S06-36C25224Q0509 0001.docx
DOCX document 5 MB Posted
- Attached to
- Amendment 0001--RFQ: Fuel Storage Tanks-Inspection/Testing/Cleaning Services Federal contract opportunity
- Solicitation number
- 36C25224Q0509_0001
About this file
This document is a solicitation amendment for a Request for Quote (RFQ) for Fuel Storage Tanks-Inspection/Testing/Cleaning Services. The amendment addresses vendor questions with answers from the contracting office. Key details include:
The solicitation number is 36C25224Q0509. The contracting agency is the Department of Veterans Affairs, Veterans Health Administration, Veterans Integrated Service Network 12. The solicitation is for inspection, testing, and cleaning services for various fuel storage tanks (diesel, gasoline, E-85) located at the Danville VA Medical Center. Tank sizes range from 300 to 15,000 gallons. The original quote due date is not extended. Vendors should refer to the original solicitation for submission requirements and the quote due date.
View the file
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE
7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office.
is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer)
36C252 Department of Veterans Affairs
GLAC (69D)
115 South 84th Street, Suite 101
Milwaukee WI 53214-1476
36C252 Department of Veterans Affairs
GLAC-MILWAUKEE (69D)
Great Lakes Acquisition Center - HC 115 South 84th Street, Suite 101 Milwaukee WI 53214-1476 To all Offerors/Bidders
36C25224Q0509 07-24-2024
X
X
See CONTINUATION Page one This amendment addresses vendor questions with answers from the contracting office.
The original due date of the solicitation is not extended.
Please see solicitation 36C25224Q0509 for the quote due date as well as to view submission requirements.
See continuation pages.
Sands, Scott Contracting Officer
Vendor Questions & Answers Q: What are the tank contents? Please be specific.
A: Bldg. 14 diesel AST 650-gal tank, Bldg. 98 diesel UST 4,000-gal tank, Bldg. 58 diesel 8,550-gal AST tank, Bldg. 104 diesel 8,000-gal UST tank, Bldg. 128/129 diesel 300-gal AST tank, Bldg. 130 diesel 375-gal AST tank, Bldg. 131 diesel 375-gal AST tank, Bldg. 132/133 diesel 1,400-gal AST tank, Bldg. 140 diesel 1,495-gal AST tank, Bldg. 211 diesel 15,000-gal UST tank, Bldg. 212 diesel 10,00-gal UST tank, Bldg. 214 diesel 6,000-gal UST tank, Bldg. 216 diesel 6,000-gal UST tank, GSA lot diesel 5,000-gal UST tank Gas 4,000-gal UST E-85 4,000-gal UST Q: What are the tank sizes in height and diameter?
A: We have no exact dimensions to the USTs, ASTs but exact gallon sizes are listed above.
Q: What is the size of the manway on the top of the tanks?
A: No manways on the tanks.
Q: Are you wanting the SP001/API-653 internal and/or external portion of the tank inspected?
A: Yes, on the AST’s
Q: Do you have any previous inspection reports of the tanks? If so, can they be shared for viewing?
A: See files below-
Q: Are blueprints of the tanks available? If so, can they be shared for viewing?
A: No, they are not available.
Q: Is there a current contract for the work being solicited? If so, please provide that awarded contract number or task order number.
A: Previous contract # 36C25220C0003 can be found at FPDS (https://www.fpds.gov/).
Q: When was the last time the tanks and fuel were filtered and tested?
A: April 2023 Q: Can a copy of the most recent lab reports on the fuel be provided?
A: See files previously listed.
Q: Line Items 0005, 1005, 2004, 3004, 4005 requests pricing for: “Additional cost to remove sediment, water, sludge over 1" per tank on fourteen (14) UST and AST with COR verification in accordance with the SOW.” I do not see anything regarding sludge over 1” in the SOW. Are you aware of excessive sludge in any of the tanks? Please explain this line item.
A: This has been added to allow for cleaning above and beyond normal cleaning but has never been a factor.
Q: What company has performed previous UST testing services for this location?
A: Information regarding previous contract # 36C25220C0003 can be found at FPDS (https://www.fpds.gov/).
Amendment 0001-Vendor Questions & Answers to Solicitation # 36C25224Q0509 3-4-2854328_XN (2).pdf
- 1 -
ĆUSTOMER: CLEAN FUELS NATIONAL
PLANT: DANVILLE VA
FUEL BLDG 214
LOCATION
FUEL TYPE: ULS #2 DIESEL FUEL
MANUFACTURER: Missing information
RECEIVED: 02-NOV-22
CONTACT 1: LACIE SAUER
REPORT: 09-NOV-22 13:37:05
SAMPLE NO: 3641-61-3-4
PO NUMBER: 60263
Spec Compliance
COMPLIANT
NOTE
• All limits derived from ASTM/CGSB specifications
Date(DD/MM/YY) 01-11-22 SPEC.
Labno 2854328
VISCOSITY /40 [ASTM D445] in cSt 40°C 2.43 1.9-4.1
WATER KARL FISHER (%) 0.005 0.02 MAX
FLASH POINT CLOSED CUP [ASTM D93] 63 125.6 °F MIN
DENSITY [ASTM D4052] 0.818 REPORT
DISTILLATION
Initial Boiling Point (°F) 351 - 10% Recovered (°F) 399 - 50% Recovered (°F) 490 510.8 TYPICAL 90% Recovered (°F) 595 539.6-640.4 Final Boiling Point (°F) - Total Recovered (°F) - Residue (%) -
API GRAVITY [ASTM D287] 41.55 34-38 TYPICAL
SULFUR in ppm 12 15 MAX
CETANE INDEX 67 40 MIN
POUR POINT [ASTM D97] , °F - REPORT
CLOUD POINT [ASTM D2500] , °F -9 REPORT
COPPER CORROSION [ASTM D130] - 3
ASH (%) [ASTM D482] - 0.01 MAX
WATER AND SEDIMENT (%) [ASTM D2709] - 0.05 MAX
TOTAL BACTERIA/MOLD KIT TEST 0 0 MAX
BIODIESEL CONTENT (%) 1.200 5.000 MAX
CETANE NUMBER [D 613] - 40 MIN
OXIDATION STABILITY [ASTM D7545] - REPORT
CARBON RESIDUE - 0.35 MAX
PARTICLE COUNT
>4 589 2500 MAX
>6 97 640 MAX
>14 30 80 MAX
>25 6 - >50 0 - >100 0 -
ISO 4406 16/ 14/ 12 18/16/13
BLDG 214
(SP) SPECTROSCOPIC ANALYSIS [ASTM D5185] (elements seen in ppm) TESTED ELEMENTS ARE: Fe, Cu, Pb, Sn, Cr, Al, Ni, Ti, Ag, V, Mg, Si, B, Na, Ba, Ca, P, Mn, Zn, Mo, Cd, K *
* elements below detection limit are not displayed on table Date(MM/DD/YY) 11-01-22 09-10-21 08-25-21 06-23-21 (n/a) (n/a) (n/a) (n/a) REF
Labno 2854328 2752051 2747504 2731116 Si-SILICON 1.0 - Mg-MAGNESIUM 1.0 - Na-SODIUM 2.0 -
P-PHOSPHORUS 4.0 -
CLEAN FUELS NATIONAL assumes sole responsibility for the total copy, reproduction, application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance. Fixed limits programmed according to laboratory or client specifications. Report indicates tests performed only and are approved and released under the authority of chemist number 1026.
