S02 - H8227138 - VA Hospital - VAMC 2nd and 3rd Floor Corridors - Asbestos and Lead Report.pdf
PDF 13 MB Posted
- Solicitation number
- 36C24825R0032-0001
About this file
This document is a Pre-Renovation Asbestos and Lead Paint Survey Report for the VA Hospital's VAMC Building 1, specifically covering the 2nd and 3rd floor corridors located at 1201 NW 16th Street in Miami, Florida. Conducted by Terracon Consultants, Inc. on June 7-8, 2023, the comprehensive survey identified multiple asbestos-containing materials (ACM) and lead-containing paint (LCP) throughout the facility.
The survey discovered asbestos in various vinyl floor tiles and black duct mastic, with asbestos percentages ranging from <1% to 5% chrysotile across different locations. Lead-containing paint was detected on multiple surfaces including metal door frames, metal doors, and a wooden door, with lead concentrations varying from <39 ppm to 350 ppm. The report recommends that any concealed materials discovered during renovation be sampled and analyzed, and that a 10-day renovation/demolition notice be sent to Miami-Dade County's Division of Environmental Resources Management prior to any abatement activities.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment 0001 - 36C24825R0032.pdf | ||
| S02 - Addendum 1.pdf | ||
| RFI Response - 546-23-112 Renovate Interior Corridors .pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Facilities | Environmental | Geotechnical | Materials I
Pre-Renovation Asbestos Survey and Lead Paint Report VA Hospital – VAMC Building 1: 2nd and 3rd Floor Corridors 1201 NW 16th Street Miami, Florida 33125
July 11, 2023| Report Number: H8227138
5371 NW 33rd Avenue, Suite 201 Fort Lauderdale, Florida 33309 P (954) 741-8282
5371 NW 33rd Avenue, Ste 201 Ft. Lauderdale, FL 33309
P: (954) 741-8282
Terracon.com
Facilities | Environmental | Geotechnical | Materials I
July 11, 2023 RDC/John Poe Architects, LLLP 116 East 3rd Street Dayton, Ohio 45402-2130
Attn: Mr. Jason Ross P 800.362.1523 E jross@rdcjohnpoe.com
RE: Pre-Renovation Asbestos Survey and Lead Paint Report VA Hospital – VAMC – Building 1: 2nd and 3rd Floor Corridors 1201 NW 16th Street
Miami, Florida Terracon Project No. H8227138
Dear Mr. Ross, Terracon Consultants, Inc. (Terracon) is pleased to submit the attached report to RDC/John Poe Architects, LLLP. The purpose of this report is to present the results of a pre-renovation asbestos and lead paint survey performed on June 7 and 8, 2023, at the above referenced location in Miami, Florida. This survey was conducted in general accordance with Terracon Proposal number PH8227138 dated January 23, 2023. We understand that this survey was requested due to the planned renovation of the second and third floor corridors of Building 1 of the hospital.
Based on the laboratory results, asbestos was detected in building materials assessed during our survey assessment. Please refer to the attached report for details.
Lead containing paint was detected in the samples taken during our survey assessment.
Please refer to the attached report for details.
Terracon appreciates the opportunity to provide this service to RDC/John Poe Architects, LLLP. If you have any questions regarding this report, please contact us at 954.741.8282.
Sincerely, Terracon Consultants, Inc.
Florida Asbestos Consulting Business License No. ZA337
Sergio A. Adasme
Project Industrial Hygienist
Mark J. Fricke, CIH, CSP, LAC
Licensed Asbestos Consultant AX132
Mitch Reiber, PG, CIH
Principal
National Director https://na3.documents.adobe.com/verifier?tx=CBJCHBCAABAAUsMN36hpjShVefmIa9mlycKkiETMUC8B https://na3.documents.adobe.com/verifier?tx=CBJCHBCAABAAUsMN36hpjShVefmIa9mlycKkiETMUC8B https://na3.documents.adobe.com/verifier?tx=CBJCHBCAABAAUsMN36hpjShVefmIa9mlycKkiETMUC8B
Facilities | Environmental | Geotechnical | Materials i
TABLE OF CONTENTS
Page
1.0 Introduction
1.1 Project Objective
1.2 Reliance
2.0 Building Description
3.0 Field Activities
3.1 Asbestos
3.2 Lead Containing Paint
4.0 Regulatory Overview
4.1 Asbestos
4.2 Lead in Construction
5.0 Findings and Recommendations
5.1 Asbestos
5.2 Lead Containing Paint
6.0 General Comments
Appendices
Appendix A Asbestos Sample Location Summary
Appendix B Asbestos Analytical Laboratory Data
Appendix C LCP Analytical Laboratory Data
Appendix D Licenses and Certifications
Appendix E Sample Location Diagram
Appendix F Photographs
Pre-Renovation Asbestos and Lead Paint Survey Report VA Hospital – VAMC Building 1: 2nd and 3rd Floor Corridors | Miami, Florida
July 11, 2023 | Terracon Report No. H8227138
Facilities | Environmental | Geotechnical | Materials 1
1.0 Introduction
Terracon Consultants, Inc. (Terracon) conducted a Pre-Renovation asbestos and lead paint survey on the 2nd and 3rd floors of the hospital Building 1 located at 1201 NW 16th Street Miami, Florida.
The survey was conducted on June 7 and 8, 2023, by Asbestos Hazard Emergency Response Act (AHERA)-accredited asbestos inspectors working under the direction of a Florida Licensed Asbestos Consultant (FLAC). The surveys performed were conducted in general accordance with Terracon proposal PH8227138, dated January 23, 2023. The structure’s components, as designated by the site representative, were surveyed and homogeneous areas of suspect asbestos-containing materials (ACM) were visually identified and documented. Additionally, Terracon obtained readily and safely accessible paint-chip samples from surfaces of the renovation areas to identify the presence and concentration of lead paint. Although reasonable effort was made to survey all accessible suspect materials, additional suspect but un-sampled materials could be located in walls, in voids, or in other concealed areas.
