S02- 561-19-160_Prosthetics Lab_ Final Bid Drawings NEW_Part2.pdf
PDF 1 MB Posted
- Attached to
- Y1DA--Upgrade prosthetics (VA-22-00010940)
- Solicitation number
- 36C24222B0005
About this file
This solicitation is for construction services to upgrade the prosthetics lab at the VA East Orange Medical Center in New Jersey. The scope of work includes demolishing existing interior walls, finishes, ceilings and mechanical, plumbing and electrical components; abating hazardous materials; and constructing new interior walls, doors, ceilings, finishes, and mechanical, plumbing and electrical systems. Specific tasks involve demolishing and replacing flooring in Stairwell A-S7, removing and installing doors, and creating new openings. The performance period is 180 calendar days from notice to proceed. The solicitation also includes an alternate to delete a pass window and fire rated coiling counter door between two rooms. The total project area is approximately 4,695 square feet on the A level of Building 1.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CENTER LINE
DETAIL INDICATOR
DETAIL INDICATOR FOR SMALL CONDITIONS
DIMENSION LINE
NEW DOOR HARDWARE AND OPENING / BORROWED LIGHT
IDENTIFIER
- SEE DOOR SCHEDULE, DETAILS, SPECIFICATIONS AND
ELEVATIONS SHEET
DRAWING BLOCK TITLE, TYPICAL
ELEVATION INDICATOR, EXTERIOR
ELEVATION INDICATOR, INTERIOR
BUILDING SECTION INDICATOR
TYPICAL DETAIL INDICATOR
EXISTING ROOM NAME AND NUMBER
COLUMN GRID
ARCHITECTURAL KEYNOTE TAG
WALL OR PARTITION TYPE
FIRE EXTINGUISHER CABINET
CORNER GUARD
NORTH ARROW
CG
FEC
A
CORRIDOR
C2
DETAIL NUMBER
SHEET WHERE
DRAWN
XX-XX
XX-XX
X
DRAWING TITLE
SCALE: 1 1/2" = 1'-0"
1"
D2
XX-XX
XX-XX
CL
XX-XX
x'-x" SPOT ELEVATION
? REVISION
REVISION CLOUD
BREAK LINE
NEW ROOM NAME AND NUMBER
CORRIDOR
C2
X
EXISTING DOOR OPENING
X
N P N
H W
-X X
XX-XX
XX-XX
ELEVATION INDICATOR, INTERIOR CORRIDOR
EXTERIOR
REFLECTED CEILING KEYNOTE TAGX
& AND
@ AT
C CENTERLINE
# NUMBER
AB ANCHOR BOLT
ABV ABOVE
ACT ACOUSTIC CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH
DISABILITIES ACT
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AIA AMERICAN INSTITUTE OF
ARCHITECTS
ALUM ALUMINUM
ALT ALTERNATE
AP ACCESS PANEL
APPROX APPROXIMATE
ARCH ARCHITECTURAL
AT ACOUSTIC TILE
AUTO AUTOMATIC
AVG AVERAGE
BD BOARD
BLDG BUILDING
BLK BLOCK
BM BEAM
BMPR BUMPER
BOT BOTTOM
BRG BEARING
BEL BELOW
BR BUMPER RAIL
BRK BRICK
C CONCRETE
CAB CABINET
CB CATCH BASIN
CEM CEMENT
CCT CUBICLE CURTAIN TRACK
CG CORNER GUARD
CI CAST IRON
CIP CAST IN PLACE
CJ CONTROL JOINT
CT CERAMIC TILE
CLG CEILING
CL CLOSET
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONT CONTINUOUS
CPT CARPET
CU CUBIC
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DISP DISPENSER
DN DOWN
DO DOOR OPENING
DOZ DOZEN
DP DAMPPROOFING
DR DOOR
DWG DRAWING
DWGS DRAWINGS
DWR DRAWER
E EAST
EA EXHAUST AIR, EACH
EL ELEVATION
ELEV ELEVATION
ELEC ELECTRICAL
EMER EMERGENCY
ENCL ENCLOSURE
ENGR ENGINEER
EP ELECTRICAL PANELBOARD
EPY EPOXY
EQ EQUAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWS EYE WASH STATION
EXP EXPANSION
EJ EXPANSION JOINT
EXIST EXISTING
EXT EXTERIOR
FA FIRE ALARM
FB FACE BRICK
FD FLOOR DRAIN
FDC FIRE DEPARTMENT
CONNECTION
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER
CABINET
FF FINISH FACE
FHC FIRE HOSE CABINET
FIN FINISH
FLR FLOOR
FLUOR FLUORESCENT
FO __ FACE OF __
FOC FACE OF CONCRETE
FOS FACE OF STUD
FOW FACE OF WALL
FPRF FIREPROOF(ING)
FR FIRE RATING, FRAME
FRMG FRAMING
FS FULL SIZE
FT FOOT OR FEET
FTG FOOTING
FUR FURRING
FUT FUTURE
GC GENERAL CONTRACTOR
GA GAUGE
GAL GALLON
GALV GALVANIZED
GALV STL GALVANIZED STEEL
GB GRAB BAR
GC GENERAL CONTRACTOR
