S02 550-22-101 Bid Drawings.pdf

PDF 13 MB Posted

Attached to
Z1DA--550-22-101: Repair Building Exteriors (B58-B60-B98)
Solicitation number
36C25223B0001
Issued by

About this file

This document provides details on a federal contract opportunity for repair work on several buildings. The solicitation number is 36C25223B0001 and concerns project 550-22-101 to repair building exteriors B58-B60-B98. The opportunity type is a solicitation issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12. The scope of work involves repairs to the exteriors of three buildings numbered B58-B60-B98. No other salient details are provided such as response dates, pricing terms, or set asides. An accompanying file references bid drawings but does not include the drawings or specify their content.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONTRACT OFFICER REPRESENTATIVE DATE

CHIEF OF ENGINEERING DATE

INTERIOR DESIGNER DATE

DEPARTMENT HEAD DATE

CONTRACT SPECIALIST DATE LEAD USER SIGNATURE DATE

GENERAL

GI1 EXISTING SURFACE OF WALL STAINED. SOURCE OF STAINING TO BE INVESTIGATED AND

ELIMINATED.

GI2 VEGETATION HAS OVERGROWN AT BASE OF BUILDING. CAUSING STAINING AND OR DAMAGE

TO EXTERIOR SURFACES.

GI3 RODENT OR BIRD SIGN. DEBRIS TO BE REMOVED.

BRICK

Bc1 SURFACE OF BRICK STAINED CHALKY SURFACE, EFFLORESCENCE Bc2 SURFACE OF BRICK STAINED DARK Bc3 SURFACE OF BRICK COVERED WITH ORGANIC MATTER, MUD AND OR OTHER Bc4 SURFACE OF BRICK COVERED WITH ORGANIC MATTER, MUD AND OR OTHER Bc5 MORTAR JOINT ORGANIC MATTER OR VEGETATION COVERING OR GROWING IN MORTAR BED.

Bc6 SURFACE HAS ORGANIC MATTER OR VEGETATION GROWING ON SURFACE.

Bc7 MORTAR JOINT STAINED DARK.

Bc8 MASONRY SURFACE HAS A DEVELOPED CRUST OVER THE SURFACE.

BR1 BRICK SURFACE DAMAGED, TO BE REPAIRED.

CONCRETE

Cc1 EXISTING CONCRETE STAINED. SOURCE UNKNOWN TO BE DETERMINED.

Cc2 EXISTING CONCRETE WITH ORGANIC MATTER GROWING ON CONCRETE.

CR1 EXISTING CONCRETE DAMAGED TO BE REPAIRED.

Cr1 EXISTING CONCRETE DAMAGED TO BE REPLACED.

GLAZING

Gc1 GLAZING TO BE CLEANED.

GR1 EXISTING GLAZING LOOSE IN SETTING.

GR2 GLAZING SETTING MATERIAL (PUTTY) BROKEN.

Gr1 EXISTING GLAZING BROKEN.

Gr2 EXISTING GLAZING SEAL APPEARS TO BE COMPROMISED.

DOOR

Dc1 EXISTING DOOR STAINED AND OR DISCOLOURED, SOURCE TO BE DETERMINED AND REPAIRED.

TO BE CLEANED.

Dc2 EXISTING DOOR ORGANIC MATTER GROWING ON DOOR. TO BE CLEANED. NO INTERFERENCE

WITH FUNCTION.

DR1 EXISTING DOOR NOT SEATED PROPERLY IN FRAME. TO BE RESET.

DR2 EXISTING DOOR FINISH DAMAGED. DOOR FINISH TO BE REPAIRED.

DR3 EXISTING DOOR MATERIAL DAMAGED. DOOR TO BE REPAIRED.

DR4 EXISTING DOOR FRAME AND OR SURROUND FINISH DAMAGED. FINISH TO BE REPAIRED.

DR5 EXISTING DOOR GLAZING DAMAGED. DOOR GLAZING TO BE REPAIRED.

Dr1 EXISTING DOOR DAMAGED BEYOND REPAIR. ENTIRE DOOR TO BE REPLACED.

METAL

Mc2 EXISTING METAL LOUVER SOILED OR STAINED TO BE CLEANED.

Mc3 EXISTING METAL PIECE SOILED OR STAINED TO BE CLEANED.

MI1 EXISTING WROUGHT IRON PIECE SOILED OR STAINED TO BE CLEANED.

MR1 EXISTING METAL FLASHING DAMAGED TO BE REPAIRED.

MR2 EXISTING METAL LOUVER DAMAGED TO BE REPAIRED.

MR3 EXISTING METAL PIECE DAMAGED TO BE REPAIRED.

MIR1 EXISTING WROUGHT IRON PIECE DAMAGED TO BE REPAIRED.

MIR2 EXISTING WROUGHT IRON PIECE RUSTED, RUST TO BE REMOVED AND WORK TO BE

REPAINTED.

Mr1 EXISTING METAL FLASHING DAMAGED TO BE REPLACED.

Mr2 EXISTING METAL LOUVER DAMAGED TO BE REPLACED.

Mr3 EXISTING METAL PIECE DAMAGED TO BE REPLACED.

MIr1 EXISTING WROUGHT IRON PIECE DAMAGED TO BE REPLACED. EXISTING METAL FLASHING

SOILED OR STAINED TO BE CLEANED.

PAINT

Pc1 EXISTING PAINT TO BE CLEANED AND PROTECTED.

Pc2 EXISTING PAINT TO BE CLEANED AND PROTECTED.

PR1 EXISTING PAINT DETERIORATED, PAINT TO BE REMOVED AND REPAIRED.

PR2 EXISTING PAINT CRACKED AND OR FLAKING. PAINT TO BE SANDED SMOOTH AND AREA TO BE

REPAINTED.

Pr1 EXISTING PAINT IN THIS AREA TO BE REPLACED. EXISTING PAINT TO BE COMPLETELY

REMOVED AND AREA TO BE REPAINTED.

Pr2 EXISTING PAINT IN THIS AREA TO BE REPLACED. EXISTING PAINT TO BE COMPLETELY

EXISTING AREA BENEATH TO BE INSPECTED AND OR REPAIRED AND AREA BENEATH TO BE

REPAINTED.

Pr3 EXISTING METAL SURFACE PAINT FLAKING AND RUST PRESENT.

STONE

Sc1 EXISTING STONE WORK TO BE CLEANED.

Sc2 EXISTING STONE TO HAVE PAINT REMOVED.

SR1 EXISTING STONE TO BE REPAIRED.

SR2 EXISTING STONE WORK TO BE REPAIRED.

Sr1 EXISTING STONE WORK TO BE REPLACED.

Sr2 EXISTING STONE WORK TO BE REPLACED.

WINDOW

Wc1 EXISTING WINDOW STAINED TO BE CLEANED.

Wc2 EXISTING WINDOW GLAZING STAINED AND OR DIRTY TO BE CLEANED.

Wc3 EXISTING WINDOW FRAME AND OR TRIM STAINED TO BE CLEANED.

Wc4 EXISTING WINDOW SILL STAINED TO BE CLEANED.

WR1 EXISTING WINDOW DAMAGED TO BE REPAIRED.

WR2 EXISTING WINDOW GLAZING DAMAGED TO BE REPAIRED.

WR3 EXISTING WINDOW FRAME AND OR TRIM DAMAGED TO BE REPAIRED,

WR4 EXISTING WINDOW SILL DAMAGED TO BE REPAIRED.

Wr1 EXISTING WINDOW DAMAGED TO BE REPLACED.

Wr2 EXISTING WINDOW GLAZING DAMAGED TO BE REPLACED.

Wr3 EXISTING WINDOW FRAME AND OR TRIM DAMAGED TO BE REPLACED, Wr4 EXISTING WINDOW SILL STAINED TO BE REPLACED.

WOODWORK

WWc1 WOODWORK STAINED, SOURCE UNKNOWN TO BE INVESTIGATED AND ELIMINATED.

WOODWORK TO BE CLEANED AND PRESERVED.

WWc2 WOODWORK FINISH FLAKING AND IN DISREPAIR. FINISH TO BE CLEANED AND RESTORED.

WWR1 WOODWORK DETERIORATED FINISH TO BE CLEANED AND RESTORED WOOD TO BE STABILIZED

AND RESTORED IN PLACE.

WWR2 EXISTING WOOD ROTTED, AREA OF ROT TO BE REMOVED AND WOOD TO BE RESTORED AND

REPLACED.

WWr1 WOODWORK DETERIORATED BEYOND REPAIR. AREA OF DETERIORATION TO BE REMOVED

AND REPLACED WITH NEW.

WWr2 EXISTING WOOD ROTTED, TOTAL PIECE OF WOOD TO BE REMOVED, REPLICATED, AND

RETURNED WITH NEW PIECE.

ARCHITECTURAL ABBREVIATIONS/ TAG INDEX

'B' BRICK

'D' DOOR

'M' METAL

'P' PAINT

'S' STEEL

'St' STONE

'W' WOOD

'Ww' WINDOW 'c' CLEAN

'R' REPAIR

'r' REPLACE

ABBREVIATION/ TAG LEGEND

B#-X-X#-XX#BUILDING NUMBER

ELEVATION FACE GRID COLUMN AND ROW

NOTE TAG

GRID TAG KEY

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

NOT F

OR

CONSTRUCTIO

N

C U s e rs \l s to y \D o c u m e n ts

\1

.5

.0

A -M

A S

S

IN

G v ls to y K

A T

J U

.r v t

/6

/2

:1

:4

P M

GI000

COVER SHEET

GUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

REPAIR BUILDING EXTERIORS

B58, B60 & B98

DANVILLE, IL

550-22-101

58, 60 & 98

07/08/2021 AS LS

550-22-101

REPAIR BUILDING EXTERIORS

B58, B60 & B98

VA ILLIANA HEALTHCARE SYSTEM

DANVILLE, IL

DESIGN DEVELOPMENT

100% BID DOCUMENTS

FULLY SPRINKLERED

SHEET INDEX

SHEET

NUMBER SHEET NAME

GENERAL

GI000 COVER SHEET

ARCHITECTURE

AS201.1 B98 - ELEVATIONS

AS201.2 B98 - ELEVATIONS

AS201.3 B98 - ELEVATIONS

AS201.4 B98 - ELEVATIONS

AS201.5 B98 - ELEVATIONS

AS201.6 B98 - ELEVATIONS

AS201.7 B98 - ELEVATIONS

AS201.8 B98 - ELEVATIONS

AS201.9 B98 - ELEVATIONS

AS201.10 B98 - ELEVATIONS

AS201.11 B98 - ELEVATIONS

AS202.1 B98 - PHOTOS

AS202.2 B98 - PHOTOS

AS202.3 B98 - PHOTOS

AS202.4 B98 - PHOTOS

AS203.1 B58 - ELEVATIONS

AS203.2 B58 - ELEVATIONS

AS203.3 B58 - ELEVATIONS

AS203.4 B58 - ELEVATIONS

AS203.5 B58 - ELEVATIONS

AS203.6 B58 - ELEVATIONS

AS203.7 B58 - ELEVATIONS

AS203.8 B58 - ELEVATIONS

AS203.9 B58 - ELEVATIONS

AS203.10 B58 - ELEVATIONS

AS203.11 B58 - ELEVATIONS

AS203.12 B58 - ELEVATIONS

AS203.13 B58 - ELEVATIONS

AS203.14 B58 - ELEVATIONS

AS203.15 B58 - ELEVATIONS

AS203.16 B58 - ELEVATIONS

AS203.17 B58 - ENLARGED DETAILS

AS204.1 B58 - PHOTOS

AS204.2 B58 - PHOTOS

AS204.3 B58 - PHOTOS

AS204.4 B58 - PHOTOS

AS204.5 B58 - PHOTOS

AS205.1 B60 - ELEVATIONS

AS205.2 B60 - ELEVATIONS

AS205.3 B60 - ENLARGED DETAILS

AS206.1 B60 - PHOTOS

AS206.2 B60 - PHOTOS

AS206.3 B60 - PHOTOS

AREA MAP

VICINITY MAP

CAMPUS MAP

Contact: Contact:

VA Illiana Health Care System

Douglas Elia, COR

1900 E Main St.

Danville, IL 61832 p: 217.554.4160 e: douglas.elia@va.gov

OWNER

GUIDON DESIGN INC.

