PROJECT NO.
JAMES H. QUILLEN VA MEDICAL CENTER
MOUNTAIN HOME, TENNESSEE
SITE PLAN
TITLE SHEET, AREA MAP
SITE PLAN, SHEET INDEX
GI-1
AREA MAP
SHEET INDEX
SYMBOLS ABBREVIATIONS
FIXTURE DESCRIPTIONS
PULLBOX
1/28/22
621-22-136
Update Mountain Home Site Lighting
GENERAL NOTES FOR PROJECT 621-22-136
1. AREAS OF WORK TO BE COMPLETED ARE CLOUDED.
2. DRAWINGS WITHOUT CONSTRUCTION CLOUDS ARE FOR
REFERENCE ONLY.
3. SEE CONSTRUCTION NOTES ON SHEET NUMBER ELS-7.
4. SEE FIXTURE SCHEDULES ON SHEET NUMBERS ELS-6 AND ELS-7.
5. FOR "Y" TYPE FIXTURES PROVIDE AND INSTALL SQUARE STRAIGHT
ALUMINUM POLES. MATCH NEARBY POLES IN HEIGHT, SHAFT SIZE,
COLOR, AND ACCESSORIES. PROVIDE LARGEST WALL THICKNESS
OFFERD FOR CORRESPONDING SHAFT SIZE.
621-22-136
Update Mountain Home Site Lighting
POLYMER CONCRETE PULL BOX 18" X 24" MINIMUM
LITHONIA FIXTURE #
KAD LED 40C 1000 40K R4 208
SPD12 PER5 PE1 DF DDB LPI
Y 6
OVERALL SITE PLAN
ESL-1
SITE PLAN
SEE ESL-2
SEE ESL-3
SEE ESL-5
SEE ESL-4
1/28/22
621-22-136
Update Mountain Home Site Lighting
PARTIAL SITE PLAN
ESL-2
KEY PLAN
8-44
1/28/22
621-22-136
Update Mountain Home Site Lighting
4 5
ESL-3
KEY PLAN
8-9
8-90B
1/28/22
621-22-136
Update Mountain Home Site Lighting
8-58A
8-90A
ESL-4
KEY PLAN
1/28/22
621-22-136
ESL-5
KEY PLAN
1/28/22
621-22-136
LIGHT FIXTURE SCHEDULES
ESL-6
SCHEDULE NOTES
621-22-136
Update Mountain Home Site Lighting
1/28/22
YY
8-58A 8-90A
8-90B MODERN-DOUBLE YY 282
LIGHT FIXTURE SCHEDULES
ESL-7
ANTIQUE POST FOUNDATION DETAIL
N.T.S
BOLT CENTERS FOR ANTIQUE POST
N.T.S (VERIFY EXACT SETTING WITH POLE PROVIDED)
CONSTRUCTION NOTES FOR PROJECT 621-22-136
THERE IS NO POWER AT EXISTING FIXTURE 116-1. INVESTIGATE AND TROUBLESHOOT EXISTING FIXTURE AND CIRCUITING. PROVIDE AND INSTALL NEW UNDERGROUND CONDUIT AND WIRE FROM
FIXTURE 116-2 TO 116-1. PROVIDE DIRECT BORE BENEATH ROADWAY, DO NOT CUT ASPHALT.
PROVIDE AND INSTALL POLYMER CONCRETE PULL BOX IF REQUIRED. MATCH EXISTING WIRE AND
CONDUIT SIZES.
CIRCUIT VOLTAGE FOR FIXTURES 8-35, 8-34, AND 8-30 IS ONLY 120 VOLTS BUT SHOULD BE 208 VOLTS.
INVESTIGATE AND TROUBLESHOOT EXISTING FIXTURES AND CIRCUITING. PROVIDE AND INSTALL NEW UNDERGROUND CONDUIT AND WIRE FOR THESE FIXTURES BACK TO EXISTING FIXTURE 8-37. PROVIDE AND INSTALL POLYMER CONCRETE PULL BOXES IF REQUIRED. MATCH EXISTING WIRE AND CONDUIT
SIZES.
