This document is an Addendum No. 1 to the Construction Documents for the VA Medical Center Cleveland project to improve the entrance to the patient parking garage (Project No. 541-23-208). The addendum, dated June 27, 2025, outlines specific revisions to architectural, mechanical, and electrical drawings. Key changes include: revising the ramp into the existing elevator lobby (A102), modifying the HVAC floor plan by changing the AC-1 unit size and associated ductwork due to refrigerant changes (M102), updating the Split System Heat Pump Units schedule (M601), and revising the electrical schedules to adjust the breaker and wire size for CU-1 (E601). These modifications appear to be technical adjustments to accommodate specific equipment and design requirements for the parking garage entrance improvement project.

View the file

Other files

File Type Posted
S02. 36C25025B0024 0003.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

IMPROVE ENTRANCE TO PATIENT PARKING GARAGE

RDC/JPA Architecture Page 1 of 1

VAMC CLEVELAND, OH

PROJECT NO. 541-23-208

ADDENDUM NO. 1

to the

CONSTRUCTION DOCUMENTS

June 27, 2025

General The following changes, additions or deletions shall be made to the following Contract Documents. All other conditions shall remain the same.

I. DRAWINGS

ARCHITECTURE

A. A102 – Revised ramp into Existing Elevator Lobby.

MECHANICAL

A. Drawing No. M102 – HVAC FLOOR PLAN – NEW WORK

• Revised AC-1 size due to refrigerant change and decreased capacity of unit.

• Modified ductwork associated with AC-1.

B. Drawings No. M601 – SCHEDULE

• Revised Split System Heat Pump Units schedule.

ELECTRICAL

A. Drawing No. E601 - ELECTRICAL SCHEDULES & DETAILS

• Revised breaker for CU-1 due to change in unit.

• Revised wire size for CU-1 due to breaker change.

END OF ADDENDUM

DN

18 19 20 23

J

Elevator Equipment

Stair 'D'

B

A301

A301

A301

S3.0

S3.0

S1.0

S2.0

S1.0

S4.0

S4.0

S4.0

Vestibule

Wheelchairs

Storage

Storage

2' - 7 1/2"

2.02

2.02

2.02

S5.0

S1.0

A

14' - 9 1/2" 6' - 2 1/2" 7' - 8 3/4" 22' - 6 1/4"

2"

78°

102°

7' - 0 3/4" 4 7/8"

5' - 6" 4 7/8"

208A

6A4

3/ A2

2/A201

1/A201

4/A201

Lobby

E1.0

E1.0

E1.1

E1.1

E1.0

E1.1

1/ 4"

3/

4"

676'-0"

676'-3"

676'-6"

11' - 2"

24' - 3 1/2"

7' - 0"

14' - 6 1/4"

6'-0"

14'-6"

6'-0"

102°

Bid Item 02

10.40

8'-0"

E1.0

2.04

32.01

11.31

32.01

5.22

5.22

7' - 0"

7' - 0"

7' - 0"

7' - 0"

7' - 0"

7' - 0"

7' - 0"

7' - 0"

7' - 0"

1' - 0"

S3.0S3.0

S3.0

S3.0

7.88

S3.0

S3.0

S3.0

S2.0

A102

A102

S3.0 A102

Sim

6'

- 7

8'

- 1

11' - 9 3/8" 9' - 2 5/8"

A401

11A4

A401

ALIG

N

56' - 11 3/4"

6' - 0 5/8"

8' - 11"

7/

8" 5'

- 7

/8

8'

- 4

/2

7.8613

A401

12 A4

A401

A401

A401 8

A401

A401

A401

AF101-F

Elevator Lobby

A103

3.11 3.11

3.11

7.25

5.22

10.41

2.06

7'

- 0

"ALIGN S1.0

E1.0

S2.0

S2.0

S4.1 S4.0

S4.1

S4.1

31' - 6 3/4" 20' - 10"

6'

- 2

/8

6'

- 7

/4

9'

- 4

/4

5/A201

Corridor 204A

S2.0

8' - 0"

8.17

3.04

3.04

1:20

1:20

676'-6"

E1.0

7.14

9.21

5.06

7.16

7.17

7.41

6.19

EXTERIOR

NON-RATED

FREE-STANDING

STRUCTURE ABOVE

FIN. CEILING

FLOOR SLAB

S1.0 INTERIOR

NON-RATED

FREE-STANDING

4 7/8"

9.219.21

9.02

7.13

7.82

1"

9.04

S2.0

9.21

9.02

7.13

7.82

7.16

4 1/4"