Suspect ACM samples were collected in general accordance with the sampling protocols outlined in EPA regulation 40 CFR 763 (AHERA). Asbestos samples were delivered to an accredited laboratory for analysis. Suspect ACM samples were analyzed by Polarized Light Microscopy.
Suspect lead-containing paint samples were obtained from representative coatings potentially containing lead. Lead paint samples were delivered to an accredited laboratory for analysis by Flame Atomic Absorption Spectrophotometry (EPA method SW846 7000B).
1.1 Project Objective
We understand this asbestos survey was requested due to the planned future renovation of the 2nd and 3rd floors of Building 1. EPA regulation 40 CFR 61, Subpart M, National Emission Standards for Hazardous Air Pollutants (NESHAP), prohibits the release of asbestos fibers to the atmosphere during renovation or demolition activities. The asbestos NESHAP requires that potentially regulated ACM (RACM) be identified, classified, and quantified prior to planned renovation or demolition activities.
In addition, suspect lead-containing paint (LCP) samples were obtained to identify potential lead exposure sources, regulated by the Occupational Safety and Health Administration (OSHA) 29 CFR
1926.62 and other applicable EPA regulations that could develop if lead-containing coatings are disturbed during planned renovation or demolition activities.
1.2 Reliance
This report is for the exclusive use of RDC/John Poe Architects, LLLP for the project being discussed. Reliance by any other party on this report is prohibited without written authorization of Terracon and RDC/John Poe Architects, LLLP. Reliance on this report by RDC/John Poe Architects, LLLP and all authorized parties will be subject to the terms, conditions, and limitations stated in the proposal, this report, and the existing agreement between RDC/John Poe Architects, LLLP and Terracon. The limitations of liability defined in Terracon’s Agreement for Services is the aggregate limit of Terracon’s liability to RDC/John Poe Architects, LLLP.
July 11, 2023 | Terracon Report No. H8227138
Facilities | Environmental | Geotechnical | Materials 2
2.0 Building Description
The multi-story building construction date is unknown. The building materials consisted of stucco and stone exterior walls atop a concrete slab. Interior finishes of the 2nd and 3rd floor corridors of building 1 consisted of lay-in ceiling tiles, drywall systems with vinyl floor tile, vinyl sheet flooring, sand/epoxy flooring, and ceramic floor and wall tiles.
3.0 Field Activities
The survey was conducted by AHERA-accredited asbestos inspectors, Mr. Ryan Nanan and Mr.
Marcello Meneses. The survey was conducted in general accordance with the sample collection protocols established in EPA regulation 40 CFR 763 (AHERA). An asbestos sample summary is included as Appendix A. Asbestos analytical laboratory data is included as Appendix B. Paint chip sampling for lead was conducted on observed painted surfaces located within the surveyed areas.
Lead containing paint analytical laboratory data is included as Appendix C. Copies of the applicable licenses and certifications are included in Appendix D. A map of sample locations is attached as Appendix E.
3.1 Asbestos
Our survey activities began with visual observations of accessible interior areas to identify homogeneous areas of suspect ACM. A homogeneous area consists of building materials that appear similar throughout in terms of color, texture, and date of application. The assessment was conducted throughout visually accessible areas of the 2nd and 3rd floors of Building 1. Materials identified as glass, wood, metal, or rubber were not considered suspect ACM.
A physical assessment of each homogeneous area of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the EPA as a material which can be crumbled, pulverized, or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.
Based on results of the visual observation, bulk samples of suspect ACM were collected in general accordance with AHERA sampling protocols. Random samples of suspect materials were collected in each homogeneous area. Samples were collected using wet methods as applicable to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.
A total of 126 bulk samples were collected from 36 homogeneous areas of suspect ACM during the survey. An asbestos sample location summary is included as Appendix A.
Bulk samples were submitted under chain of custody to Eurofins EPK Built Environment Testing, LLC (Eurofins EPK) in Ft. Lauderdale, Florida for analysis by PLM per EPA methodology EPA/600/R- 93/116. The percentage of asbestos, where applicable, was determined by microscopic visual estimation. Eurofins EPK is accredited under the National Voluntary Laboratory Accreditation Program (NVLAP Accreditation No. 200738-0).
July 11, 2023 | Terracon Report No. H8227138
Facilities | Environmental | Geotechnical | Materials 3
3.2 Lead Containing Paint
Terracon performed a visual assessment of the interior of the 2nd and 3rd floors of Building 1 to locate, and assess predominant painted surfaces for lead. Representative paint chip samples were chosen from each unique combination of paint color, component, and substrate.
A total of 16 paint chips samples were collected and submitted to Eurofins EPK of Tustin, California for analysis. The paint chips were analyzed by Flame Atomic Absorption Spectrometry (AAS) by NIOSH 7082 and EPA method 7000B Modified. Eurofins EPK is accredited under the Environmental Lead Laboratory Accreditation Program (AIHA-LAP, Accreditation No. 178697).
Analytical laboratory data for LCP samples taken during this survey are provided in Appendix C.
4.0 Regulatory Overview
4.1 Asbestos
The asbestos NESHAP (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. It also requires the identification and classification of existing materials prior to demolition or renovation activities. Under NESHAP, ACM are classified as either friable, Category I non-friable or Category II non-friable ACM. Friable materials are those that, when dry, may be crumbled, pulverized, or reduced to powder by hand pressure. Category I non-friable ACM includes packings, gaskets, resilient floor coverings and asphalt roofing products containing more than 1% asbestos. Category II non-friable ACM are any non-friable materials other than non-friable Category I materials that contain more than 1% asbestos.