GD GUARD
GL GLASS
GND GROUND
GR GRADE
GWB GYPSUM WALLBOARD
GYP BD GYPSUM WALLBOARD
HB HOSE BIBB
HC HOLLOW CORE
HD HEAD
HDPL HIGH DENSITY PLASTIC LAMINATE
HDWR HARDWARE
HDWD HARDWOOD
HT HEIGHT
HDRL HANDRAIL
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HMF HOLLOW METAL FRAME
HR HANDRAIL
HO HOLD OPEN
HORIZ HORIZONTAL
HP HIGH POINT
HR HOUR
HVAC HEATING, VENTILATION, AIR
CONDITIONING
IBC INTERNATIONAL BUILDING CODE
ID IDENTIFICATION, INSIDE
DIAMETER / DIMENSION
IN INCH
INCL INDLUDE(D)
INSUL INSULATION
INT INTERIOR
INV INVERT
JAN JANITOR
JST JOIST
JT JOINT
KP KICK PLATE
KO KNOCKOUT
L LENGTH
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LBS POUND
LED LIGHT EMITTING DIODE
LF LINEAR FEET
LH LEFT HAND
LIN LINEAR
LIQ LIQUID
LKR LOCKER
LG LONG
LL LEAD LINED
LLV LONG LEG VERTICAL
LP LOW POINT
LRG LARGE
LT LIGHT
LT WT LIGHTWEIGHT
LVR LOUVER
LVT LUXORY VINYL TILE
MAT WALK-OFF CARPET
MATL MATERIAL
MAS MASONRY
MAX MAXIMUM
MECH MECHANICAL
MTL METAL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MP MOP PLATE
MTD MOUNTED
N NORTH
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEG NEGATIVE
NFC NATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER / DIMENSION
OFF OFFICE
OH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OH OVERHEAD
OZ OUNCE
P PAINT
PAV PAVING
PC PRECAST CONCRETE
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLYWD PLYWOOD
PLBG PLUMBING
PMF PREMOLDED FILLER
PR PAIR
PT POINT
PT PORCELAIN TILE
PTN PARTITION
QT QUARRY TILE
R RADIUS, RISER
RA RETURN AIR
RAD RADIUS
RB RESILIENT BASE, RUBBER
BASE
RD ROOF DRAIN
RL ROOF LEADER
REF REFERENCE
REFR REFRIGERATOR
REQ'D REQUIRED
REV REVISION
RFI REQUEST FOR
INFORMATION
RFP REQUEST FOR PROPOSAL
RH RIGHT HAND
RM ROOM
RO ROUGH OPENING
RT RUBBER TILE
S SOUTH
S SOLID SURFACE
SA SUPPLY AIR
SAN SANITARY
SC SOLID CORE
SCHED SCHEDULE
SECT SECTION
SH SPRINKLER HEAD
SHT SHEET
SIM SIMILAR
SM SMOKE
SPEC SPECIFICATION
SPKR SPEAKER
SQ SQUARE
STA STATION
STD STANDARD
STO STORAGE
STL STEEL
SS STAINLESS STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
SYM SYMMETRICAL
SYS SYSTEM
T TREAD
TEL TELEPHONE
TEMP TEMPERED
T&G TONGUE AND GROOVE
THK THICK
TOC TOP OF CONCRETE
TOP TOP OF PAVEMENT
TOS TOP OF STEEL
TOW TOP OF WALL
TRAN TRANSITION
TV TELEVISION
TYP TYPICAL
UNFIN UNFINISHED
UON UNLESS OTHERWISE
NOTED
VB BAPOR BARRIER
VERT VERTICAL
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
VTR VET THRU ROOF
W WEST
W/ WITH
WD WOOD
W/O WITHOUT
WP WATERPROOF
WP WALL PROTECTION
WRS WINDOW ROLLER SHADE
WT WEIGHT
WWF WELDED WIRE FRAME
NOTE:
ALL ABBREVIATIONS SHOWN MAY NOT BE USED ON
THIS PROJECT. CERTAIN COMMON ABBREVIATIONS
MAY NOT BE SHOWN.
WOOD
WOOD FINISH
ALUMINUM
STEEL
EARTH
GYPSUM - PLASTER
MASONRY - CONCRETE BLOCK
RIGID INSULATION
BATT INSULATION
PLYWOOD
CONCRETE
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE REMOVED
1. SPACES AROUND THE PROJECT AREAS WILL BE OCCUPIED DURING PERFORMANCE OF WORK. IMMEDIATE AREAS OF ALTERATIONS WILL BE VACATED. ALL CONTRACTOR WORK WILL BE PERFORMED DURING NORMAL DAYTIME WORKING HOURS UNLESS INDICATED. ALL TEMPORARY SYSTEM SHUTDOWNS WILL OCCUR DURING 2ND SHIFT OR WEEKENDS AND COORDINATED AND APPROVED BY THE PROJECT COR.
2. BEFORE STARTING WORK WITHIN AN OCCUPIED AREA, THE CONTRACTOR WILL BE RESPONSIBLE TO SET-UP TEMPORARY/PERMANENT CONSTRUCTION/ICRA BARRIERS WITH ANTEROOM AND MAINTAIN NEGATIVE AIR PRESSURE. ALL TEMPORARY CONSTRUCTION BARRIERS OUTSIDE THE INDICATED CONSTRUCTION PHASE AREA WILL BE REMOVED AT THE CONCLUSION OF THE WORK SHIFT. THE CONTRACTOR WILL BE RESPONSIBLE TO CLEAN AND PREPARE THE AREA TO BE OCCUPIED BY MEDICAL CENTER STAFF AND PATIENTS.
