The document is an Equipment Specification Sheet for a York air-cooled chiller (Model YVAA0176) for the VA Columbus project. The chiller has a net cooling capacity of 140.0 tons, total power input of 172.0 kW, and operates with R-513A refrigerant. Key specifications include two VSD screw compressors, capacity control from 10-100%, and electrical operation at 460V/3/60 with voltage limits of 414V-508V.
Performance details show the chiller has an Energy Efficiency Ratio (EER) of 9.765, sound power level of 101.0 dB(A), and is designed for a Part Load Performance with efficiency varying from 10.98 Btu/W.h at 100% load to 27.62 Btu/W.h at 25% load. The unit weighs 15,467 lbs operating, has dimensions of 291.2" x 88.3" x 92.8", and is compliant with ASHRAE 90.1 standards from 2010-2022. The chiller is manufactured in Mexico and includes features like low sound fans with variable speed control and a standard factory sound reduction kit.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPENDIX 06
Equipment Specification Sheets
Full Load - Design
Unit
Model No. YVAA0176
Number of Compressors 2
Compressor Type VSD Screw - Semi Hermetic
Number of Compressor Circuits 2
Capacity Control 10% - 100%
Refrigerant R-513A
Performance Data
Net Cooling Capacity [tons.R] 140.0
Total Power Input [kW] 172.0
EER [Btu/W.h] 9.765
NPLV.IP [Btu/W.h] 17.07
A-Weighted Sound Power [dB(A)] 101.0
Sound Pressure (Hemispherical Method) [dB(A)] 71.0
Sound Pressure Measured at [ft] 30.0
Electrical Data
Nominal Voltage / Voltage Limits 460/3/60.0 / 414V - 508V
Compressor kW (each circuit) 75.79 / 78.55
Compressor RLA (each circuit) [A] 100.3 / 103.9
Fan QTY (each circuit) 6 / 6
Fan FLA (each circuit) [A] 3.4 / 3.4
Min. Circuit Ampacity [A] 274.7
Max. Fuse / CB Rating [A] 350.0
Unit Short Circuit Withstand [kA] 50 kA
Displacement Power Factor 0.95
Control kVA 2.000
Performance Impacting Options
Compressor Style Maximum Part Load Efficiency
Condenser Coil 4G Microchannel Coil - 25mm
Fan Low Sound Fans With Variable Speed Control
Sound Attenuation Standard Factory Sound Kit (Level 0 Reduction)
Weight & Dimensional Data
Shipping Weight [lbs] 14800
Operating Weight [lbs] 15467
Refrigerant Charge [lbs] 196 / 196
Length [in] 291.2
Width [in] 88.3
Height [in] 92.8
Performance Report Performance Specification
Project Name: VA Columbus Unit Tag: CH-3 Qty.: 1 Model: YVAA0176
Project Name: VA Columbus
Rating Engine Version: REV.v9_24a.idd Version: SN24.08b Generated: 2024/10/17 at 10:05
Unit Name: CH-3 CHL.2024-09.002 Page 1 of 4
Heat Exchanger Performance
Evaporator Condenser (Air Cooled)
Heat Exchanger Type Hybrid Falling Film Ambient Air Temperature* [ºF] 95.0
Entering Fluid Temperature* [ºF] 44.00 Altitude* [ft] 800
Leaving Fluid Temperature* [ºF] 36.00 Condensing Temperature [ºF] 113.90 / 115.09
Flow Rate [USGPM] 445.8 Number of Fans (Circuit 1 / Circuit 2) 6 / 6
Fouling Factor* [h ft2 F/Btu] 0.000100 Total Air Flow [cfm] 138251
Fluid Type* / Concentration* [%] Propylene Glycol / 30.0 Total Fan Power [kW] 17.69
Passes* 2
Pressure Drop [ft H2O] 24.2
Fluid Volume [USGAL] 80.0
Evaporating Temperature [ºF] 29.71
Minimum Flow Rate [USGPM] 319.0
Maximum Flow Rate [USGPM] 790.0
Bundle Code (System 1 / System 2) Tube Bundle A (3/4") / Tube Bundle A (3/4")
* Designates user specified input
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org. Unit contains freeze protection fluids in the evaporator with a leaving chilled fluid temperature above 32 DEG F [0 DEG C] and is certified when rated per the Standard with water. Auxiliary components included in total KW - Oil heaters, Chiller controls. Auxiliary power is already included in the compressor and fan power
