Salient Characteristics.docx

DOCX document 15 KB Posted

Attached to
Explosion-Proof window air conditioning unit
Solicitation number
FA480124Q0442
Issued by

About this file

This document is a set of Salient Characteristics for furnishing four (4) window air conditioners to Building 806 at Holloman AFB, New Mexico. The units must have a cooling capacity of 24,000 BTU/Hr, be compatible for use in hazardous material storage areas, and meet National Electrical Code requirements for Class 1, Division 2 and Class 1, Zone 2 hazardous locations. No installation work is required.

The related federal contract opportunity is Solicitation FA480124Q0442 issued by the Department of the Air Force Air Combat Command to purchase the explosion-proof window air conditioning units described in the Salient Characteristics document. The solicitation closes for questions on June 18, 2024 at 12:00 PM MST. Vendors must submit quotes that meet the criteria outlined in the attachments.

View the file

Other files

File Type Posted
Combo -Explosion proof AC units.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SALIENT CHARACTERISTICS

FURNISH WINDOW AIR CONDITIONERS, BLDG 806

June 4, 2024

SCOPE OF WORK:

1. The Contractor shall furnish and deliver four (4) window air conditioners to Bldg 806. The address is as follows: 1204 Wagner Street, Holloman AFB, NM 88330.

2. The units shall have the following specifications:

Cooling Capacity, Btu/Hr: 24,000 Heating Capacity: None required.

Volts Rated: 230/208 Cooling Amps: 11.8 Cooling Capacity, KW: 6.8 Volts-Amps: 250V-20 Energy Efficiency Ratio, EER: 9.7/8.5 Air Circulation, CFM: 385 Refrigerant: R-410A

3. The A/C units must be compatible for use in hazardous material storage areas. This includes enclosed storage rooms containing volatile and flammable liquids and gases, and storage rooms under extreme temperatures.

4. The units must be rated for the conditions listed below.

Hazardous Location Classes: Gases National Electrical Code, NFPA 70 ARTICLE 501: Class 1, Division 2, Group A / B / C / D, Temperature Class T4 ARTICLE 505: Class 1, Zone 2, Group II C / II B / II A, Temperature Class T4

5. No installation work is required.