This document contains drawings and specifications for an air handling unit replacement project at the Louis Stokes Cleveland VA Medical Center. The project involves replacing AHU-17 and AHU-18. The drawings provide details on the mechanical controls sequence of operation, point lists, and specifications for chilled water and heat trace controls. Key requirements include replacement of air handling units, associated controls, temperature and humidity sensors, steam and chilled water valves, variable frequency drives for fans, and a building management system integrated with the new controls. The Department of Veterans Affairs Veterans Health Administration VISN 10 is the contracting agency. Amendment 0008 updates the drawings date to May 29, 2020 but otherwise maintains the same terms.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S06. 36C25019B0060_1 Amend 0008.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Hardware Points Software Points
Point Name AI AO BI BO Trend Alarm Show On Graphic
Zone Temp X X X
Zone Current X X X
Heating Setpoint X X
Heating Percentage
Totals 3 0 0 1 4 3 3
Total Hardware 4
Loss of Power
Low Zone Temp
Low Current X
X
X
X
X X
E-65042
DAVID A.
DEMAGAL
L
G N
S S
A
ION EL
T
F E
GE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
MEPT ENGINEER:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
STRUCTURAL ENGINEER:
REPLACEMENT OF
AHU-17 & AHU-18
VAMC - WADE PARK
BARBER & HOFFMAN, INC.
2217 EAST 9TH STREET, SUITE 350
CLEVELAND, OH 4115-1257
PHONE: (216)-875-0100
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
PHONE: (440)-546-9696
541-18-104
19002
Z M y D o c u m e n ts
\1
F
F H
C F
R
J C a rt e r5
.r v t
/2
/2
:3
:0
A
M
M0.10
MECHANICAL CONTROLS
JXCDAD08/09/2019
FLOW METER CONTROLS POINT LIST
NOT TO SCALE
TEMPERATURE PROBE
FLOW METER TRANSDUCERS
TEMPERATURE PROBE
FLOW
METER
TRANSMITTER
RS232 RS485
OUTPUTS INPUTS
P O
W E
R S
U P
P L Y
CHWS
CHWR
FLOW METER CONTROLS AND SEQUENCE OF OPERATION
OUTDOOR AIR FAN CONTROLS POINT LIST
I - STATIC PRESSURE
I - DAMPER STATUS
O - INLET DAMPER
M
N.C.
THE BALANCER SHALL ADJUST AND SET THE VFD TO THE SCHEDULED AIR FLOW SETPOINT.4.
GENERATED.
THE BUILDING CONTROL SYSTEM SHALL MONITOR THE FAN STATUS. UPON FAILURE OF THE FAN, AN ALARM SHALL BE3.
START. UPON FAN FAILURE OR SHUTDOWN DAMPER SHALL CLOSE.
ON A RUN COMMAND THE TWO POSITION DAMPER SHALL OPEN, AND THE DAMPER END SWITCH SHALL ALLOW THE FAN TO2.
FAN SHALL OPERATE CONTINUOUSLY.1.
FAN OPERATION
O - SUPPLY FAN VFD SPEED
O - SUPPLY FAN ENABLE/DISABLE
VFD
I - FAN STATUS
CT
M
I - OUTDOOR AIR FAN VFD HOA
OA
SP
SEQUENCE OF OPERATION FOR OUTDOOR AIR FAN
NOT TO SCALE
Hardware Points Software Points
Point Name AI AO BI BO Trend Alarm Show On Graphic
Fan VFD Speed X X X
Fan VFD Fault X X
Fan Status X
Fan Start/Stop X X
Total Hardware 6
Isolation Damper X X
Exhaust Duct Static Pressure X X X
Fan Failure
Fan in Hand X
Totals 1 1 2 2 4 4 6
X
X
X
X
X
X
Hardware Points Software Points
Point Name AI AO BI BO Trend Alarm Show On Graphic
Water Flow Rate (Chilled Water Return) X X X
Water Temperature (Chilled Water Supply) X X
Water Temperature (Chilled Water Return)
Totals 3 2 0 0 9 1 9
Total Hardware 5
Data Outputs
Peak Flow Today
Meter Failure X
X
X
X X
BTU Measurement Outputs X
X
X
X
XX
X
XPeak Flow Year to Date
X
XCHW Usage Month to Date
CHW Usage Year to Date
RETURN AIR TEMP - MIXED AIR TEMP
RETURN AIR TEMP - OUTSIDE AIR TEMP
%OA= X 100
7. RETURN FAN(S)
7.1 THE RETURN FAN ISOLATION DAMPER SHALL OPEN AND THE RETURN FAN SHALL
RUN WHENEVER THE SUPPLY FAN RUNS. MULTIPLE
FANS SHALL RUN IN UNISON. IF A FAN SHOULD FAIL, ITS ASSOCIATED
ISOLATION DAMPER SHALL CLOSE AND REMAINING FANS SHALL RAMP UP TO
MAINTAIN SET POINT.