Andrew Schaewe

Project Architect

1221 North Pennsylvania Street Suite 200 Indianapolis, IN 46202 p: 317.800.6388 x 141 e: aschaewe@guidondesign.com

ARCHITECT

Revisions: Date:

N

E.1 E.2 E.3

W.1 W.2 W.3

N.3

N.2

N.1

S.1

S.2

S.3

A B C D E F

G H

B98-E.1-A1-W2

B98-E.1-A2-W2

B98-E.1-A3-W2

B98-E.1-A1-W1

B98-E.1-A2-W1

B98-E.1-A3-W1

B98-E.1-B1-W2

B98-E.1-B2-W2

B98-E.1-B3-W2

B98-E.1-B1-W1

B98-E.1-B2-W1

B98-E.1-B3-W1

B98-E.1-E1-W2

B98-E.1-E2-W2

B98-E.1-E3-W2

B98-E.1-E1-Dr1

B98-E.1-E2-W1

B98-E.1-E3-W1

B98-E.1-F1-W2

B98-E.1-F2-W2

B98-E.1-F3-W2

B98-E.1-F1-W1

B98-E.1-F2-W1

B98-E.1-F3-W1

B98-E.1-G1-W2

B98-E.1-G2-W2

B98-E.1-G3-W2

B98-E.1-G1-W1

B98-E.1-G2-W1

B98-E.1-G3-W1

B98-E.2-H1-W1

B98-E.2-H2-W1

B98-E.2-H3-W1

B98-E.1-B1-W2

B98-E.1-B2-W2

B98-E.1-B3-W2

B98-E.1-B1-W1

B98-E.1-B2-W1

B98-E.1-B3-W1

B98-E.1-E2-W1

B98-E.1-E3-W1

37' - 4" 36' - 0" 62' - 8" Bc2 Bc2 Bc2

Mc3Mc3Mc3

NS

Sr

Sr

ARCHITECTURAL NOTES

BRICK AND MORTAR CLEANING. THE EXISTING BRICK AND MORTAR IS STAINED AND IS TO BE

CLEANED. ANY LOOSE OR DETERIORATED MORTAR IS TO BE REMOVED AND TUCK POINTED.

BRICK AND MORTAR CLEANING. THE ENTIRE BRICK FACADE SHOWN IN THIS ELEVATION IS TO BE

GENTLY CLEANED TO REMOVED GENERAL DIRT AND DEBRIS AND TO CREATE A FACADE THAT IS

HOMOGENEOUS IN APPEARANCE.

BRICK AND MORTAR CLEANING 3. THE AREA LOCATED UNDER THE COVER ABOVE THE ENTRY

HAS HAD ROOSTING ANIMALS OVER TIME. ALL NESTS, REMNANTS, AND DEBRIS LEFT BY ANIMALS

TO BE COMPLETELY REMOVED AND AREA THOROUGHLY CLEANED.

BRICK AND MORTAR REPAIR. THE BRICK IN THIS AREA IS STAINED AND DETERIORATED AND

MORTAR IS LOOSE OR MISSING. THIS AREA IS TO BE CLEANED COMPLETELY. LOOSE OR

DETERIORATED MORTAR IS TO BE REMOVED AND REPOINTED TO MATCH EXISTING. BROKEN,

DAMAGED AND/OR DETERIORATED OR STRUCTURALLY UNFIT BRICK IS TO BE REMOVED AND

REPLACED WITH BRICK TO MATCH.

BRICK AND MORTAR REPAIR. THE MORTAR IN THIS AREA IS LOOSE. STAINED MORTAR TO BE

CLEANED. LOOSE OR DETERIORATED MORTAR IS TO BE REMOVED AND REPOINTED TO MATCH

EXISTING.

DOOR REPAIR 1. EXISTING HALLOW METAL DOOR TO BE CLEANED, HAVE DETERIORATION AND

RUST REMOVED AND DOORS TO BE REPAINTED.

DOOR REPAIR 2. EXISTING DOOR AND FRAME TO BE STRIPPED AND REPAINTED.

METAL CLEAN 1. EXISTING METAL FLASHING TO BE CLEANED AND INSPECTED TO INSURE

COMPLETE INTEGRITY. ALL SURFACE AREA TO BE CLEANED, SEAMS TO BE INSPECTED AND

PROPERLY SEALED. WHERE FLASHING INSETS INTO EXISTING MASONRY INSURE FLASHING AND

COUNTER FLASHING IS PROPERLY SET AND RESEAL WITH ELASTOMERIC SEALANT.

METAL CLEAN 2. EXISTING METAL COLUMN COPING TO BE CLEANED AND INSPECTED TO INSURE

COMPLETE INTEGRITY. ALL SURFACE AREA TO BE CLEANED, SEAMS TO BE INSPECTED AND

PROPERLY SEALED. WHERE FLASHING INSETS INTO EXISTING MASONRY INSURE FLASHING AND

COUNTER FLASHING IS PROPERLY SET AND RESEAL WITH ELASTOMETRIC SEALANT. REMOVE

EXISTING LOOSE OR CRACKED PAINT TO BE PHYSICALLY REMOVED BY SCRAPING THE AREA TO

AN EVEN OR SMOOTH SURFACE ACCEPTABLE TO RECEIVE NEW PAINT.

METAL CLEAN 3. EXISTING METAL FASCIA TO BE CLEANED AND INSPECTED TO INSURE

COMPLETE INTEGRITY. ALL SURFACE AREA TO BE CLEANED, SEAMS TO BE INSPECTED AND

PROPERLY SEALED. CONNECTION TO MEMBRANE ROOF TO BE INSPECTED AND CORRECTED AS

NECESSARY.

METAL CLEAN 4. EXISTING METAL WINDOW TRIM TO REMAIN, ALL SURFACES TO BE CLEANED.

NEW SEALANT TO BE APPLIED FOR THE ENTIRE PERIMETER AGAINST ADJOINING SURFACES.

Bc1

Bc2

Bc3

BR1

BR2

Dr1

Dr2

Mc1

Mc2

Mc3

Mc4

METAL CLEAN 5. EXISTING METAL PILASTER TO REMAIN. ALL SURFACES TO BE CLEANED. ALL

FASTENERS TO BE TIGHTENED AND MISSING FASTENERS TO BE REPLACED. NEW SEALANT TO

BE APPLIED FOR THE ENTIRE PERIMETER AGAINST ADJOINING SURFACES.

METAL REPAIR 1. EXISTING STEEL LINTEL TO REMAIN. ALL PAINT TO BE STRIPPED FROM LINTEL.

ALL RUST AND DETERIORATION TO BE REMOVED AND REPAIRED. LINTEL TO BE REPAINTED.

METAL REPLACEMENT 1. EXISTING METAL FLASHING OVER TOP OF WINDOW MOLDING TO BE

REMOVED AND REPLACED. NEW METAL FLASHING TO MATCH THE EXISTING TO BE INSTALLED IN

PLACE AND ALL EDGES TO BE SEALED INTO IMMEDIATELY ADJACENT AREAS.

METAL REPLACEMENT 2. ALL FLASHING AT EXISTING DORMERS TO BE REMOVED AND REPLACED

FOR THE ENTIRE PERIMETER OF DORMER AT ROOF.

NO SCREEN.

PAINT REPAIR 1. EXISTING PAINTED WOOD SURFACE, AREA MAY CONTAIN LEAD BASED PAINT

ON ANY OR ALL LAYERS. EXISTING LOOSE OR CRACKED PAINT TO BE PHYSICALLY REMOVED BY

SCRAPING THE AREA TO AN EVEN OR SMOOTH SURFACE ACCEPTABLE TO RECEIVE NEW PAINT.

AREA TO BE INSPECTED AND ANY DAMAGED OR DETERIORATING WOOD TO HAVE EFFECTED

AREA PATCHED, REPAIRED, REMOVED OR REPLACED. AREA TO BE REPAINTED WITH PAINTING

SYSTEM AS SPECIFIED.

PAINT REPAIR 2. EXISTING WROUGHT IRON RAILING AND PICKETS TO HAVE LOOSE AND

DETERIORATED PAINT REMOVED THROUGH MECHANICAL REMOVAL. PAINT AREA POTENTIALLY

CONTAINS LAYER OF PAINT THAT CONTAIN LET. RUSTED OR LOOSE PAINT TO REMOVED AND

ENTIRE RAILING TO BE REPAINTED.

PAINT REPAIR 3. EXISTING WOOD ENTABLATURE TO REMAIN. ALL AREA TO BE CLEANED,

INCLUDING AN ANIMAL DEBRIS. EXISTING LOOSE OR CRACKED PAINT TO BE PHYSICALLY

REMOVED BY SCRAPING THE AREA TO AN EVEN OR SMOOTH SURFACE ACCEPTABLE TO

RECEIVE NEW PAINT AREA TO BE INSPECTED AND ANY DAMAGED OR DETERIORATING WOOD TO

HAVE EFFECTED AREA PATCHED, REPAIRED, REMOVED OR REPLACED. AREA TO BE REPAINTED

WITH PAINTING SYSTEM AS SPECIFIED. MISSING OR BROKEN PIECES ARE TO BE REPAIRED OR

REPLACE.

SCREEN REPLACE.

SCREEN REPAIR.

