This addendum modifies an existing solicitation for the renovation of operating rooms at the Louis Stokes VA Medical Center in Cleveland, Ohio. Mechanical revisions include extending an air handling unit relief duct fully to the relief air plenum, removing an existing control damper and connecting to the plenum in its place, and routing the duct a minimum of six and a half feet above an electrical substation. The bid opening date of September 9, 2020 at 12:00 PM Eastern Time remains unchanged.

View the file

Other files

File Type Posted
S06. 36C25020B0022 Amend 0004.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Addendum No. 04 August 17, 2020

ADDENDUM NUMBER DATE

Renovate Operating Rooms 541-21-1-2518-003

PROJECT NAME PROJECT NUMBER

Louis Stokes VAMC - 10701 East Blvd.

Cleveland, OH 44106 June 26, 2020

PROJECT LOCATION DOCUMENTS

This Addendum hereby modifies, supplements, and amends the Contract Documents, as prepared by Perspectus Architecture. Wherein this Addendum varies or is in conflict with the Contract Documents, the requirements of this Addendum shall govern. In all other particulars, the requirements of the original Specifications and Contract Documents, including any previous Addenda, shall govern.

THIS ADDENDUM IS COMPRISED OF THE FOLLOWING ITEMS:

DRAWINGS

Item 01 Revisions to ductwork as shown on attached MSK-1

ATTACHMENTS:

Letter from FF&H dated August 17, 2020 Sketch MSK-1 dated August 17, 2020

END OF ADDENDUM

August 17, 2020

Perspectus Architecture LLC 13212 Shaker Square, Suite 204 Cleveland, OH 44120

Attention: John Walkosak

Regarding: Renovate Operating Rooms Addendum No. 4

Dear Mr. Walkosak, Please incorporate the following items in the upcoming addendum for the above referenced project.

Mechanical Items

Refer to attached sketch MSK-1:

1. Extend AHU-S-2-2 relief air duct full size to relief air plenum.

2. Remove existing control damper and associated power at relief air plenum.

3. Connect to relief air plenum at location of removed damper. Cut and patch opening as required.

Provide transition piece at connection to plenum.

4. Relief air duct shall be routed a minimum of 6’-6” above electrical substation.

5. Relief air duct shall be constructed to SMACNA 4” W.G. class.

END OF ADDENDUM NO. 4

Please contact me with any questions.

Sincerely yours, Fredrick, Fredrick & Heller Engineers, Inc

Leonard Hendrix, PE

Attachments:

MECHANICAL DRAWINGS:

MSK-1

H

X-SUBSTATION

DD

a::

<D C") X a::

<D

-T"""'T--, CONNECT TO EXISTING

RELIEF AIR DUCT.

ROUTE OVER SUBSTATION.

MAINTAIN MINIMUM 6'-6"

ABOVE TOP OF

SUBSTATION

i-----�

I I I ln ln l

REMOVE EXISTING DAMPER. '------•- Jw_Lu_l_

CONNECT RELIEF AIR DUCT - - -:; =1-.L.------'---------'

PLENUM AT LOCATION OF

,,... ,,...OPENING. CUT AND PATCH

PLENUM AS REQUIRED.

H

FREDRICK, FREDRICK Ile HEIJ..ER

ENGINEERS, INC.

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEl..(4-40)548-IMIIMI

FAX: (4-40) 548-9899

X-HVAC

PLENUM

SURGERY PENTHOUSE AHU-S-2-2

RELIEF AIR DUCTWORK PLAN

RENOVATE OPERATING ROOMS

PROJECT NAME

H

ADDENDUM 4 -

REVISIONS REFERENCE

18067 1/8"=1'-0"

PROJECT NO. SCALE

JXC 08/17/20

DRAWN BY DATE

MSK-1

SHEET NO.