BLDG 214
image3.emf
1-4-2854327_XC.pdf
FUEL BLDG 98
LOCATION
FUEL TYPE: ULS #2 DIESEL FUEL
MANUFACTURER: Missing information
RECEIVED: 02-NOV-22
CONTACT 1: LACIE SAUER
REPORT: 09-NOV-22 13:36:54
SAMPLE NO: 3641-61-1-4
NON-COMPLIANT
• Recommend to contact tank cleaning/maintenance firm as soon as possible.
• Particle Count is outside of specifed limit.
• Particles can be removed through tank filtration and cleaning
BLDG 98
Labno 2854327
VISCOSITY /40 [ASTM D445] in cSt 40°C 2.52 1.9-4.1
FLASH POINT CLOSED CUP [ASTM D93] 131 125.6 °F MIN
DENSITY [ASTM D4052] 0.830 REPORT
Initial Boiling Point (°F) 325 - 10% Recovered (°F) 380 - 50% Recovered (°F) 473 510.8 TYPICAL 90% Recovered (°F) 592 539.6-640.4 Final Boiling Point (°F) -
API GRAVITY [ASTM D287] 38.90 34-38 TYPICAL
SULFUR in ppm 8 15 MAX
CETANE INDEX 64 40 MIN
POUR POINT [ASTM D97] , °F - REPORT
CLOUD POINT [ASTM D2500] , °F -12 REPORT
COPPER CORROSION [ASTM D130] - 3
ASH (%) [ASTM D482] - 0.01 MAX
WATER AND SEDIMENT (%) [ASTM D2709] - 0.05 MAX
TOTAL BACTERIA/MOLD KIT TEST 0 0 MAX
BIODIESEL CONTENT (%) 1.200 5.000 MAX
CETANE NUMBER [D 613] - 40 MIN
OXIDATION STABILITY [ASTM D7545] - REPORT
>4 6319 2500 MAX
>6 548 640 MAX
>14 3 80 MAX
>25 0 - >50 0 -
ISO 4406 20/ 16/ 9 18/16/13
TESTED ELEMENTS ARE: Fe, Cu, Pb, Sn, Cr, Al, Ni, Ti, Ag, V, Mg, Si, B, Na, Ba, Ca, P, Mn, Zn, Mo, Cd, K *
Labno 2854327 2752053 2747507 2731108
P-PHOSPHORUS 1.0 -
CLEAN FUELS NATIONAL assumes sole responsibility for the total copy, reproduction, application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance. Fixed limits programmed according to laboratory or client specifications. Report indicates tests performed only and are approved and released under the authority of chemist number 1026.
image4.emf
7-2-2854324_XN (1).pdf
FUEL BLDG 130
LOCATION
FUEL TYPE: ULS #2 DIESEL FUEL
MANUFACTURER: Missing information
RECEIVED: 02-NOV-22
CONTACT 1: LACIE SAUER
REPORT: 09-NOV-22 13:36:16
SAMPLE NO: 3641-61-7-2
PO NUMBER: 60262
Labno 2854324
VISCOSITY /40 [ASTM D445] in cSt 40°C 2.79 1.9-4.1
FLASH POINT CLOSED CUP [ASTM D93] 145 125.6 °F MIN
DENSITY [ASTM D4052] 0.847 REPORT
Initial Boiling Point (°F) 370 - 10% Recovered (°F) 390 - 50% Recovered (°F) 486 510.8 TYPICAL 90% Recovered (°F) 600 539.6-640.4 Final Boiling Point (°F) -
API GRAVITY [ASTM D287] 35.56 34-38 TYPICAL
SULFUR in ppm 14 15 MAX
CETANE INDEX 57 40 MIN
POUR POINT [ASTM D97] , °F - REPORT
CLOUD POINT [ASTM D2500] , °F -11 REPORT
COPPER CORROSION [ASTM D130] - 3
ASH (%) [ASTM D482] - 0.01 MAX
WATER AND SEDIMENT (%) [ASTM D2709] - 0.05 MAX
TOTAL BACTERIA/MOLD KIT TEST 0 0 MAX
BIODIESEL CONTENT (%) 1.000 5.000 MAX
CETANE NUMBER [D 613] - 40 MIN
OXIDATION STABILITY [ASTM D7545] - REPORT
>4 123 2500 MAX
>6 36 640 MAX
>14 10 80 MAX
>25 0 - >50 0 -
ISO 4406 14/ 12/ 10 18/16/13
BLDG 130
TESTED ELEMENTS ARE: Fe, Cu, Pb, Sn, Cr, Al, Ni, Ti, Ag, V, Mg, Si, B, Na, Ba, Ca, P, Mn, Zn, Mo, Cd, K *
Date(MM/DD/YY) 11-01-22 06-23-21 (n/a) (n/a) (n/a) (n/a) (n/a) (n/a) REF
Labno 2854324 2731131
P-PHOSPHORUS 3.0 -
CLEAN FUELS NATIONAL assumes sole responsibility for the total copy, reproduction, application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance. Fixed limits programmed according to laboratory or client specifications. Report indicates tests performed only and are approved and released under the authority of chemist number 1026.
BLDG 130
image5.emf
5-2-2854323_XN (1).pdf
FUEL BLDG 131 AST
LOCATION
FUEL TYPE: ULS #2 DIESEL FUEL
MANUFACTURER: Missing information
RECEIVED: 02-NOV-22
CONTACT 1: LACIE SAUER
REPORT: 09-NOV-22 13:36:05
SAMPLE NO: 3641-61-5-2
Labno 2854323
VISCOSITY /40 [ASTM D445] in cSt 40°C 2.74 1.9-4.1
WATER KARL FISHER (%) 0.006 0.02 MAX
FLASH POINT CLOSED CUP [ASTM D93] 143 125.6 °F MIN
DENSITY [ASTM D4052] 0.844 REPORT
Initial Boiling Point (°F) 347 - 10% Recovered (°F) 405 - 50% Recovered (°F) 496 510.8 TYPICAL 90% Recovered (°F) 603 539.6-640.4 Final Boiling Point (°F) -
API GRAVITY [ASTM D287] 36.17 34-38 TYPICAL
SULFUR in ppm 13 15 MAX
CETANE INDEX 57 40 MIN
POUR POINT [ASTM D97] , °F - REPORT
CLOUD POINT [ASTM D2500] , °F -12 REPORT
COPPER CORROSION [ASTM D130] - 3
ASH (%) [ASTM D482] - 0.01 MAX
WATER AND SEDIMENT (%) [ASTM D2709] - 0.05 MAX
TOTAL BACTERIA/MOLD KIT TEST 0 0 MAX
BIODIESEL CONTENT (%) 1.700 5.000 MAX
CETANE NUMBER [D 613] - 40 MIN
OXIDATION STABILITY [ASTM D7545] - REPORT
>4 191 2500 MAX
>6 51 640 MAX
>14 13 80 MAX
>25 0 - >50 0 -
ISO 4406 15/ 13/ 11 18/16/13
BLDG 131 AST
TESTED ELEMENTS ARE: Fe, Cu, Pb, Sn, Cr, Al, Ni, Ti, Ag, V, Mg, Si, B, Na, Ba, Ca, P, Mn, Zn, Mo, Cd, K *
Date(MM/DD/YY) 11-01-22 06-23-21 (n/a) (n/a) (n/a) (n/a) (n/a) (n/a) REF
Labno 2854323 2731129
Mg-MAGNESIUM 2.0 - Na-SODIUM 2.0 - Ca-CALCIUM 1.0 -
CLEAN FUELS NATIONAL assumes sole responsibility for the total copy, reproduction, application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance. Fixed limits programmed according to laboratory or client specifications. Report indicates tests performed only and are approved and released under the authority of chemist number 1026.
