This document is a set of construction drawings and technical specifications for the replacement of the fire pump controller and associated equipment at the John D. Dingell VA Medical Center in Detroit, Michigan.

The key details are:

  • The project involves directly replacing the existing horizontal split case fire pump, in-line jockey pump, fire pump controller with automatic transfer switch, and all associated accessories.
  • The contractor shall provide a temporary fire pump system, piping, and all appurtenances as required for a fully functional system during construction.
  • All new fire protection equipment shall be UL listed or FM approved. The fire pump system shall comply with NFPA 20, NFPA 70, and VA fire protection requirements.
  • The solicitation number is 36C25024B0054, the project title is "Z1DA--Replace Fire Pump-Controller and ATS5 553-22-231", and the agency is the Department of Veterans Affairs, Veterans Health Administration, Veterans Integrated Service Network 10.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--Replace Fire Pump-Controller and ATS5 553-22-231, newest first.
File Type Posted
S02 Wage Determination - MI20240101 04 05 2024 - 553-22-231.pdf PDF
S02 Specifications - 553-22-231.pdf PDF
36C25024B0054_1.docx DOCX document
S02 RFI Form - 553-22-231.pdf PDF
S02 Contractor EMR Certification Form - 553-22-231.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

B ru sh S t

E Hancock St

Joh n R

S t

W oo d w ard A ve

C a s s A ve

E Canfield St

S t A n to in e

Mack Ave

In terstate 7

E W arre n Ave

Department of Veteran Affairs Medical Campus

N

102 101

Brush St

John R St

E C a n fie ld S t

E H a n c o c k S t

Building Key:

100 MAIN HOPSITAL

101 SOUTH PARKING GARAGE

- SOUTH GENERATING STATION

102 NORTH PARKING GARAGE

103 ENERGY CENTER

MEDICAL CENTER DIRECTOR

VA APPROVAL

DATE

DATEASSOCIATE MEDICAL CENTER DIRECTOR

DATECHIEF, FACILITY MANAGEMENT SERVICES

DATEASSISTANT CHIEF, FMS

DATESAFETY AND OCCUPATIONAL HEALTH MANAGER

DATEENERGY MANAGER

DIVISION 07 - THERMAL AND MOISTURE PROTECTION

SOLE SOURCE LIST

BRAND ITEM SPECIFICATION SECTION NOTES

HILTI FS1-FIRESTOP 07 84 00 BOTH SIDES OF FIRE-RATED WALLS, SMOKE BARRIERS, AND

FLOOR REGARDLESS OF FIRE RATING

DIVISION 07 - THERMAL AND MOISTURE PROTECTION

BRAND ITEM SPECIFICATION SECTION NOTES

SIEMENS BUILDING

TECHNOLOGIES

HVAC AUTOMATION

AND CONTROLS

23 09 23 ALL PROGRAMMING, CONNECTIONS, AND CONTROL PANELS

ASSOCIATED WITH CONNECTION TO AND MONITORING OF

THE STEAM SYSTEM BY THE CENTRAL MONITORING SYSTEM.

ST

A

T E O F F L O R

ID

A

RE

G

IS

T E R E D A R C H

IT

EC

T

ROGE

R A R E P

ST

IEN

A R

VA Project No.

RDC/JPA Project No.

Department of Veterans Affairs Medical Center

ARCHITECTURE PLANNING INTERIOR DESIGN

524 FERNWOOD AVENUE

ALTAMONTE SPRINGS, FLORIDA 32701

407.830.6522 P

937.461.0260 F

RDC / JOHN POE ARCHITECTS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

ABOVE GROUP

ENGINEERING

70 BIRCH ALLEY, SUITE 240

BEAVERCREEK, OHIO 45440

70 Birch Alley, Suite 240 Beavercreek OH, 45440

PH: 937.795.4440

www.abovegroupinc.com COA/CA Lic. No. 31120

:1

:4

P

M

FIRE PUMP CONTROLLER

REPLACEMENT

06.23.2023

COVER SHEET

G-001

MDMD

533-22-231

DETROIT VAMC

FIRE PUMP CONTROLLER REPLACEMENT

4646 JOHN R STREET DETROIT, MI 48201-1916 PROJECT #:533-22-231

John D. Dingell VA Medical

Center

BID DOCUMENTS 22017.00

GENERAL CONSTRUCTION NOTES

* PLEASE NOTE THAT THE TERM PROJECT ENGINEER REFERS TO THE

CONTRACTING OFFICER'S REPRESENTATIVE (C.O.R.).

1. ALL WORK SHALL COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE,

INTERNATIONAL BUILDING CODE, AND OTHER COES AS IDENTIFIED IN VHA

PROGRAM GUIDE PG-18-3, TOPIC 01, CODES, STANDARDS AND EXECUTIVE

ORDERS WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERAN AFFAIRS,

TECHNICAL INFORMATION LIBRRARY WEBSITE.

2. ALL EXPOSED NEW WORK IS TO RECEIVE NEW FINISHES UNLESS

SPECIFICALLY NOTED OTHERWISE. IF NO FINISH IS INDICATED AT A

PARTICULAR SURFACE, CONTRACTOR SHALL PROVIDE FINISH(S) AS

INDICATED AT SIMILAR CONDITIONS.

3. CONTRACTOR IS RESPONSIBLE TO VISIT THE SITE, EXAMINE AND ACCEPT

EXISTING CONDITIONS PRIOR TO BIDDING. SITE VISITS TO BE COORDINATED

WITH THE CONTRACTING OFFICER'S REPRESENTATIVE.

4. CONTRACTOR IS RESPONSIBLE TO REPAIR AND/OR REFINISH, TO MATCH

ADJACENT EXISTING SURFACES, ANY EXISTING MATERIALS TO REMAIN THAT

ARE DAMAGED DURING THE COURSE OF DEMOLITION OR NEW WORK.

5. WHERE REMOVAL OF EXISTING WORK IS REQUIRED FOR INSTALLATION OF

NEW WORK, CONTRACTOR SHALL REPAIR EXISTING CONSTRUCTION TO

REMAIN OR PROVIDE NEW CONSTRUCTION TO MATCH EXISTING ADJACENT

SURFACES TO REMAIN.

DRAWING INDEX

VICINITY MAP

6. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL CONDITIONS AND

DIMENSIONS PRIOR TO ORDERING, FABRICATING OR INSTALLING NEW

MATERIALS.

7. CONTRACTOR IS RESPONSIBLE TO VERIFY SIZES OF ALL EQUIPMENT, ETC. TO

BE INSTALLED AS PART OF THIS PROJECT, AND WHERE NECESSARY, MAKE

SPECIAL PROVISIONS TO INSTALL EQUIPMENT THAT IS TOO LARGE TO FIT

THROUGH FINISHED OPENINGS.

8. FIRE PROTECTION CONTRACTOR'S SPRINKLER DESIGN WILL BE SUBJECT TO

AN INDEPENDENT REVIEW BY A CERTIFIED FIRE PROTECTION ENGINEER

RETAINED BY THE OWNER. THE FIRE PROTECTION CONTRACTOR IS

RESPONSIBLE FOR MAKING ANY REQUIRED CHANGES TO THE DESIGN AS

IDENTIFIED BY THE OWNER'S FIRE PROTECTION ENGINEER AS NECESSARY

FOR COMPLIANCE WITH SPECIFIED NFPA REQUIREMENTS.

9. CONTRACTOR SHALL PROVIDE COMPLETE AND FULLY OPERATIONAL

SYSTEMS WHICH COMPLY WITH STATED CODES AND REGULATIONS. WHERE

THE OMISSION OF A PART OR ELEMENT OF A SYSTEM WOULD RESULT IN THE

NON-OPERATION, OR INCORRECT OPERATION OF A SYSTEM, CONTRACTOR

SHALL INCLUDE SAID PART OR ELEMENT AS PART OF THE WORK.

10. ALL PENETRATIONS THROUGH NEW AND/OR EXISTING SMOKE OR FIRE RATED

WALLS SHALL BE SMOKE/FIRE STOPPED AS REQUIRED BY THE RATING OF

THE WALL.

Revisions Date

G-000 Cover Sheet

FP-001 Fire Protection Legends, Symbols & General Notes

FP-101 Fire Protection Basement Plan-Boiler Rm

FP-801 Fire protection Schedules

E-001 Electrical Legends, Symbols & General Notes

EP101 Electrical 1st Floor Plan & Basement Plan – Boiler Room

E-601 Electrical Schedules, Detail and Oneline Diagram

G-001 Cover Sheet

FP-001 Fire Protection Legends, Symbols & General Notes

FP-100 Fire Protection Site Plan

FP-101 Fire Protection Basement Plan-Boiler Rm

FP-801 Fire protection Schedules

E-001 Electrical Legends, Symbols & General Notes

EP101 Electrical 1st Floor Plan & Basement Plan – Boiler Room

E-601 Electrical Schedules, Detail and Oneline Diagram

FIRE PROTECTION LEGEND

NOTE: SOME ABBREVIATIONS AND SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT

GENERAL LEGEND

SYMBOL DESCRIPTION

OS&Y VALVE FIRE DEPARTMENT CONNECTION

FIRE PROTECTION RISER

GATE VALVE

ALARM CHECK VALVE

BALL VALVE

PRESSURE REGULATING VALVE

BUTTERFLY VALVE

FLOW SWITCH

SYMBOL DESCRIPTION

PIPE TURNING DOWN

PIPE TURNING UP

FS FLOW SWITCH

TS TAMPER SWITCH

HOSE HOSE LINE CABINET

LH LIGHT HAZARD

OH-1 ORDINARY HAZARD - GROUP 1

OH-2 ORDINARY HAZARD - GROUP 2

POINT OF CONNECTION

FLUSHING CONNECTION OR CAP

A

B

SIM

FP

SECTION SYMBOL:

A = IDENTIFYING LETTER

B = SHEET WHERE SECTION IS SHOWN

SIM = SIMILAR

(ONLY NOTED IF IT APPLIES)

FIRE PROTECTION RISER DESIGNATION:

A = RISER IDENTIFYING SYSTEM TYPE

1 =

REVISION CLOUD AND

REVISION NUMBER

A

TITLE SYMBOL ON SHEET WHERE SHOWN

A = IDENTIFYING NUMBER/LETTER

RISER IDENTIFYING SYSTEM NUMBER

SYMBOL DESCRIPTION

FIRE PROTECTION COMPLIANCE NOTES

FIRE PROTECTION ABBREVIATIONS

AS ABOVE SLAB

AFF ABOVE FINISHED FLOOR

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

ASTM AMERICAN STANDARDS TESTING MATERIALS

ATS AUTOMATIC TRANSFER SWITCH

BFP BACKFLOW PREVENTER

BOR BOTTON OF RISER

BS BELOW SLAB

CAP CAPACITY

CONN CONNECTION

CONT CONTINUOUS

CV CHECK VALVE

DIA DIAMETER

DN DOWN

ELEV ELEVATION

ºF DEGREES FAHRENHEIT

FDC FIRE DEPARTMENT CONNECTION

FDV FIRE DEPARTMENT VALVE

FM FACTORY MUTUAL

FP FIRE PROTECTION

FP FIRE PUMP

FPC FIRE PUMP CONTROLLER

FS FLOW SWITCH

FT FEET

GA GAUGE

GAL GALLON(S)

GALV GALVANIZED

GPM GALLONS PER MINUTE

HD HEAD

HP HORSEPOWER

HR HOUR

HYD HYDRANT

HZ HERTZ

ID INTERNAL DIAMETER

IN INCHES

IPS INTERNATIONAL PIPE STANDARD

ABBR. DESCRIPTION ABBR. DESCRIPTION

JP JOCKEY PUMP

KW KILOWATT

MAX MAXIMUM

MIN MINIMUM

NA NOT APPLICABLE

NC NORMALLY CLOSED

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NTS NOT TO SCALE

OD OUTSIDE DIAMETER

OS&Y OUTSIDE SCREW AND YOLK

P PUMP

PH PHASE

POC POINT OF CONNECTION

PSI POUNDS PER SQUARE INCH

PS PRESSURE SWITCH

RPM REVOLUTIONS PER MINUTE

SF SQUARE FEET

SPEC SPECIFICATIONS

STD STANDARD

TEMP TEMPERATURE

TDH TOTAL DYNAMIC HEAD

TOR TOP OF RISER

TS TAMPER SWITCH

TYP TYPICAL

UG UNDERGROUND

UL UNDERWRITER'S LABORATORY

UNO UNLESS NOTED OTHERWISE

V VOLTS

VA U.S. DEPARTMENT OF VETERAN AFFAIRS

VLV VALVE

VOL VOLUME

W/ WITH

FIRE PROTECTION GENERAL NOTES

SCOPE OF WORK:

FIRE PROTECTION SPRINKLER CONTRACTOR SHALL DIRECTLY REPLACE THE EXISTING HORIZONTAL SPLIT CASE FIRE PUMP, IN-LINE JOCKEY PUMP, FIRE PUMP CONTROLLER WITH AUTOMATIC TRANSFER SWITCH, AND ALL ASSOCIATED ACCESSORIES. THE FIRE PUMP SYSTEM IS SERVING THE JOHN D. DINGELL VA MEDICAL CENTER AND IS

LOCATED IN THE ENERGY CENTER BASEMENT WATER SERVICE ROOM.

ALL EXISTING FIRE PROTECTION SHALL REMAIN FULLY ACTIVE AND ANY SPRINKLER IMPAIRMENTS SHALL COMPLY WITH NFPA 25 SECTION 15.5.2. CONTRACTOR SHALL PROVIDE A TEMPORARY FIRE PUMP SYSTEM, PIPING, AND ALL APPURTENANCES AS REQUIRED FOR A FULLY FUNCTIONAL SYSTEM . CONTRACTOR SHALL COORDINATE ANY REQUIRED SHUT-DOWNS WITH COR PRIOR TO START OF DEMOLITION. REFER TO SHEET FP100 FOR ADDITIONAL

INFORMATION.

FIRE PROTECTION SPRINKLER CONTRACTOR SHALL COORDINATE THE DESIGN AND INSTALLATION OF THE FIRE PROTECTION SPRINKLER SYSTEM AND DELIVER A COMPLETE, FULLY FUNCTIONAL, AND TESTED FIRE PUMP SYSTEM THAT MEETS THE REQUIREMENTS OF THE FIRE PROTECTION DRAWINGS, FIRE PROTECTION SPECIFICATIONS, LISTED CODES AND STANDARDS, AND THE REQUIREMENTS OF THE VA. THE FIRE PROTECTION SPRINKLER CONTRACTOR SHALL PROVIDE AND INSTALL NEW MATERIALS THAT ARE UL LISTED AND/OR FM APPROVED AS REQUIRED BY THE FIRE PROTECTION DRAWINGS AND THE FIRE PROTECTION SPECIFICATIONS. THE FIRE PROTECTION SPRINKLER CONTRACTOR SHALL INTEGRATE THE FIRE PUMP SYSTEM WITH THE EXISTING FIRE ALARM SYSTEM.

FLOW TEST DATA:

THE NEW FIRE PUMP AND JOCKEY PUMP SHALL BE DIRECT REPLACEMENTS OF THE EXISTING FIRE PUMP AND JOCKEY PUMP. THE PUMPS ARE SIZED BASED ON THE FOLLOWING FIRE PUMP TEST RESULTS PERFORMED BY JOHNSON CONTROLS FIRE PROTECTION PEERLESS MIDWEST, INC. ON 08/30/2022. CONTRACTOR SHALL OBTAIN THE LATEST FIRE PUMP TEST RESULTS WITHIN THE PREVIOUS 12 MONTHS PRIOR TO CONSTRUCTION.

INCOMING WATER SUPPLY: 46 PSI AT CHURN (NO FLOW); 46 PSI AT 100% FLOW; 44 PSI AT 150% FLOW.

FIRE PUMP: 123 PSI NET (169 PSI TOTAL) AT CHURN (NO FLOW); 121 PSI NET (167 PSI TOTAL) AND 756 GPM AT 100%

FLOW; 89 PSI NET (133 PSI TOTAL) AND 1134 GPM AT 150% FLOW.

QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL FIRE PROTECTION COMPONENTS:

ALL NEW FIRE PROTECTION EQUIPMENT SHALL BE UL LISTED OR FM APPROVED.

ACCEPTANCE TEST CRITERIA:

THE FIRE PUMP SHALL BE DEDICATED AND LISTED FOR FIRE PROTECTION SERVICE. FIRE PUMP SHALL BE DESIGNED PER NFPA 20, 2022 EDITION AND COMPLY WITH THE LOCAL FIRE MARSHAL AND THE VA. THE FIELD ACCEPTANCE TEST OF THE FIRE PUMP AND IT'S COMPONENTS SHALL CONSIST OF ALL APPLICABLE ITEMS SHOWN ON THESE FORMS, NFPA 20 ANNEX A (FIGURE A.14.1.3) CONTRACTOR'S MATERIAL AND TEST CERTIFICATE FOR FIRE PUMP SYSTEMS. SEE NFPA 20 CHAPTER 14 FOR SYSTEM

ACCEPTANCE, INSPECTION TESTING, AND MAINTENANCE.

1. NFPA 20 2022 CHAPTER 14, ACCEPTANCE TESTING, PERFORMANCE, AND MAINTENANCE

A. 14.1 HYDROSTATIC TESTS AND FLUSHING

B. 14.2 FIELD ACCEPTANCE TESTS

C. 14.3 RECORD DRAWINGS, TEST REPORTS, MANUALS, SPECIAL TOOLS, AND SPARE PARTS

D. 14.4 PERIODIC INSPECTION, TESTING, AND MAINTENANCE

E. 14.5 COMPONENT REPLACEMENT

APPLICABLE NFPA AND VA STANDARDS TO BE APPLIED:

1. VA FIRE PROTECTION DESIGN MANUAL - 8TH EDITION

2. INTERNATIONAL BUILDING CODE 2021 EDITION

3. NFPA 13, 2022 EDITION, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS

4. NFPA 20, 2022 EDITION, STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION

5. NFPA 25, 2023 EDITION, INSPECTION, TESTING AND MAINTENANCE OF WATER BASED FIRE PROTECTION SYSTEM

6. NFPA 70, 2023 EDITION, NATIONAL ELECTRICAL CODE

1. THE FIRE PUMP SYSTEM SHALL COMPLY WITH NFPA 20, NFPA 70, AND VA FIRE PROTECTION MANUAL.

INSPECTION, TESTING, AND MAINTENANCE SHALL COMPLY TO NFPA 20 CHAPTER 14. IN ADDITION, INSTALLATION AND INSPECTION, TESTING, AND MAINTENANCE SHALL COMPLY WITH THE PROJECT

SPECIFICATIONS AND ALL APPLICABLE VA REQUIREMENTS.

