S02. ELECTRICAL SYMBOLS AND ABREVIATIONS.pdf

PDF 574 KB Posted

Attached to
Project 757-23-101 Air Cooled Chillers
Solicitation number
36C25025R0096_1
Issued by

About this file

The document is an electrical symbols and abbreviations reference sheet for a VA project to replace air-cooled chillers at the Chalmers P. Wylie VA Ambulatory Care Center in Columbus, Ohio. The sheet contains comprehensive electrical abbreviations ranging from technical terms like "KAIC" (Kiloampere Interrupting Capacity) to common electrical indicators like "AFF" (Above Finished Floor), along with electrical equipment symbols and graphical representations of electrical components such as automatic transfer switches, circuit breakers, and switchboards.

The sheet includes several critical electrical design notes, such as requirements for branch circuit conductor sizing, fire-rated wall penetration procedures, lightning protection guidelines, and electrical system bonding specifications. Additionally, the document provides technical guidance on electrical device installations, including mounting height coordination, ground fault protection, and requirements for critical and life safety branch circuits. These notes are part of the construction documentation for project 757-23-101, which involves replacing two existing roof-mounted air-cooled chillers with three new chillers and modifying airflow in the sterile processing equipment room.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL ABBREVIATIONS

ABBREVIATION DESCRIPTION

REFER TO OTHER SCHEDULES AND NOTES FOR ADDITIONAL ABBREVIATIONS.

MOUNTING HEIGHT TO CENTERLINE (ABOVE FINISHED FLOOR)

AMPERE

AMPERE FRAME

ABOVE FINISHED FLOOR

ALUMINUM

AMPERE TRIP

CONDUIT

CIRCUIT BREAKER

CORRELATED COLOR TEMPERATURE

COPPER

DATA (WHEN APPLIED TO COMMUNICATIONS OUTLET)

DEMO (WHEN APPLIED TO EXISTING/DEMO ITEMS)

EXISTING

ELECTRICALLY OPERATED

ENERGY REDUCING MAINTENANCE SWITCH

FUSE

FULL LOAD AMPS

GROUND FAULT CIRCUIT INTERRUPTER

GROUND FAULT ALARM

GROUND FAULT PROTECTION

HORSEPOWER

KILOAMPERE INTERRUPTING CAPACITY

KILOVOLT AMPERE

KILOWATT

MAXIMUM

MINIMUM CIRCUIT AMPS

MAIN CIRCUIT BREAKER

MINIMUM

MAIN LUGS ONLY

MANUALLY OPERATED

NORMALLY CLOSED

NON-FUSED

NOT IN CONTRACT

NORMALLY OPEN

POLES

PARTIAL

RELOCATE

SHORT CIRCUIT CURRENT RATING

SURGE PROTECTIVE DEVICE

SHUNT TRIP

TYPICAL

UNLESS NOTED OTHERWISE

VOICE

WALL PHONE

WIRE

WEATHER RESISTANT

TRANSFORMER

ZONE SELECTIVE INTERLOCKING

A

AF

AFF

AL

AT

C

CB

CCT

CU

D

D

E

EO

ERMS

F

FLA

G, GFCI

GFA

GFP

HP

KAIC

KVA

KW

MAX

MCA

MCB

MIN

MLO

MO

NC

NF

NIC

NO

P

PART

R

SCCR

SPD

ST

TYP

UNO

V

W

W

WR

XFMR

ZSI

A. BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 75' SHALL UTILIZE #10 AWG CONDUCTORS.

RECEPTACLE BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 150' SHALL UTILIZE #8 AWG

CONDUCTORS.

B. FOR ALL CONDUIT AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER’S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE

SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.

C. NEW ROOF MOUNTED EQUIPMENT SHALL BE BONDED TO EXISTING BUILDING LIGHTNING PROTECTION SYSTEM. PROVIDE AIR TERMINALS ON TOP OF EQUIPMENT AND BOND TO EXISTING SYSTEM PER NFPA 780 AND UL 96A REQUIREMENTS. PROVIDE UL INSPECTION AND/OR LPI SYSTEM INSPECTION AS REQUIRED TO OBTAIN UL MASTER LABEL RECERTIFICATION, UL MASTER LABEL AND/OR LPI SYSTEM CERTIFICATE.

D. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO ADDITIONAL

COST TO THE OWNER.

E. NEW WIRING DEVICES AND ASSOCIATED COVERPLATES SHALL MATCH EXISTING FINISH OF SIMILAR

INSTALLED DEVICES.

F. THE SELECTED EQUIPMENT AIC RATINGS ARE BASED ON THE IMPEDANCES FOR CONDUCTORS AND TRANSFORMERS USED IN THE CALCULATIONS. IF DIFFERENT EQUIPMENT OR DIFFERENT CONFIGURATIONS

ARE SELECTED FOR INSTALLATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING

ADEQUATELY RATED EQUIPMENT THAT MEETS APPLICABLE SELECTIVE COORDINATION GOALS AND

PROVIDES SIMILAR INCIDENT ENERGY RISK OF ARC FLASH HAZARDS.

G. PROVIDE AN INSULATED CONTINUOUS COPPER CONDUCTOR, NOT SMALLER THAN #10, TO BOND ALL

NORMAL AND ESSENTIAL ELECTRICAL SYSTEM PANELBOARDS TOGETHER THAT SERVE THE SAME

INDIVIDUAL PATIENT VICINITY AS DEFINED IN NEC 517.14.

H. ALL CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, INCLUDING LIGHTING AND WALL RECEPTACLES, SHALL BE MECHANICALLY PROTECTED PER NEC 517.31(C)(3). NON-FLEXIBLE RACEWAY SHALL BE USED FOR CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, EXCEPT THAT THE FINAL CONNECTION TO VIBRATING EQUIPMENT OR LIGHT FIXTURES IF THE TOTAL LENGTH OF FLEXIBLE RACEWAY IS 6' OR LESS ACROSS THE

ENTIRE CIRCUIT LENGTH.

I. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO INDEPENDENTLY SUPPORT ALL EXISTING TO REMAIN

CABLING.

J. REFER TO SHEET GC001 FOR PHASING INFORMATION.

(GENERAL NOTES SHALL APPLY TO ALL SHEETS)

ELECTRICAL GENERAL NOTES:

TRACY J.