Friable ACM, Category I and Category II non-friable ACM which is in poor condition and has become friable or which will be subjected to drilling, sanding, grinding, cutting, or abrading and which could be crushed or pulverized during anticipated renovation or demolition activities are considered RACM.
The NESHAP regulations include an option for Friable materials or potential RACM that are found to contain less than 10% asbestos to be “point-counted” or analyzed by similar, advanced analytical methods, such as Transmission Electron Microscopy (TEM), to confirm the asbestos concentrations. If the additional “point-counting” or TEM analysis is not implemented then the materials are required to be categorized as ACM (>1% asbestos content) even if the initial, estimated laboratory results are reported “trace” or less than 1% (<1%) asbestos content.
In the State of Florida, asbestos activities are regulated by the Florida Department of Environmental Protection (FDEP), which is enforced locally by the Miami-Dade County Division of Environmental Resources Management, which is located at 701 NW 1st Court, Suite 400 Miami, FL 33324. RACM must be removed prior to renovation or demolition activities which will disturb the materials. The owner or operator must provide the FDEP with written notification of planned removal activities at least 10 working days prior to the commencement of asbestos abatement activities. Removal of ACM and/or RACM must be conducted by a State of Florida-licensed asbestos abatement contractor.
July 11, 2023 | Terracon Report No. H8227138
Facilities | Environmental | Geotechnical | Materials 4
The OSHA Asbestos standard for construction (29 CFR 1926.1101) regulates workplace exposure to asbestos. The OSHA standard requires that employee exposure to airborne asbestos fibers be maintained below 0.1 asbestos fibers per cubic centimeter of air (0.1 f/cc) for an 8-hour time-weighted average (TWA) permissible exposure limit (PEL) and 1.0 f/cc over a 30-minute period known as an excursion limit (EL).
The OSHA standard classifies construction and maintenance activities which could disturb ACM and specifies work practices and precautions which employers must follow when engaging in each class of regulated work. In addition, OSHA requires that activities where workers disturb materials with even “trace” amounts of asbestos content (<1%) are still regulated and require compliance with certain elements of the regulation.
4.2 Lead in Construction
Lead is regulated by the EPA, HUD, FDEP and OSHA. The EPA and FDEP regulate lead use, removal, and disposal, and OSHA regulates lead exposure to workers. The EPA and HUD, with their small child-safety focus, define Lead-Based Paint (LBP) as paint, varnish, stain, or other applied coating that contains lead equal to or greater than 1.0 mg/cm2, 5,000 ppm, or 0.5% by dry weight as determined by laboratory analysis.
However, for the purpose of the OSHA lead standard, with its focus on the safety/exposure of construction workers, paint-containing lead includes any detectable concentrations of metallic lead, all inorganic lead compounds, and organic lead soaps. A synopsis of the OSHA regulations (29 CFR 1926.62) and the applicability are as follows:
The OSHA Lead Standard for Construction (29 CFR 1926.62) applies to all construction work where an employee may be occupationally exposed to lead. All work related to construction, alteration, or repair (including painting and decorating) is included. The lead-in-construction standard applies to any detectable concentration of lead in paint, as even small concentrations of lead can result in unacceptable employee exposures depending upon on the method of removal and other workplace conditions. The OSHA standard requires employee exposure to airborne lead to be maintained below the PEL of 50 micrograms per cubic meter of air (ug/m3) over an 8-hour
TWA.
Under this standard, construction includes, but is not limited to, the following:
Demolition or salvage of structures where lead or materials containing lead are present
Removal or encapsulation of materials containing lead
New construction, alteration, repair, or renovation of structures, substrates, or portions containing lead, or materials containing lead
Installation of products containing lead
Lead contamination/emergency clean-up
Transportation, disposal, storage, or containment of lead or materials containing lead on the site or location at which construction activities are performed
Maintenance operations associated with construction activities described above
July 11, 2023 | Terracon Report No. H8227138
Facilities | Environmental | Geotechnical | Materials 5
5.0 Findings and Recommendations
5.1 Asbestos
Laboratory analysis of materials collected during our survey confirmed that some of the materials sampled contained asbestos. The table below presents a comprehensive list of the asbestos-containing materials found within the corridors of the second and third floors. Material locations are displayed in further detail in the sample location diagram presented in Appendix E.
HA
Material Description Material Location(s) Percent/Type
Asbestos Estimated Quantity*
Brown w/ White/Brown Strips 12"x12" Vinyl Floor Tile and Brown Mastic over Brown
9"x9" Vinyl Floor Tile w/ Black Mastic
2nd Floor – W Side <1% to 5% Chrysotile
6,900 ft²
Grey 12"x12" Vinyl Floor Tile and Yellow Glue over Light
Grey 12"x12" Vinyl Floor Tile and Black Mastic
2nd Floor – SW Side 5% Chrysotile 90 ft²
Grey w/ Black Dots 15"x15"
Vinyl Floor Tile w/ Black Mastic and Brown Glue
2nd Floor – N Side 2% Chrysotile 180 ft²
27 Black Duct Mastic Throughout 2nd/3rd
Floors 5% Chrysotile 8,600 ft²
12"x12" White w/ Black Speckle Vinyl Floor Tile w/
Brown Glue over Blue 9"x9" Vinyl Floor Tile w/ Black Mastic
3rd Floor – W Side 5% Chrysotile 2,300 ft²
12"x12" Pink w/ White and Grey Vinyl Floor Tile w/ Brown
Glue over Blue 9"x9" Vinyl Floor Tile and Black Mastic
3rd Floor - Center 5% Chrysotile 3,200 ft²
July 11, 2023 | Terracon Report No. H8227138
Facilities | Environmental | Geotechnical | Materials 6
HA
Material Description Material Location(s) Percent/Type
Asbestos Estimated Quantity*
12"x12" White w/ Orange and Green Speckle Vinyl Floor Tile w/ Brown Glue over White 12"x12" Vinyl Floor Tile w/
Black Mastic
3rd Floor – S Side 2% Chrysotile 80 ft²
12"x12" Light Brown w/ Dark Brown Speckle Vinyl Floor Tile w/ Brown Glue over Blue Vinyl
Floor Tile w/ Black Mastic
3rd Floor – E Side 3% Chrysotile 1,250 ft²
White w/ Green Strips 9"x9"
Vinyl Floor Tile w/ Black Mastic 3rd Floor – S Side
<1% to 2% Chrysotile
200 ft²
*Quantities above are an estimate of visually identified materials
The results of this assessment should be communicated to the renovation contractor and other subcontractors working in the building and a copy of the survey should be on-site during renovation or demolition activities. In addition, a 10-day renovation/demolition notice will need to be sent to Miami-Dade County, Division of Environmental Resources Management. We recommend a call be made to (305) 372-6925 to confirm their regulatory requirements.