7.2 ALARMS
RETURN FAN FAILURE AND INDICATE WHICH FAN FAILED
RETURN FAN VFD FAULT
8. RETURN AIRFLOW
8.1 THE RETURN FAN VFD SHALL MODULATE IN UNISON WITH THE SUPPLY FAN
VFD. RETURN AIRFLOW SETPOINT SHALL BE EQUAL TO SUPPLY AIR FLOW
MINUS 10%(ADJ.) AND MINUS EXHAUST AIR FLOW (4800 CFM). THE RETURN
FAN VFD SPEED SHALL NOT DROP BELOW 20%(ADJ.)
8.2 ALARMS
HIGH RETURN AIRFLOW (10% ABOVE SUPPLY AIRFLOW)
LOW RETURN AIRFLOW (30% BELOW SUPPLY AIRFLOW)
9. PREHEAT COIL
9.1 THE CONTROLLER SHALL MEASURE THE PREHEAT SECTION AIR TEMPERATURE
(TS-2) AND MODULATE THE PREHEAT COIL VALVE AND BYPASS DAMPER TO
MAINTAIN ITS SETPOINT. THE PREHEAT SECTION TEMPERATURE SETPOINT
SHALL EQUAL THE SUPPLY AIR TEMPERATURE SETPOINT MINUS THE FAN
HEAT OFFSET VALUE.
9.2 PREHEAT COIL SHALL BE ENABLED WHENEVER:
OUTSIDE AIR TEMPERATURE IS LESS THAN 50 DEG(ADJ),
AND THE ECONOMIZER IS DISABLED
AND THE SUPPLY FAN STATUS IS ON
9.3 THE PREHEAT COIL SHALL OPEN FOR FREEZE PROTECTION WHENEVER:
MIXED AIR TEMPERATURE (TS-1) DROPS BELOW 36 DEG F (ADJ.)
OR THE FREEZESTAT IS ON.
9.4 IF OUTDOOR TEMPERATURE IS BELOW 30 DEG F (ADJ) AND HEAT IS
REQUIRED, THEN THE STEAM VALVE FOR HEATING SHALL BE FULLY OPEN
AND TEMPERATURE CONTROL SHALL BE BY MODULATION OF THE
FACE/BYPASS DAMPER.
10. SUPPLY AIR TEMPERATURE SETPOINT
10.1 THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE (TS-4)
AND SHALL MAINTAIN A SUPPLY AIR TEMPERATURE SETPOINT RESET BASED
ON ZONE COOLING AND HEATING REQUIREMENTS.
10.2 THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE RESET FOR COOLING
BASED ON ZONE COOLING REQUIREMENTS AS FOLLOWS:
THE INITIAL SUPPLY AIR TEMPERATURE SETPOINT SHALL BE 55 DEG F(ADJ.)
AS COOLING DEMAND INCREASES, THE SETPOINT SHALL INCREMENTALLY
RESET DOWN TO A MINIMUM OF 53 DEG F(ADJ.)