HAUSER

E-82068

STATE OF OHIO

P

RR

O

F

ESS IONA L ENG

IN

E

E

REG I TERED

S

8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

GUIDON DESIGN

1221 N Pennsylvania St, Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com GD Project : 24-1012-01

ARCHITECT, STRUCTURAL ENGINEER

03/26/2025

A u to d e s k D o c s /2

.0

V A

C o lu m b u s

O H

A

E R e p la c e

A ir -C o o le d C h ill e rs

/2

.0

V A

C o lu m b u s A

E R e p la c e

A C

C S

E S

.r v t

/2

/2

:3

:0

A

M

E000

ELECTRICAL SYMBOLS AND

ABBREVIATIONS

Replace Air Cooled Chillers

Chalmers P. Wylie VA Ambulatory

Care Center

420 N. James Rd, Columbus, OH 43219

01A

03/26/2025 AEA MEA

23203.001

CONSTRUCTION

DOCUMENTS

757-23-101

ELECTRICAL EQUIPMENT

SYMBOLS

PLAN SYMBOL NAME

AUTOMATIC TRANSFER SWITCH

DISTRIBUTION PANEL

PANELBOARD - SURFACE

SWITCHBOARD

ONE LINE SYMBOL

PLAN SYMBOL NAME

AUTOMATIC TRANSFER SWITCH

CIRCUIT BREAKER

CONTINUATION

GROUND BAR

GROUNDING ELECTRODE

MOTOR

PANEL BOARD

SWITCHBOARD/SWITCHGEAR

THREE-WAY MOTOR-OPERATED

CONTROL VALVE

TWO-WAY MOTOR-OPERATED

CONTROL VAVLE

Revisions: Date:

SS4

E

ATS-CHILW1

E

ATS-C1DEA

E

ATS-D3DEB

E

SS2

E

SS3

E

SS1

E

C1SDA

E

C1DCAS1

E

C1SBEA

E

C1DAS2

E

ATS-LS

E

ATS-CR

E

ATS-EQ

E

C1SBEMA

E

KL

TRACY J.

HAUSER

E-82068

STATE OF OHIO

P

RR

O

F

ESS IONA L ENG

IN

E

E

REG I TERED

S

8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

GUIDON DESIGN

1221 N Pennsylvania St, Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com GD Project : 24-1012-01

ARCHITECT, STRUCTURAL ENGINEER

03/26/2025

A u to d e s k D o c s /2

.0

V A

C o lu m b u s

O H

A

E R e p la c e

A ir -C o o le d C h ill e rs

/2

.0

V A

C o lu m b u s A

E R e p la c e

A C

C S

E S

.r v t

/2

/2

:3

:0

A

M

ED100

FIRST FLOOR - ENLARGED -

POWER - DEMOLITION

Replace Air Cooled Chillers

Chalmers P. Wylie VA Ambulatory

Care Center

420 N. James Rd, Columbus, OH 43219

01A

03/26/2025 AEA MEA

23203.001

CONSTRUCTION

DOCUMENTS

757-23-101

N

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

1/4" = 1'-0"

FIRST FLOOR - ENLARGED - ELECTRICAL - DEMOLITION

ABCDEFGHJK

TRACY J.

HAUSER

E-82068

STATE OF OHIO

P

RR

O

F

ESS IONA L ENG

IN

E

E

REG I TERED

S

8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

AREA - A

AREA - B

AREA - C

KEY PLAN :-

GUIDON DESIGN

1221 N Pennsylvania St, Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com GD Project : 24-1012-01

ARCHITECT, STRUCTURAL ENGINEER

03/26/2025

A u to d e s k D o c s /2

.0

V A

C o lu m b u s

O H

A

E R e p la c e

A ir -C o o le d C h ill e rs

/2

.0

V A

C o lu m b u s A

E R e p la c e

A C

C S

E S

.r v t

/2

/2

:3

:0

A

M

ED103

ROOF - OVERALL - ELECTRICAL -

DEMOLITION

Replace Air Cooled Chillers

Chalmers P. Wylie VA Ambulatory

Care Center

420 N. James Rd, Columbus, OH 43219

01A

03/26/2025 AEA MEA

23203.001

CONSTRUCTION

DOCUMENTS

757-23-101

N

5 5 10 15 20 25 30 35 40 45

1/16" = 1'-0"

FEETSCALE

1/16" = 1'-0"

ROOF - OVERALL - ELECTRICAL - DEMOLITION

(E) ACH-1

(E) ACH-1

(E) RTU-9

(E) RTU-11

(E) RTU-13

ABCDEFGHJ

A. THE INTENT OF THE DEMOLITION DRAWINGS IS TO DEFINE THE SCOPE OF ELECTRICAL DEMOLITION WORK. EXISTING ELECTRICAL SYSTEMS (DEVICES, FIXTURES, EQUIPMENT, WIRING, AND RACEWAYS INCLUDING DATA/COMMUNICATION SYSTEMS). EXISTING ELECTRICAL SYSTEMS SERVING ADJACENT AREAS SHALL REMAIN UNLESS OTHERWISE INDICATED. RE-SUPPORT EXISTING CONDUITS AND CABLES THAT MUST REMAIN. REFER TO

FLOORPLANS FOR INDICATION OF DEMOLITION TYPE FOR EACH AREA:

a. SELECTIVE DEMOLITIONS AREAS:

• PROVIDE DEMOLITION FOR ITEMS AS SHOWN. EXISTING ELECTRICAL SYSTEMS WITHIN LIMITS OF

DEMOLITION SHALL REMAIN UNLESS OTHERWISE INDICATED.

B. ITEMS INDICATED WITH A SUBSCRIPT 'E' SHALL BE EXISTING TO REMAIN (E-EXISTING). ITEMS INDICATED WITH A SUBSCRIPT 'D' OR SHOWN DASHED SHALL BE REMOVED (D-DEMOLITION). ITEMS INDICATED WITH A SUBSCRIPT

'R' SHALL BE REMOVED, STORED, AND REINSTALLED PER NEW WORK (R-RELOCATION).

C. THESE DRAWINGS DO NOT IDENTIFY EACH INDIVIDUAL ITEM TO BE REMOVED. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING ITEMS WHICH MUST BE REMOVED TO FACILITATE NEW CONSTRUCTION. SEE ARCHITECTURAL PLANS FOR EXACT LIMITS OF DEMOLITION AND CONSTRUCTION. THESE PLANS ARE BASED ON PAST PROJECT DRAWINGS AND SITE OBSERVATIONS. THE DRAWINGS ARE PROVIDED TO THE CONTRACTOR AS AN AID IN DETERMINING THE EXTENT OF WORK REQUIRED FOR DEMOLITION AND TO PROVIDE GENERAL INFORMATION ABOUT EXISTING SYSTEMS. THESE DRAWINGS MAY NOT BE ACCURATE IN ALL AREAS. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING CONDITIONS AND IS ENCOURAGED

TO REVIEW FACILITY DRAWINGS PRIOR TO THE BID DATE.

