S02. ROOF - AREA-A - ROOF PLAN.pdf

PDF 2 MB Posted

Attached to
Project 757-23-101 Air Cooled Chillers
Solicitation number
36C25025R0096_1
Issued by

About this file

The document is a detailed roof plan and infection control drawing for a Veterans Affairs (VA) project at the Chalmer Wylie Columbus VA Ambulatory Care Center. The roof plan drawing (AE104) provides specific technical instructions for demolition, roof removal, and reconstruction, including requirements for:

  • Removing existing roofing assemblies and composite roof deck down to structural steel
  • Coordinating demolition with new construction
  • Installing new steel columns and roof insulation
  • Maintaining precise specifications for roof membrane, insulation, and flashing details

The accompanying infection control plan outlines strict protocols for construction work, including Class II and Class III precaution levels with extensive requirements such as dust control, critical barrier construction, negative air pressure maintenance, daily cleaning procedures, and specific work hour restrictions. The plan emphasizes minimizing contamination risks in a high-sensitivity medical environment, with particular attention to protecting patient areas during construction activities.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1/8" = 1' -0"

SCALE FEET

5 0 5 10 15 20

ABCDEFGHJ

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

COORDINATE DEMOLITION WITH NEW CONSTRUCTION. ALL DEMOLITION AND

REPAIR NECESSARY TO COMPLETE NEW AND REMODEL CONSTRUCTION

SHALL BE PROVIDED. CONTRACTOR SHALL REMOVE EXISTING

IMPROVEMENTS WHETHER OR NOT SPECIFICALLY INDICATED ON THE

DRAWINGS TO FACILITATE THE COMPLETION OF ALL REQUIRED WORK.

CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL QUANTITIES AND

ITEMS REQUIRED TO BE REMOVED.

REFER TO ARCHITECTURAL SYMBOLS ON SHEET AE001 FOR DEMOLITION

SYSTEMS AND DRAWING NOMENCLATURE.

EXISTING STRUCTURE WITHIN THE PROJECT BOUNDARY SHALL REMAIN

UNLESS OTHERWISE NOTED.

SURFACES TO BE CUT AND CONDITIONS UNDER WHICH CUTTING IS TO BE

PREFORMED SHALL BE REVIEWED BY CONTRACTOR PRIOR TO CUTTING TO

VERIFY NO UNSAFE OR UNSATISFACTORY CONDITIONS EXIST. SUCH

CONDITIONS SHALL BE RECTIFIED BEFORE WORK MAY PROCEED.

WORK REQUIRING VIBRATION OR LOAD NOISE SHALL TAKE PLACE OUTSIDE

THE HOURS OF OPERATION. EVERY EFFORT SHALL BE MADE TO KEEP NOISE

AND VIBRATION TO A MINIMUM. HOURS OF OPERATIONS ARE MONDAY

THROUGH FRIDAY FROM 5 AM TO 8 PM AND ON SATURDAY AND SUNDAY

FROM 7 AM TO 5:30 PM. SCHEDULING SHALL BE COORDINATED WITH THE VA.

DIMENSIONS SHOWN FOR EXISTING CONSTRUCTION TO BE DEMOLISHED

ARE APPROXIMATE AND ARE INTENDED TO GIVE A GENERAL SCOPE OF

WORK TO BE REMOVED OR TEMPORARILY REMOVED TO ACCOMMODATE

NEW CONSTRUCTION. COORDINATE DEMOLITION WORK WITH DESIGN

INTENT OF NEW CONSTRUCTION TO PROVIDE ADEQUATE AREA FOR THIS

WORK.

CONTRACTORS SHALL REMOVE INDICATED DEMOLITION OF CONSTRUCTION

ASSEMBLIES IN THEIR ENTIRETY, UNLESS OTHER WISE NOTED, TO

ACCOMMODATE NEW CONSTRUCTION.

MAKE ALL DEMOLITION CLEAN AND COMPLETE IN A MANNER TO RECEIVE

NEW FINISHES. DEMOLITION SHOULD BE PERFORMED IN A MANNER SUCH

THAT THE CONTRACTOR CAN SEAMLESSLY PATCH NEW WORK TO BE

SMOOTH AND UNDETECTABLE.