Any concealed building materials discovered during renovation activities not identified in this report, which are suspected to contain asbestos, should be sampled by a Florida Licensed Asbestos Consultant and analyzed by a NVLAP-accredited laboratory to confirm the presence or absence of asbestos prior to disturbing such materials. If the materials are found to contain asbestos, various regulations (EPA NESHAP, FDEP and OSHA) will apply. In addition, direct contact with the FDEP is recommended to confirm their actual regulatory requirements.
July 11, 2023 | Terracon Report No. H8227138
Facilities | Environmental | Geotechnical | Materials 7
5.2 Lead-Containing Paint
Lead-containing paint was detected in some of the samples collected during this site inspection. The table below represents a list of sampled paints and the measurement of lead concentrations analyzed from each. A comprehensive report is displayed in the laboratory data presented in Appendix C.
Sample
Description Substrate Lead
Results (ppm)
L1 White on Drywall Wall Drywall < 40 ppm
L2 Cream on Metal Door Frame Metal 41 ppm
L3 Red on Metal Door Metal 130 ppm
L4 Cream on Metal Double Door Metal < 39 ppm
L5 Brown on Drywall Drywall < 39 ppm
L6 Brown on Concrete Wall Concrete < 39 ppm
L7 White on Concrete Wall Concrete < 39 ppm
L8 Grey on Concrete Wall Concrete < 40 ppm
L9 Grey on Metal Door Frame Metal 45 ppm
L10 Blue on Concrete Wall Concrete < 40 ppm
L11 Yellow on Drywall Drywall < 40 ppm
L12 Dark Grey on Metal Door Metal < 56 ppm
L13 Dark Grey on Metal Door Frame Metal < 62 ppm
L14 Cream on Metal Door Metal < 57 ppm
L15 Cream on Metal Door Frame Metal < 99 ppm
L16 Red on Wooden Door Wood 350 ppm
Bolded entries indicate concentrations of lead analyzed above the analytical method detection limit.
< = Below laboratory analytical method detection limit.
July 11, 2023 | Terracon Report No. H8227138
Facilities | Environmental | Geotechnical | Materials 8
Any concealed building painted surfaces discovered during renovation activities not identified in this report which are suspected to contain lead, should be sampled, and analyzed.
The results of this assessment should be communicated to the renovation contractor and other subcontractors working in the building and a copy of the survey should be on-site during the renovation activities.
6.0 General Comments
It should be noted that suspect asbestos materials other than those identified during our survey may exist in locations outside of the designated surveyed areas. Should suspect materials other than those which were identified during this survey be uncovered prior to renovation activities, those materials should be assumed asbestos-containing, until sampling and analysis can confirm or refute their asbestos content.
Suspect LCP, other than those identified during the sampling, may also be present in the building. The LCP testing performed was not considered comprehensive in nature and the results are not intended to be used to determine lead hazards, develop abatement plans, or prepare detailed cost estimates for abatement. Suspect LCP which has not been specifically evaluated should be tested prior to disturbance of the material. If additional suspect LCP is identified during the demolition process, those materials should be assumed LCP until testing can be performed to determine whether lead is present in the paint.
The asbestos and LCP surveys were conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during our survey of the building. The information contained in this report is relevant to the dates on which this survey was performed and should not be relied upon to represent conditions later.
This report has been prepared on behalf of and exclusively for use by the Client. for specific application to their project as discussed. This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories or other third parties supplying information which may have been used in the preparation of this report. No warranty, express or implied is made.