2. FINAL INSPECTION AND APPROVAL BY THE VA.

3. CUTTING OF STRUCTURAL AND/OR ARCHITECTURAL MEMBERS IS PROHIBITED.

4. FITTINGS REQUIRED FOR PROPER INSTALLATION, COORDINATION WITH OTHER EXISTING TRADES, AND/OR TO

MAINTAIN PROPER CLEARANCES SHALL BE PROVIDED. VERIFY STRUCTURAL, MECHANICAL, ELECTRICAL

INSTALLATIONS AND AVOID AN/ALL OBSTRUCTIONS OR INTERFERENCES WITH FIRE PUMP.

5. IMMEDIATELY NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES FOUND BETWEEN THESE PLANS, OTHER ENGINEERING PLANS, THE ARCHITECTURAL PLANS AND/OR FIELD CONDITIONS PRIOR TO FINAL BID

PRICE OR FINAL PERMITTING.

6. IN CASE OF DISPUTE OR DOUBT AS TO INTENT OF DRAWINGS OR SPECIFICATIONS, OBTAIN ARCHITECT/ENGINEER'S WRITTEN DECISION BEFORE PROCEEDING WITH BID OR WORK INVOLVED.

7. ALL EXPOSED PIPING SHALL BE SHALL BE PAINTED RED.

8. BEFORE SUBMITTING PROPOSAL OR BID, EXAMINE ALL DRAWINGS AND SPECIFICATIONS RELATING TO THIS

PROJECT, THE AMOUNT OF SPACE AVAILABLE FOR PIPING AND CONNECTING SERVICES, THE SCOPE OF SITE OF THE WORK, THE REQUIREMENTS TO CORRELATE THE FIRE PROTECTION WORK WITH THAT OF OTHER

TRADES AND THE TIME SCHEDULE NECESSARY TO PERFORM THAT WORK.

9. PIPE SHALL BE REAMED AND CLEANED BEFORE ASSEMBLY, AND AFTER ASSEMBLY THE ENTIRE PIPING

SYSTEM SHALL BE HYDROSTATICALLY TESTED AND FLUSHED PER NFPA 20 CHAPTER 14.1.

10. ALL EXISTING FIRE PROTECTION SHALL REMAIN ACTIVE AT ALL TIMES. CONTRACTOR SHALL COORDINATE ANY REQUIRED SHUT-DOWN WITH COR PRIOR TO START OF DEMOLITION. UPON SPRINKLER SYSTEM IMPAIRMENT, 2023 NFPA 25 SECTION 15.5.2 SHALL BE FOLLOWED DURING SPRINKLER SYSTEM DOWNTIME.

THE COR OR APPROVED PERSONNEL BY THE VA SHALL COORDINATE REQUIREMENTS PER NFPA 25, SUCH AS AN APPROVED FIRE WATCH IF REQUIRED. IMPAIRMENT PROCEDURES REQUIRED TO BE TAKEN SHALL BE

INCLUDED IN CONTRACTOR'S BUDGET.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

B

IM

/0

R e p la c e

F ir e

P u m p

C o n tr o lle r D e s ig n /0

R e p la c e

F ir e

P u m p C o n tr o lle r

R

E

.r v t

/2

/2

:3

:5

P

M

FP001

FIRE PROTECTION LEGENDS,

SYMBOLS & GENERAL NOTES

FIRE PUMP CONTROLLER

REPLACEMENT

DETROIT, MICHIGAN

553-22-231

06/23/2023 ADL KDB

100% BID DOCUMENTS

SHEET LIST

SHEET NUMBER SHEET NAME

FP001 FIRE PROTECTION LEGENDS, SYMBOLS & GENERAL NOTES

FP100 FIRE PROTECTION SITE PLAN

FP101 FIRE PROTECTION BASEMENT PLAN - BOILER RM

FP801 FIRE PROTECTION SCHEDULES

Revisions Date

S

EXISTING CENTRAL ENERGY PLANT

E H

A N

C O

C K

S T

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

B

IM

/0

R e p la c e

F ir e

P u m p

C o n tr o lle r D e s ig n /0

R e p la c e

F ir e

P u m p C o n tr o lle r

R

E

.r v t

/2

/2

:3

:5

P

M

FP100

FIRE PROTECTION SITE PLAN FIRE PUMP CONTROLLER

REPLACEMENT

DETROIT, MICHIGAN

553-22-231

06/23/2023 ADL KDB

100% BID DOCUMENTS

Revisions Date

1/16" = 1'-0"

TEMPORARY FIRE PROTECTION SITE PLAN

CODED NOTES:

DRAWING NOTES:

1. THIS PLAN IS TO DISPLAY THE PREPLANNED IMPAIRMENT PROGRAM FOR A TEMPORARY WATER SUPPLY PER NFPA 25 - 15.5.2(4)(C). TEMPORARY PIPING IS SHOWN DIAGRAMMATICALLY AS A SINGLE

LINE. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH TEMPORARY FIRE PUMP

MANUFACTURER'S CERTIFIED DRAWINGS. TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND

PROVIDED FOR EQUIPMENT FURNISHED.

2. CONTRACTOR SHALL PROVIDE THE VA WITH A TEMPORARY WATER SUPPLY IMPAIRMENT PROGRAM.

IMPAIRMENT PROCEDURES REQUIRED TO BE TAKEN SHALL BE INCLUDED IN CONTRACTOR'S

BUDGET. THE PROGRAM SHALL BE APPROVED BY THE VA AND SHALL INCLUDE, BUT IS NOT LIMITED

TO:

A. 750-HP TEMPORARY MOBILE FIRE PUMP SYSTEM, TEMPORARY PIPING, AND ALL ANCILLARY

EQUIPMENT REQUIRED FOR A COMPLETE AND PROPER OPERATION. TEMPORARY PIPING SHALL

BE CONNECTED TO THE NEAREST FIRE HYDRANT. REFER TO THE TEMPORARY FIRE PROTECTION

SITE PLAN FOR PROPOSED PIPING. TEMPORARY PIPING SHALL CONNECT TO THE EXISTING

SPRINKLER SYSTEM UTILIZING THE EXISTING SYSTEM ISOLATION VALVES. NEW BYPASS

ISOLATION VALVE AND CHECK VALVE (SHOWN VIEW 4 / FP101) SHALL BE REPLACED PRIOR TO

OPERATING THE TEMPORARY FIRE PUMP.

B. TEMPORARY FIRE PUMP SYSTEM SHALL INTERFACE WITH THE EXISTING FIRE ALARM SYSTEM IN

ACCORDANCE WITH NFPA 72 CHAPTER 23.8 "SYSTEM REQUIREMENTS" OR PROVIDE A

TEMPORARY ALARM NOTIFICATION APPROVED BY THE VA.

C. MAKE ALTERATIONS TO THE EXISTING FACILITY AS REQUIRED FOR THE PROPER AND COMPLETE

OPERATION OF THE TEMPORARY WATER SUPPLY. ALTERNATIONS SHALL NOT INTERFERE WITH

THE NORMAL OPERATIONS OF THE FACILITY OR WITH THE ARCHITECTURAL AND STRUCTURAL

INTEGRITY OF THE BUILDING. ALL ALTERATIONS SHALL BE APPROVED AND COORDINATED WITH

THE VA PRIOR TO THE COMMENCEMENT OF WORK.

D. IF AT ANY TIME IT IS FOUND THAT THE TEMPORARY WATER SERVICE DOES NOT MEET THE VA

APPROVED TEMPORARY WATER SERVICE PROGRAM AND THERE WAS NO VARIANCE APPROVAL,

THE CONTRACTOR SHALL CORRECT IT AT NO ADDITIONAL COST OR TIME TO THE GOVERNMENT.

EXISTING FIRE PUMP TEST HEADER.

EXISTING FIRE DEPARTMENT CONNECTION (FDC).

TEMPORARY FIRE PUMP. PUMP SHALL MATCH NEW PUMP SPECIFICATIONS. FINAL TEMPORARY PUMP LOCATION SHALL BE COORDINATED WITH THE VA. ESTIMATED FIRE PUMP TRAILER SIZE: 30' x 10'.

EXISTING FIRE HYDRANT.

TEMPORARY PIPING FROM FIRE HYDRANT TO TEMPORARY FIRE PUMP. TEMPORARY FIRE PUMP SHALL

BE EQUIPPED WITH A DOUBLE CHECK BACKFLOW PREVENTER. APPROXIMATELY 200 FT. OF

TEMPORARY PIPING. FINAL PIPING LAYOUT SHALL BE COORDINATED WITH VA.

TEMPORARY PIPING FROM TEMPORARY FIRE PUMP TO EXISTING FDC.

TEMPORARILY REMOVE EXISTING FENCING AS REQUIRED FOR TEMPORARY PIPING. FENCING SHALL BE

SAFELY STORED DURING CONSTRUCTION AND RE-INSTALLED AFTER TEMPORARY FIRE PUMP IS

DISCONNECTED. PAINT, REPAIR, OR REPLACE DAMAGED FENCING AS REQUIRED FOR LIKE-NEW

CONDITION.

0 8' 16' 32' 48'

1/16" = 1'-0"

N

BID ALTERNATE:

1. CONTRACTOR SHALL SUBMIT A BID ALTERNATE FOR A FIRE WATCH IMPAIRMENT PROGRAM. THE ALTERNATE PROGRAM SHALL BE APPROVED BY THE VA AND SHALL INCLUDE, BUT IS NOT LIMITED TO:

A. FIRE WATCH PERSONNEL SHALL MONITOR THE OPERATION OF THE JOCKEY PUMP AT ALL TIMES

WHEN THE FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN 10 HOURS IN A 24

HOUR PERIOD PER NFPA 25 CHAPTER 15. FIRE WATCH PERSONNEL SHALL BE TRAINED TO BE

FAMILIAR WITH THE FACILITIES AND PROCEDURES. TRAINING AT A MINIMUM SHALL INCLUDE:

a. SOUNDING AN ALARM IN THE EVENT OF A FIRE.

b. FIRE-EXTINGUISHING USE AND FIRE-EXTINGUISHING EQUIPMENT SHALL BE READILY

AVAILABLE.

c. INVESTIGATING THE SYSTEM PRESSURE IF THE JOCKEY PUMP DOES NOT CEASE OPERATION

AT THE END OF ITS ANTICIPATED RUN TIME.

d. NOTIFYING THE FIRE DEPARTMENT, THE BUILDING OCCUPANTS, OR BOTH OF AN EMERGENCY

IF THE SYSTEM PRESSURE DROPS BELOW A SET POINT.