ABOVE CEILING WORK WHERE CEILINGS ARE TO REMAIN, CEILING TILES

SHALL BE REMOVED AND STORED IN A SAFE MANNER UNTIL CEILING TILES

CAN BE REINSTALLED. DAMAGED AND BROKEN CEILING TILES SHALL BE

REPLACED BY CONTRACTOR. GYPSUM BOARD CEILINGS SHALL BE PATCHED

AND PAINTED TO SEAMLESSLY MATCH EXISTING CEILING COLOR

FOLLOWING ABOVE CEILING DEMOLITION ACTIVITY. THIS SHALL INCLUDE

REPAIR TO THE CEILING GRID, SUSPENSION SYSTEM AND ALL ASSOCIATED

ASSEMBLIES AS WELL AS THE REPLACEMENT OF DAMAGED CEILING

PANELS, WITHIN AND BEYOND PROJECT LIMITS.

COORDINATE FULL SCOPE OF DEMOLITION WORK WITH ENGINEERING AND

VENDOR DRAWINGS.

WHERE EXISTING ROOF IS REMOVED, ROOF AND MEMBRANE SHALL BE

REMOVED TO PROVIDE A CLEAR OPENING FOR STRUCTURAL

MODIFICATIONS. ROOF SLAB SHALL BE FILLED/ LEVELED TO PROVIDE A

LEVEL FINISHTO MATCH EXISITING.

GENERAL NOTES

ROOF PLAN NOTES

1.

2.

REMOVE ROOFING ASSEMBLY AND COMPOSITE ROOF DECK DOWN TO

STRUCTURAL STEEL AS REQUIRED TO PERFORM STRUCTURAL WORK, SEE

STRUCTURAL DRAWINGS. COORDINATE WITH STRUCTURE FOR EXTENT OF

REMOVAL.

SEE STRUCTURAL FOR COMPOSITE DECK TO BE INFILLED ONCE NEW STEEL

COLUMNS ARE INSTALLED. SEE DETAIL 2/AE104 FOR NEW INSULATION AND

ROOFING ASSEMBLY REPAIR AND FLASHING.

REFER TO MEP DRAWINGS FOR ROOF MECHANICAL EQUIPMENT

INFORMATION.

EXISTING ROOF INSULATION

ASSEMBLY

SEE STRUCTURAL DRAWINGS FOR

CONNECTION TO ROOF STRUCTURE

PROVIDE INSULATION CANT

ALL SIDES

PROVIDE TERMINATION BAR

ALL SIDES SET IN FULL BED

OF SEALANT

STEEL COLUMN, SEE

STRUCTURAL

PROVIDE NEW MEMBRANE

0' - 8"

0'

- 1

0"

NEW PORTION OF ROOF

INSULATION TO MATCH EXISTING

INFILL ROOF TO MATCH EXISTING,

REFER TO STRUCTURAL DRAWINGS6"

NOT IN SCOPE

LEGEND

ABOVE CEILING MECHANICAL ITEMS ARE SHOWN FOR CLARITY ON AREAS

OF WORK.

8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

AREA - A

AREA - B

AREA - C

KEY PLAN :-

GUIDON DESIGN

1221 N Pennsylvania St, Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com GD Project : 24-1012-01

ARCHITECT, STRUCTURAL ENGINEER

Au to de sk

D oc s:

//2

.0

VA

C ol um bu s (O

H ) A

E R ep la ce A ir- C oo le d C hi lle rs /2

4.

