S02.STATEMENT OF WORK Chiller and laundry softener.docx

DOCX document 16 KB Posted

Attached to
4610--Equipment: Replace Chiller Plant and Laundry Water Softener
Solicitation number
36C24825Q0512
Issued by

About this file

This is a Statement of Work (SOW) for the Department of Veterans Affairs (VA) at the Lake City VAMC, detailing the requirements for replacing water softener systems at the chiller plant and laundry facility. The SOW requires a contractor to provide all labor, materials, supervision, and equipment to remove existing water softener systems, modify plumbing headers, install new systems with specific resin and bedding specifications, and perform functional testing. A mandatory site visit is scheduled for 3-20-2025 at 10:00am at the Lake City VAMC Engineering Office.

The associated federal contract opportunity (Solicitation Number 36C24825Q0512) is a 100% Service-Disabled Veteran Owned Small Business (SDVOSB) Request for Quotation (RFQ) under NAICS code 238220. Quotes are due by Tuesday, March 25, 2025 at 12:00 PM ET, to be submitted via email to victor.mercado@va.gov. The government will evaluate quotes based on technical merit, delivery, and price to determine the best value, with responses required on an all-or-none basis. Interested vendors must be registered in Veteran Small Business Certification (VetCert) and have an active System for Award Management (SAM) registration.

View the file

Other files

File Type Posted
36C24825Q0512.docx DOCX document
S02.Chiller and Laundry Water Softener Description.docx DOCX document
S02.Price _ Delivery Schedule.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATEMENT OF WORK

I. GENERAL INFORMATION

The Department of Veterans Affairs (VA) requires the installation of a new/replacement of the water softener located at the chiller plant and the re-bedding of the water softener that services laundry at the Lake City VAMC 619 S. Marion Ave Lake City, FL 32025.

II. SCOPE

***A mandatory site visit will be conducted on 3-20-2025 at 10:00am at the Lake City VAMC. Please report to the Lake City VAMC Engineering Office*** The contractor shall provide all the required tools, labor, material, and supervision necessary to accomplish the deliverables in the statement of work (SOW) and ensure that all the water systems listed in the SOW are kept within the industry standard parameters, except as may otherwise be specified.

III. SAFETY REQUIREMENTS

The contractor is solely responsible for compliance with all federal, state, and local laws, the Occupational, Safety and Health Act (OSHA) (Public Law 91-596) and the resulting standards, OSHA STANDARDS 29 CFR 1910 and 1926, as applicable, and the protection of their employees. Additionally, the contractor is responsible for the safety and health of all employees.

IV. SCOPE OF WORK

Provide all labor, material, supervision, and equipment as required to re-bed and rebuild, the water softener located at the Laundry Plant and remove and replace the water softener located at the chiller plant. The new Chiller Plant water softener must at the very least match the minimum existing softener output.

Place existing Chiller Plant water softener system in by-pass, remove existing water softener and discard all items that are no longer needed. Modify existing plumbing header to accommodate new system. Set new softener vessels with 400lbs of bedding per vessel and 15CuFt of softener resin per vessel. Attach to modified plumbing manifold, energize the system, function/leak test, document performance data, provide data to customer, bring the system online.

Place existing Laundry Plant water softener in by-pass, remove access ports for resin and gravel extraction via sump truck, examine and replace hub and laterals if damaged, place grave under-bedding (500 lbs per vessel and 20 CuFt of softener resin per vessel). Replace access portal covers, energize the system and test functionality, record performance data, provide data to customer, bring the system online.

SALIENT CHARACTERISTCS

· 30X72/2900/3948 NXTII DUPLEX-ASH-450-2-PRO

· 2-2900-CW-NXT VALVE

· 2-Distributor-CW-2” stack

· Brine Tank CW-39x48-no shelf-1/2” safety