9.04

INTERIOR

NON-RATED

FREE-STANDING

1"

S4.0

9.21

7.12

7.16

2 5/8"

9.15

9.07

INTERIOR

NON-RATED

FURRING

S3.0

1 1/2"

9.05

9.21

6"

INTERIOR

NON-RATED

FURRING

2.06

7.19 7.43

7.86

E1.0 2" 2.06

S2.0

S1.0

7.19

2"

8.23

7.86

S4.1

9.21

8.23

2 5/8"

9.15

INTERIOR

NON-RATED

FURRING

S4.0 Below

S5.0

4 7/8"

9.219.21

9.02

7.82

4'

- 0

A.

F.

F.

9.42

6.03

INTERIOR

NON-RATED

FREE-STANDING

E1.1

7.14

5.06

7.16

7.17

7.41

6.19

EXTERIOR

NON-RATED

FREE-STANDING

BID ITEM DESCRIPTIONS

1.

1.

BID ITEM 2:

All work included in BID ITEM 1, BASE BID, except: Delete alteration work in Existing Elevator Lobby 202. Lobby to remain in current state at time of bidding.

BID ITEM 3:

All work included in BID ITEM 2, except: Delete all wall protection (WP), crash rail (CR-1), and corner guards (CG-1).

Replace with paint P-1.

J

7' - 3" 2' - 0" 3' - 0" 1' - 2 5/8"

676'-3"

3.01

8.17

7.86

1:20

1:20 676'-6"8

/8

51°

2°

5.21

3.04

3.04

5' - 0"

5.22

JASON

H.

ROSS

2118221

IO

HOFOETATS

R E G I S

ET R ED RA CH

TI

E C T

VA Project No.

RDC/JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

7/ 1/

:1

0:

A M

IMPROVE ENTRANCE FROM

PATIENT PARKING GARAGE

02/14/2025

ENLARGED PLAN - SECOND FLOOR

A102

NSJR

541-23-208

Cleveland, Ohio VAMC

PPG

FINAL CONSTRUCTION

DOCUMENTS

22026.00

A. All dimensions are taken to face of gypsum wallboard or unit masonry.

B. Edge of all door jambs at hinge side not otherwise indicated are to be 6" from the face of intersecting walls. Edge of all door jambs at strike side not otherwise located are to be 18" minimum from the face of intersecting walls.

C. All wood blocking to be fire retardent treated.

D. All partitions shall be type 'S1.0' unless noted otherwise.

E. Coordinate location of all new core drilling with existing post tension reinforcing using ground penetrating radar prior to setting location of walls . Notify VA and architect of any discrepancies caused by existing conditions.

2.02 Existing structure to remain.

2.04 Existing piping to remain. Protect in place during construction.

Coordinate new construction with existing Unistrut supports.

2.06 Existing storefront system to remain. Clean oxidation from storefront.

3.01 3" bonded concrete slab. See Structural Drawings.

3.04 Concrete ramp. See plan for slopes.

3.11 Broom finish and sealant. Basis of Design: H&C Clarishield

Natural Look Sealer.

5.06 3-5/8" cold formed metal framing @ 16" O.C. See Structural

Drawings.

5.21 1-1/2" ID wall-mounted painted steel handrail. Dark grey color to match existing railings.

5.22 1-1/2" ID post-mounted painted steel handrail. Dark grey color to match existing railings.

6.03 2x wood blocking.

6.19 5/8" exterior glass mat gypsum board sheathing. Seal all joints.

7.12 Rigid thermal wall insulation, R-12 min.

7.13 Batt thermal wall insulation. R-11 min.

7.14 Batt thermal wall insulation. R-19 min.

7.16 Vapor barrier. Seal all joints and penetratons.

7.17 Air and moisture barrier. Lap air and moisture barrier over thru-wall flashing.

7.19 2" multi-faced, silicone-coated, precompressed expansion joint.

7.25 Replace downspout with PVC pipe and route to new secondary roof drain wall outlet.

7.41 2" thick, horizontal, insulated, flat, non-embossed, metal wall panel. Basis of Design: Kingspan Optimo. Color: Light Grey.

7.43 Metal panel closure trim by panel manufacturer. Color to match panel color.

7.82 Continuous acoustic sealant @ non-rated walls / fire-rated sealant @ rated walls each side.

7.86 Fire rated expansion joint cover assembly.

7.88 2" insulated building expansion joint

8.17 Push button door actuator.

8.23 Cover this row of glazing with opaque film. Color: Black.

9.02 3 5/8" non-structural metal framing @ 16" o.c.