B. 7.5-HP TEMPORARY JOCKEY PUMP SYSTEM, TEMPORARY PIPING, AND ALL ANCILLARY

EQUIPMENT AS REQUIRED TO MAINTAIN JOCKEY PUMP OPERATION DURING CONSTRUCTION. THE

TEMPORARY JOCKEY PUMP SYSTEM SHALL BE USED DURING THE REMOVAL OF THE EXISTING

FIRE PUMP SYSTEM AS SHOWN ON THE DRAWINGS. ONCE THE NEW FIRE PUMP SYSTEM IS

INSTALLED AND FULLY TESTED PER 2022 NFPA 20 CHAPTER 14, ALL TEMPORARY EQUIPMENT AND

PIPING SHALL BE COMPLETELY REMOVED.

C. IF AT ANY TIME IT IS FOUND THAT THE FIRE WATCH DOES NOT MEET THE VA APPROVED FIRE

WATCH PROGRAM AND THERE WAS NO VARIANCE APPROVAL, THE CONTRACTOR SHALL

CORRECT IT AT NO ADDITIONAL COST OR TIME TO THE GOVERNMENT.

FP100

N.T.S.

EXISTING FIRE SPRINKLER CONNECTIONS PHOTO #1

DN

F

EX

FP-1

EX

JP-1

EX 8" FM

EX 8" FM

EX 8" FM

F M

(U /G

FP101

EX 2" FM

FP101

KEY PLAN - BASEMENT

F

EX 8" FM

EX 8" FM

EX 6" FM

EX 8" FM EX 6" FM

EX 8" FM

FP-1

EX 8" FM

FPC-1

JPC-1

F

FP101

EX 8" FM

EX 2" FM

EX 8" FM

EX 8" FM

F M

(U /G

JP-1 FP-1

FPC-1

6" FM

6" FM

JPC-1

FP101

F

EX 6" FM

EX 6" FM

EX 2" FM

JP-1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

B

IM

/0

R e p la c e

F ir e

P u m p

C o n tr o lle r D e s ig n /0

R e p la c e

F ir e

P u m p C o n tr o lle r

R

E

.r v t

/2

/2

:3

:0

P

M

FP101

FIRE PROTECTION BASEMENT

PLAN - BOILER RM

FIRE PUMP CONTROLLER

REPLACEMENT

DETROIT, MICHIGAN

553-22-231

06/23/2023 ADL KDB

100% BID DOCUMENTS

1/4" = 1'-0"1

FIRE PROTECTION PLAN - BASEMENT - WATER SERVICE RM - DEMO

CODED NOTES:

DRAWING NOTES:

1. CONTRACTOR SHALL COORDINATE REQUIRED SHUT-DOWNS WITH FACILITY PRIOR TO START OF DEMOLITION. UPON SPRINKLER SYSTEM IMPAIRMENT, NFPA 25 CHAPTER15.5.2 SHALL BE FOLLOWED DURING SPRINKLER SYSTEM DOWNTIME. COORDINATE WITH FACILITY ON THE REQUIREMENTS OF

NFPA 25, SUCH AS AN APPROVED TEMPORARY WATER SUPPLY OR FIRE WATCH. IMPAIRMENT

PROCEDURES REQUIRED TO BE TAKEN SHALL BE INCLUDED IN CONTRACTOR'S BUDGET.

2. NOT ALL PIPING SYSTEMS ARE SHOWN ON THIS DRAWING.

3. EXISTING FIRE PROTECTION PIPING IS SHOWN FOR REFERENCE ONLY AND IS BASED ON LIMITED EXISTING DOCUMENTATION AND FIELD VERIFICATION. THE CONTRACTOR SHALL CONFIRM SIZE OF ALL EXISTING PIPING LOCATED WITHIN THE PROJECT SCOPE BOUNDARY PRIOR TO FABRICATION OF

ANY PIPING SHOWN ON PLANS.

REPLACE EXISTING FIRE PUMP, TRANSITION FITTINGS, AND PUMP APPURTENANCES. 1

0 2' 4' 8' 12'

1/4" = 1'-0"

N

1/4" = 1'-0"

FIRE PROTECTION WATER SERVICE ROOM - BASEMENT - SECTION 1

1/4" = 1'-0"2

FIRE PROTECTION PLAN - BASEMENT - WATER SERVICE RM - NEW WORK

N.T.S.

EXISTING FIRE PUMP PHOTO #1

REPLACE EXISTING JOCKEY PUMP AND PUMP APPURTENANCES. 2

REPLACE EXISTING FIRE PUMP CONTROLLER WITH ATS. REFER TO ELECTRICAL DRAWINGS FOR

ADDITIONAL INFORMATION.

EXISTING CONCRETE PAD TO REMAIN. CLEAN AND REPAIR EXISTING PAD AS REQUIRED FOR NEW FIRE

PUMP SYSTEM.

EXISTING (3) 2-1/2" OUTLET PUMP TEST HEADER.5

EXISTING 2-1/2"x2-1/2"x2-1/2"x6" FLUSH FDC.6

Revisions Date

REPLACE FAILING 8" BYPASS CHECK VALVE AND 8" BYPASS GROOVED BUTTERFLY VALVE WITH TAMPER SWITCH. REFER TO FIRE PUMP TEST REPORT PERFORMED BY JOHNSON CONTROLS FIRE PROTECTION

PEERLESS MIDWEST, INC. FOR TEST COMMENTS.

1/4" = 1'-0"

FIRE PROTECTION WATER SERVICE ROOM - BASEMENT - SECTION 2

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

B

IM

/0

R e p la c e

F ir e

P u m p

C o n tr o lle r D e s ig n /0

R e p la c e

F ir e

P u m p C o n tr o lle r

R

E

.r v t

/2

/2

:3

:0

P

M

FP801

FIRE PROTECTION SCHEDULES FIRE PUMP CONTROLLER

REPLACEMENT

DETROIT, MICHIGAN

553-22-231

06/23/2023 ADL KDB

100% BID DOCUMENTS

PUMP SCHEDULE

MARK

BASIS OF DESIGN

SYSTEM

FLUID DATA PUMP DATA ELECTRICAL DATA

MANUFACTURER MODEL NO. FLOW (GPM) HEAD (PSI)

FLUID TEMP.

(°F) TYPE MOTOR HP MOTOR RPM NPSHR (FT)

IMPELLER

DIA. (IN.) % EFF.

SUCT. SIZE

(IN.)

DISCH. SIZE

(IN.) DISCONNECT V/PH/HZ

FP-1 AC FIRE PUMP 6x6x9F 8100 SERIES FIRE MAIN 750 120 49 HORIZONTAL SPLIT CASE 75 3550 8.26 9.24 68.8 6 6 FPC-1 460/3/60

JP-1 GRUNDFOS CR 10-7 FIRE MAIN 60 130 49 VERTICAL MULTISTAGE 7.5 3461 12.1 3.66 68.5 2 2 JPC-1 460/3/60

NOTES:

1. PROVIDE SINGLE POINT ELECTRICAL CONNECTION.

2. PROVIDE MOTOR STARTER WITH DISCONNECTING MEANS. REFER TO CONTROLLER SCHEDULE.

3. FIRE PUMP SHALL FURNISH NOT LESS THAN 150% OF THE RATED FLOW CAPACITY AT NOT LESS THAN 65% OF RATED NET PRESSURE.

4. PROVIDE STAINLESS STEEL IMPELLER.

FIRE PUMP CONTROLLER SCHEDULE

MARK

BASIS OF DESIGN

TYPE

DIMENSIONS

(WxDxH)

AUTOMATIC

TRANSFER

SWITCH TEST BUTTON

START/STOP

BUTTON HORN BUTTON

ELECTRICAL

NOTESMANUFACTURER MODEL NO. ENCLOSURE MOTOR HP V/PH/HZ

FPC-1 METRON MP435 AUTOMATIC SOLID STATE SOFT STARTER W/ ATS 74"x16"x71" YES YES YES YES NEMA 2 75 460/3/60 1,2,3,4,5,6,7

JPC-1 METRON MP15 ACROSS-THE-LINE STARTER 16.5"x10"x22" NO NO MANUAL HOA NO NEMA 2 7.5 460/3/60 1,2,4

NOTES:

1. PROVIDE SINGLE POINT ELECTRICAL CONNECTION.

2. PROVIDE MOTOR STARTER WITH DISCONNECTING MEANS.

3. PROVIDE ATS INTEGRAL TO FIRE PUMP CONTROLLER FOR USE WITH GENSET.

4. PROVIDE TERMINALS FOR REMOTE MONITORING AND USB PORT FOR INFORMATION DOWNLOAD.

5. PROVIDE DIGITAL DISPLAY WITH READOUTS FOR VOLTAGE, AMPERAGE, AND FREQUENCY.

6. PROVIDE VOLTAGE SURGE SUPPRESSION.

7. PROVIDE AUDIBLE HORN WITH SILENCING FEATURE FOR TESTING.

1PH SINGLE-PHASE

3PH THREE-PHASE

4W FOUR-WIRE

A/E ARCHITECT/ENGINEER

AF AMPERE FRAME OR AMP FUSE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMP AMPERE

