Engine Air Cleaner - Normal Duty

Ba ery Charging Alternator

Ba ery Charger - 6 Amp, Regulated

Engine Cooling - Radiator, High Ambient Air Temperature, Ship Fi ed

Extension - Coolant Drain

Engine Coolant - 50% An freeze, 50% Water Mixture

Engine Oil Heater - 120 Volts AC, Single Phase

Coolant Heater, Extreme Cold Ambient

Engine Oil

Genset Warranty - 2 Years Base

Literature - English

Packing - Skid, Poly Bag

Larger Ba ery Rack

DC Powered Lights Inside Enclosure

Enclosure - Heater, Internal

Extension - Oil Drain

Panel, Distribu on

Green Sound Level 2 Intake Baffle - Ship Loose

Sound Level2 Baffle, Shipped Loose 1