Salient Characteristics_24QB106.pdf
PDF 285 KB Posted
- Attached to
- Dual Vertical Inline Water Pump
- Solicitation number
- FA252124QB106
About this file
This document appears to be a set of salient characteristics for the replacement of a dual vertical inline condensing water pump at the Patrick Space Force Base dining hall, building 350. The current pump has worn seals, and the replacement pump is required to maintain air conditioning operations at the dining hall which serves dormitory residents.
The key details for the replacement pump include a required flow rate of 300 gpm, a head height of 70 ft, a working pressure of 150 psig, a pump speed of 1750 rpm, a 10 HP motor with NEMA Premium efficiency, and a vertical casing type. The replacement pump must have an integrated fused disconnect and meet other specified dimensions and connection requirements.
This salient characteristics document is associated with Solicitation Number FA252124QB106 issued by the Department of the Air Force Space Command for the replacement of the dual vertical inline condensing water pump.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Questions and answers for FA252124QB106.pdf | ||
| Solicitation-FA252124QB106.pdf | ||
| brandname_justification_24QB106.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PATRICK SPACE FORCE DINING HALL DUAL VERTICAL INLINE
CONDENSING WATER PUMP REPLACEMENT, B350
Mazzone, Rocky Rocky.mazzone.1@spaceforce.mil
Abstract Salient Characteristics for Replacement of Condensing Water Pump
NEED/ REQUEST FOR DINING HALL CONDENSING WATER PUMP
REPLACEMENT
The request for a dual vertical inline condensing water pump and hardware, is required to maintain air conditioning operations at the dining hall, building 350. The current pump has worn seals. The condensing water pump provides necessary equipment and comfort cooling to the dining hall. The dormitory residents are highly encouraged to eat meals there.
COMMODITY REPLACEMENT
A condensing water pump is used to circulate chilled water to remove heat from the chiller.
SALIENT CHARACTRERISTIC
Casing Type: Vertical Flow Rate: 300 gpm Head Height: 70 ft.
Working Pressure: 150 psig Pump Speed: 1750 rpm Motor Type: Inverter Motor Efficiency: NEMA Premium 12.12 Motor Insulation Type: Class F Motor Voltage: 460/230 VAC Phase: 3 Frequency: 60 Hz Motor Power: 10 hp Flange to Flange Length: 36” Flange Diameter: 11” Bolt Circle Diameter: 9.5” Bolt Pattern: 8
Bolt Diameter: 3/4” Inlet and Outlet Connection Size: 6” Fused Disconnect: Integrated Fused Disconnect