.0

1_ A_ v2 4.

rv t

3/

/2

3:

:5

PM

AE104

ROOF - AREA-A - ROOF PLAN Replace Air Cooled Chillers Chalmers P. Wylie VA Ambulatory Care Center

420 N. James Rd, Columbus, OH

01A

03/26/2025 TD TS

CONSTRUCTION

DOCUMENTS

757-23-101

N

SCALE: 1/8" = 1'-0"AE104

1 ROOF - AREA-A - ROOF PLAN

SCALE: 1 1/2" = 1'-0"AE104

2 STEEL COLUMN DETAIL

Revisions: Date:

A

A

B

B

C

C

D

D

E

E

F

F

G

G

Endoscopy Office Space 2B024

Surgery Office 2B025

Nurse Office 2B145

GI/ Phys. Office 2B161

Men's 2B165

Resident Office 2B008

Anesth Work/Storage/Office

2B163

Women's 2B167 Cart Wash

2B292

Decontam 2B291

Prep 2B293

Transfusion 2B263

Gross Histology 2B278

Staining / Cutting 2B276

Break Room 2B009

Corridor 2B006

Sterile 2B294

ANTE

2B291A

HAC

2B291H

Shared Office 2B283A

HAC

2B268

Telecommunications 2B003

Stair No. 5 2S005

Corridor 2B001

Training 2B281 Office

2B283

Office 2B285

Staff T 2B287

HAC

2B289H

Staging 2B289

Corridor 2B280

Storage 2B288

Corridor 2B146

Corridor 2B160

Micro Lab 2B279

Scope Clean 2B143

Ante 2B141

Exam Room 4 2B042

Exam Room 5 2B044

Pace/ Exam 6 2B046

Office 2B048

Surgery 2B144

Frozen Section 2B157

Clean 2B142

Med Gas Storage 2B164

HAC

2B158

Scope Storage 2B138B

Toilet 2B141T

AER

2B141A

Corridor 2B045

Toilet 2B139T

PFT Lab & Vent Test 2B037

Patient Toilet 2B041 Patient Toilet

2B043

Scope Storage 2B137 Scope Storage

2B136B

EGD/ Colon Procedure 2B136

Soiled 2B153

Procedure Room 2B155

Sterile Storage 2B191

Clean Core 2B190

EGD/ Colon Procedure 2B138

Equip/Apparatus 2B162

Major O.R.

2B181

Sub-Sterile 2B182

O.R.

2B183

Alcove/ Corridor 2B184

C-Arm Alcove 2B180

Scrub 2B180A

Corridor 2B002

Corridor 2B007

Open Lab 2B275

Corridor 2B005Open lab

2B270

Corridor 2B159

Processing 2B272

MI

N.

C

LE

AR

6'

- 0

1.

2.

3.

NO CEILING IN THIS AREA.

REMOVE ACOUSTIC CEILING TILES AS NEEDED TO PERFORM ABOVE CEILING

WORK. REFER TO STRUCTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS

FOR MORE INFORMATION. PROVIDE NEW CEILING TILES WHERE TILES WERE

REMOVED. FINISH SHALL MATCH EXISTING EXACTLY.

PROVIDE TEMPORARY INFECTION CONTROL PLASTIC BARRIER WALL

CONSTRUCTION. REFER TO DETAIL 2/AE111. REFER TO SPECIFICATION FOR

ADDITIONAL INFORMATION.

REFLECTED CEILING PLAN NOTES

1/8" = 1' -0"

SCALE FEET

5 0 5 10 15 20

NOT IN SCOPE

LEGEND

ABOVE CEILING MECHANICAL ITEMS ARE SHOWN FOR CLARITY ON AREAS

OF WORK.

CONTINUOUSLY ADHERED FIRE

RETARDANT POLY TO FLOOR WITH TAPE

BEAD OF CONT. SEALANT

6 MIL. FIRE RETARDANT POLY

INTERIOR SIDE

CONSTRUCTION

SIDE

CONTINUOUSLY ADHERED 6 MIL. FIRE

RETARDANT POLY TO DECK WITH TAPE

UNDERSIDE OF STRUCTURAL DECK

CEILING

TO DECK

OCCUPIED

SIDE

6-MIL FIRE RETARDANT POLY

INTERIOR SIDE

EXISTING CEILING

CONTINUOUSLY ADHERE 6-MIL. FIRE

RETARDANT POLY TO CEILING WITH TAPE

CONTINUOUSLY ADHERE FIRE

RETARDANT POLY TO FLOOR WITH TAPE

EXISTING DECK

CONSTRUCTION

SIDE

OCCUPIED

SIDE

TO CEILING

CONSTRUCTION ACTIVITY - FIRE RISK: B

PATIENT RISK GROUP: HIGH (LABORATORY), HIGHEST (SPS STERILE SIDE)

CLASS OF PRECAUTION MATRIX: II (LABORATORY) & III (SPS STERILE SIDE)

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

REFER TO MEP DRAWINGS FOR PHASING OF WORK .