STEEL REPAIR. EXISTING STEEL LINTEL TO REMAIN IN PLACE. ALL EXPOSED PAINT TO BE

SCRAPED AND REMOVED TO BARE STEEL. EXISTING STEEL TO BE INSPECTED FOR CORROSION

AND ALL CORROSION REMOVED AND MITIGATED. PRIME AND PAINT STEEL TO REMAIN.

EXISTING STONE TO BE REPAIRED OR REPLACED.

STONE CLEANING. EXISTING LIMESTONE TRIM IS STAINED. STONE TO BE CLEANED AND ALL

STAINING REMOVED.

Mc5

Mr1

MR1

MR2

NS

Pc1

Pc2

Pc3

SR

Sr

Sr1

Str1

Stc1

WOOD REPAIR 1. EXISTING WOODEN LOUVER. LOUVER TO BE STRIPPED OF LOOSE OR CRACKED

PAINT TO BE PHYSICALLY REMOVED BY SCRAPING THE AREA TO AN EVEN OR SMOOTH SURFACE

ACCEPTABLE TO RECEIVE NEW PAINT. ANY BROKEN PIECES ARE TO BE REMOVED AND

REPLACED AND ANY AREAS OF DETERIORATED WOOD ARE TO BE PATCHED AND REPAIRED IN

PLACE. COMPLETELY REPLACE ALL EXISTING SCREENS IN DORMERS

WOOD REPAIR 2. EXISTING DORMER TO BE REPAIRED. EXISTING DORMER HAS MISSING OR

DETERIORATED WOOD SIDING AND TRIM. REMOVE ALL DAMAGED OR DETERIORATED SIDING AND

TRIM. REPLACE WITH LIKE KIND SIMILAR TO EXISTING. CHECK ALL EXISTING FLASHING ARE

INSURE COMPLETE INSTALLATION. REPLACE MISSING TRIM ELEMENTS. SEE PHOTO SURVEY OF

EXISTING DORMERS. REPAINT ENTIRE DORMER TO MATCH.

WOOD REPAIR 3. EXISTING WOOD COLUMNS TO BE REPAIRED. EXISTING WOOD COLUMNS TO BE

STRIPPED OF LOOSE OR CRACKED PAINT TO BE PHYSICALLY REMOVED BY SCRAPING THE AREA

TO AN EVEN OR SMOOTH SURFACE ACCEPTABLE TO RECEIVE NEW PAINT. ANY BROKEN PIECES

ARE TO BE REMOVED AND REPLACED AND ANY AREAS OF DETERIORATED WOOD ARE TO

PATCHED AND REPAIRED IN PLACE.

WOOD REPAIR 4. EXISTING WOOD COLUMN BASE HAS DETERIORATED OR MISSING PARTS.

COLUMN BASE TO BE REPAIRED OR REPLACED. BROKEN AND/OR MISSING PIECES TO BE

REPLACED. EXISTING PIECES WITH SMALL AREAS OF DETERIORATION AND/OR TO PATCH AND

FILL, ENTIRE BASE AND COLUMN TO BE REPAINTED.

WOOD REPAIR 5. EXISTING WOOD PILASTER TO BE REPAIRED. EXISTING WOOD PILASTER

CONNECTED TO BRICK FACADE TO BE STRIPPED OF LOOSE OR CRACKED PAINT TO BE

PHYSICALLY REMOVED BY SCRAPING THE AREA TO AN EVEN OR SMOOTH SURFACE

ACCEPTABLE TO RECEIVE NEW PAINT. ANY BROKEN PIECES ARE TO BE REMOVED AND

REPLACED AND ANY AREAS OF DETERIORATED WOOD ARE TO BE PATCHED AND REPAIRED IN

PLACE. ALL EXISTING SEALANT BETWEEN WOOD PILASTER AND BRICK TO BE REMOVED AND

REPLACED PRIOR TO PAINTING.

WINDOW REPLACEMENT. EXISTING WINDOW TO BE REMOVED. IMMEDIATE ADJACENT

REMAINING AREA TO BE CLEANED AND PREPARED TO RECEIVE NEW CONSTRUCTION. NEW

ALUMINUM HISTORIC WINDOW TO MATCH EXISTING TO BE INSTALLED IN PLACE OF EXISTING AND

TO BE SEALED.

WINDOW CLEANING 1. EXISTING WINDOW SYSTEM TO BE CLEANED. ALL GLAZING FRAMING TO BE

THOROUGHLY CLEANED. EXISTING SEALANT TO BE REMOVED AND REPLACED WITH NEW

BACKER ROD AND SEALANT.

WINDOW REPAIR 1. EXISTING WINDOW TO REMAIN. ALL GLAZING FROM DECORATIVE ARCHED

WINDOW TO BE REMOVED AND PRESERVED. LEADED FRAME TO BE STRIPPED OF ALL PUTTY

PAINT AND DEBRIS. LEADED FRAME TO BE CLEANED AND ANY RUST OR DETERIORATION

REMOVED AND TO BE REPAINTED. GLAZING TO BE CLEANED AND RESET INTO EXISTING

RESTORED FRAME.

EXISTING WINDOW SCREEN. EXISTING SCREEN TO REMAIN. SCREENING MATERIAL IS TORN AND

TO BE REPAIRED IN EXISTING FRAME.

Wr1

Wr2

Wr3

Wr4

Wr5

WR1

Wwc1

Wwr1

Wwr2

EXISTING STEEL LINTEL TO

REMAIN, LINTEL TO BE

CLEANED, CORROSION

REMOVED, AND REPAINTED.

ALL EXISTING SEALANT TO

BE REMOVED. NEW METAL

FLASHING TO BE INSTALLED

BETWEEN WINDOW AND

BRICK. SEE DETAIL AS201.1.

ALL NEW BACKER ROD AND

SEALANT TO BE INSTALLED.

EXISTING THROUGH WALL

LOUVER TO BE CLEANED.

EXISTING SEALANT TO BE

REMOVED AND NEW

SEALANT TO BE APPLIED

FOR THE ENTIRE

PERIMETER.

EXISTING STONE SILL TO BE

CLEANED,

UNLESS NOTED OTHERWISE, ALL WINDOWS IN

THIS ELEVATION TO BE TREATED AS SUCH.

VIF

VARIES

A A

EXISTING BRICK VENEER

EXISTING STEEL LINTEL

LINTEL TO BE CLEANED OF

CORROSION AND REPAINTED

SEAL TO WINDOW WITH NEW

SEALANT

EXISTING ALUMN. WINDOW

EXISTING DISTANCE BETWEEN OUTER

FACE OF WINDOW AND REAR FACE OF

BRICK VARIES VERIFY IN FIELD AFTER

REMOVAL OF SEALANT

NEW BREAK METAL SIDE FLASHING

FROM LINTEL TO SILL SEE JAMB DETAIL

FULLY ADHERE TO FACE OF WINDOW

AND TO FACE OF BRICK

NEW BREAK METAL SIDE FLASHING SILL

RUN FROM UNDER WINDOW

FULLY ADHERE TO FACE OF WINDOW

AND FACE OF STONE SILL

EXISTING BRICK VENEER

EXISTING STONE SILL

EXISTING ALUMN WINDOW

NEW BREAK METAL SIDE FLASHING

FROM LINTEL TO SILL SEE JAMB DETAIL

FULLY ADHERE TO FACE OF WINDOW

AND TO FACE OF BRICK

NEW CONT. BACKER ROD AND SEALANT

1 1/4" MIN.

NEW BREAK METAL SIDE FLASHING SILL

RUN FROM UNDER WINDOW

FULLY ADHERE TO FACE OF WINDOW

AND FACE OF STONE SILL

EXISTING BRICK VENEER

BEYOND

EXISTING STONE SILL

EXISTING ALUMN WINDOW

NEW BREAK METAL SIDE FLASHING

FROM LINTEL TO SILL SEE JAMB DETAIL

FULLY ADHERE TO FACE OF WINDOW

AND TO FACE OF BRICK

NEW BREAK METAL SIDE FLASHING SILL

RUN FROM FACE OF WINDOW

FULLY ADHERE TO FACE OF WINDOW

AND FACE OF STONE SILL

EXISTING BRICK VENEER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

NOT F

OR

CONSTRUCTIO

N

C U s e rs \l s to y \D o c u m e n ts

\1

.5

.0

A -M

A S

S

IN

G v ls to y K

A T

J U

.r v t

/6

/2

:1

:4

P M

AS201.1

B98 - ELEVATIONS

GUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

REPAIR BUILDING EXTERIORS

B58, B60 & B98

DANVILLE, IL

550-22-101

58, 60 & 98

07/08/2021 AS LS

100% BID DOCUMENTS

FULLY SPRINKLERED

Revisions: Date:

SCALE: 1/4" = 1'-0"AS201.1

1 B98 - E.1

SCALE: 1/2" = 1'-0"

B98 TYPICAL WINDOW SCOPE

SCALE: 1 1/2" = 1'-0"AS201.1

2 A-A JAMB DETAIL

SCALE: 1 1/2" = 1'-0"AS201.1

3 SILL DETAIL4

AS201.1

W.1 W.2 W.3

N.3

N.2

N.1

S.1

S.2

S.3

H I J K L M N

B98-E.2-H1-W1

B98-E.2-H2-W1

B98-E.2-H3-W1

B98-E.2-I1-W2

B98-E.2-I2-W2

B98-E.2-I3-W2

B98-E.2-I1-W1

B98-E.2-I3-W1

B98-E.2-N1-W1

B98-E.2-N2-W1

B98-E.2-N3-W1

B98-E.2-M1-W2

B98-E.2-M2-W2

B98-E.2-M3-W2

B98-E.2-M1-W1

B98-E.2-M2-W1

B98-E.2-M3-W1

B98-E.2-J1-W2

B98-E.2-J2-W2

B98-E.2-J3-W2

B98-E.2-J1-W1

B98-E.2-J2-W1

B98-E.2-J3-W1

B98-E.2-K1-Dr2

B98-E.2-K3-W2

B98-E.2-K1-Dr1

B98-E.2-K2-W1

B98-E.2-K3-W1

B98-E.2-L1-W2

B98-E.2-L3-W2

B98-E.2-L1-W1

B98-E.2-L2-W1

B98-E.2-L3-W1

B98-E.2-K2-W2 B98-E.2-L2-W2B98-E.2-L2-W1

Mc3Mc3Mc3

31' - 4" 76' - 0" 31' - 4" Bc2 Bc2 Bc2

Wwc1

Mc4

Mc4

Wwc1

Mc4

Mc4

Wwc1

Mc4

Mc4

Wwc1

Mc4

Mc4

Wwc1

Mc4

Mc4

Mc4

Mc4

Wwc1

Mc4

Mc4

Wwc1

Mc4

Mc4

Wwc1

Mc4

Mc4

Wwc1

Mc4

Mc4

Wwc1

Mc4

Mc4

Wwc1

Mc4

Mc4

Wwc1

Mc4

Mc4

Mc4

Mc4

Wwc1

Mc4

Mc4

Mc4

Mc4

Mc5 Mc5 Mc5 Mc5 Mc5

Wwc1 Wwc1

Mc3 Mc3

Sr

Sr

SrSr

SR

SR

Bc1

Bc1

RESEAL CAULKRESEAL CAULK

ARCHITECTURAL NOTES

BRICK AND MORTAR CLEANING. THE EXISTING BRICK AND MORTAR IS STAINED AND IS TO BE

CLEANED. ANY LOOSE OR DETERIORATED MORTAR IS TO BE REMOVED AND TUCK POINTED.

