Salient Characteristics
Purchase the following replacement parts to replace powerboard Building 1-1434 and associated hardware. This equipment support the DC power system utilized within the network.
| Description |
| Quantity |
Replacement Powerboards:
Type of powerboard: Vertiv NetSure 7100 or equivalent w/9 3500 rectifiers, that provide up to 4000 amps of current for -48 volt systems with up to 520 amps at +24 volts.
| Integrate existing Thermal Sensing Units (TSU) into powerboards for temperature and humidity monitoring. |
| 1 |
Battery Replacement: (3 String 72 Cells) Integrate the new and existing battery strings into the new powerboard
The contractor shall:
Warrant no less than one (1) year from the date of purchase Arrange for pick up and disposal of batteries by a certified recycler Ship to Fort Bragg NEC – Service Operations Branch