THERE IS NO POWER AT EXISTING FIXTURE 8-44. INVESTIGATE AND TROUBLESHOOT EXISTING FIXTURE AND CIRCUITING. PROVIDE AND INSTALL NEW UNDERGROUND CONDUIT AND WIRE FROM EXISTING BROKEN POLYMER CONCRETE PULL BOX ON THE WEST SIDE OF FIXTURE 8-43. PROVIDE AND INSTALL NEW CONCRETE POLYMER PULL BOX IN PLACE OF THE BROKEN ONE. MATCH EXISTING
WIRE AND CONDUIT SIZES.
EXISTING FIXTURE 8-23 HAS BEEN REMOVED. PROVIDE AND INSTALL NEW POLE AND FIXTURES (Y).
EXTEND EXISTING CIRCUIT AS REQUIRED. MATCH EXISTING WIRE AND CONDUIT SIZES.
REPAIR DROOPING FIXTURE HEAD ON EXISTING FIXTURE 8-22.
EXISTING FIXTURE 200-17 IS LEANING. REMOVE POLE AND FIXTURES. RETURN FIXTURES TO THE VA AND REMOVE POLE FROM PREMISES. PROVIDE AND INSTALL NEW POLE AND FIXTURES (Y). EXTEND
EXISTING CIRCUIT AS REQUIRED. MATCH EXISTING WIRE AND CONDUIT SIZES.
PROVIDE AND INSTALL POLE, FIXTURES (Y), AND POLE BASE FOR NEW FIXTURES 8-90B. LOCATE AND INTERCEPT UNDERGROUND CONDUIT AND WIRE FROM EXISTING FIXTURE 8-90. PROVIDE AND INSTALL POLYMER CONCRETE PULL BOX AND FEED NEW FIXTURE. MATCH EXISTING WIRE AND CONDUIT SIZES.
DO NOT DISTURB CHRISTMAS TREE.
PROVIDE AND INSTALL POLE BASE FOR NEW FIXTURE 8-90A. ANTIQUE FIXTURE WILL BE PROVIDED BY
THE VA FOR CONTRACTOR INSTALLATION. LOCATE AND INTERCEPT UNDERGROUND CONDUIT AND
WIRE FROM EXISTING FIXTURE 8-90. PROVIDE AND INSTALL POLYMER CONCRETE PULL BOX AND FEED NEW FIXTURE. MATCH EXISTING WIRE AND CONDUIT SIZES. DO NOT DISTURB CHRISTMAS TREE.
PROVIDE AND INSTALL POLE BASE FOR NEW FIXTURE 8-58A. ANTIQUE FIXTURE WILL BE PROVIDED BY
THE VA FOR CONTRACTOR INSTALLATION. LOCATE AND INTERCEPT UNDERGROUND CONDUIT AND
WIRE FROM EXISTING FIXTURE 8-58. PROVIDE AND INSTALL POLYMER CONCRETE PULL BOX AND FEED NEW FIXTURE. MATCH EXISTING WIRE AND CONDUIT SIZES. DO NOT DISTURB CHRISTMAS TREE.
1/28/22
621-22-136
Update Mountain Home Site Lighting
SCHEDULE NOTES
MATCH EXISTING
WIRE AND CONDUIT
SIZES
" RGS
COUDUIT 60" OUT OF EACH
SIDE OF POLE BASE
VA PROVIDED ANTIQUE LIGHTING FIXTURE
MATCH EXISTING WIRE
AND CONDUIT SIZES
(1" RGS CONDUIT MINIMUM)
MATCH EXISTING WIRE
AND CONDUIT SIZES
(1" RGS CONDUIT MINIMUM)
1 #6 GND.
1" RGS CONDUIT
3/4" X 10' DRIVIEN
GROUND ROD
FINISHED GRADE
TYPE "Y" FIXTURE POLE BASE DETAIL
N.T.S.
YY
SQUARE
SIDE WITH #4 REINFORCING BARS" RGS CONDUIT (TYP)1
EXTEND 1