9.04 Slip type deflection track. Install per manufacturer's

recommendations.

9.05 7/8" Z furring channel @ 16" o.c.

9.07 Align with top of existing concrete half wall.

9.15 2" metal 'Z' girt running horizontally @ 24" o.c.

9.21 5/8" Type X gypsum board.

9.42 Provide solid surface cap for half height wall.

10.40 Surface-mounted fire extinguisher cabinet.

10.41 Semi-recessed fire extinguisher cabinet.

11.31 Owner provided and installed bench.

32.01 Energy absorbing traffic bollard.

PLAN NOTES

GENERAL NOTES

N Scale: 1/4" = 1'-0"

ENLARGED SECOND FLOOR PLAN

Room Schedule RM # Name Area

202 Elevator Lobby 424 SF 204 Lobby 618 SF 204A Corridor 45 SF 205 Storage 48 SF 206 Storage 58 SF 207 Wheelchairs 72 SF 208 Vestibule 164 SF Grand total 1,429 SFScale: 1" = 1'-0"

Wall Types

Scale: 1 1/2" = 1'-0"2 PLAN DETAIL Scale: 1 1/2" = 1'-0"1 PLAN DETAIL

Revisions Date 1 Addendum 01 06/27/2025

N Scale: 1/2" = 1'-0"10 ENLARGED RAMP PLAN

T

19 20 23

J

K

L

M

N

Vestibule

Storage

Storage

Wheelchairs

10ø A20

350 CFM

x1

22x10

12x8

3150 CFM

8 2

AC-1

8ø x1

10ø R1

350 CFM

RS/RL UP

RS

RL

D

Lobby

Elevator Lobby

Elevator Equipment

Stair 'D'

D-2

RP-1

RP-1

RP-1

12x8

18x1010x12

REFER TO SHEET M103

FOR CONTINUATION

8x12

10ø A10

145 CFM

10ø A10

145 CFM

10ø A10

145 CFM

10ø A10

145 CFM

10ø A10

145 CFM

10ø A10

135 CFM

10ø A10

135 CFM

12x12 L2

10x8

10x8

10x8

10x8

AD-1

10ø R1

350 CFM

54x14

10ø R1

350 CFM

8x

10ø A20

365 CFM

6ø A30

100 CFM

6ø A30

100 CFM

P: 937-224-0861 www.heapy.com

VA Project No.

RDC/JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities ManagementPROJECT NO.

STATE COA FIRM NO.

/2

/2

:4

:1

P

M

IMPROVE ENTRANCE FROM

PATIENT PARKING GARAGE

02/14/2025

HVAC FLOOR PLAN - NEW WORK

M102

SMPBRB

541-23-208

Cleveland, Ohio VAMC

PPG

FINAL CONSTRUCTION

DOCUMENTS

22026.00

2022-05314

01528

PLAN NOTES

1. CORE DRILL THRU FLOOR. PROVIDE FIRESTOPPING WITH WATER RING AT PENETRATION.

2. SLOPE BOTTOM OF DUCTWORK TOWARDS EXTERIOR LOUVER.

3. BALANCE OUTSIDE AIR DAMPER TO 150 CFM.

4. ROUTE PUMPED CONDENSATE DRAIN PIPING TO FLOOR OF SECOND FLOOR PARKING

GARGAGE. DISCHARGE THRU WALL 12 "AAF. PROVIDE 1/2" ELASTOMERIC FOAM INSULATION.

5. REFRIGERANT PIPING UP TO CONDENSING UNIT ON ROOF.

6. PROVIDE INSULATION ON RETURN DUCTWORK.

7. CONNECT TO EXISTING DUCT AS SHOWN. PROVIDE ANY ACCESSORIES OR FITTINGS TO

MAKE CONNECTION.

8. PROVIDE MIN 24" DEEP 12"x12" DUCT PLENUM CONNECTED TO INTAKE LOUVER.

9. ALL WORK INCLUDED IN BID ITEM 1, BASE BID, EXCEPT: DELETE ALTERATION WORK IN

EXISTING ELEVATOR LOBBY 202. LOBBY TO REMAIN IN CURRENT STATE AT TIME OF BIDDING.

10. EXISTING TO REMAIN.

11. PROVIDE FIRE STOPPING AT PIPE PENETRATION THRU WALL.

N Scale: 1/4" = 1'-0"

SECOND FLOOR NEW WORK PLAN

Revisions Date

BID DOCUMENTS 02/14/2025

1 ADDENDUM 1 06/27/25

DUCT CONSTRUCTION, SEALING, AND INSULATION

GENERAL NOTES:

A. REFER TO SPECIFICATIONS FOR DUCT CONSTRUCTION:

SHEET METAL DUCT; INTERIOR LINING; EXTERIOR

INSULATION; FIBERGLASS DUCTBOARD; ETC.

B. DUCT CONSTRUCTION AND SEALING SHALL BE PER

LATEST S.M.A.C.N.A. STANDARDS.

NOTES:

1. WATERTIGHT SEAL.

2. INSULATE FROM 24" UPSTREAM OF BACKDRAFT / ISOLATION DAMPER TO PENETRATION OF WALL .

3. CONCEALED ROUND RUNOUT DUCTS TO AIR DEVICES MAY BE 1" S.P. CLASS.

DUCT SYSTEM

S.P. CON-

STRUCT.

SEAL

CLASS

LEAKAGE

CLASS

S.M.A.C.N.A. CLASS.

INTERNALLY

LINED

EXTERNAL

INSULATION

NOT

INSULATED

SEE

NOTE

DOUBLE

WALL

INSULATEDRECT RND

NOTE 2

16 8

A

A

A

SUPPLY DUCTWORK

+2"

GENERAL EXHAUST DUCTWORK

EF-1

-1"

OUTSIDE AND MIXED AIR DUCTWORK

AND PLENUMS

-1"

3--16 8ARETURN DUCTWORK -2" - ●

P: 937-224-0861 www.heapy.com

VA Project No.

RDC/JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities ManagementPROJECT NO.

STATE COA FIRM NO.

/2

/2

:4

:1

P

M

IMPROVE ENTRANCE FROM

PATIENT PARKING GARAGE

02/14/2025

SCHEDULES

M601

SMPBRB

541-23-208

Cleveland, Ohio VAMC

PPG

FINAL CONSTRUCTION

DOCUMENTS

22026.00

2022-05314

01528

NOTES:

1. PATTERN CONTROLLER ICE TONGS.

2. PROVIDE SHOULDER PLENUM.

GENERAL NOTES:

A. ALL LAY-IN AIR DEVICES SHALL FIT IN 24"X24" LAY-IN CLG SYSTEM.

VERIFY GRID TYPE AND COORDINATE AIR DEVICE COMPATIBILITY.

B. FINISH KEY: "W.B.E." - WHITE BAKED ENAMEL;

"E.C.L." - ETCHED CLEAR LACQUER OR ANODIZED;

"C.C.B.A." - CUSTOM COLOR SELECTED BY ARCHITECT.

C. SUPPLY AIR DIFFUSERS SHALL BE 4-WAY BLOW, UNLESS

INDICATED OTHERWISE ON DRAWINGS.

D. PROVIDE AUX. FRAMES FOR AIR DEVICES IN PLASTER,

GYPSUM BOARD, TILE OR OTHER HARD SURFACES.