Facilities | Environmental | Geotechnical | Materials
Appendix A
Asbestos Sample Location Summary
VA Hospital – VAMC Building 1 - 2nd and 3rd Floor Corridors | Miami, Florida
July 10, 2023 | Terracon Report No. H8227138
HA
Number
Sample Number
Material Description Sample Location Lab Results
1A
Grey Sand/Epoxy Floor Coating
2nd Floor - NW Side
ND1B 2nd Floor - NW Side
1C 2nd Floor - NW Side
2A Brown Line Pattern 12"x24" Vinyl
Floor Tile and Brown Mastic
2nd Floor - NW Side
ND2B 2nd Floor - NW Side
2C 2nd Floor - NW Side
3A Brown w/ White/Brown Strips
12"x12" Vinyl Floor Tile and Brown Mastic over Brown 9"x9" Vinyl Floor
Tile w/ Black Mastic
2nd Floor – W Side
<1% to 5% Chrysotile
3B 2nd Floor – W Side
3C 2nd Floor – W Side
3D 2nd Floor – W Side
3E 2nd Floor – W Side
4A Grey 12"x12" Vinyl Floor Tile and Yellow Glue over Light Grey
12"x12" Vinyl Floor Tile and Black Mastic
2nd Floor – SW Side
5% Chrysotile4B 2nd Floor – SW Side
4C 2nd Floor – SW Side
5A Purple/Pink Vinyl Floor Tile and
Brown Mastic
2nd Floor – SW Side
ND5B 2nd Floor – SW Side
5C 2nd Floor – SW Side
6A Grey/Brown 15"x15" Vinyl Floor
Tile w/ Yellow Mastic
2nd Floor – SW Side
ND6B 2nd Floor – SW Side
6C 2nd Floor – SW Side
7A Light Brown w/ White Spots 12"x12" Vinyl Floor Tile w/ Black
Mastic
2nd Floor - N Side
ND7B 2nd Floor - N Side
7C 2nd Floor - N Side
8A Grey w/ Black Dots 15"x15" Vinyl Floor Tile w/ Black Mastic and
Brown Glue
2nd Floor – N Side
2% Chrysotile8B 2nd Floor – N Side
8C 2nd Floor – N Side
9A Pink w/ Black Dots 12"x12" Vinyl
Floor Tile w/ Yellow Glue
2nd Floor - Center
ND9B 2nd Floor - Center
9C 2nd Floor - Center
10A Black Wood Patterned 4"x36" Vinyl
Floor Tile w/ Yellow Glue
2nd Floor - E Side
ND10B 2nd Floor - E Side
10C 2nd Floor - E Side
11A
Brown/Grey Carpet and Clear Glue
2nd Floor – SE Side
ND11B 2nd Floor – SE Side
11C 2nd Floor – SE Side
12A Grey w/ White Strips 12"x12" Vinyl
Floor Tile w/ Black Mastic
2nd Floor – SE Side
ND12B 2nd Floor – SE Side
12C 2nd Floor – SE Side
July 10, 2023 | Terracon Report No. H8227138
HA
Number
Sample Number
Material Description Sample Location Lab Results
13A Brown Wood Patterned Vinyl Floor Sheeting w/ Clear Glue and
Leveling Compound
2nd Floor - Center
ND13B 2nd Floor - Center
13C 2nd Floor - Center
14A
Brown w/ Large Brown Strips 12"x12" Vinyl Floor Tile w/ Black
Mastic
2nd Floor - E Side
ND
14B 2nd Floor - NE Side
14C 2nd Floor - SE Side
14D 2nd Floor - S Side
14E 2nd Floor - SW Side
15A
Interior Partition Drywall w/ Joint Compound
2nd Floor - E Side
ND
15B 2nd Floor - NE Side
15C 2nd Floor - SE Side
15D 2nd Floor - S Side
15E 2nd Floor - SW Side
16A
4" Brown Baseboard w/ Brown Glue
2nd Floor - E Side
ND16B 2nd Floor - Center
16C 2nd Floor - NE Side
17A
White 2'x2' Worm Ceiling Tile
2nd Floor - Center
ND
17B 2nd Floor - NW Side
17C 2nd Floor - Center
17D 2nd Floor - SW Side
17E 2nd Floor - SE Side
17F 3rd Floor - NE Side
17G 3rd Floor - Center
17H 3rd Floor – W Side
18A
White 2'x4' Large Worm Ceiling Tile
2nd Floor - NE Side
ND18B 2nd Floor - S Side
18C 2nd Floor - SW Side
19A Blue/Brown Plastic Wall Sheeting w/ Glue
2nd Floor - NE Side
ND19B 2nd Floor - SE Side
19C 2nd Floor - SW Side
20A
Off-White Wallpaper w/ Yellow Glue
2nd Floor - Center
ND20B 2nd Floor - Center
20C 2nd Floor - Center
21A
Grey/Pink Wallpaper w/ Brown Glue
2nd Floor - Center
ND
21B 2nd Floor – S Side
21C 2nd Floor – SW Side
21D 3rd Floor - N Side
21E 3rd Floor - NE Side
July 10, 2023 | Terracon Report No. H8227138
HA
Number
Sample Number
Material Description Sample Location Lab Results
22A
White Duct Mastic
2nd Floor - NE Side
ND
22B 2nd Floor - S Side
22C 2nd Floor - NW Side
22D 2nd Floor - SE Side
22E 2nd Floor - NE Side
23A
White Wrap Yellow Pipe Insulation
2nd Floor - E Side
ND23B 2nd Floor - E Side
23C 2nd Floor - NE Side
24A
Brown Mastic on Metal Duct
2nd Floor - E Side
ND24B 2nd Floor - SW Side
24C 2nd Floor - E Side
25A
Drywall Ceiling w/ Joint Compound
2nd Floor - E Side
ND25B 2nd Floor - E Side
25C 2nd Floor - SE Side
26A
4" Blue Baseboard w/ Brown Glue
2nd Floor - SE Side
ND26B 2nd Floor - SE Side
26C 2nd Floor - SE Side
27A
Black Duct Mastic
2nd Floor - E Side
5% Chrysotile
27B 2nd Floor - Center Side
27C 2nd Floor - SE Side
27D 3rd Floor – Center
27E 3rd Floor – W Side
27F 3rd Floor – W Side
28A
2'x2' Rough White Ceiling Tile
2nd Floor - Center
ND28B 2nd Floor - Center
28C 2nd Floor - Center