BLDG 131 AST
image6.emf
8-3-2854331_XN.pdf
FUEL BLDG 216 UST
LOCATION
FUEL TYPE: ULS #2 DIESEL FUEL
MANUFACTURER: Missing information
RECEIVED: 02-NOV-22
CONTACT 1: LACIE SAUER
REPORT: 09-NOV-22 13:37:43
SAMPLE NO: 3641-61-8-3
Labno 2854331
VISCOSITY /40 [ASTM D445] in cSt 40°C 2.87 1.9-4.1
WATER KARL FISHER (%) 0.007 0.02 MAX
FLASH POINT CLOSED CUP [ASTM D93] 61 125.6 °F MIN
DENSITY [ASTM D4052] 0.822 REPORT
Initial Boiling Point (°F) 336 -
50% Recovered (°F) 496 510.8 TYPICAL 90% Recovered (°F) 596 539.6-640.4 Final Boiling Point (°F) -
API GRAVITY [ASTM D287] 40.75 34-38 TYPICAL
SULFUR in ppm 15 15 MAX
CETANE INDEX 65 40 MIN
POUR POINT [ASTM D97] , °F - REPORT
CLOUD POINT [ASTM D2500] , °F -13 REPORT
COPPER CORROSION [ASTM D130] - 3
ASH (%) [ASTM D482] - 0.01 MAX
WATER AND SEDIMENT (%) [ASTM D2709] - 0.05 MAX
TOTAL BACTERIA/MOLD KIT TEST 0 0 MAX
BIODIESEL CONTENT (%) 1.800 5.000 MAX
CETANE NUMBER [D 613] - 40 MIN
OXIDATION STABILITY [ASTM D7545] - REPORT
>4 485 2500 MAX
>6 205 640 MAX
>14 33 80 MAX
>25 3 - >50 3 -
ISO 4406 16/ 15/ 12 18/16/13
BLDG 216 UST
TESTED ELEMENTS ARE: Fe, Cu, Pb, Sn, Cr, Al, Ni, Ti, Ag, V, Mg, Si, B, Na, Ba, Ca, P, Mn, Zn, Mo, Cd, K *
Date(MM/DD/YY) 11-01-22 09-10-21 06-23-21 (n/a) (n/a) (n/a) (n/a) (n/a) REF
Labno 2854331 2752055 2731132
CLEAN FUELS NATIONAL assumes sole responsibility for the total copy, reproduction, application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance. Fixed limits programmed according to laboratory or client specifications. Report indicates tests performed only and are approved and released under the authority of chemist number 1026.
BLDG 216 UST
image7.emf
9-4-2854332_XN.pdf
FUEL BLDG 211 UST
LOCATION
FUEL TYPE: ULS #2 DIESEL FUEL
MANUFACTURER: Missing information
RECEIVED: 02-NOV-22
CONTACT 1: LACIE SAUER
REPORT: 09-NOV-22 13:37:58
SAMPLE NO: 3641-61-9-4
Labno 2854332
VISCOSITY /40 [ASTM D445] in cSt 40°C 3.05 1.9-4.1
FLASH POINT CLOSED CUP [ASTM D93] 62 125.6 °F MIN
DENSITY [ASTM D4052] 0.833 REPORT
Initial Boiling Point (°F) 359 -
50% Recovered (°F) 489 510.8 TYPICAL 90% Recovered (°F) 590 539.6-640.4 Final Boiling Point (°F) -
API GRAVITY [ASTM D287] 38.37 34-38 TYPICAL
SULFUR in ppm 13 15 MAX
CETANE INDEX 61 40 MIN
POUR POINT [ASTM D97] , °F - REPORT
CLOUD POINT [ASTM D2500] , °F -10 REPORT
COPPER CORROSION [ASTM D130] - 3
ASH (%) [ASTM D482] - 0.01 MAX
WATER AND SEDIMENT (%) [ASTM D2709] - 0.05 MAX
TOTAL BACTERIA/MOLD KIT TEST 0 0 MAX
BIODIESEL CONTENT (%) 1.600 5.000 MAX
CETANE NUMBER [D 613] - 40 MIN
OXIDATION STABILITY [ASTM D7545] - REPORT
>4 740 2500 MAX
>6 218 640 MAX
>14 17 80 MAX
>25 3 - >50 0 -
ISO 4406 17/ 15/ 11 18/16/13
BLDG 211 UST
TESTED ELEMENTS ARE: Fe, Cu, Pb, Sn, Cr, Al, Ni, Ti, Ag, V, Mg, Si, B, Na, Ba, Ca, P, Mn, Zn, Mo, Cd, K *
Labno 2854332 2752052 2747506 2731123
CLEAN FUELS NATIONAL assumes sole responsibility for the total copy, reproduction, application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance. Fixed limits programmed according to laboratory or client specifications. Report indicates tests performed only and are approved and released under the authority of chemist number 1026.
BLDG 211 UST
image8.emf
20-3-2854333_XC.pdf
FUEL BLDG 104
LOCATION
FUEL TYPE: ULS #2 DIESEL FUEL
MANUFACTURER: Missing information
RECEIVED: 02-NOV-22
CONTACT 1: LACIE SAUER
REPORT: 09-NOV-22 13:38:09
SAMPLE NO: 3641-61-20-3
• Sulfur is outside specified limit.
• Sulfur content should be discussed with diesel fuel supplier.
BLDG 104
Labno 2854333
VISCOSITY /40 [ASTM D445] in cSt 40°C 2.79 1.9-4.1
FLASH POINT CLOSED CUP [ASTM D93] 140 125.6 °F MIN
DENSITY [ASTM D4052] 0.836 REPORT
Initial Boiling Point (°F) 338 - 10% Recovered (°F) 407 - 50% Recovered (°F) 496 510.8 TYPICAL 90% Recovered (°F) 598 539.6-640.4 Final Boiling Point (°F) -
API GRAVITY [ASTM D287] 37.82 34-38 TYPICAL
SULFUR in ppm 18 15 MAX
CETANE INDEX 60 40 MIN
POUR POINT [ASTM D97] , °F - REPORT
CLOUD POINT [ASTM D2500] , °F -12 REPORT
COPPER CORROSION [ASTM D130] - 3
ASH (%) [ASTM D482] - 0.01 MAX
WATER AND SEDIMENT (%) [ASTM D2709] - 0.05 MAX
TOTAL BACTERIA/MOLD KIT TEST 0 0 MAX
BIODIESEL CONTENT (%) 1.800 5.000 MAX
CETANE NUMBER [D 613] - 40 MIN
OXIDATION STABILITY [ASTM D7545] - REPORT
>4 434 2500 MAX
>6 119 640 MAX
>14 27 80 MAX
>25 3 - >50 0 -
ISO 4406 16/ 14/ 12 18/16/13
TESTED ELEMENTS ARE: Fe, Cu, Pb, Sn, Cr, Al, Ni, Ti, Ag, V, Mg, Si, B, Na, Ba, Ca, P, Mn, Zn, Mo, Cd, K *
Date(MM/DD/YY) 11-01-22 07-01-21 07-01-21 (n/a) (n/a) (n/a) (n/a) (n/a) REF
Labno 2854333 2733177 2733176 Sn-TIN - 3.0 - Si-SILICON 1.0 - - Ca-CALCIUM - 1.0 -
P-PHOSPHORUS 2.0 2.0 -
CLEAN FUELS NATIONAL assumes sole responsibility for the total copy, reproduction, application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance. Fixed limits programmed according to laboratory or client specifications. Report indicates tests performed only and are approved and released under the authority of chemist number 1026.