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BLDG BUILDING

C CONDUIT

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CKT CIRCUIT

CLG CEILING

COAX COAX CABLE

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUE

COORD COORDINATE

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CU COPPER

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DISC DISCONNECT

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DS DISCONNECT SWITCH

DWG DRAWING

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

ESMT EASEMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

ETR EXISTING TO REMAIN

ELECTRICAL ABBREVIATIONS

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FLA FULL LOAD AMPS

FP FIRE PROTECTION

FT FEET OR FOOT

GND GROUND

G OR GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HZ HERTZ

IESNA ILLUMINATION ENGINEERING SOCIETY OF NORTH AMERICA

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

kV KILOVOLT kVA KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWH KILOWATT HOUR

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LRA LOCKED ROTOR AMPS

LTG LIGHTING

LV LOW VOLTAGE

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT MICROWAVE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NEUT OR N NEUTRAL

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

P POLE

PA PUBLIC ADDRESS

PCB POLYCHLORINATED BIPHENYL

PH PHASE

PNL PANEL

POD POWER OPERATED DAMPER

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

RCP REFLECTED CEILING PLAN

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

REQD REQUIRED

SCC SHORT CIRCUIT CAPACITY

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

W WATT

WH WATER HEATER

WP WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

ABBR. DESCRIPTION ABBR. DESCRIPTION ABBR. DESCRIPTION

AWG AMERICAN WIRE GAUGE

KCMIL ONE-THOUSAND CIRCULAR MILS

NA NOT APPLICABLE

HD HEAT DETECTOR

ABC

PANELBOARD MAIN CIRCUIT BREAKER TYPE, ONE-LINE

### - INDICATES BREAKER RATING

ABC - INDICATES PANEL DESIGNATION

ABC

PANELBOARD MAIN LUG TYPE, ONE-LINE

### - INDICATES BUS RATING

ABC - INDICATES PANEL DESIGNATION

###A CIRCUIT BREAKER

### - INDICATES BREAKER RATING

GND GROUND BUS BAR

EARTH GROUND

ELECTRICAL SYMBOLS

DESCRIPTION

TRANSFORMER, ONE-LINE

FUSIBLE DISCONNECT SWITCH, ONE-LINE

###AF - INDICATES FUSE RATING

###AS - INDICATED SWITCH RATING

###AF

G

ABC

M

ABC

SPD SURGE PROTECTIVE DEVICE

SYMBOL

DOUBLE TUB PANELBOARD, ONE-LINE

ABC - INDICATES PANEL DESIGNATION

ISOLATION POWER PANELBOARD, ONE-LINE

ABC - INDICATES PANEL DESIGNATION

###AS

METER, ONE-LINE

TRANSFER SWITCH, ONE-LINE

GENERATOR, ONE-LINE

UNINTERRUPTIBLE POWER SUPPLY (UPS), ONE-LINE

ELECTRICAL ONE-LINE

###A

DRAWOUT CIRCUIT BREAKER

### - INDICATES BREAKER RATING

###A

BRANCH CIRCUIT BREAKER

### - INDICATES BREAKER RATING

###AS NON-FUSIBLE DISCONNECT SWITCH, ONE-LINE

###AS - INDICATED SWITCH RATING

ELECTRICAL GENERAL NOTES ELECTRICAL DEMOLITION NOTES

WHERE THERE IS A DISCREPANCY BETWEEN ABOVE GENERAL NOTES AND SPECIFICATIONS, WHERE APPLICABLE, SPECIFICATIONS SHALL BE FOLLOWED

APPLICABLE CODES

1. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), INCLUDING (BUT NOT LIMITED TO):

a. NATIONAL ELECTRICAL CODE (NEC), NFPA 70 - 2017

b. NATIONAL FIRE ALARM CODE, NFPA 72 - 2013

c. NATIONAL FIRE ALARM CODE, NFPA 25 - 2020

d. NATIONAL FIRE ALARM CODE, NFPA 101 - 2021

2. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI), INCLUDING (BUT NOT LIMITED TO):

a. NATIONAL ELECTRICAL SAFETY CODE, ANSI C2

3. OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA)

4. FEDERAL COMMUNICATION COMMISSION (FCC)

5. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

6. INSULATED CABLE ENGINEERS ASSOCIATION (ICEA)

7. INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

8. NATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)

9. AMERICAN SOCIETY OF TESTING AND MATERIALS (ASTM)

10. ANTI-FRICTION BEARING MANUFACTURERS ASSOCIATION (AFBMA)

11. BUILDING OFFICIALS AND CODE ADMINISTRATORS INTERNATIONAL, INC. (BOCA)

12. INTERNATIONAL CODE COUNCIL (ICC):

a. INTERNATIONAL BUILDING CODE (IBC)

13. UNIFORM BUILDING CODE (UBC)

14. INTERNATIONAL CONFERENCE OF BUILDING OFFICIALS (ICBO)

a. INTERNATIONAL ENERGY CONSERVATION CODE (IECC), ENDORSED BY THE U.S. DEPARTMENT OF

ENERGY (DOE)

15. NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION INSTALLATION STANDARDS (NECA)

16. AMERICANS WITH DISABILITIES ACT (ADA)

17. APPLICABLE STATE AND LOCAL CODES, AMENDMENTS, REGULATIONS, AND PRACTICES.

18. APPLICABLE REGULATORY REQUIREMENTS AND ADVISORY PRACTICES OF APPROPRIATE

a. AUTHORITIES HAVING JURISDICTION (AHJs).

19. APPLICABLE STANDARDS, REGULATIONS, AND PRACTICES OF THE OWNER.

1. THE DRAWINGS AND APPLICABLE SPECIFICATIONS SHALL BE CONSIDERED SUPPLEMENTARY,

ONE TO THE OTHER AND ARE CONSIDERED THE "CONTRACT DOCUMENTS". ALL WORKMANSHIP,

METHODS AND/OR MATERIALS DESCRIBED OR IMPLIED BY ONE AND NOT DESCRIBED OR

IMPLIED BY THE OTHER SHALL BE PROVIDED, FURNISHED OR PERFORMED AS IF IT HAD

APPEARED IN BOTH SECTIONS. THE TERM "CONTRACT DOCUMENTS" DESCRIBED HEREIN IS

NOT LIMITED SOLELY TO THE ELECTRICAL PORTION OF THE DRAWINGS AND SPECIFICATIONS,

BUT ENCOMPASSES THE DRAWINGS AND SPECIFICATIONS OF ALL DIVISIONS AS A WHOLE.

2. PROVIDE AN OPERATING AND MAINTENANCE MANUAL TO OWNER PRIOR TO THE FINAL

ACCEPTANCE. THE MANUAL SHALL INCLUDE, AS A MINIMUM, (1) SUBMITTAL DATA STATING

EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING

MAINTENANCE. ALSO PROVIDE TWO OPERATIONS AND MAINTENANCE MANUALS FOR EACH

PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS

AND METHOD OF OPERATION FOR EQUIPMENT SHALL BE CLEARLY IDENTIFIED, AND THE NAME,

PHONE NUMBER AND ADDRESS OF AT LEAST ONE QUALIFIED SERVICE AGENCY.

3. INCLUDE IN BID ALL COSTS ASSOCIATED WITH TEMPORARY ELECTRICAL SERVICE AS REQUIRED

FOR USE BY ALL TRADES DURING CONSTRUCTION. REMOVE TEMPORARY POWER AT THE

COMPLETION OF THE PROJECT. OBTAIN AND PAY FOR ALL REQUIRED PERMITS FOR

TEMPORARY POWER. ENGINEER OF RECORD SHALL BE PROVIDED WITH ADDITIONAL

COMPENSATION FROM THE CONTRACTOR WHERE SIGNED & SEALED DRAWINGS ARE

REQUESTED BY THE CONTRACTOR TO THE ENGINEER OF RECORD IF REQUIRED BY THE AHJ

FOR THE TEMPORARY POWER.

4. INCLUDE IN BID THE TRANSPORT AND DISPOSAL OR RECYCLING OF ALL WASTE MATERIALS

GENERATED BY THIS PROJECT IN ACCORDANCE WITH ALL LOCAL, STATE AND FEDERAL RULES,

REGULATIONS AND GUIDELINES APPLICABLE. COMPLY FULLY WITH STATUTES REGARDING

MERCURY-CONTAINING DEVICES, AND WITH ALL DEP AND EPA APPLICABLE GUIDELINES AT THE

TIME OF DISPOSAL. PROVIDE OWNER WITH WRITTEN CERTIFICATION OF ACCEPTED DISPOSAL.

5. ALL BRANCH CIRCUITS SHALL BE FURNISHED WITH A DEDICATED NEUTRAL. SHARED NEUTRALS

ARE NOT ALLOWED UNLESS SPECIFICALLY NOTED ON THE DRAWINGS.

6. VERIFY AND COORDINATE LOCATIONS OF ANY MISCELLANEOUS EQUIPMENT REQUIRING

ELECTRICAL CONNECTIONS WITH APPROVED SHOP DRAWINGS, OWNER-PROVIDED CUT

SHEETS, MANUFACTURER'S INSTRUCTIONS, AND EQUIPMENT NAMEPLATE INFORMATION,

PRIOR TO ROUGH IN, AND PROVIDE ALL NECESSARY ELECTRICAL REQUIRED.