Part Load Performance (Based on Standard AHRI Unloading)
Percent Load Ambient [ºF] Capacity [tons.R] Power Input [kW] Unit Efficiency [Btu/W.h]
100.0 95.0 140.0 172.0 9.765
75.0 80.1 105.0 95.72 13.16
50.0 65.1 69.99 43.24 19.42
25.0 55.0 35.00 18.61 22.56
Project Name: VA Columbus Unit Tag: CH-3 Qty.: 1 Model: YVAA0176
Project Name: VA Columbus
Unit Name: CH-3 CHL.2024-09.002 Page 2 of 4
Sound Power Levels (In Accordance with AHRI 370)
Percent Load Ambient [ºF] Octave Band Center Frequency [Hz]
LWA
63 125 250 500 1000 2000 4000 8000
100.0 95.0 97.0 97.0 98.0 101.0 97.0 92.0 87.0 83.0 101.0
75.0 80.1 93.0 94.0 94.0 94.0 92.0 85.0 81.0 77.0 96.0
50.0 65.1 90.0 91.0 90.0 91.0 88.0 82.0 78.0 74.0 92.0
25.0 55.0 86.0 87.0 87.0 88.0 85.0 79.0 75.0 71.0 89.0
Note:Unit is equipped with Low Sound Fans With Variable Speed Control.
Measurement of sound pressure used to obtain the sound power data presented is based on AHRI-370.
Air-cooled chillers are rated in terms of sound power not sound pressure. Johnson Controls provides estimates of sound pressure, but this is not the rating metric.
For an air-cooled chiller, sound pressure calculated from sound power varies depending on how the chiller is assumed to behave, i.e. the radiation model. In other words, determining sound pressure from sound power requires making assumptions that result in different answers at a given distance from the chiller. The environment also influences sound pressure in the field installation. Sound pressure estimation radiation models pertaining to air-cooled chillers include the ‘traditional’ hemispherical model, parallelepiped model and equivalent hemispherical model.
Regarding sound power, Johnson Controls references tolerance limits based on ASHRAE guidelines. These are +/- 6dB in the 63Hz octave band, +/- 4dB in all other octave bands and +/- 3dB for the overall dBA.
Tolerance limits are based on uncertainties associated with:
1. Measurement Test Procedure
2. Repeatability
3. Production / Manufacturing Variability
Standard deviation associated with air-cooled chiller sound data is a measure of spread i.e. it indicates the range of probability of sound levels. Note that for operating conditions other than AHRI’s Standard Rating Condition, higher levels of uncertainty can be expected.
Lead times for factory performance testing depend on test laboratory availability. Please confirm with Johnson Controls Customer Service.
Percent Load Ambient [ºF] Octave Band Center Frequency [Hz]
LpA 63 125 250 500 1000 2000 4000 8000
100.0 95.0 67.0 67.0 68.0 71.0 67.0 62.0 57.0 53.0 71.0
75.0 80.1 63.0 64.0 64.0 64.0 62.0 55.0 51.0 47.0 66.0
50.0 65.1 60.0 61.0 60.0 61.0 58.0 52.0 48.0 44.0 63.0
25.0 55.0 56.0 57.0 57.0 58.0 55.0 49.0 45.0 41.0 59.0
Performance at AHRI Conditions
Evaporator Condenser
EFT [ºF] 54.00 Ambient Temp. [ºF] 95.0
LFT [ºF] 44.00 Altitude [ft] 0.00
Flow Rate [USGPM] 408.8 Performance
Pressure Drop [ft H2O] 20.1 EER [Btu/W.h] 10.98
Fluid Type Water IPLV.IP [Btu/W.h] 20.45
Fouling Factor [h ft2 F/Btu] 0.000100 Net Cooling Capacity [tons.R] 170.8
Fluid Volume [USGAL] 80.0
Note:Unit rated at design condition capacity.
Project Name: VA Columbus Unit Tag: CH-3 Qty.: 1 Model: YVAA0176
Project Name: VA Columbus
Unit Name: CH-3 CHL.2024-09.002 Page 3 of 4
Part Load Performance (Based on AHRI 550/590 - 2023 (IP))
Percent Load Ambient [ºF] Capacity [tons.R] Power Input [kW] Unit Efficiency [Btu/W.h]
100.0 95.0 170.8 186.8 10.98
75.0 80.0 128.1 101.9 15.09
50.0 65.0 85.41 43.16 23.75
25.0 55.0 42.71 18.55 27.62
Notes:
Country of Origin:Mexico
Displacement Power Factor refers to compressor only. Unit Power Factor depends on fan option selected. Calculated value is available by request.