AS COOLING DEMAND DECREASES, THE SETPOINT SHALL INCREMENTALLY
RESET UP TO A MAXIMUM OF 58 DEG F(ADJ.).
11. COOLING COIL
11.1 THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE (TS-4)
AND MODULATE THE COOLING COIL VALVE TO MAINTAIN THE SUPPLY AIR
TEMPERATURE SETPOINT.
11.2 THE COOLING SHALL BE ENABLED WHENEVER:
OUTSIDE AIR TEMPERATURE IS GREATER THAN 50 DEGREES
AND THE SUPPLY FAN STATUS IS ON
AND THE HEATING IS NOT ACTIVE
11.4 THE COOLING COIL VALVE SHALL OPEN TO 50%(ADJ.) WHENEVER THE
FREEZESTAT IS ON.
11.5 ALARMS
11.5.1 HIGH SUPPLY AIR TEMPERATURE ALARM, THE CONTROLLER SHALL
ALARM IF THE SUPPLY AIR TEMPERATURE(TS-4) IS 5 DEG F(ADJ.)
GREATER THAN THE SUPPLY AIR SETPOINT.
11.5.2 LOW SUPPLY AIR TEMPERATURE ALARM, THE CONTROLLER SHALL
ALARM IF THE SUPPLY AIR TEMPERATURE IS LESS THAN 45 DEG F(ADJ.).
12. ECONOMIZER
12.1 THE CONTROLLER SHALL MEASURE THE MIXED AIR TEMPERATURE AND
MODULATE THE ECONOMIZER DAMPERS IN SEQUENCE TO MAINTAIN THE
ECONOMIZER TEMPERATURE SETPOINT. THE ECONOMIZER TEMPERATURE
SETPOINT IS EQUAL TO THE SUPPLY AIR TEMPERATURE SETPOINT
MINUS THE FAN HEAT OFFSET VALUE. THE OUTSIDE AIR DAMPERS SHALL
MAINTAIN A MINIMUM ADJUSTABLE POSITION TO MAINTAIN MINIMUM
OUTSIDE AIR REQUIRED.
12.2 THE ECONOMIZER SHALL BE ENABLED WHENEVER:
OUTSIDE AIR TEMPERATURE IS LESS THAN 60 DEG F(ADJ)
AND THE OA TEMPERATURE IS LESS THAN THE RETURN AIR TEMPERATURE
AND THE OA ENTHALPY IS LESS THAN THE RETURN AIR ENTHALPY
AND THE SUPPLY FAN STATUS IS ON
12.3 THE OUTSIDE AIR DAMPER SHALL CLOSE WHENEVER:
MIXED AIR TEMPERATURE DROPS BELOW 36 DEG F(ADJ.)
OR THE FREEZESTAT IS ON
OR THE SUPPLY FAN STATUS IS OFF
12.4 THE OUTSIDE AND EXHAUST AIR DAMPERS SHALL CLOSE AND THE RETURN
AIR DAMPER SHALL OPEN WHEN THE UNIT IS OFF.
13. HUMIDIFIER CONTROL
13.1 THE CONTROLLER SHALL MEASURE THE RETURN AIR HUMIDITY AND
MODULATE THE HUMIDIFIER TO MAINTAIN A SETPOINT OF 40% RH(ADJ.). THE
HUMIDIFIER SHALL BE ENABLED WHENEVER THE SUPPLY FAN STATUS IS ON
AND THE OUTSIDE AIR TEMPERATURE IS BELOW 65 DEGREES.
13.2 THE HUMIDIFIER SHALL TURN OFF WHENEVER:
SUPPLY AIR HUMIDITY MEASURERS 90%
OR WHEN OUTSIDE AIR TEMPERATURE IS ABOVE 65 DEGREES
OR ON A LOSS OF SUPPLY FAN STATUS
13.3 ALARMS
HIGH SUPPLY AIR HUMIDITY 90%(ADJ)
LOW SUPPLY AIR HUMIDITY 30%(ADJ)
14. AIRFLOW CONTROL
14.1 THE CONTROL SYSTEM SHALL MONITOR AND DISPLAY SUPPLY AIR FLOW,
RETURN AIR FLOW, AND MIXED AIR FLOW IN CFM. IT WILL CALCULATE, AND
DISPLAY OUTDOOR AIR PERCENTAGE FROM THE MEASURED VALUES BASED
ON THE FOLLOWING FORMULA:
14.2 THE MINIMUM OUTSIDE AIR DAMPER SHALL BE CONTROLLED AS FOLLOWS:
14.2.1 WHEN OUTSIDE AIR TEMPERATURE IS BELOW 50 DEGREES AND
THE ECONOMIZER CONTROL SEQUENCE HAS REDUCED THE OUTSIDE
AIRFLOW DOWN TO THE MINIMUM OUTSIDE AIR FLOW RATE, THE ECONOMIZER
DAMPER SHALL CLOSE AND OUTSIDE AIR DAMPER SHALL OPEN. MINIMUM
OUTDOOR AIR FAN SHALL OPERATE TO MAINTAIN MINIMUM OUTDOOR
AIR SET POINT.
14.2.2 WHEN THE AIR HANDLING UNIT CONTROLS ARE OPERATING IN
ECONOMIZER MODE, THE ECONOMIZER CONTROL SEQUENCE WILL
MODULATE THE ECONOMIZER DAMPER, WHILE THE OUTSIDE
AIR DAMPER MAINTAINS MINIMUM OUTDOOR AIR POSITION
TO MAINTAIN THE MIXED AIR ECONOMIZER TEMPERATURE SETPOINT.
THE OUTSIDE AIR CALCULATION ABOVE IN 14.1 SHALL DISPLAY THE
OUTSIDE AIR PERCENTAGE BUT WILL NOT BE USED TO CONTROL THE
OUTSIDE AIR DAMPER IN THE ECONOMIZER MODE.
14.2.3 WHEN OUTSIDE AIR TEMPERATURE IS ABOVE 60 DEGREES AND
THE ECONOMIZER IS NOT ENABLED BASED ON THE OUTSIDE AIR
TEMPERATURE OR ENTHALPY PER 12.2 ABOVE, THE CONTROL
SEQUENCE SHALL REDUCE THE OUTSIDE AIRFLOW DOWN TO THE
MINIMUM OUTSIDE AIR FLOW RATE. THE OUTSIDE METER SHALL
MEASURE THE OUTSIDE AIR FLOW. CALCULATION ABOVE IN 14.1
SHALL DISPLAY THE OUTSIDE AIR PERCENTAGE BUT WILL NOT BE
USED TO CONTROL THE OUTSIDE AIR DAMPER. WHEN THE OUTSIDE
AIR TEMPERATURE AND THE RETURN TEMPERATURE ARE EQUAL,
ADJUST THE RETURN AIR TEMPERATURE UPWARD BY 0.1 DEGREE F
TO ENABLE THE OUTSIDE AIR CALCULATION TO FUNCTION.
15. FILTERS
15.1 ALARMS
15.1.1 PREFILTER DIRTY -DIFFERENTIAL PRESSURE IS 1" GREATER THAN CLEAN
FILTER
15.1.2. FINAL FILTER DIRTY -DIFFERENTIAL PRESSURE IS 1" GREATER THAN CLEAN
FILTER
16. FAN HEAT OFFSET VALUE
16.1 FAN HEAT OFFSET (0-5)- THE BCS SHALL RESET THE FAN HEAT OFFSET
VALUE BASED UPON THE DIFFERENCE BETWEEN SUPPLY AIR SETPOINT AND
SUPPLY AIR TEMPERATURE. THE LOWER LIMIT SHALL BE 0. THE UPPER
LIMIT SHALL BE 5.
16.2 WHEN SUPPLY AIR TEMPERATURE SENSOR INDICATES A TEMPERATURE OF
2°F BELOW THE SUPPLY AIR SETPOINT, THE PID LOOP SHALL SUBTRACT 1
FROM THE FAN HEAT OFFSET VALUE. IF THE FAN HEAT OFFSET VALUE IS
GREATER THAN 0, THEN THE FAN HEAT OFFSET SHALL BE SET TO 0.