29A 12"x12" White w/ Black Speckle Vinyl Floor Tile w/ Brown Glue over Blue 9"x9" Vinyl Floor Tile w/ Black
Mastic
3rd Floor – W Side
5% Chrysotile29B 3rd Floor – W Side
29C 3rd Floor – W Side
30A
4" Pink Baseboard w/ Brown Glue
3rd Floor – N Side
ND30B 3rd Floor – W Side
30C 3rd Floor – W Side
31A 12"x12" Pink w/ White and Grey Vinyl Floor Tile w/ Brown Glue over
Blue 9"x9" Vinyl Floor Tile and Black Mastic
3rd Floor - Center
5% Chrysotile31B 3rd Floor - Center
31C 3rd Floor - Center
32A 12"x12" White w/ Orange and Green Speckle Vinyl Floor Tile w/ Brown Glue over White 12"x12" Vinyl Floor Tile w/ Black Mastic
3rd Floor – S Side
2% Chrysotile32B 3rd Floor – S Side
32C 3rd Floor – S Side
July 10, 2023 | Terracon Report No. H8227138
HA
Number
Sample Number
Material Description Sample Location Lab Results
33A 12"x12" Pink Stone Patterned Vinyl Floor Tile w/ Brown Glue over
Brown 12"x12" Vinyl Floor Tile w/ Brown Glue
3rd Floor – S Side
ND33B 3rd Floor – S Side
33C 3rd Floor – S Side
34A 12"x12" Light Brown w/ Dark Brown Speckle Vinyl Floor Tile w/ Brown Glue over Blue Vinyl Floor
Tile w/ Black Mastic
3rd Floor – E Side
3% Chrysotile34B 3rd Floor – E Side
34C 3rd Floor – E Side
35A Cream Fiber Reinforced Plastic and
Brown Glue
3rd Floor – NE Side
ND35B 3rd Floor – Center
35C 3rd Floor – W Side
36A White w/ Green Strips 9"x9" Vinyl
Floor Tile w/ Black Mastic
3rd Floor – S Side <1% to 2% Chrysotile
36B 3rd Floor – S Side
36C 3rd Floor – S Side ND – None Detected
Facilities | Environmental | Geotechnical | Materials
Appendix B
Asbestos Analytical Laboratory Data
Approved by:
Approved Signatory Balu Krishnan
Report for:
Mr. Sergio Adasme Terracon - Fort Lauderdale, FL 5371 NW 33rd Ave.
Suite 201 Fort Lauderdale, FL 33309
Regarding:
Eurofins EPK Built Environment Testing, LLC Project: VAMC - Renovate Corridors - Bldg. 1 - Floors 2-3; 1201 NW 16th Street, Miami, FL
EML ID: 3289043
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the samples as received and tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.
Eurofins EPK Built Environment Testing, LLC ("the Company"), a member of the Eurofins Built Environment Testing group of companies, shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:
Asbestos PLM: 06-13-2023 and 06-14-2023
Service SOPs: Asbestos PLM (EPA 40CFR App E to Sub E of Part 763 & EPA METHOD 600/R-93-116, SOP EM-AS-S-1267)
EMLab ID: 3289043, Page 1 of 40Eurofins EPK Built Environment Testing, LLC
Eurofins EPK Built Environment Testing, LLC 6301 NW 5th way, Suite#: 1410, Ft. Lauderdale, FL 33309
(866) 871-1984 www.eurofinsus.com/BuiltClient: Terracon - Fort Lauderdale, FL C/O: Mr. Sergio Adasme Re: VAMC - Renovate Corridors - Bldg. 1 - Floors 2- 3; 1201 NW 16th Street, Miami, FL
Date of Sampling: 06-07-2023 Date of Receipt: 06-13-2023 Date of Report: 06-14-2023
ASBESTOS PLM REPORT
Total Samples Submitted: 126 Total Samples Analyzed: 126
Total Samples with Layer Asbestos Content > 1%: 32
Location: 1A, Grey Sand/Epoxy Floor Coating Lab ID-Version‡: 15961225-1
Sample Layers Asbestos Content Gray Flooring ND
Sample Composite Homogeneity: Good
Location: 1B, Grey Sand/Epoxy Floor Coating Lab ID-Version‡: 15961226-1
Sample Layers Asbestos Content Gray Flooring ND
Sample Composite Homogeneity: Good
Location: 1C, Grey Sand/Epoxy Floor Coating Lab ID-Version‡: 15961227-1
Sample Layers Asbestos Content Gray Flooring ND
Sample Composite Homogeneity: Good
Location: 2A, Brown Line Pattern 12"x24" Vinyl Floor Tile and Brown Mastic Lab ID-Version‡: 15961228-1
Sample Layers Asbestos Content Brown Floor Tile ND
Brown Mastic ND Sample Composite Homogeneity: Moderate
EMLab ID: 3289043, Page 2 of 40Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
(866) 871-1984 www.eurofinsus.com/BuiltClient: Terracon - Fort Lauderdale, FL C/O: Mr. Sergio Adasme Re: VAMC - Renovate Corridors - Bldg. 1 - Floors 2- 3; 1201 NW 16th Street, Miami, FL
Date of Sampling: 06-07-2023 Date of Receipt: 06-13-2023 Date of Report: 06-14-2023
ASBESTOS PLM REPORT
Location: 2B, Brown Line Pattern 12"x24" Vinyl Floor Tile and Brown Mastic Lab ID-Version‡: 15961229-1
Sample Layers Asbestos Content Brown Mastic ND
Brown Floor Tile ND Sample Composite Homogeneity: Moderate
Location: 2C, Brown Line Pattern 12"x24" Vinyl Floor Tile and Brown Mastic Lab ID-Version‡: 15961230-1
Sample Layers Asbestos Content Brown Mastic ND
Brown Floor Tile ND Sample Composite Homogeneity: Moderate