Use Copper Conductors only
Minimum and maximum evaporator flow information are for full load ratings with Propylene Glycol.
Evaporator Passes:2, Condenser Type:4, Fan Type:V
Compliant with ASHRAE 90.1 - 2010,2013,2016,2019,2022.
Compliant with IECC - 2012,2015,2018.
The product image shown is for illustrative purposes only and is not representative of selected options.
Project Name: VA Columbus Unit Tag: CH-3 Qty.: 1 Model: YVAA0176
Project Name: VA Columbus
Unit Name: CH-3 CHL.2024-09.002 Page 4 of 4
LOOSE COIL
PERFORMANCE SPECIFICATION
Project Name: VA Lovell Coil Contract No.:
Printed: 10/23/2024 at 22:00 COIL-1Performance Unit Folder: 30EG Page 1 of 1
Unit Tag Quantity Coil Type Air Flow (scfm) Function
COIL-1 1 CDW (Glycol) 13850 Rate
Input Data General Air Side Fluid Side Application: Cooling Altitude (ft.): 0 EWT (°F): 36.0 Tube Diameter: 5/8” Air Flow (scfm): 13850 LWT (°F): n/a Tube Wall Thickness: 0.020” Face Velocity (ft/min): 508 Flow Rate (gpm): 325.0 Fouling Factor (hft²°F/btu): 0.00000 EAT-DB (°F): 89.4 Max. WPD (ft.): n/a Casing Material: 304 Stainless
Steel
EAT-WB (°F): 75.0 TPC: 4
Fin Type: Sine Max. APD (in. w.g): 3.00 Fluid: Propylene Glycol - 30.0
Fin Material: Aluminum Req. LAT-WB (°F): n/a Fluid Volume (ft³): 4.3 Fin Thickness: 0.006” Req. TMBH: n/a Fluid Weight (lbs): 275.4 Fin Height: 39.25” Air Flow Direction: Horizontal Fin Length: 100” Connection Material: Steel Connection Type: MPT Dry Weight (lbs.): 644.0
Note: Coil is not coated.
Output Data General Air Side Performance Fluid Side Performance Rows: 8 LAT-DB (°F): 48.54 LWT (°F): 43.71 FPI: 10 LAT-WB (°F): 48.31 Fluid Vel. (fps) 7.0 TPC: 4 TMBH: 1189.4 WPD (ft.): 26.0 Connection Size: 4” SMBH: 634.6 Flow Rate (gpm): 325.0 No. Connections: 1 APD (in. w.g): 1.32
Coil Dll Version: 7.7M
Note(s): Ratings are for coils manufactured by: Johnson Controls, Inc., 507 E. Michigan St., Milwaukee WI 53202
CDW Tube Spacing: 1.50" x 1.30"
This coil is certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the range of Standard rating conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org.
Johnson Controls suggests using red brass or copper connectors when the coil is to be attached to a copper or brass piping system.
OVERALL HEIGHT MAY BE GREATER DEPENDING ON MOTOR, ADAPTER, AND/OR
HINGE BASE.
17.00 SQ
1.75 14.60
Ø 21.80
Model: G-090-VG Direct Drive Centrifugal Roof Exhaust Fan
Dimensional Quantity 1
Weight w/o Acc's (lb) 25
Weight w/ Acc's (lb) 30
Standard Curb Cap Size (in.) 17 x 17 Roof Opening (in.) 13.5 x 13.5
Performance Requested Volume (CFM) 500
Actual Volume (CFM) 500
Total External SP (in. wg) 0.5
Fan RPM 1600
Operating Power (hp) 0.08
Elevation (ft) 807
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.073
Tip Speed (ft/min) 4,555 Static Eff. (%) 49
Misc Fan Data Fan Eff. Index (FEI) -
Outlet Velocity (ft/min) 714
Motor Motor Mounted Yes
Size (hp) 1/10
Voltage/Cycle/Phase 115/60/1
Enclosure TENV
Motor RPM 1725
Efficiency Rating High
Windings 1 FLA (Amps) 1.38
Min. Circuit Ampacity (MCA) 2 Max. Overcurrent Protection (MOP) 15
Short Circuit Current Rtg (SCCR) 5 kA
Notes:
All dimensions shown are in units of in.
*NEC FLA, MCA and MOP are for reference only – based on tables 430.248 or 430.25 of National Electric Code 2020. Actual motor FLA may vary, for sizing thermal overload, consult factory.
MCA and MOP values shown only account for the motor, not accessories (damper actuator, field supplied VFD, etc).
LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 5 ft - dBA levels are not licensed by AMCA International Sones - calculated using ANSI/AMCA 301 at 5 ft
Sound Power by Octave Band Sound Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 76 74 70 63 59 56 52 45 66 55 7.8
Cut Sheet - Not for Submittal 11/25/2024Printed Date:
EF-01AMark:
G-090-VGModel:
Generated by: dbradley@specializedeng.comCAPS 4.43.1068 Page 1 of 3 C:\Users\dbradley\OneDrive - Specialized Engineering Solutions\CAPS\Columbus VA.gfcj
Model: G-090-VG Direct Drive Centrifugal Roof Exhaust Fan Standard Construction Features:
- Aluminum housing - Backward inclined composite (sizes 60-95) or aluminum (sizes 97-300) wheel - Aluminum curb cap with prepunched mounting holes - Birdscreen - Ball bearing motors (sizes 85-300 and all Vari Green), sleeve bearing motors (sizes 60-80) - Motor isolated on shock mounts - Corrosion resistant fasteners Selected Options & Accessories:
Motor - Vari-Green EC motor Control - Dial for balancing Standard Curb Cap Size - 17 Square UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-1, Toggle, Junction Box Mounted & Wired in weather-protected motor compartment Birdscreen: Galvanized, nom. 84% Free Area Composite Wheel Material Conduit Chase Qty 1 Unit Warranty: 1 Yr (Standard)
The Vari-Green Motor included in this order has a ‘Multi-Voltage’ ability. The red wire on the motor is called a ‘Voltage Doubler’, and when it is connected the motor can be powered by 115V.
If the Red wire is disconnected, then the motor can be powered with 208-230/277V. The motor will leave the factory with the voltage doubler wired per the order.
Cut Sheet - Not for Submittal 11/25/2024Printed Date:
EF-01AMark:
G-090-VGModel:
Generated by: dbradley@specializedeng.comCAPS 4.43.1068 Page 2 of 3
AMCA
AMCA Licensed for Sound and Air Performance. Power rating (BHP/kW) does not include transmission losses.
Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP/kW) includes transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per ANSI/AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. dBA levels are not licensed by AMCA International. The AMCA Certified Ratings Seal applies to sone ratings only.
Cut Sheet - Not for Submittal 11/25/2024Printed Date:
EF-01AMark:
G-090-VGModel:
Generated by: dbradley@specializedeng.comCAPS 4.43.1068 Page 3 of 3
WIZE-882E0E8B 11/25/2024
Hydronic & Steam Equipment Co., Inc
(317) 577-8326 mkring@hydstm.com
Model: 3GB
445 US gpm
115 ft
34.5 ft
74.9 %
72.0 %
12.5 in
25 hp
17.2 bhp
1800 rpm
1617 rpm
6.87 ft
142 ft
86.7 US gpm
433 US gpm
68 ºF
Water
862 lbs
6.98 ft²
Energy Efficiency Ratings:
Pump & Motor PEIcl: 0.89 ERcl: 11 Pump, Motor & Drive: PEIvl: 0.44 ERvl: 56
3GB
1617 RPM
Performance curve meets 14.6 / ISO 9906 acceptance criteria | Available Phase: 3, Available Voltage(s) [V]: 200, 230/460, 575 WIZE-882E0E8B
Constant Speed Curve (1750 rpm)
Operating Point
Flow: 445 US gpm Head: 115 ft Speed: 1617 Efficiency: 74.9% Point BHP: 17.2 End Of Curve: 75.5%
Maximum Duty Point (at rated motor speed)
Flow: 482 US gpm Head: 135 ft Speed: 1750 Efficiency: 75% Point BHP: 21.8 NOL Flow: 638 US gpm Runout Flow: 638 US gpm NOL (BHP): 24.3
WIZE-882E0E8B
File details come from the government source that posted it. Updated .