3. DIMENSIONS SUPERSEDE DRAWINGS. DO NOT SCALE PLANS. DIMENSIONS ARE TO THE FACE OF EXISTING MATERIALS UNLESS OTHERWISE NOTED. DIMENSIONS AND ELEVATIONS SHALL BE VERIFIED AT THE SITE BEFORE PROCEEDING WITH THE WORK. NOTIFY THE ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, DIMENSIONS, AND MATERIALS REQUIRED FOR THE CONTRACTED WORK. REPORT ALL DISCREPANCIES TO ARCHITECT PRIOR TO FABRICATIONS AND ERECTION.
4. IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY TO FOLLOW ALL APPLICABLE SAFETY CODES AND REGULATIONS DURING ALL PHASES OF CONSTRUCTION. ALL CONSTRUCTION WORK SHALL BE PERFORMED IN CONTRACTOR'S RESPONSIBILITY TO DETERMINE CONSTRUCTION PROCEDURES AND SEQUENCE AND TO INSURE THE SAFETY OF THE BUILDING AND ITS COMPONENT PARTS DURING CONSTRUCTION SHALL PROVIDE ADEQUATE SHORING AND BRACING DURING DEMOLITION AND CONSTRUCTION TO SUPPORT LOADS. SUCH MATERIAL SHALL BE REMOVED AT THE COMPLETION OF WORK AND SHALL REMAIN THE CONTRACTOR'S PROPERTY AFTER THE COMPLETION OF THE PROJECT.
5. DO NOT CUT AND PATCH STRUCTURAL ELEMENTS IN A MANNER THAT WOULD REDUCE THEIR LOAD CARRYING CAPACITY OR LOAD-DEFLECTION
RATIO.
6. WHERE EXISTING CONSTRUCTION, EQUIPMENT, ETC. IS REQUIRED TO BE REMOVED, RESTORE EXPOSED FINISHES OF CUT AND PATCHED AREAS AND EXTEND FINISH RESTORATION INTO ADJOINING CONSTRUCTION IN A MANNER THAT WILL ELIMINATE EVIDENCE OF PATCHING AND REFINISHING. CUT EXISTING CONSTRUCTION USING METHODS LEAST LIKELY TO DAMAGE ELEMENTS TO BE RETAINED OR ADJOINING CONSTRUCTION. WHERE INDICATED TO REMOVE FINISHES, REMOVE SO TOTALLY, FROM PLANE TO PLANE, TREAT REMAINING SUBSURFACE TO
RECEIVE NEW FINISHES DESIGNATED.
7. WHERE EXISTING CONSTRUCTION, EQUIPMENT, ETC. SHOWN TO BE RELOCATED SHALL BE COORDINATED BY THE CONTRACTOR WITH THE VA PRIOR TO START OF WORK IN EACH AREA. THE VA WILL REMOVE ALL ITEMS OF SALVAGEABLE VALUE, INCLUDING BUT NOT LIMITED TO DOORS, HARDWARE, MOVEABLE EQUIPMENT NOT ALREADY DESIGNATED FOR REINSTALLATION/REUSE, PRIOR TO CONTRACTOR COMMENCING WORK.
8. WHERE EXISTING PARTITIONS HAVE BEEN REMOVED OR NEW SERVICES PENETRATE EXISTING SURFACES, THE OPENINGS SHALL BE PATCHED
TO MATCH THE EXISTING ADJACENT SURFACES FINISH, TEXTURE AND SHEEN.
9. WHERE EXISTING PARTITIONS HAVE BEEN REMOVED OR NEW SERVICES PENETRATE EXISTING SURFACES, THE OPENING SHALL BE PATCHED
TO MATCH THE EXISTING ADJACENT SURFACES FINISH, TEXTURE AND SHEEN.
10. IN GENERAL, WHEREVER SERVICES ARE REMOVED, THE OPENINGS SHALL BE PATCHED TO MATCH THE EXISTING ADJACENT SURFACES FINISH TEXTURE AND SHEEN. WHERE REMOVAL OF EXISTING CONSTRUCTION, PIPING, DUCTWORK AND OTHER ITEMS CREATES OPENINGS IN THE WALLS, FLOORS OR CEILINGS, PATCH OPENINGS IMMEDIATELY WITH THE SAME MATERIALS AS ADJACENT CONSTRUCTION. MAINTAIN THE REQUIRED FIRE RATING. SEE MEP DRAWINGS FOR ADDITIONAL INFORMATION. FILL IN ALL EXISTING OPENINGS THAT ARE NOT TO REMAIN, UNLESS OTHERWISE NOTED. FINISH TO MATCH FINISH OF ADJACENT SURFACE.
11. WHERE CODED NOTE DESIGNATIONS ARE SHOWN AS "TYP" OR "TYPICAL" IT IS INTENDED THAT THE NOTE GENERALLY REFERS TO ALL SIMILAR
ITEMS OR SURFACES.
12. A HAZARDOUS MATERIALS SURVEY WAS NOT CONDUCTED BY THE ARCHITECT OF RECORD. A HAZARDOUS MATERIALS SURVEY WAS SUPPLIED BY THE VA. THE RESULTS OF THE SAMPLES TAKEN ARE INCLUDED WITHIN THE CONSTRUCTION DOCUMENTS. IT IS THE CONTRACTORS RESPONSIBILITY TO TAKE PROTECTIVE MEASURES FOR ITS WORKERS PRIOR TO THE BEGINNING OF ANY RENOVATION OR DEMOLITION WORK.
13. AFTER COMPLETION OF DEMOLITION, SCHEDULE A WALK-THROUGH WITH THE COR AND ARCHITECT FOR REVIEW OF EXISTING CONDITIONS.