BRICK AND MORTAR CLEANING. THE ENTIRE BRICK FACADE SHOWN IN THIS ELEVATION IS TO BE

GENTLY CLEANED TO REMOVED GENERAL DIRT AND DEBRIS AND TO CREATE A FACADE THAT IS

HOMOGENEOUS IN APPEARANCE.

BRICK AND MORTAR CLEANING 3. THE AREA LOCATED UNDER THE COVER ABOVE THE ENTRY

HAS HAD ROOSTING ANIMALS OVER TIME. ALL NESTS, REMNANTS, AND DEBRIS LEFT BY ANIMALS

TO BE COMPLETELY REMOVED AND AREA THOROUGHLY CLEANED.

BRICK AND MORTAR REPAIR. THE BRICK IN THIS AREA IS STAINED AND DETERIORATED AND

MORTAR IS LOOSE OR MISSING. THIS AREA IS TO BE CLEANED COMPLETELY. LOOSE OR

DETERIORATED MORTAR IS TO BE REMOVED AND REPOINTED TO MATCH EXISTING. BROKEN,

DAMAGED AND/OR DETERIORATED OR STRUCTURALLY UNFIT BRICK IS TO BE REMOVED AND

REPLACED WITH BRICK TO MATCH.

BRICK AND MORTAR REPAIR. THE MORTAR IN THIS AREA IS LOOSE. STAINED MORTAR TO BE

CLEANED. LOOSE OR DETERIORATED MORTAR IS TO BE REMOVED AND REPOINTED TO MATCH

EXISTING.

DOOR REPAIR 1. EXISTING HALLOW METAL DOOR TO BE CLEANED, HAVE DETERIORATION AND

RUST REMOVED AND DOORS TO BE REPAINTED.

DOOR REPAIR 2. EXISTING DOOR AND FRAME TO BE STRIPPED AND REPAINTED.

METAL CLEAN 1. EXISTING METAL FLASHING TO BE CLEANED AND INSPECTED TO INSURE

COMPLETE INTEGRITY. ALL SURFACE AREA TO BE CLEANED, SEAMS TO BE INSPECTED AND

PROPERLY SEALED. WHERE FLASHING INSETS INTO EXISTING MASONRY INSURE FLASHING AND

COUNTER FLASHING IS PROPERLY SET AND RESEAL WITH ELASTOMERIC SEALANT.

METAL CLEAN 2. EXISTING METAL COLUMN COPING TO BE CLEANED AND INSPECTED TO INSURE

COMPLETE INTEGRITY. ALL SURFACE AREA TO BE CLEANED, SEAMS TO BE INSPECTED AND

PROPERLY SEALED. WHERE FLASHING INSETS INTO EXISTING MASONRY INSURE FLASHING AND

COUNTER FLASHING IS PROPERLY SET AND RESEAL WITH ELASTOMETRIC SEALANT. REMOVE

EXISTING LOOSE OR CRACKED PAINT TO BE PHYSICALLY REMOVED BY SCRAPING THE AREA TO

AN EVEN OR SMOOTH SURFACE ACCEPTABLE TO RECEIVE NEW PAINT.

METAL CLEAN 3. EXISTING METAL FASCIA TO BE CLEANED AND INSPECTED TO INSURE

COMPLETE INTEGRITY. ALL SURFACE AREA TO BE CLEANED, SEAMS TO BE INSPECTED AND

PROPERLY SEALED. CONNECTION TO MEMBRANE ROOF TO BE INSPECTED AND CORRECTED AS

NECESSARY.

METAL CLEAN 4. EXISTING METAL WINDOW TRIM TO REMAIN, ALL SURFACES TO BE CLEANED.

NEW SEALANT TO BE APPLIED FOR THE ENTIRE PERIMETER AGAINST ADJOINING SURFACES.

Bc1

Bc2

Bc3

BR1

BR2

Dr1

Dr2

Mc1

Mc2

Mc3

Mc4

METAL CLEAN 5. EXISTING METAL PILASTER TO REMAIN. ALL SURFACES TO BE CLEANED. ALL

FASTENERS TO BE TIGHTENED AND MISSING FASTENERS TO BE REPLACED. NEW SEALANT TO

BE APPLIED FOR THE ENTIRE PERIMETER AGAINST ADJOINING SURFACES.

METAL REPAIR 1. EXISTING STEEL LINTEL TO REMAIN. ALL PAINT TO BE STRIPPED FROM LINTEL.

ALL RUST AND DETERIORATION TO BE REMOVED AND REPAIRED. LINTEL TO BE REPAINTED.

METAL REPLACEMENT 1. EXISTING METAL FLASHING OVER TOP OF WINDOW MOLDING TO BE

REMOVED AND REPLACED. NEW METAL FLASHING TO MATCH THE EXISTING TO BE INSTALLED IN

PLACE AND ALL EDGES TO BE SEALED INTO IMMEDIATELY ADJACENT AREAS.

METAL REPLACEMENT 2. ALL FLASHING AT EXISTING DORMERS TO BE REMOVED AND REPLACED

FOR THE ENTIRE PERIMETER OF DORMER AT ROOF.

NO SCREEN.

PAINT REPAIR 1. EXISTING PAINTED WOOD SURFACE, AREA MAY CONTAIN LEAD BASED PAINT

ON ANY OR ALL LAYERS. EXISTING LOOSE OR CRACKED PAINT TO BE PHYSICALLY REMOVED BY

SCRAPING THE AREA TO AN EVEN OR SMOOTH SURFACE ACCEPTABLE TO RECEIVE NEW PAINT.

AREA TO BE INSPECTED AND ANY DAMAGED OR DETERIORATING WOOD TO HAVE EFFECTED

AREA PATCHED, REPAIRED, REMOVED OR REPLACED. AREA TO BE REPAINTED WITH PAINTING

SYSTEM AS SPECIFIED.

PAINT REPAIR 2. EXISTING WROUGHT IRON RAILING AND PICKETS TO HAVE LOOSE AND

DETERIORATED PAINT REMOVED THROUGH MECHANICAL REMOVAL. PAINT AREA POTENTIALLY

CONTAINS LAYER OF PAINT THAT CONTAIN LET. RUSTED OR LOOSE PAINT TO REMOVED AND

ENTIRE RAILING TO BE REPAINTED.

PAINT REPAIR 3. EXISTING WOOD ENTABLATURE TO REMAIN. ALL AREA TO BE CLEANED,

INCLUDING AN ANIMAL DEBRIS. EXISTING LOOSE OR CRACKED PAINT TO BE PHYSICALLY

REMOVED BY SCRAPING THE AREA TO AN EVEN OR SMOOTH SURFACE ACCEPTABLE TO

RECEIVE NEW PAINT AREA TO BE INSPECTED AND ANY DAMAGED OR DETERIORATING WOOD TO

HAVE EFFECTED AREA PATCHED, REPAIRED, REMOVED OR REPLACED. AREA TO BE REPAINTED

WITH PAINTING SYSTEM AS SPECIFIED. MISSING OR BROKEN PIECES ARE TO BE REPAIRED OR

REPLACE.

SCREEN REPLACE.

SCREEN REPAIR.

STEEL REPAIR. EXISTING STEEL LINTEL TO REMAIN IN PLACE. ALL EXPOSED PAINT TO BE

SCRAPED AND REMOVED TO BARE STEEL. EXISTING STEEL TO BE INSPECTED FOR CORROSION

AND ALL CORROSION REMOVED AND MITIGATED. PRIME AND PAINT STEEL TO REMAIN.

EXISTING STONE TO BE REPAIRED OR REPLACED.

STONE CLEANING. EXISTING LIMESTONE TRIM IS STAINED. STONE TO BE CLEANED AND ALL

STAINING REMOVED.

Mc5

Mr1

MR1

MR2

NS

Pc1

Pc2

Pc3

SR

Sr

Sr1

Str1

Stc1

WOOD REPAIR 1. EXISTING WOODEN LOUVER. LOUVER TO BE STRIPPED OF LOOSE OR CRACKED

PAINT TO BE PHYSICALLY REMOVED BY SCRAPING THE AREA TO AN EVEN OR SMOOTH SURFACE

ACCEPTABLE TO RECEIVE NEW PAINT. ANY BROKEN PIECES ARE TO BE REMOVED AND

REPLACED AND ANY AREAS OF DETERIORATED WOOD ARE TO BE PATCHED AND REPAIRED IN

PLACE. COMPLETELY REPLACE ALL EXISTING SCREENS IN DORMERS

WOOD REPAIR 2. EXISTING DORMER TO BE REPAIRED. EXISTING DORMER HAS MISSING OR

DETERIORATED WOOD SIDING AND TRIM. REMOVE ALL DAMAGED OR DETERIORATED SIDING AND

TRIM. REPLACE WITH LIKE KIND SIMILAR TO EXISTING. CHECK ALL EXISTING FLASHING ARE

INSURE COMPLETE INSTALLATION. REPLACE MISSING TRIM ELEMENTS. SEE PHOTO SURVEY OF

EXISTING DORMERS. REPAINT ENTIRE DORMER TO MATCH.

WOOD REPAIR 3. EXISTING WOOD COLUMNS TO BE REPAIRED. EXISTING WOOD COLUMNS TO BE

STRIPPED OF LOOSE OR CRACKED PAINT TO BE PHYSICALLY REMOVED BY SCRAPING THE AREA

TO AN EVEN OR SMOOTH SURFACE ACCEPTABLE TO RECEIVE NEW PAINT. ANY BROKEN PIECES

ARE TO BE REMOVED AND REPLACED AND ANY AREAS OF DETERIORATED WOOD ARE TO

PATCHED AND REPAIRED IN PLACE.

WOOD REPAIR 4. EXISTING WOOD COLUMN BASE HAS DETERIORATED OR MISSING PARTS.

COLUMN BASE TO BE REPAIRED OR REPLACED. BROKEN AND/OR MISSING PIECES TO BE

REPLACED. EXISTING PIECES WITH SMALL AREAS OF DETERIORATION AND/OR TO PATCH AND

FILL, ENTIRE BASE AND COLUMN TO BE REPAINTED.