COORDINATE FULL SCOPE OF WORK WITH ENGINEERING DRAWINGS AND

FIELD VERIFICATION. CONTRACTOR IS RESPONSIBLE FOR SCOPE OF ABOVE

CEILING WORK REQUIRED ABOVE AND BELOW THE FLOOR PLATE OF THE

PROJECT BOUNDARY.

COORDINATE LOCATION OF TEMPORARY INFECTION CONTROL (IC) BARRIER

WALL CONSTRUCTION AND INFECTION CONTROL (IC) MEASURES WITH COR

AND PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE. TEMPORARY

IC BARRIER WALL CONSTRUCTION LOCATIONS IN DRAWINGS ARE

APPROXIMATE. CONTRACTOR SHALL PROVIDE DRAWING TO COR AND

PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE ONCE ICRA

PROTOCOLS AND PLAN IS APPROVED.

SCHEDULE AND TIME OF CONSTRUCTION WORK TO BE APPROVED BY COR

AND NURSING STAFF BEFORE CONSTRUCTION MAY BEGIN. PROVIDE

PHASING INFORMATION FOR ABOVE CEILING WORK IN THE CONTRACTOR

PROVIDED SCHEDULE FOR WORK ALSO REQUIRED ABOVE AND BELOW THE

FLOOR PLATE OF THE PROJECT BOUNDARY.

ALL WORK WITHIN ENVELOPE IS ABOVE CEILING AND SHALL TAKE PLACE

OFF HOURS, BETWEEN 8 PM AND 5 AM, MONDAY THROUGH FRIDAY AND 5:30

PM TO 7 AM ON SATURDAY & SUNDAY. CEILING TILES AND GRID SHALL BE

CAREFULLY REMOVED AND SOTRED IN A SAFE MANNER UNTIL THEY CAN BE

REINSTALLED. DAMAGED AND BROKEN CEILING TILES SHALL BE REPLACED

BY CONTRACTOR.

EXIT/ACCESS FOR ADJACENT OPERATIONAL AREAS SHALL BE MAINTAINED

DURING NORMAL BUSINESS HOURS, MONDAY THROUGH FRIDAY FROM 5 AM

TO 8 PM AND ON SATURDAY AND SUNDAY FROM 7 AM TO 5:30 PM.

WORK REQUIRING VIBRATION OR LOAD NOISES, SUCH AS STRUCTURAL

WORK ON ROOF, SHALL TAKE PLACE OFF HOURS BETWEEN 8 PM AND 5 AM,

MONDAY THROUGH FRIDAY AND 5:30 PM TO 7 AM ON SATURDAY & SUNDAY.

EVERY EFFORT SHALL BE MADE TO KEEP NOISE AND VIBRATION TO A

MINIMUM. SCHEDULING SHALL BE COORDINATED WITH THE VA.

CONTRACTOR SHALL SUPPLY SPILL KIT. SPILL KIT TO INCLUDE SHOP VAC,

MULTI-PURPOSE SPILL CONTROL SORBENTS TO ABSORB NON AGGRESSIVE

LIQUIDS UP TO 30 GALLONS.

ALL NEW MATERIAL MOVED THROUGH THE FACILITY SHALL BE COVERED

WITH 6 MIL. POLY SHEET.

ALL DEMOLITION MATERIAL SHALL BE REMOVED FROM THE PROJECT

BOUNDARY THROUGH THE FACILITY TO DUMPSTER ALONG VA APPROVED

ROUTE IN ENCLOSED DUMPSTER CART DESIGNED FOR SUCH PURPOSE

WITH A LID.