14. PATCH AND FIRE STOP EXISTING ABANDONED PENETRATIONS THROUGH THE CONCRETE FLOORS AND WALLS.
1. ALL DIMENSIONS OF NEW PARTITIONS/BARRIERS SHALL BE TAKEN TO FACE OF STUD. DIMENSIONS TO EXISTING WORK SHALL BE
TAKEN TO FACE OF FINISH SURFACE.
2. DO NOT SCALE DRAWINGS. DRAWINGS ARE CONCEPTUAL PLANS.
3. THE WORK OF THE CONTRACTOR SHALL INCLUDE ALL LABOR AND MATERIALS FOR ALL TRADES CONCERNED FOR COMPLETING
THE PROJECT IN ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS.
4. THE CONTRACTOR SHALL PROCURE, COMPLETE AND APPLY FOR ALL PERMITS AS REQUIRED TO CONSTRUCT THE PROJECT.
5. THE CONTRACTOR SHALL BE FAMILIAR WITH THE CONTRACT DOCUMENTS AND MUST VISIT THE SITE AND BE ACQUAINTED WITH
THE CONDITIONS AFFECTING THE WORK.
6. WORKMANSHIP. ALL WORK TO BE FIRST RATE, HIGH QUALITY, AND ACCOMPLISHED IN A WORKMANLIKE MANNER BY SKILLED CRAFTSMEN USING ACCEPTED PRACTICES AND METHODS APPROPRIATE TO THE TRADE INVOLVED.
7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DAILY CLEANING UP OF THE WORK AREA. THE AREA SHALL BE CLEANED EACH DAY AND TRASH SHALL BE DISPOSED OF AT THE END OF EACH DAY. AT THE END OF THE PROJECT, THE CONTRACTOR
SHALL CLEAN THE WORK AREA THOROUGHLY.
8. ALL WORK SHALL BE GUARANTEED FOR ONE YEAR FROM THE TIME OF ACCEPTANCE BY THE OWNER UNLESS OTHERWISE
NOTED IN THE SPECIFICATIONS.
9. ALL PLUMBING WORK SHALL CONFORM TO THE ADOPTED EDITION OF THE INTERNATIONAL PLUMBING CODE. INSTALL ALL WATER, WASTE AND VENT PIPING IN ACCORDANCE WITH ALL APPLICABLE CODES. REVIEW DRAWINGS AND PROVIDE ALL WORK FOR A COMPLETE AND OPERABLE SYSTEM, INCLUDING ALL INCIDENTALS, REQUIRED BY CODE AGENCIES AND LOCAL GOVERNING
BODIES.
10. PRIOR TO START OF CONSTRUCTION, CONTRACTOR SHALL VERIFY ALL BUILDING CONDITIONS, COORDINATE ALL DIMENSIONS IN
FIELD AND VERIFY ALL LOCATIONS OF UTILITIES IN THE FIELD.
11. ALL HEATING, VENTILATING AND AIR CONDITIONING WORK SHALL CONFORM TO THE ADOPTED EDITION OF THE INTERNATIONAL
MECHANICAL CODE.
12. THE COMPLETE MECHANICAL AND HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SYSTEM AND INSTALLATION SHALL COMPLY AND CONFORM TO ALL 2018 INTERNATIONAL MECHANICAL AND ENERGY CONSERVATION CODES, AND 2018 FACILITIES GUIDELINE INSTITUTE (AS APPLICABLE), STATE CODES, AND ANY REQUIREMENTS OF THE LOCAL AUTHORITIES HAVING
JURISDICTION.
13. THE COMPLETE ELECTRICAL SYSTEM AND INSTALLATION SHALL COMPLY AND CONFORM TO ALL ADOPTED CODES, REGULATIONS OF THE NATIONAL ELECTRICAL CODE AS WELL AS TO ALL STATE AND LOCAL LAWS, ORDINANCES AND CODES.
SOAP & PAPER TOWEL
DISPENSER COUNTER
HAND
SANITIZER
WALL PHONE COAT HOOK ON
DOOR
NOTES:
THE DIMENSIONS SHOWN ARE FOR TYPICAL MOUNTING HEIGHTS.
SEE ELEVATIONS FOR MOUNTING HEIGHT FOR INFREQUENTLY USED ITEMS.
SEE ELEVATIONS FOR ATYPICAL MOUNTING HEIGHTS.
4"
EQ EQ
ELECTRONIC DOOR
CONTROL DEVICE
8"
DS
NC
LIGHT SWITCHES, NURSE
ASSIST, DUTY STATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
ACELA
C
U se rs \a k a n u sk y \D o c u m e n ts
\5 -1
-1
P ro s th e ti cs
L a b V
A R
C
M
-0
-2 a k a n u s k yV
B N
S Y
.r v t
/1
/2
:3 :2
P
M
GI102
GENERAL INFORMATION, SYMBOLS & GENERAL NOTES
6/18/2021 JLH
VA NEW JERSEY HEALTH CARE SYSTEM - EAST ORANGE CAMPUS
561-19-160UPGRADE PROSTHETICS LABFINAL BID DOCUMENTS
ARCHITECTURAL SYMBOLS ARCHITECTURAL ABREVIATIONS MATERIAL LEGEND GENERAL NOTES - GENERAL CONDITIONS
GENERAL NOTES - CONSTRUCTION NOTES
STANDARD MOUNTING HEIGHTS
Revisions: Date: Page 2 of 43
515 SF
LABORATORY
289 SF
MECHANICAL ROOM
677 SF
OPEN OFFICE 115 SF
OFFICE
111 SF
OFFICE
158 SF
OFFICE
64 SF
TOILET
41 SF
STORAGE
E
57 SF
ELEC.