7. VERIFY AND COORDINATE LOCATIONS AND EXACT ELECTRICAL REQUIREMENTS FOR ALL FIRE

PROTECTION EQUIPMENT PRIOR TO SUBMITTAL OF SHOP DRAWINGS OF ELECTRICAL

EQUIPMENT. PROVIDE ALL NECESSARY RACEWAYS, CONDUCTORS, BOXES, EQUIPMENT,

ACCESSORIES, ASSOCIATED DISCONNECT SWITCHES, CIRCUIT BREAKERS, CONTROL

TRANSFORMERS, FIRE ALARM SHUTDOWN, ETC. REQUIRED FOR A COMPLETE AND

OPERATIONAL SYSTEM. COORDINATE WITH APPROPRIATE TRADE'S APPROVED SHOP

DRAWINGS, MANUFACTURER'S INSTRUCTIONS, AND EQUIPMENT NAMEPLATE INFORMATION,

PRIOR TO ROUGH IN, AND PROVIDE ALL NECESSARY ELECTRICAL REQUIRED, UNLESS

OTHERWISE NOTED.

8. ALL WORK ON THE ELECTRICAL SYSTEM REQUIRED BY THE CONTRACT DOCUMENTS SHALL BE

COORDINATED WITH THE WORK OF ALL OTHER DIVISIONS/TRADES PRIOR TO COMMENCEMENT

OF WORK. AVOID INTERFERENCES WITH THE PROGRESS OF OTHER DIVISIONS/TRADES.

9. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS.

PROVIDE COMPONENTS INDICATED ON RISER DIAGRAMS WHETHER OR NOT INDICATED ON

PLANS AND VICE VERSA.

10. ROUTING OF CONDUIT IS DIAGRAMMATIC AND NOT INTENDED TO SHOW REQUIRED OFFSETS

AND DETAILS. COORDINATE EXACT ROUTING WITH FIELD CONDITIONS AND OTHER TRADES.

11. WHERE A DISCREPANCY OR CONFLICT IS FOUND BETWEEN ONE DRAWING AND ANOTHER, OR

BETWEEN A DRAWING AND APPLICABLE SPECIFICATIONS, NOTIFY THE ARCHITECT/ENGINEER

IMMEDIATELY IN WRITTEN FORM. IN GENERAL, THE MOST STRINGENT REQUIREMENT SHALL

GOVERN UNLESS THE DISCREPANCY CONFLICTS WITH APPLICABLE CODES OR OWNER'S

DESIGN STANDARDS, WHEREIN THE CODE OR OWNER'S DESIGN STANDARDS SHALL GOVERN.

12. COORDINATE ALL PROJECT SCHEDULING AND PHASING REQUIREMENTS WITH

ARCHITECT/ENGINEER AND OWNER PRIOR TO SUBMITTING BID PRICE. THIS PROJECT MAY

REQUIRE PHASING SEQUENCES AND POTENTIAL PREMIUM TIME WORK AND ALL COSTS FOR

SUCH SHALL BE INCLUDED IN THE BID PRICE. PROVIDE ADEQUATE WORK FORCE AND

EQUIPMENT, AND INCLUDE PREMIUM TIME AS MAY BE REQUIRED IN ORDER TO ADHERE TO THE

PROJECT SCHEDULE. ADDITIONALLY, ENSURE THAT LONG LEAD ITEMS DO NOT IMPACT THE

PROJECT'S SCHEDULE OR PHASING.

13. ANY TEMPORARY INTERRUPTION ON POWER REQUIRED FOR THE SYSTEM TIE-IN OR

SWITCHOVER FOR ANY PORTION OF THE ELECTRICAL SYSTEM SHALL BE PRE-APPROVED IN

WRITING BY THE OWNER AND SCHEDULED IN ADVANCE.

14. CONDUCT WORK OPERATIONS AND DEBRIS REMOVAL IN A MANNER THAT ENSURES MINIMUM

INTERFERENCE WITH NORMAL BUSINESS OPERATIONS, TRAFFIC, PARKING, ETC. ONGOING IN

ADJACENT OCCUPIED SPACES OR FACILITIES. PROVIDE ALL THAT IS REQUIRED TO

EFFECTIVELY PROTECT SURROUNDING OCCUPANTS, EQUIPMENT, FINISHES, FURNITURE, ETC.

FROM DAMAGE OR EXCESSIVE NOISE THROUGHOUT THE DURATION OF THIS PROJECT.

CONTRACTOR IS RESPONSIBLE FOR ANY LOSSES OR DAMAGE. ANY DAMAGE RESULTING FROM

THE FAILURE TO ADHERE TO THIS REQUIREMENT. RESTORE DAMAGED ELEMENTS TO ORIGINAL

CONDITION BY THE CONTRACTOR TO THE SATISFACTION OF THE ARCHITECT/ENGINEER AND

OWNER, AT NO ADDITIONAL COSTS. REPORT OF ANY SUCH OCCURRENCE TO THE

ARCHITECT/ENGINEER AND OWNER IMMEDIATELY AND AWAIT WRITTEN DIRECTION PRIOR TO

PROCEEDING WITH REPAIRS.

15. THE EXCLUSIVELY DEDICATED SPACE EXTENDING FROM FLOOR TO 6' ABOVE EQUIPMENT OR

STRUCTURAL CEILING, WHICHEVER DISTANCE IS LOWER, WITH A WIDTH AND DEPTH OF THE

PANELBOARD OR SWITCHBOARD MUST BE CLEAR OF ALL PIPING, DUCTS, EQUIPMENT FOREIGN

TO THE ELECTRICAL EQUIPMENT OR ARCHITECTURAL APPURTENANCES IN ACCORDANCE WITH

NEC.

16. PROVIDE ALL TEMPORARY NORMAL LIGHTING, EMERGENCY LIGHTING AND EXIT SIGNAGE

REQUIRED DURING THE PROJECT CONSTRUCTION PHASE.

17. UNLESS NOTED AS EXISTING, ALL ELECTRICAL INDICATED ON THE CONTRACT DOCUMENTS

SHALL BE NEW, SHALL BE U.L. LISTED, AND SHALL BEAR A U.L. LABEL. WHERE NO U.L. LABEL OR

LISTING IS AVAILABLE, THE MATERIAL SHALL BE LISTED WITH AN APPROVED, NATIONALLY

RECOGNIZED ELECTRICAL TESTING AGENCY.

18. PROVIDE EXPERIENCED, QUALIFIED AND RESPONSIBLE SUPERVISION FOR ALL WORK

REQUIRED BY THE CONTRACT DOCUMENTS. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED

IN A NEAT AND WORKMANLIKE MANNER, TO THE SATISFACTION OF THE ARCHITECT/ENGINEER

AND OWNER.

19. THE ELECTRICAL PORTION OF THE CONTRACT DOCUMENTS ARE COORDINATED WITH THE

DESIGN BASIS EQUIPMENT SPECIFIED BY DIVISION 26 AND OTHER DIVISIONS. WHERE THE

CONTRACTOR ELECTS TO SUBSTITUTE A PRODUCT IN LIEU OF PROVIDING THE DESIGN BASIS,

AND SAID SUBSTITUTION IS ACCEPTED BY THE A/E AND OWNER, THE CONTRACTOR SHALL MAKE

ALL CORRECTIONS TO THE ELECTRICAL SYSTEM NECESSARY IN ORDER TO ENSURE A

COMPLETE AND OPERATIONAL INSTALLATION OF THE EQUIPMENT AT NO ADDITIONAL COSTS.

WHERE THE CONTRACTOR'S DESIGN SUBSTITUTION RESULTS IN THE NEED FOR THE ENGINEER

TO REVISE THE CONTRACT DOCUMENTS, THE ENGINEER RESERVES THE RIGHT TO REQUEST

COMPENSATION FROM THE CONTRACTOR FOR SAID SERVICES.

20. MAINTAIN A CURRENT AND ACCURATE SET OF PROJECT RECORD DOCUMENTS (AS-BUILTS) AT

THE SITE THROUGHOUT THE DURATION OF THE PROJECT. RECORD DRAWINGS SHALL BE

UPDATED EACH DAY TO REFLECT THE ACTUAL LOCATIONS, SIZES, ROUTING, ETC. OF EACH

PORTION OF THE ELECTRICAL SYSTEM AFFECTED BY THIS WORK. A FINAL SET OF RECORD

DOCUMENTS SHALL BE ISSUED TO THE A/E FOR REVIEW AND THEN SUBMITTED TO THE OWNER

WITHIN 30 DAYS AFTER THE DATE OF FINAL ACCEPTANCE. PROVIDE RECORD DRAWINGS OF

THE ACTUAL INSTALLATION INCLUDING SINGLE LINE DIAGRAM, POWER RISER DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM, SITE PLANS AND ALL ELECTRICAL FLOOR PLANS, DETAILS, PANEL SCHEDULES, ETC.

21. OWNER FURNISHED EQUIPMENT: VERIFY AND COORDINATE ELECTRICAL ROUGH IN

REQUIREMENTS FOR OWNER FURNISHED EQUIPMENT PRIOR TO ROUGH IN.

22. WHERE SUBMITTED EQUIPMENT REQUIRES REVISION TO OVERCURRENT PROTECTION,

CONDUIT OR WIRING, MAKE CHANGES IN ACCORDANCE WITH APPLICABLE CODES.

D1. THE FACILITY WILL REMAIN OCCUPIED DURING RENOVATIONS.

D2. EQUIPMENT SHOWN IN DASHED LINE TYPE ARE EXISTING TO BE DEMOLISHED; DEVICES, LIGHT

FIXTURES AND EQUIPMENT SHOWN IN LIGHT SOLID LINE TYPE ARE EXISTING TO REMAIN,

UNLESS OTHERWISE NOTED.