ALL MATERIAL, DEBRIS AND HAZARDOUS MATERIALS SHALL BE PROPERLY

STORED IN DESIGNATED AREAS AND APPROVED CONTAINERS. FLAMMABLE

MATERIALS SHALL NOT BE STORED IN THE FACILITY.

PROVIDE CONTAINMENT CART FOR ABOVE CEILING ACCESS OUTSIDE

PROJECT BOUNDARY.

INFECTION CONTROL GENERAL NOTES

INFECTION CONTROL PROJECT INFORMATION

NOTE: THIS PRELIMINARY INFECTION CONTROL RISK ASSESSMENT (ICRA) WAS

COMPLETED DURING DESIGN IN ANTICIPATION OF WORK REQUIRED TO BE

COMPLETED BY THE CONTRACTOR DURING CONSTRUCTION. ACTUAL ICRA SHALL BE

COMPLETED BY THE VA ONCE CONSTRUCTION CONTRACT IS AWARDED. CONTRACTOR

SHALL COMPLY WITH ALL REQUIREMENTS AS DIRECTED BY THE VA INFECTION

CONTROL REPRESENTATIVE.

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

M.

N.

O.

P.

Q.

R.

S.

CLASS II:

(NOTE: CLASS II MUST ALSO INCLUDE ALL CLASS I REQUIREMENTS,

INCLUDED BELOW)

PERFORM WORK ACTIVITY IN A MANNER THAT DOES NOT CREATE DUST.

(CLASS I REQUIREMENT)

IMMEDIATELY REPLACE ANY CEILING TILE, CLOSE ACCESS PANELS, ETC.,

UPON COMPLETION OF WORK. (CLASS I REQUIREMENT)

ANY MATERIALS AND EQUIPMENT BEING BROUGHT INTO THE FACILITY MUST

BE FREE OF CONTAMINANTS AND LOOSE MATERIAL. (CLASS I REQUIREMENT)

PROVIDE ACTIVE MEANS TO CONTROL AIRBORNE DUST FROM DISPERSING

INTO OCCUPIED AREAS AND/OR WATER MIST SURFACE TO CONTROL DUST.

ENSURE WORKER CLOTHING IS CLEAN AND FREE OF VISIBLE DUST BEFORE

LEAVING WORK AREA.

REMOVE OR ISOLATE AIR DIFFUSERS, BOTH SUPPLY AND RETURN, TO

PROTECT HVAC SYSTEM FROM DUST AND REDUCE AIR TURBULENCE.

REBALANCE SYSTEM TO ADDRESS DIFFUSER ISOLATION.

WHEN THE WORK INVOLVES OR IMPACTS PORTABLE WATER SYSTEMS

INCLUDING STAGNATION DUE TO REDUCE USAGE, THE PIPING SHALL BE

FLUSHED TWICE A WEEK OR ISOLATED FROM THE MAIN SYSTEM.

SEAL DOORS TO PREVENT DUST MIGRATION.

CONTAIN ALL TRASH AND DEBRIS IN THE WORK AREA. PERFORM DAILY

CLEANING AND DISPOSAL OF TRASH, WHICH MUST BE COVERED, FROM

WORK AREA USING AN IDENTIFIED EXIT ROUTE.

ANY EQUIPMENT, TOOLS, OR MATERIALS REMOVED FROM THE WORK AREA

MUST BE IN SEALED CONTAINERS AND/OR CLEANED OF DUST AND DEBRIS

PRIOR TO REMOVAL FROM AREA.

NONPOROUS/SMOOTH AND CLEANABLE CONTAINERS, WITH A HARD LID,

MUST BE USED TO TRANSPORT TRASH AND DEBRIS FROM CONSTRUCTION

AREAS. THESE CONTAINERS MUST BE DAMPED-WIPED CLEANED AND FREE

OF VISIBLE DUST/DEBRIS BEFORE LEAVING THE CONTAINED WORK AREA.

INSTALL STICKY, DUST COLLECTION, MAT AT ENTRANCE OF CONTAINED

WORK AREA BASED ON FACILITY POLICY. STICKY MATT MUST BE CHANGE

ROUTINELY AND WHEN VISIBLY SOILED.