Location: 3A, Brown w/ White/Brown Strips 12"x12" Vinyl Floor Tile and Brown Mastic over Brown 9"x9" Vinyl Floor Tile w/ Black Mastic Lab ID-Version‡: 15961231-1
Sample Layers Asbestos Content Light Brown Floor Tile < 1% Chrysotile
Brown Mastic ND Brown Floor Tile < 1% Chrysotile
Black Mastic 5% Chrysotile Sample Composite Homogeneity: Moderate
Location: 3B, Brown w/ White/Brown Strips 12"x12" Vinyl Floor Tile and Brown Mastic over Brown 9"x9" Vinyl Floor Tile w/ Black Mastic Lab ID-Version‡: 15961232-1
Sample Layers Asbestos Content Light Brown Floor Tile < 1% Chrysotile
Brown Mastic ND Brown Floor Tile < 1% Chrysotile
Black Mastic 5% Chrysotile Sample Composite Homogeneity: Moderate
EMLab ID: 3289043, Page 3 of 40Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Terracon - Fort Lauderdale, FL C/O: Mr. Sergio Adasme Re: VAMC - Renovate Corridors - Bldg. 1 - Floors 2- 3; 1201 NW 16th Street, Miami, FL
Date of Sampling: 06-07-2023 Date of Receipt: 06-13-2023 Date of Report: 06-14-2023
ASBESTOS PLM REPORT
Location: 3C, Brown w/ White/Brown Strips 12"x12" Vinyl Floor Tile and Brown Mastic over Brown 9"x9" Vinyl Floor Tile w/ Black Mastic Lab ID-Version‡: 15961233-1
Sample Layers Asbestos Content Light Brown Floor Tile < 1% Chrysotile
Brown Mastic ND Brown Floor Tile < 1% Chrysotile
Black Mastic 5% Chrysotile Sample Composite Homogeneity: Moderate
Location: 3D, Brown w/ White/Brown Strips 12"x12" Vinyl Floor Tile and Brown Mastic over Brown 9"x9" Vinyl Floor Tile w/ Black Mastic Lab ID-Version‡: 15961234-1
Sample Layers Asbestos Content Light Brown Floor Tile < 1% Chrysotile
Brown Mastic ND Brown Floor Tile < 1% Chrysotile
Black Mastic 5% Chrysotile Sample Composite Homogeneity: Moderate
Location: 3E, Brown w/ White/Brown Strips 12"x12" Vinyl Floor Tile and Brown Mastic over Brown 9"x9" Vinyl Floor Tile w/ Black Mastic Lab ID-Version‡: 15961235-1
Sample Layers Asbestos Content Light Brown Floor Tile < 1% Chrysotile
Brown Mastic ND Brown Floor Tile < 1% Chrysotile
Black Mastic 5% Chrysotile Sample Composite Homogeneity: Moderate
EMLab ID: 3289043, Page 4 of 40Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Terracon - Fort Lauderdale, FL C/O: Mr. Sergio Adasme Re: VAMC - Renovate Corridors - Bldg. 1 - Floors 2- 3; 1201 NW 16th Street, Miami, FL
Date of Sampling: 06-07-2023 Date of Receipt: 06-13-2023 Date of Report: 06-14-2023
ASBESTOS PLM REPORT
Location: 4A, Grey 12"x12" Vinyl Floor Tile and Yellow Glue over Light Grey 12"x12" Vinyl Floor Tile and Black Mastic Lab ID-Version‡: 15961236-1
Sample Layers Asbestos Content Gray Floor Tile ND
Yellow Glue ND Light Gray Floor Tile ND
Black Mastic 5% Chrysotile Sample Composite Homogeneity: Moderate
EMLab ID: 3289043, Page 5 of 40Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Terracon - Fort Lauderdale, FL C/O: Mr. Sergio Adasme Re: VAMC - Renovate Corridors - Bldg. 1 - Floors 2- 3; 1201 NW 16th Street, Miami, FL
Date of Sampling: 06-07-2023 Date of Receipt: 06-13-2023 Date of Report: 06-14-2023
ASBESTOS PLM REPORT
Location: 4B, Grey 12"x12" Vinyl Floor Tile and Yellow Glue over Light Grey 12"x12" Vinyl Floor Tile and Black Mastic Lab ID-Version‡: 15961237-1
Sample Layers Asbestos Content Black Mastic 5% Chrysotile
Light Gray Floor Tile ND Yellow Glue ND
Gray Floor Tile ND Sample Composite Homogeneity: Moderate
Location: 4C, Grey 12"x12" Vinyl Floor Tile and Yellow Glue over Light Grey 12"x12" Vinyl Floor Tile and Black Mastic Lab ID-Version‡: 15961238-1
Sample Layers Asbestos Content Black Mastic 5% Chrysotile
Light Gray Floor Tile ND Yellow Glue ND
Gray Floor Tile ND Sample Composite Homogeneity: Moderate
Location: 5A, Purple/Pink Vinyl Floor Tile and Brown Mastic Lab ID-Version‡: 15961239-1
Sample Layers Asbestos Content Brown Mastic 2 ND Pink Floor Tile ND Brown Mastic 1 ND Purple Floor Tile ND
Sample Composite Homogeneity: Moderate
EMLab ID: 3289043, Page 6 of 40Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Terracon - Fort Lauderdale, FL C/O: Mr. Sergio Adasme Re: VAMC - Renovate Corridors - Bldg. 1 - Floors 2- 3; 1201 NW 16th Street, Miami, FL
Date of Sampling: 06-07-2023 Date of Receipt: 06-13-2023 Date of Report: 06-14-2023
ASBESTOS PLM REPORT
Location: 5B, Purple/Pink Vinyl Floor Tile and Brown Mastic Lab ID-Version‡: 15961240-1
Sample Layers Asbestos Content Brown Mastic 2 ND Pink Floor Tile ND Brown Mastic 1 ND Purple Floor Tile ND
Sample Composite Homogeneity: Moderate
EMLab ID: 3289043, Page 7 of 40Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Terracon - Fort Lauderdale, FL C/O: Mr. Sergio Adasme Re: VAMC - Renovate Corridors - Bldg. 1 - Floors 2- 3; 1201 NW 16th Street, Miami, FL
Date of Sampling: 06-07-2023 Date of Receipt: 06-13-2023 Date of Report: 06-14-2023
ASBESTOS PLM REPORT
Location: 5C, Purple/Pink Vinyl Floor Tile and Brown Mastic Lab ID-Version‡: 15961241-1
Sample Layers Asbestos Content Brown Mastic 2 ND Pink Floor Tile ND Brown Mastic 1 ND Purple Floor Tile ND
Sample Composite Homogeneity: Moderate
Location: 6A, Grey/Brown 15"x15" Vinyl Floor Tile w/ Yellow Mastic Lab ID-Version‡: 15961242-1
Sample Layers Asbestos Content Yellow Mastic ND
Brown/Gray Floor Tile ND Sample Composite Homogeneity: Moderate
Location: 6B, Grey/Brown 15"x15" Vinyl Floor Tile w/ Yellow Mastic Lab ID-Version‡: 15961243-1
Sample Layers Asbestos Content Yellow Mastic ND
Brown/Gray Floor Tile ND Sample Composite Homogeneity: Moderate
Location: 6C, Grey/Brown 15"x15" Vinyl Floor Tile w/ Yellow Mastic Lab ID-Version‡: 15961244-1
Sample Layers Asbestos Content Yellow Mastic ND
Brown/Gray Floor Tile ND Sample Composite Homogeneity: Moderate
EMLab ID: 3289043, Page 8 of 40Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Terracon - Fort Lauderdale, FL C/O: Mr. Sergio Adasme Re: VAMC - Renovate Corridors - Bldg. 1 - Floors 2- 3; 1201 NW 16th Street, Miami, FL
Date of Sampling: 06-07-2023 Date of Receipt: 06-13-2023 Date of Report: 06-14-2023
ASBESTOS PLM REPORT
Location: 7A, Light Brown w/ White Spots 12"x12" Vinyl Floor Tile w/ Black Mastic Lab ID-Version‡: 15961245-1
Sample Layers Asbestos Content Black Mastic ND
Light Brown Floor Tile ND Composite Non-Asbestos Content: 1% Cellulose Sample Composite Homogeneity: Moderate
Location: 7B, Light Brown w/ White Spots 12"x12" Vinyl Floor Tile w/ Black Mastic Lab ID-Version‡: 15961246-1
Sample Layers Asbestos Content Black Mastic ND
Light Brown Floor Tile ND Composite Non-Asbestos Content: 1% Cellulose Sample Composite Homogeneity: Moderate
Location: 7C, Light Brown w/ White Spots 12"x12" Vinyl Floor Tile w/ Black Mastic Lab ID-Version‡: 15961247-1
Sample Layers Asbestos Content Black Mastic ND
Light Brown Floor Tile ND Composite Non-Asbestos Content: 1% Cellulose Sample Composite Homogeneity: Moderate
Location: 8A, Grey w/ Black Dots 15"x15" Vinyl Floor Tile w/ Black Mastic and Brown Glue Lab ID-Version‡: 15961248-1
Sample Layers Asbestos Content Brown Glue ND Black Mastic 2% Chrysotile
Gray/Black Floor Tile ND Sample Composite Homogeneity: Moderate
EMLab ID: 3289043, Page 9 of 40Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Terracon - Fort Lauderdale, FL C/O: Mr. Sergio Adasme Re: VAMC - Renovate Corridors - Bldg. 1 - Floors 2- 3; 1201 NW 16th Street, Miami, FL
Date of Sampling: 06-07-2023 Date of Receipt: 06-13-2023 Date of Report: 06-14-2023
ASBESTOS PLM REPORT
Location: 8B, Grey w/ Black Dots 15"x15" Vinyl Floor Tile w/ Black Mastic and Brown Glue Lab ID-Version‡: 15961249-1
Sample Layers Asbestos Content Brown Glue ND Black Mastic 2% Chrysotile
Gray/Black Floor Tile ND Sample Composite Homogeneity: Moderate
Location: 8C, Grey w/ Black Dots 15"x15" Vinyl Floor Tile w/ Black Mastic and Brown Glue Lab ID-Version‡: 15961250-1
Sample Layers Asbestos Content Brown Glue ND Black Mastic 2% Chrysotile
Gray/Black Floor Tile ND Sample Composite Homogeneity: Moderate
Location: 9A, Pink w/ Black Dots 12"x12" Vinyl Floor Tile w/ Yellow Glue Lab ID-Version‡: 15961251-1
Sample Layers Asbestos Content Yellow Glue ND
Pink Floor Tile ND Sample Composite Homogeneity: Moderate
Location: 9B, Pink w/ Black Dots 12"x12" Vinyl Floor Tile w/ Yellow Glue Lab ID-Version‡: 15961252-1
Sample Layers Asbestos Content Yellow Glue ND
Pink Floor Tile ND Sample Composite Homogeneity: Moderate
EMLab ID: 3289043, Page 10 of 40Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Terracon - Fort Lauderdale, FL C/O: Mr. Sergio Adasme Re: VAMC - Renovate Corridors - Bldg. 1 - Floors 2- 3; 1201 NW 16th Street, Miami, FL
Date of Sampling: 06-07-2023 Date of Receipt: 06-13-2023 Date of Report: 06-14-2023
ASBESTOS PLM REPORT
Location: 9C, Pink w/ Black Dots 12"x12" Vinyl Floor Tile w/ Yellow Glue Lab ID-Version‡: 15961253-1
Sample Layers Asbestos Content Yellow Glue ND
Pink Floor Tile ND Sample Composite…
This is the start of the file's text. The full file is on GovTribe.