AFTER AN ADJUSTABLE PERIOD OF 15 MINUTES THE PID LOOP SHALL
COMPARE THE SUPPLY TEMPERATURE TO THE SETPOINT AND ADJUST THE
VALUE.
16.3 WHEN SUPPLY AIR TEMPERATURE SENSOR INDICATES A TEMPERATURE +
OR - 2°F OF THE SUPPLY AIR SETPOINT, THE PID LOOP SHALL ADD ZERO TO
THE FAN HEAT OFFSET VALUE. AFTER AN ADJUSTABLE PERIOD OF 15
MINUTES THE PID LOOP SHALL COMPARE THE SUPPLY TEMPERATURE TO
THE SETPOINT AND ADJUST THE VALUE.
16.4 WHEN SUPPLY AIR TEMPERATURE SENSOR INDICATES A TEMPERATURE OF
2°F ABOVE THE SUPPLY AIR SETPOINT, THE PID LOOP SHALL ADD 1 TO THE
FAN HEAT OFFSET VALUE. IF THE FAN HEAT OFFSET VALUE IS GREATER
THAN 5, THEN THE FAN HEAT OFFSET SHALL BE SET TO 5. AFTER AN
ADJUSTABLE PERIOD OF 15 MINUTES THE PID LOOP SHALL COMPARE THE
SUPPLY TEMPERATURE TO THE SETPOINT AND ADJUST THE VALUE.
17. CONTINUOUS COMMISSIONING ALARMS
17.1 IF IN COOLING MODE (OUTSIDE AIR IS GREATER THAN 50 DEGREES):
TS-2 IS GREATER THAN TS-1 BY 1 DEG F, OR MORE, THEN ALARM "STEAM
VALVE OPEN IN COOLING MODE"
17.2 IF IN HEATING MODE (OUTSIDE AIR IS LESS THAN 50 DEGREES):
TS-3 IS LESS THAN TS-2 BY 1 DEG F, OR MORE, THEN ALARM "CHILLED
WATER VALVE IS OPEN IN HEATING MODE"
18. COLD START SEQUENCE
18.1 WHENEVER UNIT IS STARTED AND OUTDOOR AIR TEMPERATURE IS
BELOW 30 DEG F INITIATE THE FOLLOWING SEQUENCE.
18.2.1 OA DAMPER SHALL BE CLOSED (MIN OA FAN SHALL BE OFF), RELIEF AIR
DAMPER SHALL BE CLOSED, RETURN AIR DAMPER SHALL BE 100% OPEN
(ECONOMIZER DISABLED).
18.2.2 COMMAND ON STEAM PREHEAT VALVE.
18.2.3 STEAM PREHEAT VALVE SHALL MAINTAIN 80 DEGREE SUPPLY AIR
TEMPERATURE.
18.2.4 SMOKE DAMPER SHALL BE OPEN.
18.2.5 COMMAND ON SUPPLY AND RETURN (DRIVE) ALLOW TO RAMP UP
NORMALLY.
18.2.6 SET MIXED AIR SETPOINT TO 70 DEG F ONCE SUPPLY/RETURN FAN-ON
STATUS HAS BEEN PROVEN.
18.2.7 FIVE MINUTES AFTER SUPPLY/RETURN FAN-ON STATUS HAS BEEN
PROVEN, OA FAN SHALL DELIVER 5% OF CFM RA AND EX
DAMPERS SHOULD OPEN/CLOSE SIMULTANEOUSLY WITH OA DAMPER.
(OA=5% RA= 95% EX=5%).
18.2.8 FIVE MINUTES AFTER OA FAN STARTED DELIVERING 5%, RELEASE OA, RA,
RELIEF AIR DAMPERS TO CONTROL TO MEET MIXED AIR SETPOINT.
18.2.9 LOWER MIXED SET POINT TO 60 DEGREES FOR 10 MINUTES.
18.2.10 RELEASE MIXED AIR SET POINT BACK TO ORIGINAL SETTING.
19. MINIMUM OUTDOOR AIR FAN
19.1 THE OUTDOOR AIR FAN SHALL RUN WHENEVER ECONOMIZER IS
DISABLED. WHEN ECONOMIZER IS ENABLED MINIMUM OUTDOOR AIR FAN
SHALL SHUTDOWN AND OUTDOOR AIR DAMPER SHALL CLOSE.
19.2 ALARMS
HIGH OUTDOOR AIR AIRFLOW (10% ABOVE OUTDOOR AIRFLOW)
LOW OUTDOOR AIR AIRFLOW (30% BELOW OUTDOOR AIRFLOW)
1. RUN CONDITIONS - SCHEDULED
1.1 THE UNIT SHALL RUN BASED UPON AN OPERATOR ADJUSTABLE SCHEDULE.
2. FREEZE PROTECTION
2.1 WHEN THE FREEZE STAT SENSES A TEMPERATURE BELOW 40 DEG. F THE
FOLLOWING SEQUENCE SHALL OCCUR:
2.1.1 THE UNIT SHALL SHUTDOWN AND GENERATE AN ALARM
2.1.2 THE OUTSIDE AIR AND ECONOMIZER DAMPERS SHALL CLOSE
2.1.3 STEAM PREHEAT COIL VALVE SHALL OPEN TO 100%(ADJ)
2.1.4 COOLING COIL VALVE SHALL OPEN TO 50%(ADJ)
3. HIGH/LOW STATIC SAFETY SHUTDOWN
3.1 THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A
HIGH STATIC SHUTDOWN SIGNAL. HIGH STATIC ALARM SETPOINT SHALL BE
1" BELOW DUCTWORK PRESSURE CLASS.
3.2 THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A
LOW STATIC SHUTDOWN SIGNAL. LOW STATIC ALARM SETPOINT SHALL BE
NEGATIVE 2" S.P.
4. SMOKE DETECTION
4.1 THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON A DETECTOR
TRIP ON SUPPLY AIR OR RETURN AIR SMOKE DETECTOR. DISCHARGE AND
RETURN SMOKE DAMPERS SHALL CLOSE IN THIS EVENT.
5. SUPPLY FAN(S)
5.1 THE SUPPLY FAN ISOLATION DAMPER SHALL OPEN AND THE SUPPLY FAN SHALL
RUN ANYTIME THE UNIT IS COMMANDED TO RUN,
UNLESS SHUTDOWN ON SAFETIES. TO PREVENT SHORT CYCLING, THE
SUPPLY FAN SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME.
MULTIPLE FANS SHALL RUN IN UNISON. IF A FAN SHOULD FAIL, ITS
ASSOCIATED ISOLATION DAMPER SHALL CLOSE AND REMAINING FANS SHALL
RAMP-UP TO MAINTAIN SET POINT.
5.2 ALARMS:
SUPPLY FAN FAILURE
6. SUPPLY AIR DUCT STATIC PRESSURE CONTROL
6.1 THE CONTROLLER SHALL MEASURE DUCT STATIC PRESSURE AND SHALL
MODULATE THE SUPPLY FAN VFD SPEED TO MAINTAIN THE DUCT STATIC
PRESSURE SETPOINT. THE SUPPLY FAN VFD SPEED SHALL NOT DROP
BELOW 30%(ADJ.). THE INITIAL DUCT STATIC PRESSURE SETPOINT SHALL BE
1.0", AND BE ADJUSTED UP DURING THE BALANCING PROCESS.
THE FINAL DUCT STATIC PRESSURE SETPOINT SHALL BE DETERMINED, SET, AND
DOCUMENTED BY THE BALANCING CONTRACTOR. THE SETPOINT SHALL BE
SUFFICIENT TO MEET THE VAV BOX AIRFLOW REQUIREMENTS DURING DESIGN
CONDITIONS AND SHALL NOT BE SET LOWER THAN 0.5".
6.2 ALARMS:
HIGH SUPPLY FAN STATIC PRESSURE
LOW SUPPLY FAN STATIC PRESSURE
SUPPLY FAN VFD FAULT
SEQUENCE OF OPERATION FOR AIR HANDLING UNIT
UNIT HEATER SEQUENCE OF OPERATIONS
T
UNIT HEATER
LPR
LPS
HEATER OPERATION:
A. REMOTE THERMOSTAT SHALL SEQUENCE FAN
AND COIL TO MAINTAIN SETPOINT (65°F).
B. BMS SHALL GENERATE AN ALARM IF STAT TEMPERATURE
FALLS BELOW 38 DEGREES (ADJUSTABLE)
NOT TO SCALE
UNIT HEATER CONTROLS POINT LIST
Hardware Points Software Points
Point Name AI AO BI BO Trend Alarm Show On Graphic
Unit Heater Steam Valve X X X
Low Space Temperature X X
Total Hardware 2
Totals 0 1 0 0 2 1 3
Space Temperature X X
HEAT TRACE CONTROL PANEL SEQUENCE
PACKAGED CONTROL PANEL SHALL BE PROVIDED WITH THE FOLLOWING:
A. EACH HEAT TRACE CIRCUIT SHALL BE PROVIDED WITH 30mA GFCI CIRCUIT BREAKER
B. ALARM ACTIVATION FOR EACH CIRCUIT
1. LOSS OF POWER
2. LOW TEMPERATURE
3. LOW CURRENT
C. DRY CONTACTS FOR B.A.S. TERMINATION
FROM ELECTRICAL PANEL
208/120V-3PHASE
TO B.A.S.
TO HEAT TRACE JUNCTION
BOX FOR EACH PIPE (TYP) HEAT TRACE
CONTROL PANEL
NOT TO SCALE
HEAT TRACE PANEL CONTROLS POINT LIST
T T
AMBIENT TEMPERATURE
SENSOR
PROVIDE PIPE TEMPERATURE
SENSORS FOR CHWS, CHWR,
LPR, LPS & CD
Revisions: Date:
BID ISSUE 08/09/2019
AMENDMENT 2 05/29/2020
TIED INTO BMS
NEW DDC
THERMOSTAT 4. SENSOR FAILURE
SEQUENCE OF OPERATIONS - CHWR, CHWS & CD
HEAT TRACE SHALL BE ENABLED WHEN OUTDOOR AIR TEMPERATURE FALLS BELOW 37°F (ADJ.).
HEAT TRACE SHALL BE DISABLED WHEN OUTDOOR AIR TEMPERATURE IS ABOVE 40°F (ADJ.).
SEQUENCE OF OPERATIONS - LPS & LPC
THE HEAT TRACE SYSTEM SHALL BE CONTROLLED BY A LINE SENSING THERMOSTAT
THAT SHALL CALL FOR THE SYSTEM TO OPERATE WHEN THE PIPE TEMPERATURE
FALLS BELOW 37°F (ADJ.). PIPE SENSING THERMOSTAT SHALL BE PROVIDED FOR EACH CIRCUIT, UPON DETECTION OF TEMPERATURE OF 32°F LOW TEMPERATURE ALARM SHALL SIGNAL TO
B.A.S.
ON ANY ALARM CONDITION B.A.S. SHALL ANNUNCIATE "TROUBLE" ALARM WITH ALARM
DESCRIPTION AS SHOWN ABOVE.
PROVIDE INDIVIDUAL HEAT TRACING CIRCUIT FOR CHWS, CHWR, LPR, LPS AND CD.
LPS AND LPR HEAT TRACE CABLE SHALL BE RATED FOR MAXIMUM CONTINUOUS EXPOSURE
TEMPERATURE OF 420°F.
D.
E.
F.
G.
H.
| Sheets |
| M0.10 - MECHANICAL CONTROLS |