AIR DISTRIBUTION DEVICES

M A

R K

DESCRIPTION

MOUNTING TYPE MATERIAL FINISH

O P

P O

S E

D B

L A

D E

D A

M P

E R

S Q

-T O

-R D

N E

C K

A D

A P

T O

R

BASIS OF DESIGN

S E

E N

O T

E

L A

Y -I

N

S U

R F

A C

E

D U

C T

S P

L

IN

E

S N

A P

-I N

S T

E E

L

A L U

M

IN

U M

S T

A

IN

L E

S S

S T

E E

L

W .B

.E

E .C

.L

C .C

.B .A

MANUFACTURER MODEL

A10 48" - 2 SLOT 1" WIDTH SLOT

DIFFUSER

● PRICE SDS 1,2

A20 24x24 STANDARD SQ. PLAQUE

CEILING DIFFUSE

● ● ● PRICE SPD

A30 12x12 STANDARD SQ. PLAQUE

CEILING DIFFUSER

● ● ● ● PRICE SPD

L2 INTAKE LOUVER ● ● ● ● GREENHECK ESD-403

R1 48" - 4 SLOT 1" WIDTH SLOT

DIFFUSER

PRICE SDR 2

INDOOR UNIT

M A

R K

DESCRIPTION

TYPE LOCATION FAN COIL CAPACITY FILTERS

ELECTRIC

HEAT /

REHEAT ELECTRICAL SERVICE APPROX. DIMENSIONS

C O

O L

IN

G C

O

IL

C O

N D

E N

S A

T E

D R

A

IN

P U

M P

N

O T

E I

V

IB

R A

T

IO

N I S

O L A

T O

R T

Y P

E

SEISMIC

RESTRAINTS BASIS OF DESIGN

W A

L L -M

O U

N T

E D

C E

IL

IN

G -M

O U

N T

E D

C E

IL

IN

G R

E C

E S

S E

D

D U

C T

E D

ROOM NAME R

O

O M

N U

M B

E R

C F

M

E X

T E

R N

A L

S T

A T

IC

P

R E

S S

U R

E

IN

W

.C

M O

T O

R k W

E L

E C

T R

O N

IC

A

L L

Y C

O M

M U

T A

T E

D M

O T

O R

COOLING HEATING

M E

R V

R A

T

IN

G

M A

X

IM

U M

F A

C E

V E

L O

C

IT

Y

F P

M

M

IN

IM

U

M N

O S

T A

G E

S

N O

T I N

C L

U D

IN

G

O

F F

S C

R C

O N

T R

O L

S E

R V

E D

T H

R U

O U

T D

O O

R U

N

IT

N

O T

E

V O

L T

A G

E

P H

A S

E

F U

L L

L O

A D

A M

P S

F

L A

M

IN

C

IR

C U

IT

A

M P

S

M C

A

M A

X O

V E

R C

U R

R E

N T

P R

O T

E C

T

IO

N

M O

C P

M

IN

IM

U

M S

C C

R

A M

P S

L E

N G

T H

W

ID

T H

H E

IG

H

T

R E

Q U

IR

E

D

I M

P O

R T

A N

C E

F A

C T

O R

MANUFACTURER MODEL E

N

T A

IR

T

E M

P D

B /W

B

T O

T A

L S

E N

S

IB

L E

C A

P A

C

IT

Y

M B

H

E N

T E

R

IN

G A

IR

T

E M

P D

B

C A

P A

C

IT

Y

M B

H

AC-1 HORIZONTAL DUCTED UNIT - - - ● LOBBY 205 1201 0.4 .3 - 80/67 35.6/23.6 70/60 36.8 - - 208-1 3.5 15 5kA 55" 28" 10" ● - - TRANE PEAD-AA36NL

OUTDOOR HEAT PUMP CONDENSING UNIT - AIR COOLED

REFRIGERANT

CONN. SIZE

H O

T G

A S

B Y

P A

S S

S E

E N

O T

E

M A

R K

DESCRIPTION N

O

M

IN

A L

T O

N S

S

IZ

E

D T

O M

A T

C H

C O

IL

V A

R

IA

B L

E S

P E

E D

C O

M P

R E

S S

O R

(S

ELECTRICAL SERVICE

V

IB

R A

T

IO

N I S

O L A

T O

R T

Y P

E

BASIS OF DESIGN

L

IQ

U

ID

L

IN

E

S U

C T

IO

N

L

IN

E

V O

L T

A G

E

P H

A S

E

F U

L L

L O

A D

A M

P S

F

L A

M

IN

C

IR

C U

IT

A

M P

S

M C

A

M A

X O

V E

R C

U R

R E

N T

P R

O T

E C

T

IO

N

M O

C

IM

U

M S

C C

R

A M

P S

MANUFACTURER MODEL

CU-1 CONDENSING UNIT 3 - 208-1 29 48 5K TRANE PUZ-AK36NLHZ - 1,2,3,4

NOTES:

1. POWER FOR INDOOR UNIT IS TO BE FED THRU THE OUTDOOR UNIT POWER SUPPLY.

GENERAL NOTES:

A. UNLESS NOTED OTHERWISE, CAPACITIES SHALL BE BASED ON INTERIOR DESIGN

CONDITIONS OF 75 DB / 63 WB COOLING; 72 DB HEATING.

B. HEAT PUMP COOLING CAPACITY SHALL BE BASED ON 95°F AMBIENT CONDITIONS.

C. HEAT PUMP HEATING CAPACITY SHALL BE BASED ON 0°F AMBIENT CONDITIONS.

D. CONDENSING UNITS SHALL INCLUDE LOW AMBIENT COOLING & HEATING

CONTROLS AND ACCESSORIES, OPERATIONAL TO 0°F.

SPLIT SYSTEM HEAT PUMP UNITS

E. WHEN APPLICABLE, REFER TO SPECIFICATIONS FOR VIBRATION ISOLATOR TYPES

AND SEISMIC RESTRAINT REQUIREMENTS.