WOOD REPAIR 5. EXISTING WOOD PILASTER TO BE REPAIRED. EXISTING WOOD PILASTER

CONNECTED TO BRICK FACADE TO BE STRIPPED OF LOOSE OR CRACKED PAINT TO BE

PHYSICALLY REMOVED BY SCRAPING THE AREA TO AN EVEN OR SMOOTH SURFACE

ACCEPTABLE TO RECEIVE NEW PAINT. ANY BROKEN PIECES ARE TO BE REMOVED AND

REPLACED AND ANY AREAS OF DETERIORATED WOOD ARE TO BE PATCHED AND REPAIRED IN

PLACE. ALL EXISTING SEALANT BETWEEN WOOD PILASTER AND BRICK TO BE REMOVED AND

REPLACED PRIOR TO PAINTING.

WINDOW REPLACEMENT. EXISTING WINDOW TO BE REMOVED. IMMEDIATE ADJACENT

REMAINING AREA TO BE CLEANED AND PREPARED TO RECEIVE NEW CONSTRUCTION. NEW

ALUMINUM HISTORIC WINDOW TO MATCH EXISTING TO BE INSTALLED IN PLACE OF EXISTING AND

TO BE SEALED.

WINDOW CLEANING 1. EXISTING WINDOW SYSTEM TO BE CLEANED. ALL GLAZING FRAMING TO BE

THOROUGHLY CLEANED. EXISTING SEALANT TO BE REMOVED AND REPLACED WITH NEW

BACKER ROD AND SEALANT.

WINDOW REPAIR 1. EXISTING WINDOW TO REMAIN. ALL GLAZING FROM DECORATIVE ARCHED

WINDOW TO BE REMOVED AND PRESERVED. LEADED FRAME TO BE STRIPPED OF ALL PUTTY

PAINT AND DEBRIS. LEADED FRAME TO BE CLEANED AND ANY RUST OR DETERIORATION

REMOVED AND TO BE REPAINTED. GLAZING TO BE CLEANED AND RESET INTO EXISTING

RESTORED FRAME.

EXISTING WINDOW SCREEN. EXISTING SCREEN TO REMAIN. SCREENING MATERIAL IS TORN AND

TO BE REPAIRED IN EXISTING FRAME.

Wr1

Wr2

Wr3

Wr4

Wr5

WR1

Wwc1

Wwr1

Wwr2

EXISTING STEEL LINTEL TO

REMAIN, LINTEL TO BE

CLEANED, CORROSION

REMOVED, AND REPAINTED.

ALL EXISTING SEALANT TO

BE REMOVED. NEW METAL

FLASHING TO BE INSTALLED

BETWEEN WINDOW AND

BRICK. SEE DETAIL AS201.1.

ALL NEW BACKER ROD AND

SEALANT TO BE INSTALLED.

EXISTING THROUGH WALL

LOUVER TO BE CLEANED.

EXISTING SEALANT TO BE

REMOVED AND NEW

SEALANT TO BE APPLIED

FOR THE ENTIRE

PERIMETER.

EXISTING STONE SILL TO BE

CLEANED,

UNLESS NOTED OTHERWISE, ALL WINDOWS IN

THIS ELEVATION TO BE TREATED AS SUCH.

VIF

VARIES

A A

EXISTING BRICK VENEER

EXISTING STEEL LINTEL

LINTEL TO BE CLEANED OF

CORROSION AND REPAINTED

SEAL TO WINDOW WITH NEW

SEALANT

EXISTING ALUMN. WINDOW

EXISTING DISTANCE BETWEEN OUTER

FACE OF WINDOW AND REAR FACE OF

BRICK VARIES VERIFY IN FIELD AFTER

REMOVAL OF SEALANT

NEW BREAK METAL SIDE FLASHING

FROM LINTEL TO SILL SEE JAMB DETAIL

FULLY ADHERE TO FACE OF WINDOW

AND TO FACE OF BRICK

NEW BREAK METAL SIDE FLASHING SILL

RUN FROM UNDER WINDOW

FULLY ADHERE TO FACE OF WINDOW

AND FACE OF STONE SILL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

NOT F

OR

CONSTRUCTIO

N

C U s e rs \l s to y \D o c u m e n ts

\1

.5

.0

A -M

A S

S

IN

G v ls to y K

A T

J U

.r v t

/6

/2

:1

:4

P M

AS201.2

B98 - ELEVATIONS

GUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

REPAIR BUILDING EXTERIORS

B58, B60 & B98

DANVILLE, IL

550-22-101

58, 60 & 98

07/08/2021 AS LS

100% BID DOCUMENTS

FULLY SPRINKLERED

Revisions: Date:

SCALE: 1/4" = 1'-0"AS201.2

1 B98 - E.2

SCALE: 1/2" = 1'-0"

B98 TYPICAL WINDOW SCOPE2

AS201.2

W.1 W.2 W.3

N.3

N.2

N.1

S.1

S.2

S.3

O P Q R S T U

B98-E.2-N1-W1

B98-E.2-N2-W1

B98-E.2-N3-W1

B98-E.3-O1-W1

B98-E.3-O2-W1

B98-E.3-O3-W1

B98-E.3-O1-W2

B98-E.3-O2-W2

B98-E.3-O3-W2

B98-E.3-P1-W1

B98-E.3-P2-W1

B98-E.3-P3-W1

B98-E.3-P1-W2

B98-E.3-P2-W2

B98-E.3-P3-W2

B98-E.3-Q1-W1

B98-E.3-Q2-W1

B98-E.3-Q3-W1

B98-E.3-Q1-Dr1

B98-E.3-Q2-W2

B98-E.3-Q3-W2

B98-E.3-T1-W1

B98-E.3-T2-W1

B98-E.3-T3-W1

B98-E.3-T1-W2

B98-E.3-T2-W2

B98-E.3-T3-W2

B98-E.3-U1-W1

B98-E.3-U2-W1

B98-E.3-U3-W1

B98-E.3-U1-W2

B98-E.3-U2-W2

B98-E.3-U3-W2

B98-E.3-U1-W1

B98-E.3-U2-W1

B98-E.3-U3-W1

B98-E.3-U1-W2

B98-E.3-U2-W2

B98-E.3-U3-W2

Mc3Mc3Mc3

62' - 8" 36' - 0" 37' - 4" Bc2 Bc2 Bc2

Sr

Sr

NS

RESEAL BRICK JOINT

IN CORNER

ARCHITECTURAL NOTES

BRICK AND MORTAR CLEANING. THE EXISTING BRICK AND MORTAR IS STAINED AND IS TO BE

CLEANED. ANY LOOSE OR DETERIORATED MORTAR IS TO BE REMOVED AND TUCK POINTED.

BRICK AND MORTAR CLEANING. THE ENTIRE BRICK FACADE SHOWN IN THIS ELEVATION IS TO BE

GENTLY CLEANED TO REMOVED GENERAL DIRT AND DEBRIS AND TO CREATE A FACADE THAT IS

HOMOGENEOUS IN APPEARANCE.

BRICK AND MORTAR CLEANING 3. THE AREA LOCATED UNDER THE COVER ABOVE THE ENTRY

HAS HAD ROOSTING ANIMALS OVER TIME. ALL NESTS, REMNANTS, AND DEBRIS LEFT BY ANIMALS

TO BE COMPLETELY REMOVED AND AREA THOROUGHLY CLEANED.

BRICK AND MORTAR REPAIR. THE BRICK IN THIS AREA IS STAINED AND DETERIORATED AND

MORTAR IS LOOSE OR MISSING. THIS AREA IS TO BE CLEANED COMPLETELY. LOOSE OR

DETERIORATED MORTAR IS TO BE REMOVED AND REPOINTED TO MATCH EXISTING. BROKEN,

DAMAGED AND/OR DETERIORATED OR STRUCTURALLY UNFIT BRICK IS TO BE REMOVED AND

REPLACED WITH BRICK TO MATCH.

BRICK AND MORTAR REPAIR. THE MORTAR IN THIS AREA IS LOOSE. STAINED MORTAR TO BE

CLEANED. LOOSE OR DETERIORATED MORTAR IS TO BE REMOVED AND REPOINTED TO MATCH

EXISTING.

DOOR REPAIR 1. EXISTING HALLOW METAL DOOR TO BE CLEANED, HAVE DETERIORATION AND

RUST REMOVED AND DOORS TO BE REPAINTED.

DOOR REPAIR 2. EXISTING DOOR AND FRAME TO BE STRIPPED AND REPAINTED.

METAL CLEAN 1. EXISTING METAL FLASHING TO BE CLEANED AND INSPECTED TO INSURE

COMPLETE INTEGRITY. ALL SURFACE AREA TO BE CLEANED, SEAMS TO BE INSPECTED AND

PROPERLY SEALED. WHERE FLASHING INSETS INTO EXISTING MASONRY INSURE FLASHING AND

COUNTER FLASHING IS PROPERLY SET AND RESEAL WITH ELASTOMERIC SEALANT.

METAL CLEAN 2. EXISTING METAL COLUMN COPING TO BE CLEANED AND INSPECTED TO INSURE

COMPLETE INTEGRITY. ALL SURFACE AREA TO BE CLEANED, SEAMS TO BE INSPECTED AND

PROPERLY SEALED. WHERE FLASHING INSETS INTO EXISTING MASONRY INSURE FLASHING AND

COUNTER FLASHING IS PROPERLY SET AND RESEAL WITH ELASTOMETRIC SEALANT. REMOVE

EXISTING LOOSE OR CRACKED PAINT TO BE PHYSICALLY REMOVED BY SCRAPING THE AREA TO

AN EVEN OR SMOOTH SURFACE ACCEPTABLE TO RECEIVE NEW PAINT.

METAL CLEAN 3. EXISTING METAL FASCIA TO BE CLEANED AND INSPECTED TO INSURE

COMPLETE INTEGRITY. ALL SURFACE AREA TO BE CLEANED, SEAMS TO BE INSPECTED AND

PROPERLY SEALED. CONNECTION TO MEMBRANE ROOF TO BE INSPECTED AND CORRECTED AS

NECESSARY.

METAL CLEAN 4. EXISTING METAL WINDOW TRIM TO REMAIN, ALL SURFACES TO BE CLEANED.

NEW SEALANT TO BE APPLIED FOR THE ENTIRE PERIMETER AGAINST ADJOINING SURFACES.

Bc1

Bc2

Bc3

BR1

BR2

Dr1

Dr2

Mc1

Mc2

Mc3

Mc4

METAL CLEAN 5. EXISTING METAL PILASTER TO REMAIN. ALL SURFACES TO BE CLEANED. ALL

FASTENERS TO BE TIGHTENED AND MISSING FASTENERS TO BE REPLACED. NEW SEALANT TO

BE APPLIED FOR THE ENTIRE PERIMETER AGAINST ADJOINING SURFACES.