E90
E90
E90
E90
E90
E90
E90
E90 E90
E90 E90
E90
E90
E90
E90
E60
E60
E
E90
60 60
EXIT A
STAIR A
EXIT B
STAIR
.3"/OCC
CODE MIN:
PROVIDED:
(E)
(52)
32"
46"
16"
CORRIDOR
.2"/OCC
CODE MIN:
PROVIDED:
44"
72"
12"
DOOR
.2"/OCC
CODE MIN:
PROVIDED:
(E)
32"
72"
12"
C R
S T
A
IR
A
6'
C
R E
X
IT
B
2'
LA
B
E X
IT
A
5'
EXIT B = 87'
PLAN NOTES:
1. SEE ELECTRICAL PLANS FOR EMERGENCY LIGHTS, SMOKE
DETECTORS, EXIT SIGNS, ETC...
1088 SF
STORAGE
175 SF
EXAM
90 SF
SHOE FITTING
259 SF
EXAM
127 SF
RECEPTION
157 SF
W/C REPAIR
WALL
MOUNTED
FE
NOT FOR WHEELCHAIR
ACCESS/ EXIT
A E
E
E
GENERAL NOTES
A. PARTITIONS SHALL BE TYPE A1 UNLESS NOTED OTHERWISE.
B. REFER TO SPECIFICATIONS AND PARTITION TYPE SCHEDULE FOR ADDITIONAL NOTES.
C. NEW PARTITIONS ARE DIMENSIONED TO FACE OF METAL STUD OR MASONRY UNLESS NOTED OTHERWISE.
D. EXISTING PARTITIONS ARE DIMENSIONED TO FINISH FACE UNLESS NOTED OTHERWISE.
E. REFER TO ELECTRICAL DRAWINGS FOR EXIT LIGHT LOCATIONS.
FIRE RATING LEGEND
SYMBOL
(NUMBER SHOWS OPENING RATING) BARRIER OPENING RATING
60 MIN.ONE HOUR
EXISTING
SMOKE BARRIER
EXISTING
NOTE: FOR SCHEDULED OPENINGS WHERE SMOKE AND FIRE SEPARATIONS COINCIDE,THE MORE
STRINGENT FIRE RATING SHALL APPLY. REFER TO THE PARTITION SCHEDULE FOR FIRE RESISTIVE
REFERENCES.
FIRE EXTINGUISHER IN RECESSED CABINET UNLESS OTHERWISE NOTED
60 60 60
E60 E60 E60
E90 E90 E90
HAZARDOUS AREA
EXIT SIGNAGE W/ DIRECTIONAL ARROWS- REFER TO ELECTRICAL PLANS
FOR MORE INFORMATION
LIFE SAFETY ANALYSIS
PROJECT OVERVIEW:
RENOVATE _______
APPLICABLE CODES:
• NFPA 13-2019 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS
• NFPA 14-2019 STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOUSE SYSTEMS
• NFPA 24-2019 STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES
• NFPA 72-2019 NATIONAL FIRE ALARM CODE
• NFPA 90A-2018 STANDARD FOR HEALTH CARE FACILITIES
• NFPA 99-2018 STANDARD FOR HEALTH CARE FACILITIES
• NFPA 101-2021 LIFE SAFETY CODE
• NFPA 220-2018 STANDARD ON TYPES OF BUILDING CONSTRUCTION
• NFPA 291-2019 RECOMMENDED PRACTICE FOR FIRE FLOW TESTING AND MARKING OF HYDRANTS
• NFPA 1963-2009 STANDARD FOR FIRE HOSE CONNECTIONS
• VA DESIGN GUIDE AND TECHNICAL GUIDE
• VA FIRE PROTECTION DESIGN MANUAL - DECEMBER 2015
• UNIFORM FEDERAL ACCESSIBILITY STANDARDS WITH VA BARRIER FREE DESIGN GUIDE (PG 18-13)
BUILDING USE CLASSIFICATION:
HEALTH CARE
EXISTING HEALTH CARE OCCUPANCY (NFPA 101 - CHAPTER 18)
BUILDING CONSTRUCTION:
BUILDING STRUCTURE: STEEL COLUMNS/BEAMS, ENCASED IN CONCRETE, CONCRETE SLABS
NUMBER OF STORIES _____
CONSTRUCTION TYPE: TYPE II (222) NFPA-101
SPRINKLER: FULLY SPRINKLERED IN ACCORDANCE WITH NFPA13- INSTALLATION OF SPRINKLER SYSTEMS
FIRE EXTINGUISHERS: PROVIDE IN ACCORDANCE WITH NFPA-10-PORTABLE FIRE EXTINGUISHERS WITH
TRAVEL DISTANCE OF 75 FT.