MAINTAIN CLEAN SURROUNDINGS WHEN AREA IS NOT CONTAINED BY DAMP

MOPPING OR HEPA VACUUMING SURFACES AT LEAST DAILY.

CLASS III:

(NOTE: CLASS III MUST INCLUDE ALL CLASS I & II REQUIREMENTS LISTED

ABOVE AS WELL AS THE REQUIREMENTS LISTED BELOW)

ENSURE AVAILABILITY OF EQUIPMENT FOR CLEANING HANDS

CONSTRUCT AND COMPLETE CRITICAL BARRIERS MEETING NFPA 241

REQUIREMENTS. BARRIERS MUST EXTEND TO THE CEILING OR IF CEILING

TILES ARE REMOVED, TO THE DECK ABOVE.

ALL PLASTIC OR HARD BARRIER CONSTRUCTION ACTIVITIES MUST BE

COMPLETED IN A MANNER THAT PREVENTS DUST RELEASE. PLASTIC

BARRIERS MUST BE EFFECTIVELY AFFIXED TO FLOOR AND CEILING, OR

DECK ABOVE, AND SECURE FROM MOVEMENT OR DAMAGE.

SEAL ALL PENETRATIONS IN CONTAINMENT BARRIERS, INCLUDING FLOOR

AND CEILING, USING APPROVED MATERIAL. (UL BARRIER FIRESTOP IF

APPLICABLE)

MAINTAIN 0.01 INCHES/WATER GUAGE NEGATIVE PRESSURIZATION OF THE

ENTIRE WORKSPACE BY USE OF HEPA EXHAUST AIR SYSTEMS DIRECTLY

OUTDOORS, OR COMPLY WITH ALTERNATIVE METHODS. THESE CONTROL

METHODS MUST BE MAINTAINED CONTINOUSLY 24/7 FOR THE DURATION OF

THE PROJECT. HEPA FILTERED EXHAUST IF DIRECTLY DISCHARGED TO THE

OUTDOORS MUST BE AT A DISTANCE OF 25 OR GREATER FROM ENTRANCES,

AIR INTAKES OR OPERABLE WINDOWS. EXHAUSTING DISCHARGED AIR INTO

SHARED OR RECIRCULATING HVAC SYSTEMS OR OTHER SHARED EXHAUST

SYSTEMS, SUCH AS BATHROOMS, IS PROHIBITED.

INSTALL A DIFFERENTIAL PRESSURE SENSING DEVICE OR EXTERIOR OF

WORK CONTAINEMENT TO CONTINUALLY MONITOR AND DOCUMENT

NEGATIVE PRESSURIZATION. THE "BALL IN THE WALL" OR SIMILAR

APPARATUS ARE NOT ACCEPTABLE.

LEVEL OF PRECAUTIONS

8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

AREA - A

AREA - B

AREA - C

KEY PLAN :-

GUIDON DESIGN

1221 N Pennsylvania St, Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com GD Project : 24-1012-01

ARCHITECT, STRUCTURAL ENGINEER

Au to de sk

D oc s:

//2

.0

VA

C ol um bu s (O

H ) A

E R ep la ce A ir- C oo le d C hi lle rs /2

4.

.0

1_ A_ v2 4.

rv t

3/

/2

3:

:0

PM

AE111

SECOND LEVEL - AREA-A - RCP &

ICRA PLAN

Replace Air Cooled Chillers Chalmers P. Wylie VA Ambulatory Care Center

420 N. James Rd, Columbus, OH

01A

03/26/2025 TD TS

CONSTRUCTION

DOCUMENTS

757-23-101

SCALE: 1/8" = 1'-0"AE111

1 SECOND LEVEL - AREA-A - REFLECTED CEILING PLAN & INFECTION CONTROL PLAN

N

SCALE: 1 1/2" = 1'-0"AE111

2 TEMPORARY INFECTION CONTROL PLASTIC BARRIER

Revisions: Date:

AE104 - ROOF - AREA-A - ROOF PLAN
AE111 - SECOND LEVEL - AREA-A - RCP & ICRA PLAN