METAL REPAIR 1. EXISTING STEEL LINTEL TO REMAIN. ALL PAINT TO BE STRIPPED FROM LINTEL.

ALL RUST AND DETERIORATION TO BE REMOVED AND REPAIRED. LINTEL TO BE REPAINTED.

METAL REPLACEMENT 1. EXISTING METAL FLASHING OVER TOP OF WINDOW MOLDING TO BE

REMOVED AND REPLACED. NEW METAL FLASHING TO MATCH THE EXISTING TO BE INSTALLED IN

PLACE AND ALL EDGES TO BE SEALED INTO IMMEDIATELY ADJACENT AREAS.

METAL REPLACEMENT 2. ALL FLASHING AT EXISTING DORMERS TO BE REMOVED AND REPLACED

FOR THE ENTIRE PERIMETER OF DORMER AT ROOF.

NO SCREEN.

PAINT REPAIR 1. EXISTING PAINTED WOOD SURFACE, AREA MAY CONTAIN LEAD BASED PAINT

ON ANY OR ALL LAYERS. EXISTING LOOSE OR CRACKED PAINT TO BE PHYSICALLY REMOVED BY

SCRAPING THE AREA TO AN EVEN OR SMOOTH SURFACE ACCEPTABLE TO RECEIVE NEW PAINT.

AREA TO BE INSPECTED AND ANY DAMAGED OR DETERIORATING WOOD TO HAVE EFFECTED

AREA PATCHED, REPAIRED, REMOVED OR REPLACED. AREA TO BE REPAINTED WITH PAINTING

SYSTEM AS SPECIFIED.

PAINT REPAIR 2. EXISTING WROUGHT IRON RAILING AND PICKETS TO HAVE LOOSE AND

DETERIORATED PAINT REMOVED THROUGH MECHANICAL REMOVAL. PAINT AREA POTENTIALLY

CONTAINS LAYER OF PAINT THAT CONTAIN LET. RUSTED OR LOOSE PAINT TO REMOVED AND

ENTIRE RAILING TO BE REPAINTED.

PAINT REPAIR 3. EXISTING WOOD ENTABLATURE TO REMAIN. ALL AREA TO BE CLEANED,

INCLUDING AN ANIMAL DEBRIS. EXISTING LOOSE OR CRACKED PAINT TO BE PHYSICALLY

REMOVED BY SCRAPING THE AREA TO AN EVEN OR SMOOTH SURFACE ACCEPTABLE TO

RECEIVE NEW PAINT AREA TO BE INSPECTED AND ANY DAMAGED OR DETERIORATING WOOD TO

HAVE EFFECTED AREA PATCHED, REPAIRED, REMOVED OR REPLACED. AREA TO BE REPAINTED

WITH PAINTING SYSTEM AS SPECIFIED. MISSING OR BROKEN PIECES ARE TO BE REPAIRED OR

REPLACE.

SCREEN REPLACE.

SCREEN REPAIR.

STEEL REPAIR. EXISTING STEEL LINTEL TO REMAIN IN PLACE. ALL EXPOSED PAINT TO BE

SCRAPED AND REMOVED TO BARE STEEL. EXISTING STEEL TO BE INSPECTED FOR CORROSION

AND ALL CORROSION REMOVED AND MITIGATED. PRIME AND PAINT STEEL TO REMAIN.

EXISTING STONE TO BE REPAIRED OR REPLACED.

STONE CLEANING. EXISTING LIMESTONE TRIM IS STAINED. STONE TO BE CLEANED AND ALL

STAINING REMOVED.

Mc5

Mr1

MR1

MR2

NS

Pc1

Pc2

Pc3

SR

Sr

Sr1

Str1

Stc1

WOOD REPAIR 1. EXISTING WOODEN LOUVER. LOUVER TO BE STRIPPED OF LOOSE OR CRACKED

PAINT TO BE PHYSICALLY REMOVED BY SCRAPING THE AREA TO AN EVEN OR SMOOTH SURFACE

ACCEPTABLE TO RECEIVE NEW PAINT. ANY BROKEN PIECES ARE TO BE REMOVED AND

REPLACED AND ANY AREAS OF DETERIORATED WOOD ARE TO BE PATCHED AND REPAIRED IN

PLACE. COMPLETELY REPLACE ALL EXISTING SCREENS IN DORMERS

WOOD REPAIR 2. EXISTING DORMER TO BE REPAIRED. EXISTING DORMER HAS MISSING OR

DETERIORATED WOOD SIDING AND TRIM. REMOVE ALL DAMAGED OR DETERIORATED SIDING AND

TRIM. REPLACE WITH LIKE KIND SIMILAR TO EXISTING. CHECK ALL EXISTING FLASHING ARE

INSURE COMPLETE INSTALLATION. REPLACE MISSING TRIM ELEMENTS. SEE PHOTO SURVEY OF

EXISTING DORMERS. REPAINT ENTIRE DORMER TO MATCH.

WOOD REPAIR 3. EXISTING WOOD COLUMNS TO BE REPAIRED. EXISTING WOOD COLUMNS TO BE

STRIPPED OF LOOSE OR CRACKED PAINT TO BE PHYSICALLY REMOVED BY SCRAPING THE AREA

TO AN EVEN OR SMOOTH SURFACE ACCEPTABLE TO RECEIVE NEW PAINT. ANY BROKEN PIECES

ARE TO BE REMOVED AND REPLACED AND ANY AREAS OF DETERIORATED WOOD ARE TO

PATCHED AND REPAIRED IN PLACE.

WOOD REPAIR 4. EXISTING WOOD COLUMN BASE HAS DETERIORATED OR MISSING PARTS.

COLUMN BASE TO BE REPAIRED OR REPLACED. BROKEN AND/OR MISSING PIECES TO BE

REPLACED. EXISTING PIECES WITH SMALL AREAS OF DETERIORATION AND/OR TO PATCH AND

FILL, ENTIRE BASE AND COLUMN TO BE REPAINTED.

WOOD REPAIR 5. EXISTING WOOD PILASTER TO BE REPAIRED. EXISTING WOOD PILASTER

CONNECTED TO BRICK FACADE TO BE STRIPPED OF LOOSE OR CRACKED PAINT TO BE

PHYSICALLY REMOVED BY SCRAPING THE AREA TO AN EVEN OR SMOOTH SURFACE

ACCEPTABLE TO RECEIVE NEW PAINT. ANY BROKEN PIECES ARE TO BE REMOVED AND

REPLACED AND ANY AREAS OF DETERIORATED WOOD ARE TO BE PATCHED AND REPAIRED IN

PLACE. ALL EXISTING SEALANT BETWEEN WOOD PILASTER AND BRICK TO BE REMOVED AND

REPLACED PRIOR TO PAINTING.

WINDOW REPLACEMENT. EXISTING WINDOW TO BE REMOVED. IMMEDIATE ADJACENT

REMAINING AREA TO BE CLEANED AND PREPARED TO RECEIVE NEW CONSTRUCTION. NEW

ALUMINUM HISTORIC WINDOW TO MATCH EXISTING TO BE INSTALLED IN PLACE OF EXISTING AND

TO BE SEALED.

WINDOW CLEANING 1. EXISTING WINDOW SYSTEM TO BE CLEANED. ALL GLAZING FRAMING TO BE

THOROUGHLY CLEANED. EXISTING SEALANT TO BE REMOVED AND REPLACED WITH NEW

BACKER ROD AND SEALANT.

WINDOW REPAIR 1. EXISTING WINDOW TO REMAIN. ALL GLAZING FROM DECORATIVE ARCHED

WINDOW TO BE REMOVED AND PRESERVED. LEADED FRAME TO BE STRIPPED OF ALL PUTTY

PAINT AND DEBRIS. LEADED FRAME TO BE CLEANED AND ANY RUST OR DETERIORATION

REMOVED AND TO BE REPAINTED. GLAZING TO BE CLEANED AND RESET INTO EXISTING

RESTORED FRAME.

EXISTING WINDOW SCREEN. EXISTING SCREEN TO REMAIN. SCREENING MATERIAL IS TORN AND

TO BE REPAIRED IN EXISTING FRAME.

Wr1

Wr2

Wr3

Wr4

Wr5

WR1

Wwc1

Wwr1

Wwr2

EXISTING STEEL LINTEL TO

REMAIN, LINTEL TO BE

CLEANED, CORROSION

REMOVED, AND REPAINTED.

ALL EXISTING SEALANT TO

BE REMOVED. NEW METAL

FLASHING TO BE INSTALLED

BETWEEN WINDOW AND

BRICK. SEE DETAIL AS201.1.

ALL NEW BACKER ROD AND

SEALANT TO BE INSTALLED.

EXISTING THROUGH WALL

LOUVER TO BE CLEANED.

EXISTING SEALANT TO BE

REMOVED AND NEW

SEALANT TO BE APPLIED

FOR THE ENTIRE

PERIMETER.

EXISTING STONE SILL TO BE

CLEANED,

UNLESS NOTED OTHERWISE, ALL WINDOWS IN

THIS ELEVATION TO BE TREATED AS SUCH.

VIF

VARIES

A A

EXISTING BRICK VENEER

EXISTING STEEL LINTEL

LINTEL TO BE CLEANED OF

CORROSION AND REPAINTED

SEAL TO WINDOW WITH NEW

SEALANT

EXISTING ALUMN. WINDOW

EXISTING DISTANCE BETWEEN OUTER

FACE OF WINDOW AND REAR FACE OF

BRICK VARIES VERIFY IN FIELD AFTER

REMOVAL OF SEALANT

NEW BREAK METAL SIDE FLASHING

FROM LINTEL TO SILL SEE JAMB DETAIL

FULLY ADHERE TO FACE OF WINDOW

AND TO FACE OF BRICK

NEW BREAK METAL SIDE FLASHING SILL

RUN FROM UNDER WINDOW

FULLY ADHERE TO FACE OF WINDOW

AND FACE OF STONE SILL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

NOT F

OR

CONSTRUCTIO

N

C U s e rs \l s to y \D o c u m e n ts

\1

.5

.0

A -M

A S

S

IN

G v ls to y K

A T

J U

.r v t

/6

/2

:1

:4

P M

AS201.3

B98 - ELEVATIONS

GUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

REPAIR BUILDING EXTERIORS

B58, B60 & B98

DANVILLE, IL

550-22-101

58, 60 & 98

07/08/2021 AS LS

100% BID DOCUMENTS

FULLY SPRINKLERED

Revisions: Date:

SCALE: 1/4" = 1'-0"AS201.3

1 B98 - E.3

SCALE: 1/2" = 1'-0"

AS201.3

W.1 W.2 W.3

N.3

N.2

N.1

S.1

S.2

S.3

OPQRS NTU

B98-W.3-U1-W1

B98-W.3-U2-W1

B98-W.3-U3-W1

B98-W.3-U1-W2

B98-W.3-U2-W2

B98-W.3-U3-W2

B98-W.3-T1-W1

B98-W.3-T2-W1

B98-W.3-T3-W1

B98-W.3-T1-W2

B98-W.3-T2-W2

B98-W.3-T3-W2

B98-W.3-Q1-Dr1

B98-W.3-Q2-W1

B98-W.3-Q3-W1

B98-W.3-Q1-Dr2

B98-W.3-Q2-W2

B98-W.3-Q3-W2

B98-W.3-P1-W1

B98-W.3-P2-W1

B98-W.3-P3-W1

B98-W.3-P1-W2

B98-W.3-P2-W2

B98-W.3-P3-W2

B98-W.3-O1-W1

B98-W.3-O2-W1

B98-W.3-O3-W1

B98-W.3-O1-W2

B98-W.3-O2-W2

B98-W.3-O3-W2

B98-W.2-N1-W1

B98-W.2-N2-W1

B98-W.2-N3-W1

SR SR SR SR

SRSRSRSR

Sr

Sr

Sr

NSNS

Sr

BR2

REMOVE STEEL

POSTS AND

RECAULK CORNER

ARCHITECTURAL NOTES

BRICK AND MORTAR CLEANING. THE EXISTING BRICK AND MORTAR IS STAINED AND IS TO BE

CLEANED. ANY LOOSE OR DETERIORATED MORTAR IS TO BE REMOVED AND TUCK POINTED.