D. THE OWNER SHALL HAVE FIRST SALVAGE RIGHTS TO ALL ITEMS REMOVED. IF OWNER REFUSES SALVAGE, CONTRACTOR IS RESPONSIBLE FOR DISPOSAL.

E. COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY POWER AND LIGHTING AS

REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED.

F. PROTECT EXISTING ELECTRICAL EQUIPMENT THAT REMAINS. IF DAMAGED OR DISTURBED IN THE COURSE OF THE WORK, REMOVE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY, QUALITY, AND

FUNCTIONALITY.

G. PATCH AND REPAIR OPENINGS IN EXISTING WALLS AND FLOORS RESULTANT FROM SPECIFIED ELECTRICAL DEMOLITION. PATCH SHALL MATCH EXISTING CONSTRUCTION, FIRE RATING, AND FINISH. SEE ARCHITECTURAL

SPECIFICATIONS FOR MEANS AND METHODS.

H. THIS PROJECT WILL BE PHASED. SEE PROJECT MANUAL AND ARCHITECTURAL PLANS FOR DETAILS. SYSTEM SERVICES TO AREAS NOT IN THE CURRENT PHASE OF CONSTRUCTION SHALL BE MAINTAINED AT ALL TIMES.

I. WHERE DEMOLITION OF EQUIPMENT INVOLVES REMOVAL OF EQUIPMENT LOCATED ON CONCRETE HOUSEKEEPING PADS, PADS SHALL ALSO BE REMOVED AND FLOOR/GRADE SHALL BE FINISHED TO MATCH

ADJACENT SURFACE.

J. ALL UNLABELED ELECTRICAL DEVICES THAT EXIST IN ALL ROOMS WHERE THERE IS WORK WITHIN SCOPE SHALL

BE CIRCUIT TRACED AS NEEDED WITH A LABEL PROVIDED.

(ELECTRICAL DEMOLITION NOTES APPLY TO ALL ELECTRICAL DEMOLITION PLANS AND

ALL ELECTRICAL DEMOLITION WORK)

ELECTRICAL DEMOLITION GENERAL NOTES:

TRACY J.

HAUSER

E-82068

STATE OF OHIO

P

RR

O

F

ESS IONA L ENG

IN

E

E

REG I TERED

S

8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

AREA - A

AREA - B

AREA - C

KEY PLAN :-

GUIDON DESIGN

1221 N Pennsylvania St, Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com GD Project : 24-1012-01

ARCHITECT, STRUCTURAL ENGINEER

03/26/2025

A u to d e s k D o c s /2

.0

V A

C o lu m b u s

O H

A

E R e p la c e

A ir -C o o le d C h ill e rs

/2

.0

V A

C o lu m b u s A

E R e p la c e

A C

C S

E S

.r v t

/2

/2

:3

:1

A

M

ED103A

ROOF - AREA-A - ELECTRICAL -

DEMOLITION

Replace Air Cooled Chillers

Chalmers P. Wylie VA Ambulatory

Care Center

420 N. James Rd, Columbus, OH 43219

01A

03/26/2025 AEA MEA

23203.001

CONSTRUCTION

DOCUMENTS

757-23-101

1/8" = 1'-0"

ROOF - AREA A - ELECTRICAL - DEMOLITION

N

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

SHEET NOTES:

1. DISCONNECT AND REMOVE CONDUIT AND FEEDERS BACK TO POINT OF ORIGIN IN PANEL C1SBEA. REMOVE

EXISTING LIGHTNING CONTROL FROM EQUIPMENT. MAINTAIN EXISTING SYSTEM TO CONNECT IN NEW WORK

EQUIPMENT.

2. EXISTING EQUIPMENT. NO ELECTRICAL SCOPE.

CHWP-3 (E)

EFGHJ

D3DEA SEC2

D3DEA SEC1

2 2

TRACY J.

HAUSER

E-82068

STATE OF OHIO

P

RR

O

F

ESS IONA L ENG

IN

E

E

REG I TERED

S

8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

AREA - A

AREA - B

AREA - C

KEY PLAN :-

GUIDON DESIGN

1221 N Pennsylvania St, Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com GD Project : 24-1012-01

ARCHITECT, STRUCTURAL ENGINEER

03/26/2025

A u to d e s k D o c s /2

.0

V A

C o lu m b u s

O H

A

E R e p la c e

A ir -C o o le d C h ill e rs

/2

.0

V A

C o lu m b u s A

E R e p la c e

A C

C S

E S

.r v t

/2

/2

:3

:1

A

M

ED103B

ROOF - AREA-B - ELECTRICAL -

DEMOLITION

Replace Air Cooled Chillers

Chalmers P. Wylie VA Ambulatory

Care Center

420 N. James Rd, Columbus, OH 43219

01A

03/26/2025 AEA MEA

23203.001

CONSTRUCTION

DOCUMENTS

757-23-101

1/8" = 1'-0"

ROOF - AREA B - ELECTRICAL - DEMOLITION

N

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

SHEET NOTES:

1. PUMPS CHWP-3 AND CHWP-4 ARE STACKED. CONTRACTOR SHALL DISCONNECT AND REMOVE CONDUIT AND

FEEDERS BACK TO POINT OF ORIGIN FOR BOTH PUMPS.

ABCD

(E) RTU-10

(E) RTU-8

TRACY J.

HAUSER

E-82068

STATE OF OHIO

P

RR

O

F

ESS IONA L ENG

IN

E

E

REG I TERED

S

8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

AREA - A

AREA - B

AREA - C

KEY PLAN :-

GUIDON DESIGN

1221 N Pennsylvania St, Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com GD Project : 24-1012-01

ARCHITECT, STRUCTURAL ENGINEER

03/26/2025

A u to d e s k D o c s /2

.0

V A

C o lu m b u s

O H

A

E R e p la c e

A ir -C o o le d C h ill e rs

/2

.0

V A

C o lu m b u s A

E R e p la c e

A C

C S

E S

.r v t

/2

/2

:3

:1

A

M

ED103C

ROOF - AREA-C - ELECTRICAL -

DEMOLITION

Replace Air Cooled Chillers

Chalmers P. Wylie VA Ambulatory

Care Center

420 N. James Rd, Columbus, OH 43219

01A

03/26/2025 AEA MEA

23203.001

CONSTRUCTION

DOCUMENTS

757-23-101

1/8" = 1'-0"

03_ROOF - AREA C - ELECTRICAL - DEMOLITION

N

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

SHEET NOTES:

1. EXISTING EQUIPMENT. NO ELECTRICAL SCOPE.

SS4

E

ATS-CHILW1

E

ATS-C1DEA

E

ATS-D3DEB

E

SS2

E

SS3

E

SS1

E

C1SDA

E

C1DCAS1

E

C1SBEA

E

C1DAS2

E

C1SBEMA

E

ATS-EQ

E

ATS-CR

E

ATS-LS

E

KL

TRACY J.

HAUSER

E-82068

STATE OF OHIO

P

RR

O

F

ESS IONA L ENG

IN

E

E

REG I TERED

S

8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

GUIDON DESIGN

1221 N Pennsylvania St, Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com GD Project : 24-1012-01

ARCHITECT, STRUCTURAL ENGINEER

03/26/2025

A u to d e s k D o c s /2

.0

V A

C o lu m b u s

O H

A

E R e p la c e

A ir -C o o le d C h ill e rs

/2

.0

V A

C o lu m b u s A

E R e p la c e

A C

C S

E S

.r v t

/2

/2

:3

:1

A

M

EP200

FIRST FLOOR - ENLARGED -

POWER

Replace Air Cooled Chillers

Chalmers P. Wylie VA Ambulatory

Care Center

420 N. James Rd, Columbus, OH 43219

01A

03/26/2025 AEA MEA

23203.001

CONSTRUCTION

DOCUMENTS

757-23-101

1/4" = 1'-0"

FIRST FLOOR - ENLARGED - ELECTRICAL

N

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

ABCDEFGHJK

TRACY J.

HAUSER

E-82068

STATE OF OHIO

P

RR

O

F

ESS IONA L ENG

IN

E

E

REG I TERED

S

8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

AREA - A

AREA - B

AREA - C

KEY PLAN :-

GUIDON DESIGN

1221 N Pennsylvania St, Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com GD Project : 24-1012-01

ARCHITECT, STRUCTURAL ENGINEER

03/26/2025

A u to d e s k D o c s /2

.0

V A

C o lu m b u s

O H

A

E R e p la c e

A ir -C o o le d C h ill e rs

/2

.0

V A

C o lu m b u s A

E R e p la c e

A C

C S

E S

.r v t

/2

/2

:3

:1

A

M

EP203

ROOF - OVERALL - POWER Replace Air Cooled Chillers

Chalmers P. Wylie VA Ambulatory

Care Center

420 N. James Rd, Columbus, OH 43219

01A

03/26/2025 AEA MEA

23203.001

CONSTRUCTION

DOCUMENTS

757-23-101

N

5 5 10 15 20 25 30 35 40 45

1/16" = 1'-0"

FEETSCALE

1/16" = 1'-0"

ROOF - OVERALL - POWER

ACH-3

ACH-1

ACH-2

(E) RTU-11

(E) RTU-13

(E) RTU-9

EF-01A

ABCDEFGHJ

A. ELECTRICAL DEVICE MOUNTING HEIGHTS ARE NOT INDICATED ON ELECTRICAL FLOOR PLANS.

CONTRACTOR SHALL COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH

ARCHITECTURAL INTERIOR ELEVATIONS. WHERE DEVICE MOUNTING HEIGHTS ARE NOT INDICATED PER ARCHITECT, MOUNT DEVICES AT HEIGHT INDICATED IN ELECTRICAL PROJECT SPECIFICATIONS.

B. REFER TO DETAILS, SCHEDULES, AND SYMBOL LEGENDS FOR ADDITIONAL REQUIREMENTS.

C. GFCI TYPE RECEPTACLES ARE NOTED AS SUCH ON THE PLANS FOR PRICING PURPOSES. HOWEVER, CONTRACTOR SHALL BE RESPONSIBLE TO ENSURE ALL RECEPTACLES INSTALLED WHERE A 6' CORD

LENGTH COULD REACH THE EDGE OF A SINK HAVE GFCI PROTECTION.

(POWER GENERAL NOTES SHALL APPLY TO ALL SHEETS)

POWER GENERAL NOTES:

TRACY J.

HAUSER

E-82068

STATE OF OHIO

P

RR

O

F

ESS IONA L ENG

IN

E

E

REG I TERED

S

8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

AREA - A

AREA - B

AREA - C

KEY PLAN :-

GUIDON DESIGN

1221 N Pennsylvania St, Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com GD Project : 24-1012-01

ARCHITECT, STRUCTURAL ENGINEER

03/26/2025

A u to d e s k D o c s /2

.0

V A

C o lu m b u s

O H

A

E R e p la c e

A ir -C o o le d C h ill e rs

/2

.0

V A

C o lu m b u s A

E R e p la c e

A C

C S

E S

.r v t

/2

/2

:3

:1

A

M

EP203A

ROOF - AREA-A - POWER Replace Air Cooled Chillers

Chalmers P. Wylie VA Ambulatory

Care Center

420 N. James Rd, Columbus, OH 43219

01A

03/26/2025 AEA MEA

23203.001

CONSTRUCTION

DOCUMENTS

757-23-101

1/8" = 1'-0"

ROOF - AREA-A - POWER

N

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

SHEET NOTES:

1. REFER TO SHEET E700 FOR ELECTRICAL REQUIREMENTS FOR EQUIPMENT. PROVIDE LIGHTNING CONTROL

TO NEW EQUIPMENT. CONNECT TO EXISTING SYSTEM AND MAINTAIN UL LISTING.

AS-4

CHWP-3

CHWP-4

CHWP-5

EFGHJ

GT-1

(E) RTU-6 (E) RTU-7

2 2

D3DEA SEC2

D3DEA SEC1

Mechanical Room

3B001

TRACY J.

HAUSER

E-82068

STATE OF OHIO

P

RR

O

F

ESS IONA L ENG

IN

E

E

REG I TERED

S

8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

AREA - A

AREA - B

AREA - C

KEY PLAN :-

GUIDON DESIGN

1221 N Pennsylvania St, Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com GD Project : 24-1012-01

ARCHITECT, STRUCTURAL ENGINEER

03/26/2025

A u to d e s k D o c s /2

.0

V A

C o lu m b u s

O H

A

E R e p la c e

A ir -C o o le d C h ill e rs

/2

.0

V A

C o lu m b u s A

E R e p la c e

A C

C S

E S

.r v t

/2

/2

:3

:1

A

M

EP203B

ROOF - AREA-B - POWER Replace Air Cooled Chillers

Chalmers P. Wylie VA Ambulatory

Care Center

420 N. James Rd, Columbus, OH 43219

01A

03/26/2025 AEA MEA

23203.001

CONSTRUCTION

DOCUMENTS

757-23-101

1/8" = 1'-0"

ROOF - AREA-B - POWER

N

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

SHEET NOTES:

1. REFER TO SHEET E700 FOR ELECTRICAL REQUIREMENTS FOR EQUIPMENT.

2. EXISTING EQUIPMENT. NO ELECTRICAL SCOPE.

3. NEW EQUIPMENT. NO ELECTRICAL SCOPE.

ABCD

(E) RTU-10

(E) RTU-8

TRACY J.

HAUSER

E-82068

STATE OF OHIO

P

RR

O

F

ESS IONA L ENG

IN

E

E

REG I TERED

S

8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

AREA - A

AREA - B

AREA - C

KEY PLAN :-

GUIDON DESIGN

1221 N Pennsylvania St, Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com GD Project : 24-1012-01

ARCHITECT, STRUCTURAL ENGINEER

03/26/2025

A u to d e s k D o c s /2

.0

V A

C o lu m b u s

O H

A

E R e p la c e

A ir -C o o le d C h ill e rs

/2

.0

V A

C o lu m b u s A

E R e p la c e

A C

C S

E S

.r v t

/2

/2

:3

:1

A

M

EP203C

ROOF - AREA-C - POWER Replace Air Cooled Chillers

Chalmers P. Wylie VA Ambulatory

Care Center

420 N. James Rd, Columbus, OH 43219

01A

03/26/2025 AEA MEA

23203.001

CONSTRUCTION

DOCUMENTS

757-23-101

1/8" = 1'-0"

ROOF - AREA-C - POWER

N

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

SHEET NOTES:

1. EXISTING EQUIPMENT. NO ELECTRICAL SCOPE.

600/3 600/3

1200/3

ACH-1

298 KVA

ACH-2

298 KVA

ATS-EQ

1200A, 480/277, 3PH, 4W

1200/3

4000/3

MV SYSTEM 1

1 1

SS#3

400A, 480/277, 3PH, 4W

85 KAIC

C1SBEA

1200A, 480/277, 3PH, 4W

50 KAIC

400/3600/3

SPACE

G1EA

480/277, 3PH, 4W

15/3

VFD FIRE

PUMP

15/3

JOCKEY

PUMP

100/3

P4 ELEV

100/3

J1E1

100/3

P5 ELEV

125/3

S2 D3DEA SEC1

480/277

3PH, 4W

80/3

VFD

CHWP-4

30 HP

80/3

VFD

CHWP-3

30 HP

15/3

SPARE

D3DEA SEC2

600A, 480/277, 3PH, 4W

65 KAIC

4 4

A. MECHANICAL EQUIPMENT NOT SHOWN ON ONE-LINE. REFER TO PANEL SCHEDULES FOR COMPLETE LIST

OF CIRCUIT BREAKER SIZES AND QUANTITIES REQUIRED.

B. PANEL LOAD CAPACITY TO BE CONFIRMED WITH METER DATA PRIOR TO BEGINNING OF CONSTRUCTION.

C. CONTRACTOR SHALL UTILIZE EXISTING FACILITY POWER STUDY. CONTRACTOR SHALL UPDATE EXISTING

STUDY WITH THE NEW EQUIPMENT

(GENERAL NOTES SHALL APPLY TO ALL ONE-LINE SHEETS)

ONE-LINE GENERAL NOTES:

MEC

ACH-1 ACH-2

MEC

PANEL C1SBEA

EXISTING METER LOAD: 721A

REMOVED CHILLER LOAD: 552A

REMOVED PUMP LOAD: 64A

ADDED NEW CHILLER LOAD: 659A

ADDED NEW PUMP LOAD: 102A

TOTAL: 866A

PANEL RATING: 1200A

350/3 350/3

1200/3

ATS-EQ

1200A, 480/277, 3PH, 4W

1200/3

4000/3

MV SYSTEM 1

2 2

SS#3

400A, 480/277, 3PH, 4W

85 KAIC

C1SBEA

1200A, 480/277, 3PH, 4W

50 KAIC

400/3600/3

G1EA

480/277, 3PH, 4W

15/3

VFD FIRE

PUMP

15/3

JOCKEY

PUMP

100/3

P4 ELEV

100/3

J1E1

100/3

P5 ELEV

125/3

S2 D3DEA SEC1

480/277

3PH, 4W

90/3

VFD

CHWP-4

25 HP

90/3

VFD

CHWP-3

25 HP

90/3

VFD

CHWP-5

25 HP

ACH-3

MEC

350/3

D3DEA SEC2

600A, 480/277, 3PH, 4W

65 KAIC

MEC MEC MEC

MEC MEC MEC

4 4

TRACY J.

HAUSER

E-82068

STATE OF OHIO

P

RR

O

F

ESS IONA L ENG

IN

E

E

REG I TERED

S

8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

GUIDON DESIGN

1221 N Pennsylvania St, Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com GD Project : 24-1012-01

ARCHITECT, STRUCTURAL ENGINEER

03/26/2025

A u to d e s k D o c s /2

.0

V A

C o lu m b u s

O H

A

E R e p la c e

A ir -C o o le d C h ill e rs

/2

.0

V A

C o lu m b u s A

E R e p la c e

A C

C S

E S

.r v t

/2

/2

:3

:0

A

M

E500

ONE-LINE DIAGRAM Replace Air Cooled Chillers

Chalmers P. Wylie VA Ambulatory

Care Center

420 N. James Rd, Columbus, OH 43219

01A

03/26/2025 AEA MEA

23203.001

CONSTRUCTION

DOCUMENTS

757-23-101

NO SCALEE500

ELECTRICAL DEMOLITION ONE-LINE1

FEEDER SCHEDULE - COPPER

FEEDER NOMINAL SIZE WIRE AND CONDUIT

MEC -- REFER TO EQUIPMENT CONNECTION SCHEDULE

NO SCALEE500

ELECTRICAL NEW WORK ONE-LINE2

1. EXISTING BREAKER TO BE REMOVED. REFER TO NEW WORK FOR NEW BREAKER SIZING.

2. PROVIDE NEW BREAKER IN PREPARED SPACE.

3. REPLACE EXISTING BREAKER WITH NEW.

4. CONTRACTOR TO TEST CONDUIT AND FEEDERS. PROVIDED CONDUIT AND FEEDERS ARE ACCEPTABLE THEY ARE TO BE

REUSED FOR NEW CHILLER FEEDS.

SHEET NOTES:

REMARKS: (EQUIPMENT CONNECTION SCHEDULE)

1. CIRCUIT SHOWN IS BASED ON PICTURE OF THE DISTRIBUTION BOARD. CONTRACTOR TO REVIEW ON SITE.

2. CIRCUIT SHOWN IN BASED ON EXISTING SHORT CIRCUIT STUDY INFORMATION. CONTRACTOR TO REVIEW ON SITE. PANEL IS LOCATED ON THE SECOND FLOOR. IT IS APPROXIMATELY 330' AWAY. CONTRACTOR TO

VERIFY EXACT DISTANCE.

GENERAL NOTES: (EQUIPMENT CONNECTION SCHEDULE)

A. EQUIPMENT LISTED MAY NOT BE UNIQUE, VERIFY QUANTITY WITH FLOOR PLANS. WHERE LOCATIONS ARE NOT INDICATED ON ELECTRICAL FLOOR PLANS, REFER TO MECHANICAL SHEETS. REFER TO DEFINITIONS

BELOW FOR CLARIFICATIONS OF CONNECTION REQUIREMENTS.

B. PROVIDE WIRING AND EQUIPMENT CONNECTIONS FOR INTERNAL EQUIPMENT COMPONENTS AS REQUIRED. COORDINATE REQUIREMENTS WITH MECHANICAL CONTRACTOR.

C. ITEMS NOTED AS "NA" ARE NOT APPLICABLE TO THE CONNECTION.

D. "CONTROL TYPE" - PROVIDE CONTROL AND CONNECTIONS:

• "INT" = CONTROLS ARE MANUFACTURED INTEGRAL TO THE EQUIPMENT (SELF-CONTAINED).

• "CONT" = EQUIPMENT OPERATES CONTINUOUSLY (NO CONTROLS). FOR MOTORS WITHOUT INTERNAL OVERLOAD PROTECTION, PROVIDE SEPARATE OVERLOAD PROTECTION. OVERLOAD PROTECTION MAY BE

PROVIDED AS PART OF A MANUAL MOTOR STARTER.

• "DDC" = CONTROL SIGNAL FROM TEMPERATURE CONTROL SYSTEM PROVIDED BY MECHANICAL CONTRACTOR OR TEMPERATURE CONTROLS CONTRACTOR.

• "TIME SW" = CONTROL SIGNAL FROM TIME SWITCH PROVIDED BY ELECTRICAL CONTRACTOR.

• TIME SWITCH SHALL BE 7-DAY DIGITAL TYPE WITH AUTOMATIC DAYLIGHT SAVINGS ADJUSTMENTS AND BATTERY BACKUP. LOCATE TIMESWITCH IN NEAREST MECHANICAL OR ELECTRICAL UTILITY ROOM.

LABEL TIME SWITCH. COORDINATE TIME SCHEDULE WITH OWNER AND MECHANICAL ENGINEER.

• "WALL SW" = CONTROL SIGNAL FROM WALL SWITCH PROVIDED BY ELECTRICAL CONTRACTOR.

• COORDINATE LOCATION OF WALL SWITCH WITH OWNER. LABEL WALL SWITCH.

• "FA STOP" = FANS WITH CFM OF 2000 OR GREATER AND FANS SERVING DUCTS CONTAINING SMOKE DAMPERS.

• PROVIDE FIRE ALARM SYSTEM DUCT SMOKE DETECTORS AT RETURN-SIDE AND SUPPLY-SIDE OF FAN/UNIT. PROVIDE MULTIPLE DETECTORS IF REQUIRED TO ACCOMMODATE MAIN DUCT TAKE-OFFS WHERE A

SINGLE DETECTOR CANNOT BE INSTALLED TO CAPTURE ALL AIRFLOW. FIRE ALARM SYSTEM SHALL SHUTDOWN FAN UPON DETECTION OF SMOKE IN DUCT OR ROOMS SERVED FROM THIS EQUIPMENT.

PROVIDE WITH INDIVIDUAL FIRE ALARM SYSTEM ADDRESSABLE CONTROL MODULE AT MOTOR CONTROLLER/STARTER AND CONNECT TO SHUTDOWN FAN.

• "WF STOP" = HIGH VOLUME LOW SPEED (HVLS) FANS SHUT DOWN HVLS FAN UPON WATERFLOW ALARM. PROVIDE WITH INDIVIDUAL FIRE ALARM SYSTEM ADDRESSABLE CONTROL MODULE AT MOTOR AND

CONNECT TO SHUT DOWN FAN.

• "FA START" = FANS USED FOR SMOKE EVACUATION OR PRESSURIZATION.

• FIRE ALARM SYSTEM SHALL START FAN UPON DETECTION OF SMOKE IN DUCT OR ROOMS SERVED FROM THIS EQUIPMENT. PROVIDE WITH INDIVIDUAL FIRE ALARM SYSTEM ADDRESSABLE CONTROL MODULE

AT MOTOR CONTROLLER/STARTER AND CONNECT TO START FAN.

• "DATA" = PROVIDE WITH DATA CONNECTION FROM NEAREST DATA NETWORK COMMUNICATIONS ROOM.

• "CONDUIT" = PROVIDE EMPTY 3/4" CONTROLS CONDUIT BETWEEN INDOOR AND OUTDOOR UNIT TO ACCOMMODATE CONTROL CABLING BY MECHANICAL OR TEMPERATURE CONTROLS CONTRACTOR.

• "EPO" = PROVIDE EMERGENCY POWER OFF. REFER TO FLOOR PLANS FOR DEVICE LOCATION.

E. "DISCONNECT BY" :

• "MECHANICAL" = DISCONNECT IS FURNISHED BY MECHANICAL CONTRACTOR OR PROVIDED WITH MECHANICAL EQUIPMENT.

• ELECTRICAL CONTRACTOR SHALL PROVIDE MOUNTING AND ADDITIONAL CONNECTIONS REQUIRED FOR LOOSE DISCONNECTS FURNISHED BY THE MECHANICAL CONTRACTOR.

• "ELECTRICAL" = DISCONNECT IS FURNISHED BY ELECTRICAL CONTRACTOR. COORDINATE EXACT REQUIREMENTS WITH EQUIPMENT FURNISHED BY MECHANICAL CONTRACTOR.

• "MANUFACTURER" = DISCONNECT IS FURNISHED BY EQUIPMENT MANUFACTURER. ELECTRICAL CONTRACTOR SHALL PROVIDE MOUNTING AND ADDITIONAL CONNECTIONS REQUIRED FOR LOOSE DISCONNECTS

FURNISHED BY EQUIPMENT MANUFACTURER.

F. "DISCONNECT TYPE" - PROVIDE DISCONNECT/RECEPTACLE AT EQUIPMENT LOCATION AND ASSOCIATED CONNECTION TO EQUIPMENT AND BRANCH CIRCUIT:

• "NEMA-___" = DUPLEX (TYP) RECEPTACLE TO ACCOMMODATE CORD AND PLUG CONNECTION (CORD AND PLUG FURNISHED WITH EQUIPMENT UNLESS NOTED OTHERWISE)

• "REC/SW" = PROVIDE 20A 120V RECEPTACLE OR 20A TOGGLE SWITCH DISCONNECT.

• COORDINATE REQUIRED SELECTION WITH EQUIPMENT.

• "NF" = NON-FUSED DISCONNECT. SIZE AND POLE QUANTITY AS INDICATED. 20/1 AND SMALLER SHALL BE TOGGLE SWITCH DISCONNECT.

• "F" = FUSED DISCONNECT. SIZE AND POLE QUANTITY AS INDICATED.

• FUSE PER MANUFACTURER'S RECOMMENDATIONS.

• "FUSTAT" = SWITCH AND FUSTAT. FUSE SIZE PER EQUIPMENT MANUFACTURER.

• LOCATE SWITCH IN CONCEALED ACCESSIBLE LOCATION.

• "ENCL CB" = ENCLOSED CIRCUIT BREAKER DISCONNECT.

• SIZE, POLE QUANTITY, AND FLUSH/SURFACE MOUNTING AS INDICATED.

• "ENCL MCSW" = ENCLOSED MOLDED CASE SWITCH DISCONNECT.

• SIZE, POLE QUANTITY, AND FLUSH/SURFACE MOUNTING AS INDICATED.

• "SHUNT ENCL CB" = SHUNT TRIP ENCLOSED CIRCUIT BREAKER DISCONNECT.

• SIZE, POLE QUANTITY, AND FLUSH/SURFACE MOUNTING AS INDICATED. PROVIDE WITH INTEGRAL 120V CONTROL TRANSFORMER SERVED FROM LINE SOURCE WITH PRIMARY AND SECONDARY FUSING.

COORDINATE ENCLOSURE AND COVER SIZE TO ACCOMMODATE TRANSFORMER. PROVIDE WITH EQUIPMENT GROUND BAR AND SEPARATE INSULATED ISOLATED GROUND BAR. WHERE NEUTRAL CONDUCTOR IS UTILIZED. PROVIDE SOLID NEUTRAL BAR. CONNECT SHUNT TRIP VOLTAGE SOURCE AND ACTUATOR TO ASSOCIATED EMERGENCY POWER (EPO) SWITCHES. PROVIDE EPO AND COORDINATE

LOCATION.

• "LOCK CB" = CIRCUIT BREAKER CAPABLE OF BEING LOCKED IN THE OPEN POSITION, LOCATED IN THE SOURCE ELECTRICAL PANEL. THE PROVISIONS FOR LOCKING MUST REMAIN IN PLACE WITH OR WITHOUT THE

LOCK INSTALLED.

• "MAG" = COMBINATION MAGNETIC MOTOR STARTER WITH DISCONNECT (COORDINATE COIL VOLTAGE WITH CONTROL SOURCE). LOCATE COMBINATION MAGNETIC MOTOR STARTER TO SERVE AS THE MOTOR DISCONNECT. WHERE STARTER SERVES OUTDOOR EQUIPMENT, LOCATE STARTER IN THE SOURCE ELECTRICAL ROOM.

• "MAN" = COMBINATION MANUAL MOTOR STARTER WITH DISCONNECT. LOCATE COMBINATION MANUAL MOTOR STARTER TO SERVE AS THE MOTOR DISCONNECT. WHERE STARTER SERVES OUTDOOR

EQUIPMENT, LOCATE STARTER IN THE SOURCE ELECTRICAL ROOM.

• "VFD" = VARIABLE FREQUENCY DRIVE CONTROLLER. LOCATE VARIABLE FREQUENCY DRIVE CONTROL TO SERVE AS THE MOTOR DISCONNECT.

• "INT" = DISCONNECT IS MANUFACTURED INTEGRAL TO THE EQUIPMENT.

• "HW" = HARDWIRE. DISCONNECT NOT REQUIRED.

• LOCATE DISCONNECT ADJACENT TO EQUIPMENT PER NEC - PROVIDE WITH STRUT MOUNTING AS REQUIRED.

• LOCATE RECEPTACLE OR JUNCTION BOX TO DIRECTLY SERVE EQUIPMENT.

• COORDINATE EXACT LOCATION WITH ARCHITECT, ARCHITECTURAL DETAILS, AND EQUIPMENT MANUFACTURER'S REQUIREMENTS.

• WHERE DISCONNECT SERVES OUTDOOR EQUIPMENT, PROVIDE AS NEMA-3R.

• PROVIDE DISCONNECT WITH EQUIPMENT GROUND KIT.

• WHERE FEEDER INDICATED UTILIZES A NEUTRAL, PROVIDE DISCONNECT WITH SOLID NEUTRAL KIT.

• WHERE FEEDER INDICATED UTILIZES AN ISOLATED GROUND, PROVIDE DISCONNECT WITH ADDITIONAL INSULATED GROUND KIT.

• DISCONNECTS NOT SHOWN AS "F" OR "NF" SHALL BE NON-FUSED.

• DISCONNECTS OF MOTORS SERVED FROM A VFD SHALL CONTAIN AUXILIARY CONTACTS CONNECTED TO THE VFD TO DISABLE VFD UPON DISCONNECTION.

• WHERE STARTERS OR VFD'S CONTAIN INTEGRAL DISCONNECTS AND ARE LOCATED PER NEC TO SATISFY AS THE EQUIPMENT DISCONNECT, AN ADDITIONAL EQUIPMENT DISCONNECT IS NOT REQUIRED.

G. "FEEDER":

• PROVIDE CONDUCTORS AND RACEWAY AS INDICATED. TYPICAL FORMAT IS: (FEEDER TAG) (NOMINAL SIZE) CONDUCTORS AND RACEWAY REQUIRED.

H. "GEN" - EQUIPMENT IS SERVED FROM A SOURCE PANEL PROVIDED WITH GENERATOR BACK-UP.

I. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF

THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR

TRACY J.

HAUSER

E-82068

STATE OF OHIO

P

RR

O

F

ESS IONA L ENG

IN

E

E

REG I TERED

S

8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

U.S. Department of Veterans Affairs

GUIDON DESIGN

1221 N Pennsylvania St, Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com GD Project : 24-1012-01

ARCHITECT, STRUCTURAL ENGINEER

03/26/2025

A u to d e s k D o c s /2

.0

V A

C o lu m b u s

O H

A

E R e p la c e

A ir -C o o le d C h ill e rs

/2

.0

V A

C o lu m b u s A

E R e p la c e

A C

C S

E S

.r v t

/2

/2

:3

:0

A

M

E700

ELECTRICAL SCHEDULES Replace Air Cooled Chillers

Chalmers P. Wylie VA Ambulatory

Care Center

420 N. James Rd, Columbus, OH 43219

01A

03/26/2025 AEA MEA

23203.001

CONSTRUCTION

DOCUMENTS

757-23-101

EQUIPMENT CONNECTION SCHEDULE

MARK DESCRIPTION ROOM NAME ROOM # HP KW FLA MCA MOCP VOLTS PHASE POLES

LOAD

[VA]

CONTROL

TYPE

DISCONNECT

BY

DISCONNECT

TYPE FEEDER PANEL

CIRCUIT

NUMBER SCCR GEN REMARKS

ACH-1 AIR COOLED CHILLER 0 0 0 274.4 350 480 3 3 228132 DDC MECHANICAL INTEGRAL (35) (350A) 3-500 KCMIL CU, #3 CU GND - 3"C. C1SBEA 7 0 No 1

ACH-2 AIR COOLED CHILLER 0 0 0 274.4 350 480 3 3 228132 DDC MECHANICAL INTEGRAL (35) (350A) 3-500 KCMIL CU, #3 CU GND - 3"C. C1SBEA 8 0 No 1

ACH-3 AIR COOLED CHILLER 0 0 0 274.4 350 480 3 3 228132 DDC MECHANICAL INTEGRAL (35) (350A) 3-500 KCMIL CU, #3 CU GND - 3"C. C1SBEA 21 0 No 1

CHWP-3 CHILLED WATER PUMP 25 0 34 43 90 480 3 3 28267 DDC MECHANICAL VFD (25M4) (25 HP 480V) 3-#6 CU, #8 CU GND - 1"C. D3DEA SEC2 14 0 No 1

CHWP-4 CHILLED WATER PUMP Mechanical Room 3B001 25 0 34 43 90 480 3 3 28267 DDC MECHANICAL VFD (25M4) (25 HP 480V) 3-#6 CU, #8 CU GND - 1"C. D3DEA SEC2 13 0 No 1

CHWP-5 CHILLED WATER PUMP Mechanical Room 3B001 25 0 34 43 90 480 3 3 28267 DDC MECHANICAL VFD (25M4) (25 HP 480V) 3-#6 CU, #8 CU GND - 1"C. D3DEA SEC2 9 0 No 1

EF-01A EXHAUST FAN 0.1 0 4.4 5.5 15 120 1 1 528 DDC MECHANICAL INTEGRAL (1M1) (1/6 - 1 HP 120V) 2-#12 CU, #12 CU GND - 3/4"C. C2EA 33 0 No 2

GT-1 GLYCOL FEEDER Mechanical Room 3B001 0.5 0 9.8 12.3 15 120 1 1 1176 DDC MECHANICAL INTEGRAL (1M1) (1/6 - 1 HP 120V) 2-#12 CU, #12 CU GND - 3/4"C. C2EA 29 0 No 2

COORDINATION OF WORK SCHEDULE

ITEM SUPPLIER INSTALLER POWER CONTROL (4)

MOTORS MC MC (3) EC CC

MOTOR CONTROL CENTER EC EC EC CC

EQUIPMENT MOUNTED ELECTRICAL COMPONENTS MC MC EC CC

LOOSE MOUNTED ELECTRICAL COMPONENTS EC EC EC CC

CONTROL RELAYS, TRANSFORMERS, POWER MC EC EC (4) CC

120V THERMOSTATS MC MC MC CC (1)

TEMPERATURE CONTROL SENSORS MC MC CC CC

TEMPERATURE CONTROL PANELS MC CC EC (4) CC

VARIABLE SPEED DRIVES MC MC EC CC

TERMINAL BOX CONTROLS MC MC EC (4) CC

PE/EP SWITCHES, SOLENOID VALVES, ACTUATORS CC CC EC (4) CC

PUSHBUTTON STATIONS EC EC EC (4) EC

ELECTRIC HEATERS MC MC EC EC

TIME CLOCKS EC EC EC EC

FAN COIL UNITS MC MC EC CC (1)

DX CONDENSING UNITS AND CONDENSERS MC MC EC CC (1)

WATER SOURCE HEAT PUMP UNITS MC MC EC EC

SMOKE DAMPERS MC MC EC EC

MEDICAL GAS ALARM WIRING MC MC EC MC (2)

E000 - ELECTRICAL SYMBOLS AND ABBREVIATIONS
ED100 - FIRST FLOOR -ENLARGED -POWER -DEMOLITION
ED103 - ROOF -OVERALL -ELECTRICAL -DEMOLITION
ED103A - ROOF -AREA-A -ELECTRICAL -DEMOLITION
ED103B - ROOF -AREA-B -ELECTRICAL -DEMOLITION
ED103C - ROOF -AREA-C -ELECTRICAL -DEMOLITION
EP200 - FIRST FLOOR -ENLARGED -POWER
EP203 - ROOF -OVERALL -POWER
EP203A - ROOF -AREA-A -POWER
EP203B - ROOF -AREA-B -POWER
EP203C - ROOF -AREA-C -POWER
E500 - ONE-LINE DIAGRAM
E700 - ELECTRICAL SCHEDULES

File details come from the government source that posted it. Updated .