F. REFRIGERANT PIPING - SIZES LISTED ARE APPROX. CIRCUITING, SIZING, NUMBER

OF PIPES AND CIRCUITS, ARRANGEMENT, ETC. SHALL BE IN ACCORDANCE WITH

MANUFACTURER'S RECOMMENDATIONS.

G. ELECTRIC SERVICES FOR OUTDOOR UNIT AND INDOOR UNIT - SINGLE POINT

POWER SERVICE CONNECTIONS TO EACH UNIT. UNLESS NOTED OTHERWISE,

ADEQUACY OF LISTED CIRCUIT SIZES MUST BE VERIFIED BY H.C. AND UNIT

SUPPLIER. COST FOR INCREASE OR CHANGE OF ELECTRIC SERVICE FOR

EQUIPMENT SELECTED SHALL BE BORNE BY H.C.

H. IF EC MOTORS ARE INDICATED OR SPECIFIED, EACH MOTOR SHALL BE

PROVIDED WITH FACTORY DISCONNECTING MEANS, INTERNAL OVERLOAD

PROTECTION, FIELD ADJUSTABLE SPEED CONTROL, AND REMOTE ANALOG

SPEED CONTROL INPUT WHEN REMOTE CONTROL IS SPECIFIED, COORDINATED

WITH THE BUILDING AUTOMATION SYSTEM.

I. COOLING COIL CONDENSATE PUMPS SHALL BE FACTORY-FURNISHED,

COMPATIBLE WITH INDOOR FAN COIL UNIT VOLTAGE AND POWERED FROM

THE INDOOR FAN COIL UNIT SINGLE POINT POWER CONNECTION.

NOTES:

1.

GENERAL NOTES:

A.

RADIANT ELECTRIC HEATING SYSTEMS

M A

R K

DESCRIPTION

TYPE CAPACITY PANELS MISC.

SEISMIC

RESTRAINTS BASIS OF DESIGN

S E

E N

O T

E

I N

-F L

O O

R

C E

IL

IN

G P

A N

E L

W A

L L

P A

N E

L

ELECTRIC

S M

O O

T H

F A

C E

D

P E

R F

O R

A T

E D

N O

N -P

E R

F O

R A

T E

D

F L

U T

E D

COLOR DIMENSIONS

M A

N

IF

O L

D

S U

P P

L Y

M A

N

IF

O L D

R

E T

U R

N

I N

S U

L A

T

IO

N P

A D

S

I N

-F L

O O

R T

U B

IN

G

L

IN

E V

O L

T A

G E

T H

E R

M O

S T

A T

R E

Q U

IR

E

D

I M

P O

R T

A N

C E

F A

C T

O R

MANUFACTURER MODEL W

A

T T

S P

A N

E L

V O

L T

A G

E

P H

A S

E

O F

F -W

H

IT

E

C O

L O

R B

Y A

R C

H

IT

E C

T

C U

S T

O M

L E

N G

T H

IN

C H

E S

W

ID

T H

IN

C H

E S

T H

IC

K

N E

S S

IN

C H

E S

RP-1 RADIANT CEILING PANEL - ● - 750 208-1 - - - - - ● - 24" 48" 6" - - ● - - - - MARLEY ATH24488A

2. MANUFACTURER SHALL SIZE LIQUID AND SUCTION REFRIGERANT LINES. 3. PROVIDE MANUFACTURER PACKAGED CONTROLS.

NOTES:

1.

GENERAL NOTES:

A. SINGLE POINT POWER CONNECTION. COORDINATE POWER REQUIREMENTS AND

ELECTRICAL CONNECTIONS.

B. IF EC MOTORS ARE INDICATED OR SPECIFIED, EACH MOTOR SHALL BE PROVIDED WITH

FACTORY DISCONNECTING MEANS, INTERNAL OVERLOAD PROTECTION, FIELD ADJUSTABLE

SPEED CONTROL, AND REMOTE ANALOG SPEED CONTROL INPUT WHEN REMOTE CONTROL IS

SPECIFIED, COORDINATED WITH THE BUILDING AUTOMATION SYSTEM.

AIR CURTAIN UNITS

M A

R K

DESCRIPTION

LOCATION

TY

PE CAPACITY NOZZLE SUPPLY FAN(S) DIMENSIONS ELECTRICAL SERVICE MISCELLANEOUS BASIS OF DESIGN

S E

E N

O T

E

ROOM NAME R

O

O M

N U

M B

E R

E L

E C

T R

IC

C F

M

M B

H

ELEC.

C E

IL

IN

G R

E C

E S

S E

D

E X

P O

S E

D

M

IN

IM

U

M V

E L O

C

IT

Y

F P

M

M A

X

IM

U M

V E

L O

C

IT

Y

F P

M

T O

T A

L C

F M

M O

T O

R Q

U A

N T

IT

Y

M O

T O

R

H P

E

A C

H

E L

E C

T R

O N

IC

A

L L Y

C O

M M

U T

A T

E D

M O

T O

R S

U N

IT

L

E N

G T

H

U N

IT

H

E

IG

H T

U N

IT

D

E P

T H

A P

P R

O X

IM

A

T E

W E

IG

H

T

L B

S

V O

L T

A G

E

P H

A S

E

F U

L L

L O

A D

A M

P S

F

L A

M

IN

C

IR

C U

IT

A

M P

S

M C

A

M A

X O

V E

R C

U R

R E

N T

P R

O T

E C

T

IO

N

M O

C

IM

U

M S

C C

R

A M

P S

M A

X S

O U

N D

L E

V E

L d B

CONTROLS

S T

A R

T E

R C

O N

T R

O L

P A

N E

L

MANUFACTURER MODEL K

W

D O

O R

S W

IT

C

H

R E

M O

T E

S

IG

N A

L

AD-1 RECESSED AIR

CURTAIN

VESTIBULE 208 ● 1713 47.8 6 ● - 1468 7300 1713 1 0.5 - 48" 15" 26" 118 208-1 33.1 45 ● - - BERNER ARD12-1048E

Revisions Date

BID DOCUMENTS 02/14/2025

1 ADDENDUM 1 06/27/25

4. REFRIGERANT TO BE R454B OR APPROVED EQUAL. 1

EXISTING

1HC

1-LE2

45A, 3P

3 - #6, 1- #10 GROUND, IN 1" C

4 - #3, 1- #8 GROUND, IN 1.5" C

T1 K=13

30 KVA

208/120V

1-#8 GROUND, IN 1.25" C

P: 937-224-0861 www.heapy.com

VA Project No.

RDC/JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities ManagementPROJECT NO.

STATE COA FIRM NO.

/2

/2

:4

:4

P

M

IMPROVE ENTRANCE FROM

PATIENT PARKING GARAGE

02/14/2025

ELECTRICAL SCHEDULES &

DETAILS

E601

DMBDED

541-23-208

Cleveland, Ohio VAMC

PPG

FINAL CONSTRUCTION

DOCUMENTS

22026.00

2022-05314

01528

SCALE: NONE

PARTIAL SINGLE-LINE

57.79 kVA 59.9 kVA (72 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: 1. THIS PANEL IS FED FROM THE NORMAL BRANCH.

2. [N] REPRESENTS PROVIDE NEW BREAKER TO MATCH EXISTING IN PANEL.

Total Est. Demand: 72 A

Spare 40161 VA 100.00% 40161 VA Total Conn.: 70 A

Receptacle 3150 VA 100.00% 3150 VA Total Est. Demand: 59.9 kVA

Motor 12896 VA 113.31% 14612 VA Total Conn. Load: 57.79 kVA

Lighting 1580 VA 125.00% 1975 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 21.52 kVA 19.11 kVA 17.16 kVA

17 -- -- -- 4557... 3324... 1 20 A EXISTING 18

15 -- -- -- 4321... 3324... 1 20 A EXISTING 16

13 [N] T1 45 A 3 7168... 2880... -- -- -- 14

11 [N] LGT Vestibule 208 20 A 1 1580... 2880... 2 20 A EXISTING 12

9 EXISTING 20 A 1 3324... -- 1 -- Space 10

7 Spare 20 A 1 0 VA 4819... -- -- -- 8

5 Spare 20 A 1 0 VA 4819... -- -- -- 6

3 EXISTING 20 A 1 3324... 4819... 3 35 A EXISTING 4

1 EXISTING 20 A 1 3324... 3324... 1 20 A EXISTING 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 480/277 Wye-3PH-4W Mains Rating: 100 A

Supply From: Enclosure: Type 1 Mains Type: MLO

Location: Elevator Equipment 203 Mounting: Surface A.I.C. Rating: EXISTING

Panel: 1HC(EXISTING TO REMAIN)

NOTES:

1. INDOOR UNIT IS FED FROM THE OUTDOOR UNIT. PROVIDE

INTERCONNECTING WIRE AS REQUIRED.

2. 1 POLE 20A HORSE POWER RATED SWITCH TO SERVE AS

DISCONNECT MEANS.