BRICK AND MORTAR CLEANING. THE ENTIRE BRICK FACADE SHOWN IN THIS ELEVATION IS TO BE

GENTLY CLEANED TO REMOVED GENERAL DIRT AND DEBRIS AND TO CREATE A FACADE THAT IS

HOMOGENEOUS IN APPEARANCE.

BRICK AND MORTAR CLEANING 3. THE AREA LOCATED UNDER THE COVER ABOVE THE ENTRY

HAS HAD ROOSTING ANIMALS OVER TIME. ALL NESTS, REMNANTS, AND DEBRIS LEFT BY ANIMALS

TO BE COMPLETELY REMOVED AND AREA THOROUGHLY CLEANED.

BRICK AND MORTAR REPAIR. THE BRICK IN THIS AREA IS STAINED AND DETERIORATED AND

MORTAR IS LOOSE OR MISSING. THIS AREA IS TO BE CLEANED COMPLETELY. LOOSE OR

DETERIORATED MORTAR IS TO BE REMOVED AND REPOINTED TO MATCH EXISTING. BROKEN,

DAMAGED AND/OR DETERIORATED OR STRUCTURALLY UNFIT BRICK IS TO BE REMOVED AND

REPLACED WITH BRICK TO MATCH.

BRICK AND MORTAR REPAIR. THE MORTAR IN THIS AREA IS LOOSE. STAINED MORTAR TO BE

CLEANED. LOOSE OR DETERIORATED MORTAR IS TO BE REMOVED AND REPOINTED TO MATCH

EXISTING.

DOOR REPAIR 1. EXISTING HALLOW METAL DOOR TO BE CLEANED, HAVE DETERIORATION AND

RUST REMOVED AND DOORS TO BE REPAINTED.

DOOR REPAIR 2. EXISTING DOOR AND FRAME TO BE STRIPPED AND REPAINTED.

METAL CLEAN 1. EXISTING METAL FLASHING TO BE CLEANED AND INSPECTED TO INSURE

COMPLETE INTEGRITY. ALL SURFACE AREA TO BE CLEANED, SEAMS TO BE INSPECTED AND

PROPERLY SEALED. WHERE FLASHING INSETS INTO EXISTING MASONRY INSURE FLASHING AND

COUNTER FLASHING IS PROPERLY SET AND RESEAL WITH ELASTOMERIC SEALANT.

METAL CLEAN 2. EXISTING METAL COLUMN COPING TO BE CLEANED AND INSPECTED TO INSURE

COMPLETE INTEGRITY. ALL SURFACE AREA TO BE CLEANED, SEAMS TO BE INSPECTED AND

PROPERLY SEALED. WHERE FLASHING INSETS INTO EXISTING MASONRY INSURE FLASHING AND

COUNTER FLASHING IS PROPERLY SET AND RESEAL WITH ELASTOMETRIC SEALANT. REMOVE

EXISTING LOOSE OR CRACKED PAINT TO BE PHYSICALLY REMOVED BY SCRAPING THE AREA TO

AN EVEN OR SMOOTH SURFACE ACCEPTABLE TO RECEIVE NEW PAINT.

METAL CLEAN 3. EXISTING METAL FASCIA TO BE CLEANED AND INSPECTED TO INSURE

COMPLETE INTEGRITY. ALL SURFACE AREA TO BE CLEANED, SEAMS TO BE INSPECTED AND

PROPERLY SEALED. CONNECTION TO MEMBRANE ROOF TO BE INSPECTED AND CORRECTED AS

NECESSARY.

METAL CLEAN 4. EXISTING METAL WINDOW TRIM TO REMAIN, ALL SURFACES TO BE CLEANED.

NEW SEALANT TO BE APPLIED FOR THE ENTIRE PERIMETER AGAINST ADJOINING SURFACES.

Bc1

Bc2

Bc3

BR1

BR2

Dr1

Dr2

Mc1

Mc2

Mc3

Mc4

METAL CLEAN 5. EXISTING METAL PILASTER TO REMAIN. ALL SURFACES TO BE CLEANED. ALL

FASTENERS TO BE TIGHTENED AND MISSING FASTENERS TO BE REPLACED. NEW SEALANT TO

BE APPLIED FOR THE ENTIRE PERIMETER AGAINST ADJOINING SURFACES.

METAL REPAIR 1. EXISTING STEEL LINTEL TO REMAIN. ALL PAINT TO BE STRIPPED FROM LINTEL.

ALL RUST AND DETERIORATION TO BE REMOVED AND REPAIRED. LINTEL TO BE REPAINTED.

METAL REPLACEMENT 1. EXISTING METAL FLASHING OVER TOP OF WINDOW MOLDING TO BE

REMOVED AND REPLACED. NEW METAL FLASHING TO MATCH THE EXISTING TO BE INSTALLED IN

PLACE AND ALL EDGES TO BE SEALED INTO IMMEDIATELY ADJACENT AREAS.

METAL REPLACEMENT 2. ALL FLASHING AT EXISTING DORMERS TO BE REMOVED AND REPLACED

FOR THE ENTIRE PERIMETER OF DORMER AT ROOF.

NO SCREEN.

PAINT REPAIR 1. EXISTING PAINTED WOOD SURFACE, AREA MAY CONTAIN LEAD BASED PAINT

ON ANY OR ALL LAYERS. EXISTING LOOSE OR CRACKED PAINT TO BE PHYSICALLY REMOVED BY

SCRAPING THE AREA TO AN EVEN OR SMOOTH SURFACE ACCEPTABLE TO RECEIVE NEW PAINT.

AREA TO BE INSPECTED AND ANY DAMAGED OR DETERIORATING WOOD TO HAVE EFFECTED

AREA PATCHED, REPAIRED, REMOVED OR REPLACED. AREA TO BE REPAINTED WITH PAINTING

SYSTEM AS SPECIFIED.

PAINT REPAIR 2. EXISTING WROUGHT IRON RAILING AND PICKETS TO HAVE LOOSE AND

DETERIORATED PAINT REMOVED THROUGH MECHANICAL REMOVAL. PAINT AREA POTENTIALLY

CONTAINS LAYER OF PAINT THAT CONTAIN LET. RUSTED OR LOOSE PAINT TO REMOVED AND

ENTIRE RAILING TO BE REPAINTED.

PAINT REPAIR 3. EXISTING WOOD ENTABLATURE TO REMAIN. ALL AREA TO BE CLEANED,

INCLUDING AN ANIMAL DEBRIS. EXISTING LOOSE OR CRACKED PAINT TO BE PHYSICALLY

REMOVED BY SCRAPING THE AREA TO AN EVEN OR SMOOTH SURFACE ACCEPTABLE TO

RECEIVE NEW PAINT AREA TO BE INSPECTED AND ANY DAMAGED OR DETERIORATING WOOD TO

HAVE EFFECTED AREA PATCHED, REPAIRED, REMOVED OR REPLACED. AREA TO BE REPAINTED

WITH PAINTING SYSTEM AS SPECIFIED. MISSING OR BROKEN PIECES ARE TO BE REPAIRED OR

REPLACE.

SCREEN REPLACE.

SCREEN REPAIR.

STEEL REPAIR. EXISTING STEEL LINTEL TO REMAIN IN PLACE. ALL EXPOSED PAINT TO BE

SCRAPED AND REMOVED TO BARE STEEL. EXISTING STEEL TO BE INSPECTED FOR CORROSION

AND ALL CORROSION REMOVED AND MITIGATED. PRIME AND PAINT STEEL TO REMAIN.

EXISTING STONE TO BE REPAIRED OR REPLACED.

STONE CLEANING. EXISTING LIMESTONE TRIM IS STAINED. STONE TO BE CLEANED AND ALL

STAINING REMOVED.

Mc5

Mr1

MR1

MR2

NS

Pc1

Pc2

Pc3

SR

Sr

Sr1

Str1

Stc1

WOOD REPAIR 1. EXISTING WOODEN LOUVER. LOUVER TO BE STRIPPED OF LOOSE OR CRACKED

PAINT TO BE PHYSICALLY REMOVED BY SCRAPING THE AREA TO AN EVEN OR SMOOTH SURFACE

ACCEPTABLE TO RECEIVE NEW PAINT. ANY BROKEN PIECES ARE TO BE REMOVED AND

REPLACED AND ANY AREAS OF DETERIORATED WOOD ARE TO BE PATCHED AND REPAIRED IN

PLACE. COMPLETELY REPLACE ALL EXISTING SCREENS IN DORMERS

WOOD REPAIR 2. EXISTING DORMER TO BE REPAIRED. EXISTING DORMER HAS MISSING OR

DETERIORATED WOOD SIDING AND TRIM. REMOVE ALL DAMAGED OR DETERIORATED SIDING AND

TRIM. REPLACE WITH LIKE KIND SIMILAR TO EXISTING. CHECK ALL EXISTING FLASHING ARE

INSURE COMPLETE INSTALLATION. REPLACE MISSING TRIM ELEMENTS. SEE PHOTO SURVEY OF

EXISTING DORMERS. REPAINT ENTIRE DORMER TO MATCH.

WOOD REPAIR 3. EXISTING WOOD COLUMNS TO BE REPAIRED. EXISTING WOOD COLUMNS TO BE

STRIPPED OF LOOSE OR CRACKED PAINT TO BE PHYSICALLY REMOVED BY SCRAPING THE AREA

TO AN EVEN OR SMOOTH SURFACE ACCEPTABLE TO RECEIVE NEW PAINT. ANY BROKEN PIECES

ARE TO BE REMOVED AND REPLACED AND ANY AREAS OF DETERIORATED WOOD ARE TO

PATCHED AND REPAIRED IN PLACE.