BLDG 104
image9.emf
10-3-2854325_XC.pdf
FUEL BLDG 14
LOCATION
FUEL TYPE: ULS #2 DIESEL FUEL
MANUFACTURER: Missing information
RECEIVED: 02-NOV-22
CONTACT 1: LACIE SAUER
REPORT: 09-NOV-22 13:36:28
SAMPLE NO: 3641-61-10-3
• All limits derived from ASTM/CGSB specifications.
• Sulfur and Par ticle Count are outside of specifed limit.
• Sulfur content should be discussed with diesel fuel supplier
• Particulate can be removed through tank filtration and cleaning.
BLDG 14
Labno 2854325
VISCOSITY /40 [ASTM D445] in cSt 40°C 2.74 1.9-4.1
FLASH POINT CLOSED CUP [ASTM D93] 147 125.6 °F MIN
Initial Boiling Point (°F) 356 - 10% Recovered (°F) 405 - 50% Recovered (°F) 492 510.8 TYPICAL 90% Recovered (°F) 595 539.6-640.4 Final Boiling Point (°F) -
API GRAVITY [ASTM D287] 37.82 34-38 TYPICAL
SULFUR in ppm 26 15 MAX
CETANE INDEX 60 40 MIN
POUR POINT [ASTM D97] , °F - REPORT
CLOUD POINT [ASTM D2500] , °F -12 REPORT
COPPER CORROSION [ASTM D130] - 3
ASH (%) [ASTM D482] - 0.01 MAX
WATER AND SEDIMENT (%) [ASTM D2709] - 0.05 MAX
TOTAL BACTERIA/MOLD KIT TEST 0 0 MAX
BIODIESEL CONTENT (%) 1.800 5.000 MAX
CETANE NUMBER [D 613] - 40 MIN
OXIDATION STABILITY [ASTM D7545] - REPORT
>4 45921 2500 MAX
>6 12311 640 MAX
>14 93 80 MAX
>25 3 - >50 0 -
ISO 4406 23/ 21/ 14 18/16/13
TESTED ELEMENTS ARE: Fe, Cu, Pb, Sn, Cr, Al, Ni, Ti, Ag, V, Mg, Si, B, Na, Ba, Ca, P, Mn, Zn, Mo, Cd, K *
Date(MM/DD/YY) 11-01-22 08-25-21 06-23-21 (n/a) (n/a) (n/a) (n/a) (n/a) REF
Labno 2854325 2747505 2731134
P-PHOSPHORUS 2.0 -
CLEAN FUELS NATIONAL assumes sole responsibility for the total copy, reproduction, application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance. Fixed limits programmed according to laboratory or client specifications. Report indicates tests performed only and are approved and released under the authority of chemist number 1026.
image10.emf
2023.01.26 - BLDG_14_4 (2).pdf
FUEL BLDG 14
LOCATION
FUEL TYPE: ULS #2 DIESEL FUEL
MANUFACTURER: Missing information
RECEIVED: 19-JAN-23
CONTACT 1: LACIE SAUER
REPORT: 24-JAN-23 16:23:39
SAMPLE NO: 3641-61-10-4
PO NUMBER: 60422
• All limits derived from ASTM/ CGSB specifications.
• Particle count is outside specified limit.
Date(DD/MM/YY) 17-01-23 SPEC.
Labno 2872635
VISCOSITY /40 [ASTM D445] in cSt 40°C 2.66 1.9-4.1
WATER KARL FISHER (%) 0.004 0.02 MAX
FLASH POINT CLOSED CUP [ASTM D93] 158 125.6 °F MIN
Initial Boiling Point (°F) 348 - 10% Recovered (°F) 391 - 50% Recovered (°F) 493 510.8 TYPICAL 90% Recovered (°F) 606 539.6-640.4 Final Boiling Point (°F) -
API GRAVITY [ASTM D287] 38.43 34-38 TYPICAL
SULFUR in ppm 12 15 MAX
CETANE INDEX 61 40 MIN
POUR POINT [ASTM D97] , °F - REPORT
CLOUD POINT [ASTM D2500] , °F -12 REPORT
COPPER CORROSION [ASTM D130] - 3
ASH (%) [ASTM D482] - 0.01 MAX
WATER AND SEDIMENT (%) [ASTM D2709] - 0.05 MAX
TOTAL BACTERIA/MOLD KIT TEST 0 0 MAX
BIODIESEL CONTENT (%) 0.000 5.000 MAX
CETANE NUMBER [D 613] - 40 MIN
OXIDATION STABILITY [ASTM D7545] - REPORT
>4 6484 2500 MAX
>6 2497 640 MAX
>14 260 80 MAX
>25 30 - >50 0 -
ISO 4406 20/ 18/ 15 18/16/13
TESTED ELEMENTS ARE: Fe, Cu, Pb, Sn, Cr, Al, Ni, Ti, Ag, V, Mg, Si, B, Na, Ba, Ca, P, Mn, Zn, Mo, Cd, K *
Date(MM/DD/YY) 01-17-23 11-01-22 08-25-21 06-23-21 (n/a) (n/a) (n/a) (n/a) REF
Labno 2872635 2854325 2747505 2731134 Si-SILICON 1.0 1.0 -
P-PHOSPHORUS - 2.0 -
Zn-ZINC 1.0 - -
CLEAN FUELS NATIONAL assumes sole responsibility for the total copy, reproduction, application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance. Fixed limits programmed according to laboratory or client specifications. Report indicates tests performed only and are approved and released under the authority of chemist number 1026.
image11.emf
24-1-2854326_XN (2).pdf
FUEL BLDG 128
LOCATION
FUEL TYPE: ULS #2 DIESEL FUEL
MANUFACTURER: Missing information
RECEIVED: 02-NOV-22
CONTACT 1: LACIE SAUER
REPORT: 09-NOV-22 13:36:41
SAMPLE NO: 3641-61-24-1
Labno 2854326
VISCOSITY /40 [ASTM D445] in cSt 40°C 2.61 1.9-4.1
FLASH POINT CLOSED CUP [ASTM D93] 66 125.6 °F MIN
Initial Boiling Point (°F) 370 - 10% Recovered (°F) 403 - 50% Recovered (°F) 484 510.8 TYPICAL 90% Recovered (°F) 589 539.6-640.4 Final Boiling Point (°F) -
API GRAVITY [ASTM D287] 37.80 34-38 TYPICAL
CETANE INDEX 61 40 MIN
POUR POINT [ASTM D97] , °F - REPORT
CLOUD POINT [ASTM D2500] , °F -11 REPORT
COPPER CORROSION [ASTM D130] - 3
ASH (%) [ASTM D482] - 0.01 MAX
WATER AND SEDIMENT (%) [ASTM D2709] - 0.05 MAX
TOTAL BACTERIA/MOLD KIT TEST 0 0 MAX
BIODIESEL CONTENT (%) 1.400 5.000 MAX
CETANE NUMBER [D 613] - 40 MIN
OXIDATION STABILITY [ASTM D7545] - REPORT
>4 1430 2500 MAX
>6 126 640 MAX
>14 10 80 MAX
>25 0 - >50 0 -
ISO 4406 18/ 14/ 10 18/16/13
BLDG 128
TESTED ELEMENTS ARE: Fe, Cu, Pb, Sn, Cr, Al, Ni, Ti, Ag, V, Mg, Si, B, Na, Ba, Ca, P, Mn, Zn, Mo, Cd, K *
Date(MM/DD/YY) 11-01-22 (n/a) (n/a) (n/a) (n/a) (n/a) (n/a) (n/a) REF
Labno 2854326
CLEAN FUELS NATIONAL assumes sole responsibility for the total copy, reproduction, application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance. Fixed limits programmed according to laboratory or client specifications. Report indicates tests performed only and are approved and released under the authority of chemist number 1026.
BLDG 128
image12.emf
2023.01.26 - BLDG_58_4 (1).pdf
FUEL BLDG 58
LOCATION
FUEL TYPE: ULS #2 DIESEL FUEL
MANUFACTURER: Missing information
RECEIVED: 19-JAN-23
CONTACT 1: LACIE SAUER
REPORT: 24-JAN-23 16:22:01
SAMPLE NO: 3641-61-6-4
BLDG 58
Labno 2872634
VISCOSITY /40 [ASTM D445] in cSt 40°C 2.30 1.9-4.1
WATER KARL FISHER (%) 0.007 0.02 MAX
FLASH POINT CLOSED CUP [ASTM D93] 140 125.6 °F MIN
DENSITY [ASTM D4052] 0.834 REPORT
Initial Boiling Point (°F) 334 - 10% Recovered (°F) 374 - 50% Recovered (°F) 474 510.8 TYPICAL 90% Recovered (°F) 579 539.6-640.4 Final Boiling Point (°F) -
API GRAVITY [ASTM D287] 38.21 34-38 TYPICAL
CETANE INDEX 62 40 MIN
POUR POINT [ASTM D97] , °F - REPORT
CLOUD POINT [ASTM D2500] , °F -22 REPORT
COPPER CORROSION [ASTM D130] - 3
ASH (%) [ASTM D482] - 0.01 MAX
WATER AND SEDIMENT (%) [ASTM D2709] - 0.05 MAX
TOTAL BACTERIA/MOLD KIT TEST 0 0 MAX
BIODIESEL CONTENT (%) 1.200 5.000 MAX
CETANE NUMBER [D 613] - 40 MIN
OXIDATION STABILITY [ASTM D7545] - REPORT
>4 8677 2500 MAX
>6 1332 640 MAX
>14 87 80 MAX
>25 20 - >50 0 -
ISO 4406 20/ 18/ 14 18/16/13
TESTED ELEMENTS ARE: Fe, Cu, Pb, Sn, Cr, Al, Ni, Ti, Ag, V, Mg, Si, B, Na, Ba, Ca, P, Mn, Zn, Mo, Cd, K *
Date(MM/DD/YY) 01-17-23 11-01-22 08-25-21 06-23-21 (n/a) (n/a) (n/a) (n/a) REF
Labno 2872634 2854330 2747508 2731119 Sn-TIN 1.0 - - Si-SILICON - 1.0 -
P-PHOSPHORUS - 2.0 -
CLEAN FUELS NATIONAL assumes sole responsibility for the total copy, reproduction, application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance. Fixed limits programmed according to laboratory or client specifications. Report indicates tests performed only and are approved and released under the authority of chemist number 1026.
BLDG 58
image13.emf
2023.01.26 - BLDG_98_5 (1).pdf
FUEL BLDG 98
LOCATION
FUEL TYPE: ULS #2 DIESEL FUEL
MANUFACTURER: Missing information
RECEIVED: 19-JAN-23
CONTACT 1: LACIE SAUER
REPORT: 24-JAN-23 16:21:51
SAMPLE NO: 3641-61-1-5
Labno 2872633
VISCOSITY /40 [ASTM D445] in cSt 40°C 2.32 1.9-4.1
FLASH POINT CLOSED CUP [ASTM D93] 136 125.6 °F MIN
Initial Boiling Point (°F) 324 - 10% Recovered (°F) 388 - 50% Recovered (°F) 479 510.8 TYPICAL 90% Recovered (°F) 602 539.6-640.4 Final Boiling Point (°F) -
API GRAVITY [ASTM D287] 38.41 34-38 TYPICAL
CETANE INDEX 62 40 MIN
POUR POINT [ASTM D97] , °F - REPORT
CLOUD POINT [ASTM D2500] , °F -18 REPORT
COPPER CORROSION [ASTM D130] - 3
ASH (%) [ASTM D482] - 0.01 MAX
WATER AND SEDIMENT (%) [ASTM D2709] - 0.05 MAX
TOTAL BACTERIA/MOLD KIT TEST 0 0 MAX
BIODIESEL CONTENT (%) 0.000 5.000 MAX
CETANE NUMBER [D 613] - 40 MIN
OXIDATION STABILITY [ASTM D7545] - REPORT
>4 12077 2500 MAX
>6 2320 640 MAX
>14 154 80 MAX
>25 23 - >50 0 -
ISO 4406 21/ 18/ 14 18/16/13
TESTED ELEMENTS ARE: Fe, Cu, Pb, Sn, Cr, Al, Ni, Ti, Ag, V, Mg, Si, B, Na, Ba, Ca, P, Mn, Zn, Mo, Cd, K *
Date(MM/DD/YY) 01-17-23 11-01-22 09-10-21 08-25-21 06-23-21 (n/a) (n/a) (n/a) REF
Labno 2872633 2854327 2752053 2747507 2731108 Si-SILICON - 1.0 -
P-PHOSPHORUS 1.0 1.0 -
CLEAN FUELS NATIONAL assumes sole responsibility for the total copy, reproduction, application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance. Fixed limits programmed according to laboratory or client specifications. Report indicates tests performed only and are approved and released under the authority of chemist number 1026.
image14.emf
23DanvilleVAMedicalCenter Annual.pdf
Annual Compliance Testing Report
Customer & Location Info Customer Location Address City, State Zip Code Contact Info Date OSFM Green Tag Date
Facility ID# Annual Testing Due Date
The enclosed reports are the result of the Compliance testing completed at the above location.
1. A report to be posted at the job site to give to the State Fire Marshal during his inspection.
2. A checklist showing the items inspected and the results from that inspection.
Tank/Line System info Tank System
ID #
Product Stored
Notes:
Precision Line Testing Results Line ID Type Results
Leak Detection Results
Type
ATG Certification Make of Tank Monitor Model of Tank Monitor Tank ID
Sensor Test Results Sensor ID Type
Technician performing inspection: Bob Kath ICC Certification #9126471
Please note the following maintenance needs to be completed:
1.
2.
3.
4.
5.
6.
Thank you for the opportunity to be of service. Please contact me if you have any questions.
PHONE: (309) 347-1819 EMAIL: compliance@iome.com
Respectfully submitted, Zak Paxton Compliance Department
Customer Danville VA Medical Center Location Building 98 Address 1900 East Main Street City, State Zip Code Danville, IL 61832 Contact Info Michael Miller 765-585-5466 E-mail Michael.miller16@va.gov Date 10/27/2022 OSFM Green Tag Date 2024 Facility ID# 11148 Triennial Testing Date 08/02/2022 Due 08/02/2025
Annual Compliance Testing Tank & Line ID (15) 4,000
Product Diesel
Tank/Line ID N/A
Notes: European Suction.
Tank/Line ID 15 15
Product Diesel Diesel Type Sump Sensor Tank Sensor
Results Passed Passed
Make of Tank Monitor Veeder Root Model of Tank Monitor TLS-350 with CSLD
Tank ID 15
Results Passed
Notes: 1 Probe and 2 Sensors.
Technician Name John (Bob) Kath Certification # d9b1c40d
Signature
Triennial Compliance Testing Report
Triennial STP Containment Sump Testing (3 Year Testing) Sump ID 15
Date 08/02/2022
Triennial Spill Container Containment Testing (3 Year Testing) Sump ID 15
Notes: Double Walled.
Triennial Dispenser Containment Sump Testing (3 Year Testing) Sump ID N/A
Date
Triennial Overfill Prevention Testing (3 Year Testing) Tank ID 15
Notes: 1 Ball float.
Compliance@iome.com
Customer Danville VA Medical Center Location Building 104
City, State Zip Code Danville, IL 61832 Contact Info Michael Miller 765-585-5466 E-mail Michael.miller16@va.gov
Tank & Line ID (17) 8,000
Line Leak Detection Results Tank/Line ID 17 17 17
Product Diesel Diesel Diesel Type Sump Sensor Sump Sensor Tank Sensor
Results Passed Passed Passed
Make of Tank Monitor Veeder Root Model of Tank Monitor TLS-350 with CSLD
Tank ID 17
Notes: 1 Probe and 3 Sensors.
Sump ID 17
Sump ID 17
Tank ID 17
Notes: 1 Overfill Valve.
Customer Danville VA Medical Center Location Building 211
City, State Zip Code Danville, IL 61832 Contact Info Michael Miller 765-585-5466 E-mail Michael.miller16@va.gov
Tank & Line ID (30) 15,000
Tank/Line ID 30 30 30
Make of Tank Monitor INCON Model of Tank Monitor TS-550
Tank ID 30
Sump ID 30 30
Date 08/02/2022 08/02/2022
Sump ID 30
Tank ID 30 Valve
Notes: 1 Valve and 1 Alarm.
Customer Danville VA Medical Center Location Building 212
City, State Zip Code Danville, IL 61832 Contact Info Michael Miller 765-585-5466 E-mail Michael.miller16@va.gov
Tank & Line ID (31) 10,000
Tank/Line ID
Notes: European Suction Piping.
Tank/Line ID 31 31 31
Tank ID 31
Sump ID 31
Sump ID 31
Tank ID 31
Notes: 1 Overfill Valve.
Customer Danville VA Medical Center Location Building 214 Address 1900 East Main Street City, State Zip Code Danville, IL 61832 Contact Info Michael Miller 765-585-5466 E-mail Michael.miller16@va.gov
Tank & Line ID (32) 6,000
Tank/Line ID 32 32 32
Tank ID 32
Sump ID 32 32
Sump ID 32
Tank ID 32
Notes: 1 Overfill Valve and 1 Overfill Alarm.
Customer Danville VA Medical Center Location Building 216 Address 1900 East Main Street City, State Zip Code Danville, IL 61832 Contact Info Michael Miller 765-585-5466 E-mail Michael.miller16@va.gov
Tank & Line ID (33) 6,000
Tank/Line ID 33 33 33
Tank ID 33
Results FAILED
Notes: 1 Probe and 3 Sensors. Probe is Bad and needs to be replaced.
Sump ID 33 33
Sump ID 33
Tank ID 33
Notes: 1 Overfill Valve 1 Alarm.
Customer Danville VA Medical Center Location GSA Lot Address 1900 East Main Street City, State Zip Code Danville, IL 61832 Contact Info Michael Miller 765-585-5466 E-mail Michael.miller16@va.gov
Tank & Line ID (34) 4,000 (35) 4,000 (36) 5,000
Product Diesel Gasoline E-85
Tank/Line ID N/A N/A N/A
Tank/Line ID 34 34 35 35 36 36
Product Diesel Diesel Gasoline Gasoline E-85 E-85 Type 2 Sump Sensors Tank Sensor 2 Sump Sensors Tank sensor 2 Sump Sensors Tank Sensor
Results Passed Passed Passed Passed Passed Passed
Make of Tank Monitor Veedet Root Model of Tank Monitor TLS-350 with CSLD
Tank ID 34 35 36
Notes: 3 Probes and 9 Sensors. 4 E Stops.
Sump ID 34 35 36
Date 08/02/2022 08/2/2022 08/02/2022
Tank ID 34 35 36
Notes: 3 Drop Tube Overfill Valves.
Customer Location Address City, State Zip Code Contact Info Date OSFM Green Tag Date
Facility ID# Annual Testing Due Date
Tank/Line System info Tank System
ID #
Stored
Type
Type
Make of Tank Monitor Model of Tank Monitor Tank ID
Sensor Test Results
Technician performing inspection: Bob Kath ICC Certification #9126471
Please note the following maintenance needs to be completed:
1.
2.
3.
4.
5.
6.
PHONE: (309) 347-1819 EMAIL: compliance@iome.com
Facility #: 4016258
Facility Address: 1900 East Main Street, Danville, IL 61832
Annual Walkthrough Inspection Report: 2022 (year)
Inspections Required Annually (Inspections of piping sump areas must be performed by a certified employee of a contractor licensed in either the Install/Retrofit or Tank Tightness Testing modules.) All piping sumps areas shall be checked annually. Sump lids must be lifted and dispenser cabinets opened to inspect piping containment sump areas.
Contractor must initial and enter date of Annual Walkthrough Inspection.
Day/Month/Year of Inspection
Contractor Initials
Enter comments below corresponding to inspections listed at left.
Visual check for damage to piping containment sump areas: Check lids, covers & containment for damage & leaks.
10/27/2022 JK COMMENTS & ACTIONS TAKEN:
Check sumps for the presence of regulated substances or any indication that a release may have occurred. Remove any liquid or debris if present.
Check that interstices of double wall containment sumps are free of water or product.
DW on 4 newer spill buckets.
If applicable: Check gauge stick (manual tank gauging) or bailer (GW monitoring).
Contractor Employee Conducting Annual Inspection of Piping Containment Sump Areas:
1) Signature:
2) Print Name & Title: John R Kath Compliance Technician
Annual Test & Inspection: May be Performed by Contractor or A/B Operator Contractor or A/B Operator must initial and enter date of Annual Emergency Stops Test.
Day/Month/Year of Emergency Stop Test
10/27/2022
Operator Initials
JK
Enter comments below regarding Annual Emergency Stops Test. Attach OSFM Operational Testing of Emergency Stops Report to Walkthrough Inspection Report & keep at facility.
Test Emergency Stops for interconnection and STP shutdown.
Attach OSFM report form.
COMMENTS:
Tested 4 Switches (GSA Lot.)
Operator must initial and enter date of Annual Shear Valve Inspection.
Shear Valve Inspection
Enter comments below regarding Annual Shear Valve Inspection. Attach OSFM Annual Inspection of Shear Valves Report to Walkthrough Inspection Report & keep at facility.
Check shear valves for proper height, secure mounting & free operation of trip arm & poppet.
3 Shear points under Euro Suction dispenser Pumps. (GSA Lot.)
A/B Operator Signature (if applicable):
Print Name of A/B Operator (if applicable):
4016258
Veterans Administration Medical Center
1900 East Main Street
Danville IL 61832
Danville Vermilion
4 (1 main & 3 wireless)
John R Kath
10/26/2023
State of Illinois Office of the State Fire Marshal
Certification of Annual Inspection of All Dispenser Shear Valves
KEEP FORM AT FACILITY
DO NOT MAIL OR FAX TO OSFM
(217) 785-1020 or (217) 785-5878
(1) OWNER OF TANKS: (2) FACILITY - name and address where tanks are located:
Name: Veterans Administration Medical Center Name: Veterans Administration Medical Center
Street Address: 1900 East Main Street Street Address: 1900 East Main Street
City: Danville State: IL Zip: 61832 City: Danville County: Vermillion
Contact Name: Contact Name:
Phone #: Fax #: Phone #: Fax #:
The regulations of the Office of the State Fire Marshal ("OSFM") in Sections 175.210, 175.220, 175.230, 175.240 and 175.250 require that facilities dispensing motor fuels, such as attended and unattended self-service stations, full-service stations, fleet facilities and marinas, perform visual inspections of all under-dispenser shear valves at least annually.
The following criteria shall be used when inspecting the shear valves:
1) All shear valves shall be mounted using a listed rigid anchor.
2) All shear valves shall be mounted securely to the listed rigid anchor.
3) All shear valves shall be mounted at the proper height relative to grade following the shear valve manufacturer's installation instructions.
4) All shear valves shall be maintained in proper working condition.
5) In addition, the dispensers themselves will also be inspected when the shear valves are checked to confirm that each dispenser is properly and securely mounted to its island.
It is the duty of OSFM to make sure that these shear valves have all been inspected and found to be properly mounted, which is critical to their operation as a fuel shut-off safety device. The shear valves must also be verified as having been maintained in proper working condition, including having the fusible link correctly holding the valve arm, to ensure closure of the poppet valves when released upon a dispenser being damaged or a fire melting the link.
OSFM inspectors will confirm that all shear valves comply with the above requirements during an inspection. The OSFM inspectors will also check for documentation showing that a visual inspection of all shear valves has been performed annually.
This form, filled out and signed, can provide such documentation.
Under the penalties as provided by law pursuant to Section 1-109 of the Code of Civil Procedure, the undersigned certifies that the statements set forth in this instrument are true and correct, except as to matters stated to be on information and belief and as to such matters the undersigned certifies as aforesaid that he/she verily believes the same to be true.
By signing this document, I certify that I personally inspected the shear valves at the facility identified above by its OSFM Facility Number. I confirmed that all shear valves are properly secured and mounted correctly, that there are shear valves present on each dispensing device, and that all shear valves are in proper working order with fusible links and arms engaged.
Euro suction 3 Shear Points 10/26/2023
(Number of Shear Valves Inspected) (Date of Test)
(Name of Tester) (Signature of Tester)
DPCS - Shear Valve Report (4/15)
OFFICE OF THE ILLINOIS STATE FIRE MARSHAL
Annual Leak Detection Certification Test Form
Contractor Name Illinois Oil Marketing Equipment, Inc.
Address 850 Brenkman Drive Pekin, IL 61554
Phone Number (309) 347-1819
Licensed Contractor - IL1293
Facility Name Veterans Administration Medical Center
Address 1900 East Main Street, Bldg.
#14
Danville, IL 61832 County Vermilion
Contact Person Michael M.
Phone Number (217) 554-5994
Facility - 4016258
Test Results Per 175.610(a)(4), a test of the proper operation of leak detection systems and components must be performed at installation of the equipment and at least annually thereafter and, at a minimum, as applicable to the facility, shall cover the following components and criteria:
Tank 15 - 4,000 gallons - Diesel Fuel - Piping - Single Wall STP/Tanktop Sump - Leak Detect - Piping - Sump Sensor
Probes and Sensors:
1. Does the sensor activate with a float mechanism Pass Fail N/A
2. Cables are Free of Kinks Pass Fail
3. Alarm Operates Pass Fail
4. Alarm Communicates with Controller Pass Fail Stand Alone
5. Floats Move Freely Pass Fail
6. Shaft not Damaged or Bent Pass Fail
Vacuum Pumps & Pressure Gauges:
1. Proper Communication with Sensors Pass Fail N/A
2. Proper Communication with Controller Pass Fail N/A
Test Date 10/26/2023
Tank 15 - 4,000 gallons - Diesel Fuel - Leak Detect - Tank - Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD
Automatic Tank Gauge and other controllers:
1. Test Alarm Pass Fail
2. Verify System Configuration Pass Fail
3. Test Battery Backup Pass Fail N/A
4. Verify positive shutdown (Mandatory for systems installed after 9/1/2010 or if using low level containment test option) Pass Fail N/A
PDF Generated: 11/7/2023 9:00:24 AM Page 1 of 12
Tank 15 - 4,000 gallons - Diesel Fuel - Leak Detect - Tank - Hydrostatic Reservoir Interstitial Monitoring Sensors
Tank 16 - 4,000 gallons - Diesel Fuel - Piping - Single Wall STP/Tanktop Sump - Leak Detect - Piping - Sump
1. Does the sensor activate with a float mechanism ***Failed Test*** Pass Fail N/A
2. Cables are Free of Kinks ***Failed Test*** Pass Fail
3. Alarm Operates ***Failed Test*** Pass Fail
4. Alarm Communicates with Controller ***Failed Test*** Pass Fail Stand Alone
5. Sensor tested per manufacture instructions ***Failed Test*** Pass Fail
Test Comments Veeder Root ATG consul was found to have been removed for site renovations. Sensors and probe are inoperable without
ATG.
Tank 16 - 4,000 gallons - Diesel Fuel - Leak Detect - Tank - Automatic Tank Gauging Veeder Root TLS 350 Plus
1. Test Alarm ***Failed Test*** Pass Fail
2. Verify System Configuration ***Failed Test*** Pass Fail
3. Test Battery Backup ***Failed Test*** Pass Fail N/A
Veeder Root ATG consul was found to have been removed for site renovations. Sensors and probe are inoperable without
PDF Generated: 11/7/2023 9:00:24 AM Page 2 of 12
Tank 16 - 4,000 gallons - Diesel Fuel - Leak Detect - Tank - Hydrostatic Reservoir Interstitial Monitoring Sensors
Veeder Root ATG consul was found to have been removed for site renovations. Sensors and probe are inoperable without
Tank 17 - 8,000 gallons - Diesel Fuel - Piping - Single Wall STP/Tanktop Sump - Leak Detect - Piping - Sump
Tank 17 - 8,000 gallons - Diesel Fuel - Piping - Single Wall Transition Sump - Leak Detect - Piping - Sump
PDF Generated: 11/7/2023 9:00:24 AM Page 3 of 12
Tank 17 - 8,000 gallons - Diesel Fuel - Leak Detect - Tank - Automatic Tank Gauging Veeder Root TLS 350 Plus
Tank 17 - 8,000 gallons - Diesel Fuel - Leak Detect - Tank - Hydrostatic Reservoir Interstitial Monitoring Sensors
Tank 30 - 15,000 gallons - Diesel Fuel - Piping - Single Wall STP/Tanktop Sump - Leak Detect - Piping - Sump Sensor with positive shutdown
PDF Generated: 11/7/2023 9:00:24 AM Page 4 of 12
Tank 30 - 15,000 gallons - Diesel Fuel - Leak Detect - Tank - Automatic Tank Gauging Incon TS 550
Tank 30 - 15,000 gallons - Diesel Fuel - Leak Detect - Tank - Non-Discriminating Interstitial Monitoring Sensors
Tank 31 - 10,000 gallons - Diesel Fuel - Piping - Single Wall STP/Tanktop Sump - Leak Detect - Piping - Sump
PDF Generated: 11/7/2023 9:00:24 AM Page 5 of 12
Tank 31 - 10,000 gallons - Diesel Fuel - Leak Detect - Tank - Automatic Tank Gauging Incon TS 550
Tank 31 - 10,000 gallons - Diesel Fuel - Leak Detect - Tank - Non-Discriminating Interstitial Monitoring Sensors
Tank 32 - 6,000 gallons - Diesel Fuel - Piping - Single Wall STP/Tanktop Sump - Leak Detect - Piping - Sump
PDF Generated: 11/7/2023 9:00:24 AM Page 6 of 12
Tank 32 - 6,000 gallons - Diesel Fuel - Leak Detect - Tank - Automatic Tank Gauging Incon TS 550
1. Test Alarm ***Failed Test*** Pass Fail
2. Verify System Configuration ***Failed Test*** Pass Fail
3. Test Battery Backup ***Failed Test*** Pass Fail N/A
Probe is bad and not communicating with ATG.
Tank 32 - 6,000 gallons - Diesel Fuel - Leak Detect - Tank - Non-Discriminating Interstitial Monitoring Sensors
Tank 33 - 6,000 gallons - Diesel Fuel - Piping - Single Wall STP/Tanktop Sump - Leak Detect - Piping - Sump
PDF Generated: 11/7/2023 9:00:24 AM Page 7 of 12
Tank 33 - 6,000 gallons - Diesel Fuel - Leak Detect - Tank - Automatic Tank Gauging Incon TS 550
Tank 33 - 6,000 gallons - Diesel Fuel - Leak Detect - Tank - Non-Discriminating Interstitial Monitoring Sensors
Tank 34 - 4,000 gallons - Diesel Fuel - Piping - Single Wall STP/Tanktop Sump - Leak Detect - Piping - Sump
PDF Generated: 11/7/2023 9:00:24 AM Page 8 of 12
Tank 34 - 4,000 gallons - Diesel Fuel - Leak Detect - Tank - Automatic Tank Gauging Veeder Root TLS 350
Tank 34 - 4,000 gallons - Diesel Fuel - Leak Detect - Tank - Non-Discriminating Interstitial Monitoring Sensors
Tank 35 - 4,000 gallons - Gasoline - Regular - Piping - Single Wall STP/Tanktop Sump - Leak Detect - Piping - Sump Sensor with positive shutdown
PDF Generated: 11/7/2023 9:00:24 AM Page 9 of 12
Tank 35 - 4,000 gallons - Gasoline - Regular - Leak Detect - Tank - Automatic Tank Gauging Veeder Root TLS
Tank 35 - 4,000 gallons - Gasoline - Regular - Leak Detect - Tank - Non-Discriminating Interstitial Monitoring Sensors
Tank 36 - 5,000 gallons - E85 - Piping - Single Wall STP/Tanktop Sump - Leak Detect - Piping - Sump Sensor with positive shutdown
PDF Generated: 11/7/2023 9:00:24 AM Page 10 of 12
Tank 36 - 5,000 gallons - E85 - Leak Detect - Tank - Automatic Tank Gauging Veeder Root TLS 350
Tank 36 - 5,000 gallons - E85 - Leak Detect - Tank - Non-Discriminating Interstitial Monitoring Sensors
Dispenser Diesel - Dispenser - Single Wall UDC Sump - Leak Detect - Piping - Sump Sensor with positive shutdown
PDF Generated: 11/7/2023 9:00:24 AM Page 11 of 12
Dispenser Gasoline - Dispenser - Single Wall UDC Sump - Leak Detect - Piping - Sump Sensor with positive shutdown
Dispenser E85 - Dispenser - Single Wall UDC Sump - Leak Detect - Piping - Sump Sensor with positive shutdown
Date Description File
Contractor Employee Conducting Test Employee Name Kath, John Robert Title Compliance Tech
Terms And Conditions Under the penalties as provided by law pursuant to Section 1-109 of the Code of Civil Procedure, the undersigned certifies that the statements set forth in this instrument are true and correct, except as to matters stated to be on information and belief and as to such matters the undersigned certifies as aforesaid that he/she verily believes the same to be true.
By checking this box, I certify that the Annual Leak Detection Certification Report Form has been completed as required by OSFM rules.
Submitter Name John Kath
Email compliance@iome.com
PDF Generated: 11/7/2023 9:00:24 AM Page 12 of 12
Contractor Name Illinois Oil Marketing Equipment, Inc.
NOV - E0020231103
Nov Type NOV Status Pending
Nov Date 5/3/2023 Expiration Date 7/2/2023
Owner / Operator Veterans Administration Medical Center
Facility
Address
1900 East Main Street, Bldg. #14
NOV Extension Form
NOV Information
Reason We are asking for a 90 extension to complete quoting process, permit process and repairs to be made. The plan is to remove ball float and install Overfill alarm on this tank.
Supporting Documents Contract/Quote Documents
Document Name Last Uploaded
VA Danville Overfill Alarm.pdf 06/23/2023 9:43:16
Down Payment Documents I certify that Illinois Oil Marketing Equipment, Inc. does not require a down payment to start the work required to comply with the above referenced Notice of Violation.
undersigned certifies that the statements set forth in this instrument are true and correct, except as to matters stated to be on information and belief and as to such matters the undersigned certifies as aforesaid
By checking this box, I certify that the NOV Extension Form has been completed as required by OSFM rules.
Contact Information Submitter Name Zak Paxton
Approved EXTENSION GRANTED: Our office has received a request for an extension of the above referenced No�ce of Viola�on. If compliance is not made by 10/2/2023, your underground storage tank system could be subject to RED TAG. Tanks that are red tagged will be prohibited from having product placed into the UST system when a RED TAG exists. This case could then be forwarded to the Illinois A�orney General’s Office for prosecu�on with the possibility of fines and/or removal of the UST system.
Sincerely
Submitted Date & Time: 6/28/2023 9:01:01 AM Page 1 of 2
Scott Johnson
6/28/2023
Submitted Date & Time: 6/28/2023 9:01:01 AM Page 2 of 2
Overfill Prevention Equipment Inspection Form
Inspection Tank 15 - 4000 gallons - Diesel Fuel - * Overfill Prev Device - Overfill Alarm
Replacing via Permit 01115-2023UPG
1. Are electronic device and Probe operating properly? Yes No
2. Does alarm activate at 90% of tank capacity? Yes No
3. Can alarm be heard and seen from tank fueling area? Yes No
Result of Inspection Pass Inspection Date 09/22/2023
Inspection Results
Contractor Employee Conducting Inspection Employee Name White, Nathan Title Service Tech undersigned certifies that the statements set forth in this instrument are true and correct, except as to matters stated to be on information and belief and as to such matters the undersigned certifies as aforesaid
By checking this box, I certify that the Overfill Prevention Equipment Inspection Report Form has been completed as
Submitter Name Zak Paxton
PDF Generated: 10/4/2023 12:44:23 PM Page 1 of 1
Facility Address: 1900 East Main Street, Danville, IL 61832
Annual Walkthrough Inspection Report: 2022 (year)
Inspections Required Annually (Inspections of piping sump areas must be performed by a certified employee of a contractor licensed in either the Install/Retrofit or Tank Tightness Testing modules.) All piping sumps areas shall be checked annually. Sump lids must be lifted and dispenser cabinets opened to inspect piping containment sump areas.
Contractor must initial and enter date of Annual Walkthrough Inspection.
Day/Month/Year of Inspection
Contractor Initials
Enter comments below corresponding to inspections listed at left.
Visual check for damage to piping containment sump areas: Check lids, covers & containment for damage & leaks.
Check sumps for the presence of regulated substances or any indication that a release may have occurred. Remove any liquid or debris if present.
Check that interstices of double wall containment sumps are free of water or product.
DW on 4 newer spill buckets.
If applicable: Check gauge stick (manual tank gauging) or bailer (GW monitoring).
Contractor Employee Conducting Annual Inspection of Piping Containment Sump Areas:
1) Signature:
2) Print Name & Title: John R Kath Compliance Technician
Annual Test & Inspection: May be Performed by Contractor or A/B Operator
Operator must initial and enter date of Annual Emergency Stops Test.
Emergency Stop Test
Enter comments below regarding Annual Emergency Stops Test. Attach OSFM Operational Testing of Emergency Stops Report to Walkthrough Inspection Report & keep at facility.
Test Emergency Stops for interconnection and STP shutdown.
Attach OSFM report form.
Tested 4 Switches (GSA Lot.)
Operator must initial and enter date of Annual Shear Valve Inspection.
Shear Valve Inspection
Enter comments below regarding Annual Shear Valve Inspection.