MOTORS, STARTERS, DISCONNECTS & CONTROLS

MARK

MOTOR STARTER DISCONNECT MEANS CONTROL FEEDER

S E

E N

O T

E

NAMEPLATE

CHARACTERISTICS LOCATION

N E

M A

S

IZ

E

TYPE LOCATION

F U

R N

IS

H

E D

B Y

TYPE LOCATION

F U

R N

IS

H

E D

B Y

I N

T E

R L O

C K

W

IT

H M

O T

O R

N O

B

Y E

.C

A

N U

A L A

T S

T A

R T

E R

I N

T E

G R

A L

W

IT

H E

Q U

IP

M

E N

T

F U

R N

IS

H

E D

B Y

S E

E N

O T

E

N U

M B

E R

O F

C O

N D

U C

T O

R S

W

IR

E S

IZ

E

G R

O U

N D

S

IZ

E

C O

N D

U

IT

S

IZ

E

H O

R S

E P

O W

E R

H

P

L O

A D k V

A

V

-1 P

H

V

-1 P

H

V

-3 P

H

V

-1 P

H

V

-3 P

H

V

-1 P

H

V

-1 P

H

V

-3 P

H

R O

O M

N U

M B

E R

ROOM NAME M

A

N U

A L

M A

G N

E T

IC

B U

IL

T

-I N

M O

T O

R O

/L

-S

P E

E D

V F

D

S E

E N

O T

E

N E

A R

M O

T O

R

M O

T O

R C

O N

T C

E N

T E

R

E Q

U

IP

C O

N T

P A

N E

L

R O

O M

N U

M B

E R

S E

E N

O T

E

D

IS

C S

W

IT

C H

M A

N U

A L S

T A

R T

E R

R E

C E

P T

A C

L E

F E

E D

E R

S W

O R

B R

E A

K E

R

N E

M A

T Y

P E

D

IS

C S

IZ

E

F U

S E

S

IZ

E

N E

A R

M O

T O

R

M O

T O

R C

O N

T C

E N

T E

R

E Q

U

IP

C O

N T

P A

N E

L

P A

N E

L B

O A

R D

S E

E N

O T

E

AC-1 SPLIT SYSTEM HEAT PUMP 0.73 ● 204 Lobby ● ● HC ● ● 2 EC ● HC 3 12 12 0.75" 1

AD-1 AIR CURTAIN 6.86 ● 208 Vestibule ● ● HC ● 1 60 NF ● EC ● HC 3 8 10 0.75"

CU-1 OUTDOOR CONDENSING UNIT 6.03 ● ROOF ● ● HC ● 3R 60 NF ● EC ● HC 3 8 10 0.75"

16.05 kVA 17.76 kVA (49 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: 1. THIS PANEL IS FED FROM THE NORMAL BRANCH.

Total Est. Demand: 49 A

Total Conn.: 45 A

Total Est. Demand: 17.76 kVA

Receptacle 3150 VA 100.00% 3150 VA Total Conn. Load: 16.05 kVA

Motor 12896 VA 113.31% 14612 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 7.17 kVA 4.32 kVA 4.56 kVA

29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30

27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28

25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26

23 Space -- 1 -- -- 1 -- Space 24

21 Space -- 1 -- -- 1 -- Space 22

19 Space -- 1 -- -- 1 -- Space 20

17 Space -- 1 -- -- 1 -- Space 18

15 Space -- 1 -- -- 1 -- Space 16

13 Space -- 1 -- -- 1 -- Space 14

11 Space -- 1 -- -- 1 -- Space 12

9 Space -- 1 -- 3016... -- -- -- 10

7 -- -- -- 3432... 3016... 2 45 A CU-1 8

5 AD-1 45 A 2 3432... 1125... -- -- -- 6

3 Rec CU-1 20 A 1 180 VA 1125... 2 20 A RP-1 4

1 Rec Lobby 205 20 A 1 540 VA 180 VA 1 20 A AUTO DOOR 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W Mains Rating: 80 A

Supply From: T1 Enclosure: Type 1 Mains Type: MB

Location: Storage 206 Mounting: Surface A.I.C. Rating: 10000

Panel: 1-LE2

EXISTING

Revisions Date

BID DOCUMENTS 02/14/2025

1 ADDENDUM 1 06/27/25

1 1

M102-HVAC FLOOR PLAN - NEW WORK
M102 - HVAC FLOOR PLAN - NEW WORK
M601-SCHEDULES
M601 - SCHEDULES

E601 - ELECTRICAL SCHEDULES & DETAILS