WOOD REPAIR 4. EXISTING WOOD COLUMN BASE HAS DETERIORATED OR MISSING PARTS.

COLUMN BASE TO BE REPAIRED OR REPLACED. BROKEN AND/OR MISSING PIECES TO BE

REPLACED. EXISTING PIECES WITH SMALL AREAS OF DETERIORATION AND/OR TO PATCH AND

FILL, ENTIRE BASE AND COLUMN TO BE REPAINTED.

WOOD REPAIR 5. EXISTING WOOD PILASTER TO BE REPAIRED. EXISTING WOOD PILASTER

CONNECTED TO BRICK FACADE TO BE STRIPPED OF LOOSE OR CRACKED PAINT TO BE

PHYSICALLY REMOVED BY SCRAPING THE AREA TO AN EVEN OR SMOOTH SURFACE

ACCEPTABLE TO RECEIVE NEW PAINT. ANY BROKEN PIECES ARE TO BE REMOVED AND

REPLACED AND ANY AREAS OF DETERIORATED WOOD ARE TO BE PATCHED AND REPAIRED IN

PLACE. ALL EXISTING SEALANT BETWEEN WOOD PILASTER AND BRICK TO BE REMOVED AND

REPLACED PRIOR TO PAINTING.

WINDOW REPLACEMENT. EXISTING WINDOW TO BE REMOVED. IMMEDIATE ADJACENT

REMAINING AREA TO BE CLEANED AND PREPARED TO RECEIVE NEW CONSTRUCTION. NEW

ALUMINUM HISTORIC WINDOW TO MATCH EXISTING TO BE INSTALLED IN PLACE OF EXISTING AND

TO BE SEALED.

WINDOW CLEANING 1. EXISTING WINDOW SYSTEM TO BE CLEANED. ALL GLAZING FRAMING TO BE

THOROUGHLY CLEANED. EXISTING SEALANT TO BE REMOVED AND REPLACED WITH NEW

BACKER ROD AND SEALANT.

WINDOW REPAIR 1. EXISTING WINDOW TO REMAIN. ALL GLAZING FROM DECORATIVE ARCHED

WINDOW TO BE REMOVED AND PRESERVED. LEADED FRAME TO BE STRIPPED OF ALL PUTTY

PAINT AND DEBRIS. LEADED FRAME TO BE CLEANED AND ANY RUST OR DETERIORATION

REMOVED AND TO BE REPAINTED. GLAZING TO BE CLEANED AND RESET INTO EXISTING

RESTORED FRAME.

EXISTING WINDOW SCREEN. EXISTING SCREEN TO REMAIN. SCREENING MATERIAL IS TORN AND

TO BE REPAIRED IN EXISTING FRAME.

Wr1

Wr2

Wr3

Wr4

Wr5

WR1

Wwc1

Wwr1

Wwr2

EXISTING STEEL LINTEL TO

REMAIN, LINTEL TO BE

CLEANED, CORROSION

REMOVED, AND REPAINTED.

ALL EXISTING SEALANT TO

BE REMOVED. NEW METAL

FLASHING TO BE INSTALLED

BETWEEN WINDOW AND

BRICK. SEE DETAIL AS201.1.

ALL NEW BACKER ROD AND

SEALANT TO BE INSTALLED.

EXISTING THROUGH WALL

LOUVER TO BE CLEANED.

EXISTING SEALANT TO BE

REMOVED AND NEW

SEALANT TO BE APPLIED

FOR THE ENTIRE

PERIMETER.

EXISTING STONE SILL TO BE

CLEANED,

UNLESS NOTED OTHERWISE, ALL WINDOWS IN

THIS ELEVATION TO BE TREATED AS SUCH.

VIF

VARIES

A A

EXISTING BRICK VENEER

EXISTING STEEL LINTEL

LINTEL TO BE CLEANED OF

CORROSION AND REPAINTED

SEAL TO WINDOW WITH NEW

SEALANT

EXISTING ALUMN. WINDOW

EXISTING DISTANCE BETWEEN OUTER

FACE OF WINDOW AND REAR FACE OF

BRICK VARIES VERIFY IN FIELD AFTER

REMOVAL OF SEALANT

NEW BREAK METAL SIDE FLASHING

FROM LINTEL TO SILL SEE JAMB DETAIL

FULLY ADHERE TO FACE OF WINDOW

AND TO FACE OF BRICK

NEW BREAK METAL SIDE FLASHING SILL

RUN FROM UNDER WINDOW

FULLY ADHERE TO FACE OF WINDOW

AND FACE OF STONE SILL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

NOT F

OR

CONSTRUCTIO

N

C U s e rs \l s to y \D o c u m e n ts

\1

.5

.0

A -M

A S

S

IN

G v ls to y K

A T

J U

.r v t

/6

/2

:1

:4

P M

AS201.4

B98 - ELEVATIONS

GUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

REPAIR BUILDING EXTERIORS

B58, B60 & B98

DANVILLE, IL

550-22-101

58, 60 & 98

07/08/2021 AS LS

100% BID DOCUMENTS

FULLY SPRINKLERED

Revisions: Date:

SCALE: 1/4" = 1'-0"AS201.4

1 B98 - W.3

SCALE: 1/2" = 1'-0"

AS201.4

W.1 W.2 W.3

N.3

N.2

N.1

S.1

S.2

S.3

HIJKLMN

B98-W.2-N1-W1

B98-W.2-N2-W1

B98-W.2-N3-W1

B98-W.2-M1-W1

B98-W.2-M2-W1

B98-W.2-M3-W1

B98-W.2-L1-W1

B98-W.2-L2-W1

B98-W.2-L3-W1

B98-W.2-K1-W1

B98-W.2-K2-W1

B98-W.2-K3-W1

B98-W.2-J2-W1

B98-W.2-J3-W1

B98-W.2-I1-W1

B98-W.2-I2-W1

B98-W.2-I3-W1

B98-W.2-H1-W1

B98-W.2-H2-W1

B98-W.2-H3-W1

B98-W.2-M1-W2

B98-W.2-M2-W2

B98-W.2-M3-W2

B98-W.2-K1-W2

B98-W.2-K2-W2

B98-W.2-K3-W2

B98-W.2-I1-W2

B98-W.2-I2-W2

B98-W.2-I3-W2

B98-W.2-K2-W3

B98-W.2-K3-W3

B98-W.2-J1-Dr1 B98-W.2-J1-Dr2

Wwr2Wwr2

Wwr2

B98-W.2-K1-W3

Sr

Sr

Sr

Sr

SR NS

NS

NS

ARCHITECTURAL NOTES

BRICK AND MORTAR CLEANING. THE EXISTING BRICK AND MORTAR IS STAINED AND IS TO BE

CLEANED. ANY LOOSE OR DETERIORATED MORTAR IS TO BE REMOVED AND TUCK POINTED.

BRICK AND MORTAR CLEANING. THE ENTIRE BRICK FACADE SHOWN IN THIS ELEVATION IS TO BE

GENTLY CLEANED TO REMOVED GENERAL DIRT AND DEBRIS AND TO CREATE A FACADE THAT IS

HOMOGENEOUS IN APPEARANCE.

BRICK AND MORTAR CLEANING 3. THE AREA LOCATED UNDER THE COVER ABOVE THE ENTRY

HAS HAD ROOSTING ANIMALS OVER TIME. ALL NESTS, REMNANTS, AND DEBRIS LEFT BY ANIMALS

TO BE COMPLETELY REMOVED AND AREA THOROUGHLY CLEANED.

BRICK AND MORTAR REPAIR. THE BRICK IN THIS AREA IS STAINED AND DETERIORATED AND

MORTAR IS LOOSE OR MISSING. THIS AREA IS TO BE CLEANED COMPLETELY. LOOSE OR

DETERIORATED MORTAR IS TO BE REMOVED AND REPOINTED TO MATCH EXISTING. BROKEN,

DAMAGED AND/OR DETERIORATED OR STRUCTURALLY UNFIT BRICK IS TO BE REMOVED AND

REPLACED WITH BRICK TO MATCH.

BRICK AND MORTAR REPAIR. THE MORTAR IN THIS AREA IS LOOSE. STAINED MORTAR TO BE

CLEANED. LOOSE OR DETERIORATED MORTAR IS TO BE REMOVED AND REPOINTED TO MATCH

EXISTING.

DOOR REPAIR 1. EXISTING HALLOW METAL DOOR TO BE CLEANED, HAVE DETERIORATION AND

RUST REMOVED AND DOORS TO BE REPAINTED.

DOOR REPAIR 2. EXISTING DOOR AND FRAME TO BE STRIPPED AND REPAINTED.

METAL CLEAN 1. EXISTING METAL FLASHING TO BE CLEANED AND INSPECTED TO INSURE

COMPLETE INTEGRITY. ALL SURFACE AREA TO BE CLEANED, SEAMS TO BE INSPECTED AND

PROPERLY SEALED. WHERE FLASHING INSETS INTO EXISTING MASONRY INSURE FLASHING AND

COUNTER FLASHING IS PROPERLY SET AND RESEAL WITH ELASTOMERIC SEALANT.

METAL CLEAN 2. EXISTING METAL COLUMN COPING TO BE CLEANED AND INSPECTED TO INSURE

COMPLETE INTEGRITY. ALL SURFACE AREA TO BE CLEANED, SEAMS TO BE INSPECTED AND

PROPERLY SEALED. WHERE FLASHING INSETS INTO EXISTING MASONRY INSURE FLASHING AND

COUNTER FLASHING IS PROPERLY SET AND RESEAL WITH ELASTOMETRIC SEALANT. REMOVE

EXISTING LOOSE OR CRACKED PAINT TO BE PHYSICALLY REMOVED BY SCRAPING THE AREA TO

AN EVEN OR SMOOTH SURFACE ACCEPTABLE TO RECEIVE NEW PAINT.

METAL CLEAN 3. EXISTING METAL FASCIA TO BE CLEANED AND INSPECTED TO INSURE

COMPLETE INTEGRITY. ALL SURFACE AREA TO BE CLEANED, SEAMS TO BE INSPECTED AND

PROPERLY SEALED. CONNECTION TO MEMBRANE ROOF TO BE INSPECTED AND CORRECTED AS

NECESSARY.

METAL CLEAN 4. EXISTING METAL WINDOW TRIM TO REMAIN, ALL SURFACES TO BE CLEANED.

NEW SEALANT TO BE APPLIED FOR THE ENTIRE PERIMETER AGAINST ADJOINING SURFACES.

Bc1

Bc2

Bc3

BR1

BR2

Dr1

Dr2

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .