S02 - ATTACHMENT A - STATMENT OF WORK.pdf

PDF 112 KB Posted

Attached to
4320--Boiler Plant Fuel Oil Pump Set
Solicitation number
36C24822Q1083
Issued by

View the file

Other files

File Type Posted
S02 - ATTACHMENT C - CLAUSES.pdf PDF
36C24822Q1083_1.docx DOCX document
S02 - ATTACHMENT B - SCHEDULE.pdf PDF
S02 - ATTACHMENT D - LIMITATION OF SUBCONTRACTING.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment A 36C24822Q1083

C.W. Bill Young VA Medical Center

Bay Pines, FL 33744

Duplex Oil Pump Set - Brand Name or Equal

*** Reference manufacturer – Phillips ***

Statement of Work Replace Boiler Plant Fuel Oil Pump Set

Scope of Work:

Contractor shall provide all parts, labor, materials, supervision, and specialty services to remove and replace existing Boiler Plant fuel Oil Pump Set.

Power down and remove existing pump set.

Furnish and install new simplex duplex pump set (Brand Name or Equal).

Supply SCH. 40 black piping and fittings to tie in new pump set with the existing fuel lines for the boiler.

Connect all electrical and electronic components of the fuel oil system being installed.

Start up and test new fuel oil pump set system.

Clean up work area.

Contractor shall include all start-up and verification upon completion of installation.

Salient Characteristics

Qty: 1 Package Pump Set - Duplex – SKID White and Blue (Brand Name or Equal).

Motor Data:

TEFC 460/3/60 Motor.

HP: 2 HP

Volts: 230/460 VAC, AC, 3-Phase, 60Hertz

Duplex Pump Standard Features:

(2) check valves, (2) wye-strainers, (4) manual pump isolation valves, (2) pressure relief valves, containment leak alarm, control panel disconnect switch, pump running indicators, pump run-off-auto mode switches, motor starters, duplex alternating pump controls, pump/motor, control power transformer (if required).

Item Description:

Pressure gauge with isolation valve, 2” Vacuum gauge with isolation valve, 2” Flow switch w/loss of flow alarm 25 GPM high lift pump with lip seal

File details come from the government source that posted it. Updated .