MAX. ALLOWABLE NUMBER OF STORIES (ABOVE GRADE):
EXISTING
MAX. ALLOWABLE AREAS:
LIFE SAFETY CODE: UNLIMITED
BUILDING COMPONENTS NFPA 220 2012
NFPA 101 2018
PROJECT SQUARE FOOTAGE
AREA A (PATIENT AREA) 2,422 SF
AREA B (ADMINISTRATION AREA) 2,273 SF
RATED CONSTRUCTION FIRE RATING (IN HOURS)
EXTERIOR WALLS -
LOAD BEARING 2
NON-LOAD BEARING 0
INTERIOR BEARING WALLS 2
RATED CONSTRUCTION FIRE RATING (IN HOURS)
EXIT, EXIT HALLWAY STAIRWAY ENCLOSURE 2 (4 OR MORE STORIES)
MECHANICAL SHAFTS, ELEVATOR HOIST WAYS 2 (4 OR MORE)
EXIT ACCESS CORRIDORS 0 (SMOKE TIGHT)
HORIZONTAL EXITS NA
MIN. # OF EXITS/FLOOR (<500 OCC. LOAD) 2
(> 500-1000) 3
SMOKE BARRIERS 1
COLUMNS 2
COLUMNS (ROOF ONLY) 1
BEAMS 1
BEAMS (ROOF ONLY) 1
FLOOR CONSTRUCTION (INCLUDING BEAMS) 2
ROOF CONSTRUCTION -
SOILED LINEN ROOMS 1 HR
STORAGE ROOMS MORE THAN 100 SF 1 HR
TRAVEL DISTANCE (FT)
• FROM ANY POINT TO EXIT (WITH AUTO FIRE SUPP. SYS.) 200 FEET
• MAX. DEAD END LENGTH REQUIRED (SPRINKLERED BLDG) 30 FEET (18.2.5.2)
• COMMON PATH OF TRAVEL 100 FEET (18.2.5.3)
REQUIRED EGRESS WIDTH:
DOORWAYS 34" MIN.
STAIR DOORS 36" WIDE
STAIRS 44"
CORRIDOR WIDTH 44"
OPENING PROTECTIVES IN RATED CONSTRUCTION
DOORS IN OTHER 1 HR RATED CONSTRUCTION 3/4 HR, "C" LABEL
DOORS IN 2 HR RATED CONST. (SELF CLOSING) 1 1/2 HR, "B" LABEL
DOORS IN SMOKE BARRIER PARTITIONS (SELF CLOSING) 3/4 HR
SMOKE COMPARTMENT
• MINIMUM OF TWO PER FLOOR 18.3.7.1 (2)
• MAXIMUM OF 40,000 SF PER SMOKE COMPARTMENT 18.3.7.1 (4)
• TRAVEL DISTANCE FROM ANY POINT TO REACH A DOOR: 200 FEET 18.3.7.1 (5)
TRAVEL DISTANCE LIMITS
OCCUPANCY DISTANCE
COMMON PATH OF TRAVEL (2018 NFPA 39.2.5.3) 100'
DEAD END (2018 NFPA 39.2.5.2) 20'
TRAVEL DISTANCE LIMIT (2018 NFPA 39.2.6.3) 300'
* TRAVEL DISTANCES ARE FOR SPRINKLERED BUILDINGS
B
B
B
EXIT CAPACITIES LEGEND
DOORS
DOOR
.2"/OCC
CODE MIN:
PROVIDED:
32"
WIDTH PER OCCUPANT (NFPA T 7.3.3.1)
OCCUPANTS (AREA/OCC. LOAD FACTOR)
MIN WIDTH (0.2" X OCC.)
CODE MIN (18 IBC 1010.1.1)
CLEARANCE PROVIDED
CLEARANCE SHOWN W/ DOOR OPEN 90° BETWEEN STOP & OPEN DOOR FACE
CORRIDORS
WIDTH PER OCCUPANT (NFPA T 7.3.3.1)
OCCUPANTS (AREA/OCC. LOAD FACTOR)
MIN WIDTH (0.2" X OCC.)
CODE MIN (2018 NFPA 39.2.3.2)
CLEARANCE PROVIDED
CLEARANCE SHOWN BETWEEN FACE OF WALLS
STAIRS
WIDTH PER OCCUPANT (NFPA T 7.3.3.1)
OCCUPANTS (AREA/OCC. LOAD FACTOR)
MIN WIDTH (0.3" X OCC.)
CODE MIN (18 IBC 1010.1.1)
CLEARANCE PROVIDED
* 2018 NFPA TABLE 7.2.2.2.1.1(b) EXISTING STAIRS
CORRIDOR
.2"/OCC
CODE MIN:
PROVIDED:
44"
STAIR
.3"/OCC
CODE MIN:
PROVIDED:
36" *
(2018 NFPA 101, TABLE 7.3.1.2 OCCUPANT LOAD FACTOR)
OCCUPANT LOAD FACTORS
SPACE FUNCTION SF/OCC
ASSEMBLY 15 NET
BUSINESS 150 GROSS
EXERCISE 50 GROSS
STORAGE 500 GROSS
ADMIN SUPPORT
SUITE
1,885 SF
CLINIC SUITE
2,454 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
ACELA
C
U se rs \a k a n u sk y \D o c u m e n ts
\5 -1
-1
P ro s th e ti cs
L a b V
A R
C
M
-0
-2 a k a n u s k yV
B N
S Y
.r v t
/1
/2
:3 :2
P
M
GI201
LIFE SAFETY PLAN
6/18/2021 JLH
VA NEW JERSEY HEALTH CARE SYSTEM - EAST ORANGE CAMPUS
561-19-160UPGRADE PROSTHETICS LABFINAL BID DOCUMENTS
1/16" = 1'-0"1
LEVEL A - LIFE SAFETY PLAN SQUARE FOOTAGE PLAN
Revisions: Date: Page 3 of 43
UP
GENERAL AREA OF
WORK
N
PROJECT
NORTH
A
B
C
P Q R S
RECEPTION
A-103K
CONTRACTOR ENTRANCE: EXISTING LOCK TO
RECEIVE NEW CORE DURING DEMOLITION &
CONSTRUCTION. SHOP & UTILITY
OPERATORS TO RECEIVE KEYS AS REQUIRED
ICRA
ANTEROOM
T1
T1
CONSTRUCTION
STICKY WALK-OFF MAT
1 11
S G
1 11
S G
H W
-0
H W
-0
OFFICE
TELEPHONE
SWITCH
A-101A
ORTHOTIC LAB
A-103D
ORTHOTIC LAB
A-103E
ORTHOTIC
STORAGE
A-103F
RECEPTION
A-103C
TOILET
A-103B
MAIN
WASTE
A-103G
MECH. RM.
A-103J
PROSTHETIC
FITTING ROOM
A-103 ELECTRIC
A-E-102
ELEC.
CLOSET
A-E-102D
STAIR
A-S7
TELEPHONE OPERATOR
SUITE
A-102C
TOILET
A-102D
CHIEF
PROSTHETICS
PROS.
A-102E
ASST.
CHIEF
A-102B
ORTHOTIC
FITTING ROOM
A-103A
CORRIDOR
A-114
PROS.
SVC
A-102E
PROS.
SVC
A-102F
PROS.
SVC
A-102G
PSAS SERVICE
A-102
MECH.
A-102H
TELEPHONE
EQUIPMENT
A-101C
VESTIBULE
A-101BMEN'S TOILET
A-103B
CLOSET
TELEPHONE OPERATOR
SUITE
A-102D
PROSTHETIC &
ORTHOTIC LAB
A-103C
PROSTHETIC &
ORTHOTIC LAB
A-103C
CONSTRUCTION
STICKY WALK-OFF
MAT
EXISTING DOOR TO RECEIVE NEW
STOREROOM LOCKSET WITH
KEYPAD LOCK DURING
CONSTRUCTION. DOOR TO
RECEIVE SIGNAGE STATING 'NO
ACCESS' DURING DEMOLITION &
CONSTRUCTION. SHOP & UTILITY
OPERATORS TO RECEIVE KEYPAD
CODE AS REQUIRED
CONSTRUCTION
STICKY WALK-OFF
MAT
T2
T3
T3
SIM
SIM
SECTION
PLAN
/8
3 5/8" METAL STUDS @ 16" O.C., TYP
5/8" GYPSUM BOARD, BOTH SIDES, SEE
ROOM FINISH SCHEDULE FOR FINISHES
CONTINUOUS METAL STUD TOP TRACK. PROVIDE
DEFLECTION TRACK AT ROOF
CONTINUOUS METAL STUD BOTTOM TRACK
LINE OF EXISTING FLOOR
CONTINUOUS 3 1/2" SOUND ATTENUATION
BATTS, TYP
CONTINUOUS METAL HORIZONTAL BRIDGING
CHANNEL @ MID HEIGHT, TYP
FIRE-RATED SEALANT, BOTH SIDES
3 5/8" METAL STUDS @ 16" O.C., 25-GAGE, TYPICAL
5/8" TYPE "X" GYPSUM BOARD, BOTH SIDES
WITH STAGGERED UNFINISHED TAPED
JOINTS ON OPPOSITE SIDES OF ROOM.
PAINT WALL ON PUBLIC SIDE.
TEMPORARY CONSTRUCTION FIRE BARRIER
EXISTING UNDERSIDE OF DECK
T1
1 HOUR RATED
FIRE-RATED SEALANT, BOTH SIDES
ICRA CLASS II PROJECT
PRECAUTIONS DURING CONSTRUCTION
1. EXECUTE WORK BY METHODS TO MINIMIZE RAISING DUST FROM CONSTRUCTION OPERATIONS
2. IMMEDIATELY REPLACE A CEILING TILE DISPLACED FOR VISUAL INSPECTION
3. PROVIDE ACTIVE MEANS TO PREVENT AIRBORNE DUST FROM DISPERSING INTO ATMOSPHERE
4. WATER MIST WORK SURFACES TO CONTROL DUST WHILE CUTTING DRY WALL FOR BARRIERS
5. SEAL UNUSED DOORS WITH DUCT TAPE IN THE CONSTRUCTION AREA
6. BLOCK OFF AND SEAL AIR VENTS IN THE CONSTRUCTION AREA
7. PLACE DUST MAT AT ENTRANCE AND EXIT OF WORK AREA
8. REMOVE OR ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT
CONTAMINATION OF DUCT SYSTEM
9. REMOVE CONSTRUCTION WASTE DAILY
10. PROVIDE TEMPORARY 1 HR. FIRE BARRIER PARTITIONS AS INDICATED AND SEAL UNUSED DOORS AT PERIMETER OF THE WORK AREA WITH PAINTER'S TAPE TO SEAL AREA FROM NON-WORK AREA BEFORE
CONSTRUCTION BEGINS
11. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA FILTER EQUIPPED AIR FILTRATION UNITS. COORDINATE LOCATION OF WINDOW AND ABOVE FLOOR PENETRATIONS WITH COR.
SPACE SHALL BE CONTINUOUSLY MONITORED. BALL IN THE WALL IS NOT ACCEPTABLE. PATCH FLOOR
PENETRATION AND REPLACE WINDOW GLAZING AFTER CONSTRUCTION AS REQUIRED TO MATCH
EXISTING.
12. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS OR BY COVERING IN PLASTIC AND SEALING WITH DUCT TAPE. REMOVE WASTE DAILY EITHER AFTER 5 PM AND
BEFORE 7 AM
13. USE ROUTE AGREED UPON BY THE ICRA TEAM AND COR FOR TRANSPORT OF CONTAINERS THROUGH
THE FACILITY
14. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES AIRTIGHT AND/OR FIRE SEAL AS REQUIRED
15. CONSTRUCT AN AIRTIGHT ONE-HOUR RATED ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH THIS ROOM SO THEY CAN BE VACUUMED USING HEPA VACUUM CLEANER BEFORE LEAVING WORK SITE; OR WEAR PAPER COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE THE WORK SITE
16. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR SHOE COVERS. SHOE COVERS MUST
BE CHANGED EACH TIME THE WORKER EXITS THE WORK AREA THROUGH THE ANTEROOM
17. WORK OUTSIDE THE PRIMARY WORK AREA (AREA OF CONTAINMENT) WILL BE PERFORMED WITHIN A FIRE-RATED PLASTIC ENCLOSURE WITH NEGATIVE AIR HEPA FILTER SYSTEM TO CONTROL DUST.
ENCLOSURE TO BE CONSTRUCTED AND REMOVED DAILY AS REQUIRED BY THE COR. CONTRACTOR TO
SANITIZE WORK AREA PRIOR TO REMOVING PLASTIC CONTAINMENT AREA
GLAZING PANEL
REMOVAL
EXISTING WALL CONSTRUCTION TO REMAIN
EXISTING GLAZING PANEL TO BE REMOVED FROM
EXISTING WINDOW SYSTEM PRIOR TO START OF
ABATEMENT. GC TO STORE GLAZING PANEL IN A
SAFE LOCATION UNTIL WORK IS COMPLETE AND
REPLACE TO IT'S EXISTING CONDITION. IF
DAMAGED, GC WILL REPLACE TO MATCH EXISTING
EXISTING ALUMINUM FRAME TO REMAIN
HEPA EXHAUST
EXISTING WALL CONSTRUCTION TO REMAIN
PROVIDE HEPA FILTRATION EXHAUST DUCTING
THROUGH NEW TEMPORARY PLYWOOD PANEL
EXISTING ALUMINUM FRAME TO REMAIN
PROVIDE 3/4" FIRE TREATED PLYWOOD PANEL
WITHIN EXISTING ALUMINUM FRAME
NOTE:
1. GENERAL CONTRACTOR TO LOCATE PER
QUANTITIES REQUIRED.
PROVIDE DUCT SEALING TAPE AROUND
PENETRATION (TYPICAL)
EXTERIORINTERIOR EXTERIOR
INTERIOR
(NEGATIVE SPACE)
ACCESS ZIPPER
LINE OF FINISHED FLOOR, SEE ROOM FINISH
SCHEDULE FOR FLOOR & BASE TYPE
CONTINUOUSLY SEAL FIRE RETARDANT POLYSTYRENE
TO EXISTING FINISHED FLOOR.
6-MIL FIRE RETARDANT POLYSTYRENE, SEE
SPECIFICATIONS. PROVIDE ZIPPER ACCESS WHERE
REQUIRED
EXISTING UNDERSIDE OF DECK
T2
FIRE RETARDANT DUST CONTROL BARRIER
CONTINUOUSLY SECURE AND SEAL EDGE OF FIRE
RETARDANT POLYSTYRENE TO UNDERSIDE OF
DECK
EXISTING FINISHED CEILING SYSTEM. REMOVE AND
REINSTALL CEILING PANELS AS REQUIRED
CONTINUOUSLY SECURE FIRE RETARDANT
POLYSTYRENE SHEET TO UNDERSIDE OF METAL
CEILING TRACK AND ABOVE METAL CEILING TRACK
SECURE AND SEAL ALL SIDES OF
EXISTING DUCTS, CONDUIT, PIPES, ETC.
6-MIL FIRE RETARDANT
POLYSTYRENE
CONTINUOUSLY SECURE EDGE OF FIRE
RETARDANT POLYSTYRENE TO
EXISTING HOLLOW METAL FRAME
EXISTING HOLLOW METAL
FRAME
EXISTING DOOR SYSTEM
BEYOND
CONTINUOUSLY SECURE/SEAL FIRE RETARDANT
POLYSTYRENE TO EXISTING WALL. TYPICAL ALL WALLS AS
REQUIRED. PATCH/REPAIR EXISTING WALLS AS REQUIRED
TO MATCH EXISTING PRIOR TO CONSTRUCTION
T3
FIRE RETARDANT DUST CONTROL
DETAIL AT DOOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
ACELA
C
U s e rs
\a k a n u s k y \D o c u m e n ts
\5 -1
-1
P ro s th e ti c s L a b V
A R
C
M
-0
-2 a k a n u s k y V
B N
S Y
.r v t
/1
/2
:3 :5
P
M
GI301
ICRA PLAN, DETAILS & NOTES
6/18/2021 JLH
VA NEW JERSEY HEALTH CARE SYSTEM - EAST ORANGE CAMPUS
561-19-160UPGRADE PROSTHETICS LABFINAL BID DOCUMENTS
A LEVEL KEY PLAN1/8" = 1'-0"1
ICRA PLAN
ICRA CONTROL POLICY
NOTE:
CONTRACTOR TO MAINTAIN NEGATIVE AIR
PRESSURE THROUGH-OUT THE DURATION
OF DEMOLITION & NEW WORK.
1" = 1'-0"A
TYPICAL HEPA FILTRATION THROUGH WINDOW DETAIL
Revisions: Date: Page 4 of 43