D3. EXISTING EQUIPMENT SHOWN ARE BASED ON FIELD SURVEYS AND RECORD DRAWINGS

PROVIDED BY THE OWNER, AND IS NOT NECESSARILY ALL INCLUSIVE IN EVERY AREA AS FAR AS

EXISTING ELECTRICAL EQUIPMENT. EXISTING CIRCUITING SHOWN IS BASED ON RECORD

DRAWINGS AND THE SURVEYED PANEL DIRECTORIES, WHERE THEY WERE AVAILABLE. THE

ACTUAL CONDITIONS MAY VARY. ALL EXISTING CONDITIONS MUST BE VERIFIED PRIOR TO BID.

THE CONDITIONS SHOWN ARE INTENDED TO SHOW THE LOCATIONS OF EXISTING EQUIPMENT,

WHERE SHOWN ON THE PLAN DRAWINGS, AND IN NO WAY RELIEVES THE CONTRACTOR FROM

PROVIDING ANY AND ALL COORDINATION NECESSARY TO COMPLETE THE NEW WORK. FIELD

CONDITIONS SHALL GOVERN.

D4. PRIOR TO DEMOLITION, FIELD VERIFY CONDUIT AND WIRING WHICH SERVES AREAS OUTSIDE

THE SCOPE OF WORK AND PASSES THROUGH THE AREA OF WORK. MAINTAIN CONTINUITY OF

SYSTEMS.

D5. WHERE EXISTING DEVICES ARE TO REMAIN, CONTRACTOR MUST EXTEND EXISTING CIRCUITING

WHERE NECESSARY TO MAINTAIN CONTINUITY OF CIRCUIT.

D6. COORDINATE WITH THE OWNER FOR DISPOSITION OF ELECTRICAL ITEMS TO BE DEMOLISHED.

OWNER SHALL HAVE THE OPTION TO RETAIN REUSABLE ITEMS NOT BEING USED IN

THE FINISHED WORK. COORDINATE WITH THE OWNER PRIOR TO START OF DEMOLITION.

PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT AND MATERIALS BEING REMOVED.

D7. WHERE EXISTING DEVICES, EQUIPMENT ARE INDICATED TO BE DEMOLISHED, REMOVE

ASSOCIATED CONDUIT AND WIRING BACK TO SOURCE PANEL OR TO NEAREST JUNCTION BOX

TO MAINTAIN CIRCUIT CONTINUITY OF DEVICES TO REMAIN AND EQUIPMENT TO REMAIN. WHERE

PANELS ARE TO BE REMAIN, TURN BREAKER TO "OFF" POSITION AND LABEL THE CIRCUIT AS

"SPARE" ON THE PANEL DIRECTORY.

D8. ALL AREAS OUTSIDE THE SCOPE OF CONSTRUCTION ARE TO REMAIN ENERGIZED. COORDINATE

PHASING WITH CONSTRUCTION MANAGER AND OWNER PRIOR TO DEMOLITION WHICH MAY

RESULT IN INTERRUPTION OF POWER.

D9. REFER TO ELECTRICAL PLANS FOR EXTENT OF AREA REQUIRING DEMOLITION AND ADDITIONAL

INFORMATION ON ELECTRICAL DEMOLITION WITHIN THAT AREA. DISCONNECT ELECTRICAL

SERVICE TO ALL EQUIPMENT BEING REMOVED. DEMOLITION SHALL BE PHASED AS

REQUIRED BY DIVISION 1, OR DIRECTED BY THE OWNER.

D10. REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND CEILINGS IN REMODELED

OR RENOVATED AREA. CAP BOTH ENDS OF REMAINING CONDUIT IN WALL OR FLOOR WHERE

CUT. REMOVE ALL ASSOCIATED SUPPORTS. REMOVE WIRING BACK TO SOURCE OF VOLTAGE.

D11. ELECTRICAL DEVICES WITHIN THE AREA OF WORK., AND NOT NOTED ON THE DEMOLITION

DRAWINGS, WHETHER DUE TO CONCEALMENT BY STORAGE SHELVING, CASEWORK,

FURNITURE OR FOR OTHER REASONS, ARE TO BE REMOVED AS REQUIRED, UNLESS SHOWN AS

EXISTING TO REMAIN.

D12. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING ALL OPENINGS IN EXISTING

CONSTRUCTION AFTER REMOVAL OF EQUIPMENT AND ELECTRICAL DEVICES, UNLESS

OTHERWISE NOTED ON ARCHITECTURAL PLANS. REPAIRS ARE TO BE DONE TO LOGICAL EDGES

OF SURFACES AFFECTED AND SHALL MATCH IMMEDIATE ADJACENT AREAS IN CONSTRUCTION,

MATERIAL, FIRE RATING, FINISH AND COLOR.

D13. PROVIDE BLANK COVERPLATES WHERE DEVICES ARE BEING REMOVED FROM EXISTING WALLS

TO REMAIN. MATCH COLOR OF NEW ADJACENT DEVICE COVERPLATES.

D14. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR TO COMMENCEMENT OF

WORK AND OBTAIN CLARIFICATIONS FROM ARCHITECT/ENGINEER IF NECESSARY.

D15. COORDINATE SERVICE INTERRUPTION WITH CONSTRUCTION MANAGER, OWNER, LANDLORD,

AND UTILITY COMPANY, WHERE APPLICABLE, AND DO NOT INTERRUPT POWER WITHOUT

WRITTEN PERMISSION. PROVIDE A MINIMUM OF ONE WEEK'S WRITTEN NOTIFICATION WHEN

POWER IS DESIRED TO BE INTERRUPTED.

D16. EXERCISE EXTREME CAUTION WHEN REMOVING/ RELOCATING WIRING AND EQUIPMENT. IT IS

THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT OTHER WIRING DEVICES, EQUIPMENT

AND LIGHT FIXTURES THAT MAY BE CONNECTED TO THE SAME CIRCUIT REMAIN OPERATIONAL

AND ACTIVE.

D17. INFORMATION INDICATED IN THE DEMOLITION PORTION OF THE CONTRACT DRAWINGS IS

DIAGRAMMATIC IN NATURE. FIELD VERIFY ELECTRICAL CIRCUIT HOMERUNS TO ALL ELECTRICAL

ITEMS SCHEDULED TO BE DEMOLISHED AND PERFORM THE WORK AS INTENDED AND DEPICTED

ON THE DRAWINGS.

D18. UPDATE ALL EXISTING ELECTRICAL EQUIPMENT NAMEPLATES AND DIRECTORIES AS

NECESSARY TO REFLECT FINAL AS-BUILT CONDITIONS AT THE END OF CONSTRUCTION.

D19. STORE ITEMS INDICATED TO BE RETURNED TO THE OWNER IN A DRY, CLEAN AND PROTECTED

AREA. NOTIFY OWNER WHEN ITEMS ARE READY TO BE REMOVED.

D20. COORDINATE ANY ALTERATION AND CHANGES TO THE ELECTRICAL SERVICE WITH THE LOCAL

UTILITY COMPANY AND THE OWNER PRIOR TO COMMENCEMENT OF WORK.

D21. SCHEDULE ALL POWER INTERRUPTION WITH OWNER FOR EXACT DATE, TIME AND DURATION.

PROVIDE A MINIMUM OF 72 HOURS NOTICE PRIOR TO DISCONNECTING ANY POWER TO ANY

PORTION OF THE BUILDING, AND MAKE ARRANGEMENTS TO MAINTAIN POWER TO ALL CRITICAL

EQUIPMENT AS NEEDED AND REQUESTED BY THE OWNER PRIOR TO COMMENCEMENT OF

WORK.

D22. PROVIDE ANY NECESSARY REPROGRAMMING OF EXISTING BUILDING FIRE ALARM SYSTEMS TO

DISABLE FIRE ALARM DEVICES THAT ARE BEING DISCONNECTED AND REMOVED, AND FOR ANY

NEW DEVICES THAT ARE ADDED, AS PART OF BID PRICE.

D23. THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL ELECTRICAL DEVICES WITHIN THE PROJECT

AREA. IT IS INTENDED TO PROVIDE A GENERAL KNOWLEDGE OF THE EXISTING CONDITIONS

WITHIN THE PROJECT AREA. ANY DISCREPANCIES OR CONDITIONS NOT SHOWN ON THE PLAN

SHALL BE BROUGHT TO THE ATTENTION OF THE A/E. THE CONTRACTOR IS RESPONSIBLE FOR

ALL REQUIRED ELECTRICAL DEMOLITION WHETHER INDICATED ON THE PLANS OR NOT.

D24. ALL CONDUITS SERVING OTHER SPACES THAT RUN THROUGH THE PROJECT AREA SHALL

REMAIN ACTIVE DURING CONSTRUCTION SO AS NOT TO CAUSE DISRUPTION TO THESE OTHER

SPACES. ENSURE THAT ALL CONDUITS, NEW OR EXISTING WITHIN THE PROJECT AREA ARE

PROPERLY SUPPORTED IN ACCORDANCE WITH THE NEC. ANY EXISTING CONDUIT IS INSTALLED

BELOW THE HEIGHT OF THE NEW CEILING SHALL BE RELOCATED TO ABOVE THE NEW CEILING

HEIGHT.

D25. REMOVE ALL ABANDONED WIRING AND CONDUIT THAT IS WITHIN THE PROJECT AREA PRIOR TO

THE END OF CONSTRUCTION.

D26. UPDATE PANELBOARD DIRECTORIES WHICH ARE MODIFIED BY THIS PROJECT.

D27. REPAIR DISTURBED AREAS TO MATCH EXISTING CONDITIONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

B

IM

/0

R e p la c e

F ir e

P u m p

C o n tr o lle r D e s ig n /0

R e p la c e

F ir e

P u m p C o n tr o lle r

R

E

.r v t

/2

/2

:5

:5

A

M

E-001

ELECTRICAL LEGENDS, SYMBOLS

& GENERAL NOTES

FIRE PUMP CONTROLLER

REPLACEMENT

DETROIT, MICHIGAN

553-22-231

06/23/2023 JFR KEM

100% BID DOCUMENTS

SHEET LIST

SHEET NUMBER SHEET NAME

E-001 ELECTRICAL LEGENDS, SYMBOLS & GENERAL NOTES

EP101 ELECTRICAL 1ST FLR, PENTHOUSE & BASEMENT PLAN

E-601 ELECTRICAL SCHEDULES, DETAIL AND ONE-LINE DIAGRAM

SEC11

CHILLERS

EC104

BOILERS

EC105

AC SHOP

EC103

SWITCHBOARD

SUBSTATION

EC101

EMERGENCY

GENERATOR

EC102

KEY PLAN - 1ST FLR

KEY PLAN - BASEMENT

F

EX. SWITCHGEAR

SUBSTATION #14

EX. SWITCHGEAR

SUBSTATION #15

EX. SUBSTATION

SWITCHGEAR #13

EX. GENERATOR

EX. GENERATOR

EX. GENERATOR

EX. GENERATOR

SWITCHBOARD

SUBSTATION RM EC101

EMERGECNY GENERATOR

RM EC102

EX. PP-EQEC

EX. RC-CECA

EX. LP-CEC1

EX. RP-EECA

EX. LP-CECA

EX. LP-EEC1

EX. PP-EEC

EX. TEECA

EX. ENCLOSED CIRCUIT BREAKER "FIRE PUMP"

EX. ESA

FIRE RATED WALL

37 36 35

F

EX. EMERGENCY

SWITCHBOARD "ESA"

LOCATED IN PENTHOUSE

ON THE ROOF. REFER TO

DETAIL 2 THIS SHEET.

EX. SWITCHGEAR

SUBSTATION #14

LOCATED ON LEVEL

ABOVE

EXISTING NORMAL FEEDER SHALL BE REUSED

EXISTING EMERGENCY FEEDER SHALL BE REUSED.

NOTE : CONDUIT ROUTING SHOWN THIS PLAN IS AN

APPROXIMATION ONLY. FIELD VERIFY EXACT LOCATION.

EX. MCC-EQEC1

JP-1

FP-1

EP101

JOCKY PUMP CONTROLLER

FIRE PUMP

CONTROLLER

JPC-1

FPC-1

EP101

DEMO WORK

NEW WORK

EX. ENCLOSED CIRCUIT

BREAKER "FIRE PUMP"

LOCATED ON LEVEL ABOVE

FP-1

FP-1

JP-1

JPC-1

ETR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

B

IM

/0

R e p la c e

F ir e

P u m p

C o n tr o lle r D e s ig n /0

R e p la c e

F ir e

P u m p C o n tr o lle r

R

E

.r v t

/2

/2

:5

:5

A

M

EP101

ELECTRICAL 1ST FLR,

PENTHOUSE & BASEMENT PLAN

FIRE PUMP CONTROLLER

REPLACEMENT

DETROIT, MICHIGAN

553-22-231

06/23/2023 JFR KEM

100% BID DOCUMENTS

CODED NOTES:

DRAWING NOTES:

1. REFER TO FIRE PROTECTION DRAWINGS FOR INFORMATION ON THE TEMPORARY WATER SUPPLY

IMPAIRMENT PROGRAM.

2. WIRING METHODS IN THE FIRE PUMP ROOM SHALL BE IN ACCORDANCE WITH NEC 695.6 D.

3. CONTRACTOR TO ORDER AND HAVE ALL EQUIPMENT AND MATERIALS ON SITE BEFORE BEGINNING CONSTRUCTION. PERIOD OF PERFORMANCE INCLUDING LEAD TIMES IS SIX (6) MONTHS. ADJUST

CALENDAR DAYS BASED ON P.O.P.

0 2' 4' 8' 12'

1/4" = 1'-0"

N

1 NEW FIRE PUMP CONTROLLER SHALL BE PROVIDED BY FIRE PROTECTION AND WIRED BY ELECTRICAL.

RECONNECT EXISTING POWER CIRCUIT, FIRE ALARM CIRCUIT AND CONTROL WIRING TO NEW FIRE

PUMP AND PAD MOUNT FIRE PUMP CONTROLLER PROVIDED BY FIRE PROTECTION TO MATCH

EXISTING. REFER TO DIV 21 FOR SPECIFICATION. COORDINATE LOCATION AND REQUIREMENTS

PRIOR TO WORK.

2 THE FOLLOWING EQUIPMENT SERVED AS THE OLD SWITCHBOARD ESA. IT IS CURRENTLY GUTTED AND LEFT IN PLACE AS A LARGE SPLICE BOX. REFER TO DETAIL 4 THIS SHEET FOR CURRENT

LOCATION OF SWITCHBOARD ESA.

3 DE-ENERGIZE, DISCONNECT FIRE PUMP AND FIRE PUMP CONTROLLER. EXISTING CIRCUIT AND

CONTROL WIRING SHALL BE REUSED FOR NEW FIRE PUMP CONTROLLER AND NEW FIRE PUMP.

MAINTAIN CIRCUIT CONTINUITY DURING DEMO PHASE.

4 DE-ENERGIZE, DISCONNECT JOCKEY PUMP AND JOCKEY PUMP CONTROLLER. EXISTING CIRCUIT

SHALL BE REUSED FOR NEW JOCKEY PUMP AND JOCKEY PUMP CONTROLLER. MAINTAIN CIRCUIT

CONTINUITY DURING DEMO PHASE.

5 NEW JOCKEY PUMP CONTROLLER SHALL BE PROVIDED BY FIRE PROTECTION AND WIRED BY

ELECTRICAL. RECONNECT EXISTING CIRCUIT TO NEW JOCKEY PUMP AND WALL MOUNTED JOCKEY PUMP CONTROLLER PROVIDED BY FIRE PROTECTION TO MATCH EXISTING. REFER TO DIV 21 FOR

SPECIFICATION.

1/8" = 1'-0"

ENLARGED PLAN - 1ST FLOOR - ELECTRICAL RM

1/16" = 1'-0"

OVERALL PLAN - BASEMENT

0 8' 16' 32' 48'

1/16" = 1'-0"

1/4" = 1'-0"

ENLARGED PLAN - BASEMENT - FIRE PUMP ROOM - NEW WORK

0 4' 8' 16' 24'

1/8" = 1'-0"

Revisions Date

1/4" = 1'-0"

ENLARGED PLAN - BASEMENT - FIRE PUMP ROOM- DEMO WORK

LOCATED ON PENTHOUSE LEVEL ABOVE

FIRE PUMP CONTROLLER/ATS

CONTRACTOR SHALL RECONNECT AND TEST

EXISTING START/STOP SIGNAL AND COMMUNICATION

WIRING TO ENSURE FULLY OPERATIONAL SYSTEM.

IF TESTING OF WIRING FAILS, NOTIFY ENGINEER ON

RECORD. VERIFY EXACT REQUIREMENT WITH

MANUFACTURER SPECIFICATIONS PRIOR TO WORK.

EX. EMERGECNY

SWITCHBOARD "ESA"

MASTER CONTROLLER

PANEL

EX. EMERGENCY SWITCHBOARD ESA

FPC-1

FIRE PUMP CONTROLLER

FIRE PUMP

75 HP

REUSE EXISTING

REUSE EXISTING

4000 A

277/480V, 3-PHASE, 4 WIRE

13.2kV-480/277V, 3PH

600A

EX. SWITCHGEAR #14

5000 A

277/480V, 3-PHASE, 4 WIRE

EX. MCC-EQEC1

JPC-1

JOCKEY PUMP

CONTROLLER

JOCKEY PUMP

7.5 HP

REUSE EXISTING

5000 A

277/480V, 3-PHASE, 4 WIRE

EX. SWITCHGEAR #15

ATS-6

480V, 600A, 3P

EX. ENCLOSED CIRCUIT BREAKER

"FIRE PUMP"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

B

IM

/0

R e p la c e

F ir e

P u m p

C o n tr o lle r D e s ig n /0

R e p la c e

F ir e

P u m p C o n tr o lle r

R

E

.r v t

/2

/2

:5

:5

A

M

E-601

ELECTRICAL SCHEDULES, DETAIL

AND ONE-LINE DIAGRAM

FIRE PUMP CONTROLLER

REPLACEMENT

DETROIT, MICHIGAN

553-22-231

06/23/2023 JFR KEM

100% BID DOCUMENTS

N.T.S.

FIRE PUMP CONTROL WIRING DETAIL

EQUIPMENT CONNECTION SCHEDULE

TAG IDENTIFICATION HP FLA / MCA

VOLT / PH / LOAD

(kVA) CB AMPS PANEL CKT # FEEDER SIZE CONDUIT DISC MEANS CONTROL NOTES

FP-1 FIRE PUMP 75 480 V/3-79.7 kVA REUSE EXISTING REUSE EXISTING BY FIRE PROTECTION BY FIRE PROTECTION

JPC-1 JOCKEY PUMP 7.5 480 V/3-9.1 kVA REUSE EXISTING REUSE EXISTING BY FIRE PROTECTION BY FIRE PROTECTION

REUSE EXISTING

REUSE EXISTING

REUSE EXISTING

REUSE EXISTING

REUSE EXISTING

REUSE EXISTING