PAGE 1 OF1. REQUISITION NO.
2. CONTRACT NO. 3. AWARD/EFFECTIVE DATE 4. ORDER NO. 5. SOLICITATION NUMBER 6. SOLICITATION ISSUE DATE
a. NAME b. TELEPHONE NO. (No Collect Calls) 8. OFFER DUE DATE/LOCAL
TIME
9. ISSUED BY CODE 10. THIS ACQUISITION IS UNRESTRICTED OR SET ASIDE: % FOR:
SMALL BUSINESS
HUBZONE SMALL
BUSINESS
SERVICE-DISABLED
VETERAN-OWNED
SMALL BUSINESS
WOMEN-OWNED SMALL BUSINESS
(WOSB) ELIGIBLE UNDER THE WOMEN-OWNED
SMALL BUSINESS PROGRAM
EDWOSB
8(A)
NAICS:
SIZE STANDARD:
11. DELIVERY FOR FOB DESTINA-
TION UNLESS BLOCK IS
MARKED
SEE SCHEDULE
12. DISCOUNT TERMS
13a. THIS CONTRACT IS A
RATED ORDER UNDER
DPAS (15 CFR 700)
13b. RATING
14. METHOD OF SOLICITATION
RFQ IFB RFP
15. DELIVER TO CODE 16. ADMINISTERED BY CODE
17a. CONTRACTOR/OFFEROR CODE FACILITY CODE 18a. PAYMENT WILL BE MADE BY CODE
TELEPHONE NO. DUNS: DUNS+4:
PHONE: FAX:
17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT SUCH ADDRESS IN OFFER
18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a UNLESS BLOCK BELOW IS CHECKED
SEE ADDENDUM
19. 20. 21. 22. 23. 24.
ITEM NO. SCHEDULE OF SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
(Use Reverse and/or Attach Additional Sheets as Necessary)
25. ACCOUNTING AND APPROPRIATION DATA 26. TOTAL AWARD AMOUNT (For Govt. Use Only)
27a. SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1, 52.212-4. FAR 52.212-3 AND 52.212-5 ARE ATTACHED. ADDENDA ARE ARE NOT ATTACHED.
27b. CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212-4. FAR 52.212-5 IS ATTACHED. ADDENDA ARE ARE NOT ATTACHED
28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN _______________ 29. AWARD OF CONTRACT: REF. ___________________________________ OFFER COPIES TO ISSUING OFFICE. CONTRACTOR AGREES TO FURNISH AND DATED ________________________________. YOUR OFFER ON SOLICITATION DELIVER ALL ITEMS SET FORTH OR OTHERWISE IDENTIFIED ABOVE AND ON ANY (BLOCK 5), INCLUDING ANY ADDITIONS OR CHANGES WHICH ARE ADDITIONAL SHEETS SUBJECT TO THE TERMS AND CONDITIONS SPECIFIED SET FORTH HEREIN IS ACCEPTED AS TO ITEMS:
30a. SIGNATURE OF OFFEROR/CONTRACTOR 31a. UNITED STATES OF AMERICA (SIGNATURE OF CONTRACTING OFFICER)
30b. NAME AND TITLE OF SIGNER (TYPE OR PRINT) 30c. DATE SIGNED 31b. NAME OF CONTRACTING OFFICER (TYPE OR PRINT) 31c. DATE SIGNED
AUTHORIZED FOR LOCAL REPRODUCTION (REV. NOV 2021)
PREVIOUS EDITION IS NOT USABLE Prescribed by GSA - FAR (48 CFR) 53.212
7. FOR SOLICITATION
INFORMATION CALL:
STANDARD FORM 1449
SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES
OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, & 30
36C26322Q0434 04-19-2022
Cameron Rick 651-293-3036 05-03-2022 12:00pm CDT
36C263 Department of Veterans Affairs
NETWORK 23 CONTRACTING OFFICE
316 Robert Street N. STE. 506 St. Paul MN 55101 Cameron Rick cameron.rick@va.gov
X 100
X
541380
$16.5 Million
N/A
X
36C568
Department of Veterans Affairs Ft. Meade VAMC 113 Comanche Road
Ft. Meade SD 57741
36C263
Department of Veterans Affairs
NETWORK 23 CONTRACTING OFFICE
316 Robert Street N. STE. 506 St. Paul MN 55101
Y
Department of Veterans Affairs Financial Services Center PO Box 149971
Austin TX 78714-9971
See CONTINUATION Page
This solicitation is to provide service to the Ft. Meade & Hot Springs VAMCs.
See attached SOW for Pharmacy and Laboratory Certification of Equipment and Rooms services in the VAMC facilities.
Note block 30 - This document must be signed and returned in order to be considered. Email all required and completed documents to: cameron.rick@va.gov.
Submit written questions via email by 12:00pm April 27, 2022
**No telephonic questions will be accepted.**
Responses to questions will be posted as an amendment to the solicitation.
Solicitation will close at 12:00 PM CDT on May 03, 2022.
This solicitation is a total VOSB set-aside.
See CONTINUATION Page
X
X 1
Pamela Phillips
36C26322Q0434
Table of Contents
SECTION A
A.1 SF 1449 SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL PRODUCTS
AND COMMERCIAL SERVICES
SECTION B - CONTINUATION OF SF 1449 BLOCKS
B.1 CONTRACT ADMINISTRATION DATA
STATEMENT OF WORK
VHA Supplemental Contract Requirements for Combatting COVID-19
B.2 PRICE/COST SCHEDULE
ITEM INFORMATION
B.3 TERMS AND CONDITIONS
B.4 ADMINISTRATIVE DATA
B.5 PRICING
B.6 GENERAL SERVICES ORDERS
B.7 NONPERSONAL SERVICES
B.8 AUTHORIZED LIMITS
B.9 OBLIGATION OF FUNDS
B.10 PERIOD OF PERFORMANCE
B.11 AUTHORIZED INDIVIDUALS
B.12 ORDER FORMAT
B.13 AUTHORIZED REPRESENTATIVES
B.14 FEDERAL HOLIDAYS
B.15 PROHIBIT ACTIVITIES
B.16 INVOICES
B.17 PRECEDENCE
SECTION C - CONTRACT CLAUSES
C.1 52.212-4 CONTRACT TERMS AND CONDITIONS—COMMERCIAL PRODUCTS
AND COMMERCIAL SERVICES (NOV 2021)
C.2 52.222-55 MINIMUM WAGES FOR CONTRACTOR WORKERS UNDER
EXECUTIVE ORDER 14026 (JAN 2022)
C.3 52.217-8 OPTION TO EXTEND SERVICES (NOV 1999)
52.217-8 ADDENDUM:
C.4 52.217-9 OPTION TO EXTEND THE TERM OF THE CONTRACT (MAR 2000) ...51
C.5 VAAR 852.212-70 PROVISIONS AND CLAUSES APPLICABLE TO VA
ACQUISITION OF COMMERCIAL ITEMS (APR 2020)
C.6 VAAR 852.219-74 LIMITATIONS ON SUBCONTRACTING—MONITORING AND
COMPLIANCE (JUL 2018)
C.7 VAAR 852.219-77 VA NOTICE OF LIMITATIONS ON SUBCONTRACTING—
CERTIFICATE OF COMPLIANCE FOR SERVICES AND CONSTRUCTION (SEP 2021)
(DEVIATION)
C.8 VAAR 852.219-75 SUBCONTRACTING COMMITMENTS MONITORING AND
COMPLIANCE (JUL 2018)
C.9 NOTICE LISTING CLAUSES INCORPORATED BY REFERENCE
C.10 52.212-5 CONTRACT TERMS AND CONDITIONS REQUIRED TO IMPLEMENT
STATUTES OR EXECUTIVE ORDERS—COMMERCIAL ITEMS (JAN 2021) (JUL 2020)
(DEVIATION)
SECTION D - CONTRACT DOCUMENTS, EXHIBITS, OR ATTACHMENTS
SECTION E - SOLICITATION PROVISIONS
E.1 52.212-1 INSTRUCTIONS TO OFFERORS—COMMERCIAL PRODUCTS AND
COMMERCIAL SERVICES (NOV 2021)
ADDENDUM to FAR 52.212-1 INSTRUCTIONS TO OFFERORS—COMMERCIAL
ITEMS
E.2 52.204-24 REPRESENTATION REGARDING CERTAIN TELECOMMUNICATIONS
AND VIDEO SURVEILLANCE SERVICES OR EQUIPMENT (NOV 2021)
E.3 52.212-2 EVALUATION—COMMERCIAL ITEMS (OCT 2014)
E.4 52.216-1 TYPE OF CONTRACT (APR 1984)
E.5 52.233-2 SERVICE OF PROTEST (SEP 2006)
E.6 52.212-3 OFFEROR REPRESENTATIONS AND CERTIFICATIONS—
COMMERCIAL ITEMS (FEB 2021) (JUL 2020) (DEVIATION)
SECTION B - CONTINUATION OF SF 1449 BLOCKS
B.1 CONTRACT ADMINISTRATION DATA
1. Contract Administration: All contract administration matters will be handled by the following individuals:
a. CONTRACTOR:
b. GOVERNMENT: Contracting Officer 36C263 Pamela Phillips
Department of Veterans Affairs
NETWORK 23 CONTRACTING OFFICE
316 Robert Street N. STE. 506
St. Paul MN 55101
2. CONTRACTOR REMITTANCE ADDRESS: All payments by the Government to the contractor will be made in accordance with:
[X] 52.232-33, Payment by Electronic Funds Transfer—System For Award Management, or
[] 52.232-36, Payment by Third Party
3. INVOICES: Invoices shall be submitted in arrears:
a. Quarterly []
b. Semi-Annually []
c. Other [X] Monthly
4. GOVERNMENT INVOICE ADDRESS: All Invoices from the contractor shall be submitted electronically in accordance with VAAR Clause 852.232-72 Electronic Submission of Payment Requests.
Department of Veterans Affairs
Financial Services Center
PO Box 149971
Austin TX 78714-9971
ACKNOWLEDGMENT OF AMENDMENTS: The offeror acknowledges receipt of amendments to the Solicitation numbered and dated as follows:
AMENDMENT NO DATE
STATEMENT OF WORK
Pharmacy and Laboratory Certification of Equipment and Rooms
1.0General:
1.1Background
VA Black Hills Health Care System (BHHCS) is requesting a service contract for the certification of laboratory class II biologic safety cabinets (BSC), certification of pharmacy United States Pharmacopeia (USP) 795, 797, and 800 equipment and rooms, and the decontamination of two (2) laboratory class II BSC.
1.2 Objective
The contractor will perform work detailed in this statement of work (SOW) on the date and time mutually agreed upon by the Contractor and Contracting Officer Representavie (COR). The contractor shall notify the COR or authorized representative at least two weeks in advance of the date of planned testing or certification. The contractor is responsible for contacting the COR for the scheduling of services.
1.2Scope of Work
Pharmacy: Will be certified every 5-6 months with each site, Fort Meade and Hot Springs alternating certification every 3 months. This will result in off set certification dates for both sites.
Laboratory: Will be certified annually at Fort Meade and Hot Springs.
Decomissioning decontamination of laboratory hoods will occur within the first year of this contract.
Bidders will not have the opportunity to inspect equipment or spaces listed before submitting bids.
The contractor shall provide all labor, equipment, materials (including replacement parts), supplies, tools, transportation, and round trip travel necessary to perform all inspections, testing, certifications/recertifications, preventative maintenance and repairs for all equipment and rooms listed below as required throughout the contract period in accordance with manufacturer recommendations or practice standards. Parts that cost less than or equal to $100.00 dollars will be provided by the contractor.
Minor repairs are repairs that can be completed on site, in less than three
(3) hours at no additional cost. Preventative maintenance also includes replacement of High-Efficiency Particulate Air (HEPA) filters for all equipment and rooms listed below as recommended/required.
If traveling to both Fort Meade and Hot Springs in a single trip, travel will be charged at the further of the two sites not both.
The contractor shall conduct a rate recovery test of the cleanrooms (including the containment segregated compounding area (C-SCA)) to determine impacts to temperature, humidity, pressure differentials, air changes per hour (ACPH), and internationalclassification for standards (ISO) classification when the heating, ventilation, and air conditioning (HVAC) and exhaust is shut off. May include viables as determined. Rate recovery test limited to rooms B36, B37 and B38 at Fort Meade and rooms D016B, D016C and D016D at Hot Springs. The goal of this testing is to detemine the amount of time the rooms remain functional for compounding sterile compounds and to determine the level of cleaning needed with outages. The requested time frame is up to 6 hours or until failure. Rate recovery testing will occur within the first year of this contract.
Additional Services as needed:
If certification fails parameters that cause the shut-down of equipment or rooms or decreases the beyound use dating (BUD) of compounded products, repair and/or recertification must be coordinated with the COR or authroized representative within two business days upon determination of failure. Repair and/or recertification should be conducted within 2 weeks and must be conducted within 4 weeks of failure.
Recertification of rooms and equipment for either equipment failure, room or equipment changes causing a need for certification, or an additional certification needed in a years timeframe to meet the requirements for receiving results.
BHHCS uses a variety of engineering controls to limit employee exposures to hazardous contaminants while also providing a safe and effective preparation for patients.
Pharmacy: Pharmacy Service has both secondary engineering controls (SECs) and containment secondary engineering controls (C-SECs) which make up the USP 797 and USP 800 compliant cleanroom suite and the C- SCA. The cleanroom suite and the C-SCA contain a variety of primary engineering controls (PECs) and contaiment primary engineering controls (C-PECs). The PECs include laminar airflow work-benches (LAFW) for all non-hazardous sterile compounding and the C-PECs include externally vented Class II biological safety cabinets (BSCs), an externally vented compounding aseptic containment isolator (CACI) for hazardous sterile compounding, and a containment ventilated enclosure (CVE) for hazardous non-sterile compounding. HEPA-filtered pass throughs are also present in the cleanroom suites.
Lab: The class II BSC used for processing and culturing biosafety agents are comprised of externally vented class II BSC type A1, class II BSC type A/B3, and recirculated air with class II BSC type A2 devices.
Section 5 below is the best estimate of the number and types of rooms and equipment expected to be tested, sampled, serviced, and certified by the contractor. BHHCS reserves the right to delete or add units as required. No work is authorized outside the scope of this SOW without the prior written approval of the Contracting Officer (CO). Only the CO has the right to obligate funding or order work not expressly detailed in this SOW.
The Government shall not be held responsible for payment for any work performed by the contractor that is outside the scope of this contract or without the prior approval of the CO.
1.3 Place of Performance
VA Black Hills Health Care System
Fort Meade VA
Building 148 Police Office Badging location
Building 113 Hood/Room locations
113 Comanche Road
Fort Meade, SD 57741
Hot Springs VA
Building 14 Engineering Badging
Building 12 Hood/Room locations
500 North 5th Street
Hot Springs, SD 57747
2.0 Specific Requirements/Tasks
2.1 CONTRACTOR QUALIFICATIONS:
Contractor must have a current controlled enviroment testing association (CETA) National Board of Testing (CNBT) accredited Cleanroom Certified Technician for Sterile Compounding Facilities with 5 or more years of experience. All cleanroom performance testing and signing of reports must be performed by an individual with the aforementioned accreditations.
Furthermore, per VHA Directive 1108.12; All vendors used to conduct primary and secondary engineering controls certifications/assessments must be registered with CETA. In addition, the contractor must certify against NSF/ANSI 49 standards for biosafety level 2 clinical microbiology operations.
Verification of experience may be requested by BHHCS. Contractor shall provide references as proof, prior to bid, of 5+ years the company has performed equipment and room certifications as outlined in this SOW.
Contractor shall provide two recent certification reports from two sites, similar in scope, prior to bid.
Copies of pertinent certifications and/or licenses will also be required prior to beginning any work.
2.2 GENERAL REQUIREMENTS BY CONTRACTOR:
2.2.1 Attendance of an on-site pre-certification meeting with identified BHHCS staff to review site policies, operations, hazardous drug areas/equipment, etc. prior to beginning any work.
2.2.2 Ensure equipment functions in conformance with the most up to date published edition of the applicable standards including the USP, CETA, American Soceity of Heating, Refridgerating and Air-Conditioning Engineers (ASHRAE), Clinical and Laboratory Standards institute (CLSI), National Sanitation Foundation (NSF)/American National Standards Institute (ANSI), National Institutes of Health (NIH), Enviromental Protection Agency (EPA), Joint Commission, Underwriter Laboratories (UL), Occupational Safety and Health Administration (OSHA), CNBT and VA standards.
2.2.3 Any classified or unclassified room or equipment that is not certifiable must be communicated to the COR or authroized representative, by the contractor, within 30 minutes of failure or inability to certify. In addition, the engineering control in question will be marked as such with clear signage that the unit is out of service until further notice. Any "Failed" room or equipment tested must be communicated verbally and in writing. The COR or authorized representative may request recommendations from contractor in developing a corrective action plan.
2.2.4 For each PEC passing the required certification tests, the contractor will supply each unit with a certification sticker with the following information:
company name, address, and phone number, date tested, reference report number, recertification month/year, and technician signature.
3.0 Description of Work:
3.1 Pharmacy:
3.1.1 The contractor shall perform all required facility related testing and sampling according to manufacturer recommendations and to the current versions of CETA application guides (CAGs) to determine whether the facility’s rooms and equipment, as detetailed below, meet certification requirements as outlined in the current version of USP 795, 797 and 800.
CETA CAGs are the mandatory standard and no “equivalent” standards may be used for certification purposes.
3.2 Laboratory:
3.2.1 The contractor shall perform all required facility related testing and sampling according to manufacturer recommendations and to the most current versions of NSF/ANSI 49 and/or their replacement application guides to determine whether the facility’s laboratory BSCs used for culturing level 2 biosafety agents can be certified for use under current Clinical and Laboratory Standards Institute approved clinical laboratory safety guidelines (CLSI GP17 A3).
3.2.2 The contractor shall appropriately decontaminate unused laboraotry class II BSC, to include appropriate disposal of used HEPA filters. The decontamination shall be performed to the extent the BSC can be safely removed and safe construction can take place after removal.
3.3 For Meade, SD (See Appendix A, B, E, & F):
3.3.1 Pharmacy:
3.3.1.1 Rooms:
Building 113, Room B31, Hazardous drug storage/Non-sterile hazardous drug compounding, One in-ceiling HEPA Filter FFU-1
Building 113, Room B36, Pharmacy Sterile Non-Haz Buffer (PHSC1), 8.04 m2 (ISO 7), One in-ceiling HEPA Filter FFU-2
Building 113, Room B37, Ante-Room (PHAR1), 7.41 m2 (ISO 7), One in-ceiling HEPA Filter FFU-2
Building 113, Room B38, Sterile Hazardous Buffer (PHAR1),
13.45 m2 (ISO 7), Two in-ceiling HEPA Filter FFU-2
Building 113, Room B39, Pharmacy receiving/Hazardous drug storage room
Building 113, Room B40, Hazardous waste storage room Building 113, Room 191F, Hazardous drug storage, One in-ceiling HEPA Filter FFU-1
Building 113, Room 237 or a similar room, Temporary/Backup Non-Haz SCA
Building 113, Room 128G or a similar room, Temporary/Backup Haz C-SCA
3.3.1.2 Equipment:
Pharmacy AireGard ES 5-foot Horizontal Laminar Airflow Workstation (NU-240-530), SN: 202358112020, Building 113, Room B36, qty:1
Pass-through, Building 113, Room B36, qty:1 (Pass-through from B36 to general pharmacy area) Clean Air Products, Pass through wall mount HEPA Filter Stainless Steel - Model: CAP18WFBHF-SST-12Wx12Hx12D
Pharmacy LabGard ES AIR 4-foot Class II, Type A2 Biosafety Cabinet (NU-543-400), SN: 194505101519, Building 113, Room B38, qty:1
Pharmacy NuAire, CACI, NU-NR 800-400, SN:185656042518, Building 113, Room B38, qty:1
Pass-through, Building 113, Room B38, qty:1 (Pass-through from B38 to general pharmacy area) Clean Air Products, Pass through wall mount HEPA Filter Stainless Steel - Model: CAP18WFBHF-SST-12Wx12Hx12D
Pharmacy LabGard 4 foot Bench Top Containment Ventilated Enclosure (NU-813-400), SN: 194380100819, Building 113, Room B31, qty:1
Mid wall air exhaust, Building 113, Room B39, qty:1 Mid wall air exhaust, Building 113, Room 191F, qty 1 PharmGard Positive Pressure Recirculating Compounding
Aseptic Isolator (CAI), Nuaire NU-PR797-400, Serial Number 112300012507 or LFWB, Building 113, Room 237 or similar room, qty 1
BSC Hood or rental unit, Building 113, Room 128G or similar room, qty 1
3.3.2 Lab:
3.3.2.1 Equipment:
NuAire NU – 425-400, Class II Type A/B3, Biological Safety Cabinet, SN: 14898030102, Room 138, Qty:1
3.4 Hot Springs (See Appendix C, D, & F drawings):
3.4.1 Pharmacy:
3.4.1.2 Rooms:
Building 12, Room D012, Pharmacy Receiving 17.84 m2 Building 12, Room D016B, Pharmacy Sterile Non-Haz
Buffer, 6.93 m2 (ISO 7), One in-ceiling HEPA Filter FFU-2
Building 12, Room D016C, Pharmacy Ante-Room, 7.05 m2 (ISO 8), One in-ceiling HEPA Filter FFU-2
Building 12, Room D016D, Pharmacy Hazardous Drug Containment Segregated Compounding Area (C-SCA), 5.77 m2, One in-ceiling HEPA Filter FFU-2
Building 12, Room D016E, Pharmacy Non-Sterile Hazardous Drug Compounding/HD Storage, 11.89 m2
Building 12, Room D005, Hazardous Waste Storage Room,
10.41 m2
3.4.1.3 Equipment:
Pharmacy AireGard ES 4 foot Horizontal Laminar Airflow Workstation (NU-240-430), SN: 202459112420, Building 12, Room, D016B, qty:1
Pharmacy LabGard ES AIR 4 foot Class II, Type A2 Biosafety Cabinet (NU-543-400), SN: 19444810119, Building 12, Room, D016D, qty:1
Pharmacy LabGard 4 foot Bench Top Containment Ventilated Enclosure (NU-813-400), SN: 194381100819, Building 12, Room, D016E, qty:1
Mid wall air exhaust, Building 12, Room D012, Qty:1 Pass-through, Building 12 Room D016B, qty:1 (Pass-through from D016B to D016C) Clean Air Products, Pass through wall mount HEPA Filter Stainless Steel - Model:
CAP18WFBHF-SST-12Wx12Hx12D
3.4.2 Lab:
3.4.2.1 Equipment:
LabGard ES 4 foot, Class II Type A2, Biological Safety Cabinet, SN: 198175042320, Room 400, qty:1
Decomissioning decontaminate: Labconco Model 70152, BSC class II type A1, SN 2577, room 400, qty: 1, outlined in red on appendix D
Decomissioning decontaminate: The Baker Company Model VBM600, BSC class II type A1, SN SG-21586V, room 400, qty: 1, outlined in red on appendix D
3.5 Secondary Engineering Control (SEC) Testing:
3.5.1 Contractor must calculate the total room volume for all rooms being tested/certified. A sketch of the room with dimensions, exhaust/supply diffuser locations and equipment locations must be included in the report.
The report provided will specify measured flow rates detailing returns and supply that were obtained during the testing.
3.5.2 Facility related testing for rooms and equipment certifications (listed above 5C and 5D) will include but is not limited to the below. It is expected the contractor will provide guidance on this prior to the site visit to vet out any discrepancies or missed tests. The following guidelines will be followed USP 795, 797, 800, CAG-006-2010, CAG-002-2006, GAG-
003-2006, NSF/ANSI 49.
Airflow test HEPA filter integrity testing for ceiling units, pass-throughs, and hoods.
Induction leak/backstreaming test
Dynamic Airflow viualization test (smoke pattern) in hoods and if needed in the rooms o Airflow smoke pattern test shall be provided digitally, capable of being viewed on Windows 10 computer system
Chamber pressure test Site installation assessment tests Particle containment integreity test and enclosure leak test Cabinet integrity/leak test Exhaust Alarm Test (for BCS and/or CACI certification only) Vibration test upon request Noise level test upon request Air Changes Per Hour (ACPH)/Air Change Rate Testing Verification of Temperature and Humidity Pressure differential testing of each opening (reported in inch water column) o The contractor should report all pressures to an accuracy of
0.001” water column (3 decimal places). Pressure differentials will be reflected on a report showing the sketch of the room(s)
3.6 Environmental sampling:
3.6.1 Non-Viable Particle Testing: The contractor shall perform environmental nonviable particle testing. The contractor shall derive the minimum number of sampling locations using current CAG-003-2006 and report based on ISO Standard 14644-1. Testing shall be performed by qualified operators using current, state-of-the-art electronic equipment with results of the following:
3.6.1.1 ISO Class 5: not more than 3520 particles 0.5 μm and
larger size per cubic meter of air.
3.6.1.2 ISO Class 7: not more than 352,000 particles 0.5 μm and larger size per cubic meter of air.
3.6.1.3 ISO Class 8: not more than 3,520,000 particles 0.5 μm and larger size per cubic meter of air.
3.6.2 Viable air sampling: bacterial and fungal testing for air quality in accordance with USP 797 and CAG-009.
3.6.2.1 A high volume impaction sampler device shall be used.
Each air sample shall be a minimum of 1000 liters of air volume in all classified areas. Air samples shall be collecting during dynamic operations. The number of samples taken may be adjusted based on the contractor’s recommendations.
3.6.2.1.1 Each PEC shall have 1 bacterial and 1 fungal air
test performed. One sample TSA and the other fungal media (e.g., malt extract agar (MEA) or sabouraud dextrose agar (SDA)). Control samples will be submitted and positive control will be inoculated per CETA.
3.6.2.1.2 Each classified area shall have 4 bacterial and 4
fungal air tests performed. One plate can be used as outlined in USP 797 for dual incubation or if requested both samples could be TSA or one sample could be TSA and the other fungal media (e.g., malt extract agar (MEA) or sabouraud dextrose agar (SDA)). Control samples will be submitted, and positive control will be inoculated per CETA.
3.6.2.1.3 Each pass-through shall have 1 bacterial and 1
fungal air tests performed. One plate can be used as outlined in USP 797 for dual incubation or if requested both samples could be TSA or one sample could be TSA and the other fungal media (e.g., malt extract agar (MEA) or sabouraud dextrose agar (SDA)). Control samples will be submitted, and positive control will be inoculated per CETA.
3.6.3 Viable Surface Sampling: bacterial and fungal testing in accordance with USP 797 and CAG-009.
3.6.3.1 Surface sampling should be performed at the end of
significant compounding activity. Surface areas to be tested shall include inside each PEC, staging areas for compounding activity within the cleanrooms, frequently touched areas, and pass-throughs.
3.6.3.1.1 Each PEC shall have 1 bacterial and 1 fungal
surface sample performed. If equipment is present in the PEC it will also be sampled as written in previous sentence.
One sample TSA and the other fungal media (e.g., malt extract agar (MEA) or sabouraud dextrose agar (SDA)).
Control samples will be submitted, and positive control will be inoculated per CETA.
3.6.3.1.2 Each classified room shall have 1 bacterial and 1
fungal surface sample performed. One plate can be used as outlined in USP 797 for dual incubation or if requested both samples could be TSA or one sample could be TSA and the other fungal media (e.g., malt extract agar (MEA) or sabouraud dextrose agar (SDA)). Control samples will be submitted, and positive control will be inoculated per CETA.
3.6.3.1.3 Each pass-through shall have 1 bacterial and 1
fungal surface sample performed. One plate can be used as outlined in USP 797 for dual incubation or if requested both samples could be or one sample could be TSA and the other fungal media (e.g., malt extract agar (MEA) or sabouraud dextrose agar (SDA)). Control samples will be submitted, and positive control will be inoculated per CETA.
4.0 Performance Requirement Details:
4.1 Technician(s) performing certifications must:
4.1.1 Be certified by the CETA National Board of Testing (CNBT) for Pharmacy Sterile Compounding Facilities. It is required the technician have 5 or more years of experience in testing pharmacy sterile compounding areas. It is also required that the technician have at least 5 years of experience in certifying NUAIRE equipment specifically CVE, LFWB, and BSCs (contractor shall provide contact references as proof, prior to bid).
4.1.1.1 For reference, this technician will be identified as the “Lead Technician”
4.1.2 Any vendor technician that does not meet the requirements of
4.1.1 must comply with the following requirements:
4.1.2.1 Technicians without CNBT certification
Technician must be actively supervised by the Lead Technician (same room or direct oversight during actives)
The uncertified technician shall not work independently of the Lead Technician during the certification process.
4.1.2.2 Technicians with CNBT certification but without 5-
years’ experience.
The technician can work independently of the Lead Technician, but they must both be actively working within the pharmacy space and available to collaborate to address any concerns.
4.1.3 Only the Lead Technician shall sign the test reports and equipment labels.
4.1.4 Provide copies of pertinent certifications and/or licenses.
4.1.5 Be a direct employee of the contractor. Hence outsourcing of technicians will not be accepted.
4.1.6 Be competent in United States Pharmacopeia (USP) relevant codes: 795, 797 and 800. The USP and CETA standards have not been provided due to copyright laws, hence the contractor shall have their own copy.
GENERAL NOTE: USP 797 states that certification procedures “such as” those outlined in CAG-003-2006 shall be performed, BHHCS is specifically requiring that the current CAG-003-2006 be used in lieu or any other “such as” procedures that may exist.
4.1.7 Be competent in NSF International Standard / American
National Standard 49 and Clinical Laboratory Standards Institute GP17 A3. NSF/ANSI and CLSI standards have not been provided due to copyright laws, hence the contractor shall have their own copy.
4.1.8 Be proficient with the VA HVAC design guide relative to pharmacy type rooms regarding potential conflicts i.e. ACPH with USP. (See Attachment 3)
4.1.9 Become familiar (prior to site visit) and be compliant with the BHHCS Donning and Doffing Cleanroom Suites policies and procedures (Attachments 1-2). This is a living document.
4.1.10 Become familiar and compliant with BHHCS policies and
procedures pertaining to safety, fire, severe weather, and emergency procedures, once onsite.
5.0 Additional Requirements:
5.1 Certification Reports- The contractor shall provide to the COR or authorized representative a certification report for rooms and equipment within 15 business days from testing date. Pharmacy and lab reports will be two separate reports and each emailed to the corresponding COR and authorized representative.
5.1.1 Each certification report from the contractor shall contain items outlined in GAG-003-2006 and at a minimum, the following information:
5.1.1.1 Contractor name, address and contact information also listing contract personnel with appropriate accreditations.
5.1.1.2 Confirming remark that the most current version of this CAG was referenced for this certification and the actual date the certification was completed.
5.1.1.3 Simple and clear method of identification of the
approximate location of the collected data in relation to the physical layout of the equipment or facility tested, including specific and clear nomenclature for the data locations.
5.1.1.4 Explanation of test procedure used for data collection and justification for any deviations from established industry practices encountered during the certification process.
5.1.1.5 Collected data will be compared to expected values or specific equipment performance criteria established in Standard Operating Procedures supplied by the client. In the absence of client SOPs, the certifying organizations SOPs or industry accepted standards, recommended practices and manufacturer’s specifications would be used.
5.1.1.6 Date and time testing/sampling was performed.
5.1.1.7 Date of next required certification.
5.1.1.8 A list of equipment utilized in data collection to include make, model, serial number, and calibration date.
5.1.1.9 A copy, upon request, of the current calibration
documentation for each piece of equipment utilized in data collection, when applicable.
5.1.1.10 A written interpretation of the airflow smoke pattern test that was recorded and a backup file shall be provided via portable flash drive to the COR or authorized representative.
5.1.1.11 Communication between the COR or authorized
representative to aid in developing recommendations and mitigation strategies will be provided at no additional cost.
5.1.1.12 Fail notifications, as described above in general
requirements by contractor.
5.1.1.13 Listing of repairs performed and replacement parts
provided, when applicable.
5.1.1.14 Reports will indicate what catergory of sterile
compounding can be completed in the rooms containing hoods.
5.1.1.15 The contractor shall calculate air changes per hour
(ACPH) and include their findings in the report. Documentation of ACPH from HVAC, Hood (if applicable) and the total ACPH must be separately identified on the certification report.
6.0 Enviromental Sampling Reports:
6.1 The contractor must contact the COR or authroized representative upon completion of work to verbally report any sampling issues before the contractor leaves the facility.
6.2 Failed air or surface samples must be verbally communicated to the COR or authroized representative within one (1) business day of the receipt of the results from a properly accredited laboratory. If the deadline is unable to be met, the contractor, will immediately relay both verbally and in writing (email) to the COR or authorized representative with explanation and new time line.
6.3 Reports that include viable sampling results must be submitted via email to the COR or authorized representative within 15 business days following the collection of the viable air sampling and/or surface sampling.
If the deadline is unable to be met, the contractor, will immediately relay both verbally and in writing (email) to the COR or authorized representative with explanation and new time line.
6.4 Each sampling report from the contractor shall contain outlined items in current CAG-009 and at a minimum, the following information:
6.4.1 Contractor name, address and contact information also listing contract personnel with appropriate accreditations.
6.4.2 A sampling map of the cleanroom suite and all PECs/C-
PECs noting the locations and types of samples to be taken, where applicable.
6.4.3 Media type, lot numbers and expiration dates. Provide
certificate of analysis of media upon request.
6.4.4 All microorganisms recovered will be identified to the genus level and if able to the species level.
6.4.5 Purpose of sampling, volume sampled, date and time
collected, ISO classification, method of collection, activity level (include # of people present), action levels, media types, laboratory analysis, incubation time and temperature.
6.4.6 List of equipment used, identification number, callibration due date.
6.4.7 Processing lab name and address, date samples receivied by lab, total microbial count in CFU, incubation tempatures, dates and time.
6.4.8 Any deviations or noted possible contamination.
6.4.9 A chain of custody form.
6.4.10 Growth and sterility control reports. If any negative control fails or a positive control has no growth, all enviromental resampling will be conducted at no cost.
6.4.11 An SOP or protocol that describes the procedures used for sampling to be provided upon request.
7.0 Operational Coverage:
The contractor shall perform certification services during normal work hours of 8:00am to 4:30pm, Monday-Friday (excluding weekends and federal holidays).
Exception: work may be performed outside of regular administrative working hours when deemed necessary. The contractor shall receive prior approval from the COR for irregular testing hours.
8.0 Contract Monitoring and Oversight Management:
Quality assurance and administrative oversight of the overall contract agreement and basic processes of contract operations are the primary responsibilities of the
COR.
Attachments:
Attachment 1: FM Donning and Doffing Cleanroom Suites.pptx
Attachment 2: HS Donning and Doffing Cleanroom Suites.pptx
Attachment 3: VA HVAC design guide Rev Nov 1, 2021
VHA Supplemental Contract Requirements for Combatting COVID-19
1. Contractor employees who work in or travel to VHA locations must comply with the following:
a. Documentation requirements:
1) If fully vaccinated, contractors shall show proof of vaccination.
i. NOTE: Acceptable proof of vaccination includes a signed record of immunization from a health care provider or pharmacy, a copy of the COVID-19 Vaccination Record Card (CDC Form MLS-319813_r, published on September 3, 2020), or a copy of medical records documenting the vaccination.
2) If unvaccinated, contractors shall show negative COVID-19 test results dated within three calendar days prior to desired entry date. Test must be approved by the Food and Drug Administration (FDA) for emergency use or full approval. This includes tests available by a doctor’s order or an FDA approved over-the-counter test that includes an affiliated telehealth service.
3) Documentation cited in this section shall be digitally or physically maintained on each contractor employee while in a VA facility and is subject to inspection prior to entry to VA facilities and after entry for spot inspections by Contracting Officer Representatives (CORs) or other hospital personnel.
4) Documentation will not be collected by the VA; contractors shall, at all times, adhere to and ensure compliance with federal laws designed to protect contractor employee health information and personally identifiable information.
2. Contractor employees are subject to daily screening for COVID-19 and may be denied entry to VA facilities if they fail to pass screening protocols. As part of the screening process contractors may be asked screening questions found on the COVID-19 Screening Tool. Check regularly for updates.
a. Contractor employees who work away from VA locations, but who will have direct contact with VA patients shall self-screen utilizing the COVID-19 Screening Tool, in advance, each day that they will have direct patient contact and in accordance with their person or persons who coordinate COVID-19 workplace safety efforts at covered contractor workplaces. Contractors shall, at all times, adhere to and ensure compliance with federal laws designed to protect contractor employee health information and personally identifiable information.
3. Contractor must immediately notify their COR or Contracting Officer if contract performance is jeopardized due to contractor employees being denied entry into VA Facilities.
4. For indefinite delivery contracts: Contractor agrees to comply with VHA Supplemental Contract Requirements for any task or delivery orders issued prior to this modification when performance has already commenced.
B.2 PRICE/COST SCHEDULE
ITEM INFORMATION
ITEM
NUMBE
R
DESCRIPTION OF
SUPPLIES/SERVIC
ES
QUANTIT
Y
UNI
T UNIT PRICE AMOUNT
0001 18.00 EA ________________
In-Ceiling HEPA Filter Test Contract Period: Base POP Begin: 05-15-2022 POP End: 05-14-2023
0002 18.00 EA ________________
Cleanroom Certification Contract Period: Base POP Begin: 05-15-2022 POP End: 05-14-2023
0003 12.00 EA ________________
Room Certification Contract Period: Base POP Begin: 05-15-2022 POP End: 05-14-2023
0004 10.00 EA ________________
Cleanroom Non-viable Count Contract Period: Base POP Begin: 05-15-2022 POP End: 05-14-2023
0005 146.00 EA ________________
Cleanroom/Hoods Viable Air and Surface Sampling Contract Period: Base POP Begin: 05-15-2022 POP End: 05-14-2023
0006 6.00 EA ________________
Pass through testing of HEPA filter Contract Period: Base POP Begin: 05-15-2022 POP End: 05-14-2023
0007 6.00 EA ________________
Mid wall Air Exhaust Contract Period: Base
POP Begin: 05-15-2022 POP End: 05-14-2023
0008 6.00 EA ________________
Horizontal Laminar Airflow Workstation Contract Period: Base POP Begin: 05-15-2022 POP End: 05-14-2023
0009 6.00 EA ________________
LabGard ES AIR 4-foot Class II, Type A2 Contract Period: Base POP Begin: 05-15-2022 POP End: 05-14-2023
0010 4.00 EA ________________
LabGard 4 foot Bench Top Containment Ventilated Enclosure Contract Period: Base POP Begin: 05-15-2022 POP End: 05-14-2023
0011 6.00 EA ________________
Rate Recovery Test; Base Only Contract Period: Base POP Begin: 05-15-2022 POP End: 05-14-2023
0012 2.00 EA ________________
Pharmacy NuAire, CACI (semi-annual) Contract Period: Base POP Begin: 05-15-2022 POP End: 05-14-2023
0013 1.00 EA ________________
NuAire NU – 425- 400, Class II Type A/B3, Biological Safety Cabinet (annual) Contract Period: Base POP Begin: 05-15-2022 POP End: 05-14-2023
0014 1.00 EA ________________
LabGard ES 4 foot, Class II Type A2, Biological Safety Cabinet (annual) Contract Period: Base POP Begin: 05-15-2022 POP End: 05-14-2023
0015 2.00 EA ________________
Decomissioning decontaminate BSC class II type A1; Base Only Contract Period: Base POP Begin: 05-15-2022 POP End: 05-14-2023
0016 20.00 EA ________________
Resampling due to failures; As needed Contract Period: Base POP Begin: 05-15-2022 POP End: 05-14-2023
0017 12.00 HR ________________
USP 797/795/800 troubleshoot consulting; As needed Contract Period: Base POP Begin: 05-15-2022 POP End: 05-14-2023
0018 24.00 EA ________________
Recertification of hood; As needed Contract Period: Base POP Begin: 05-15-2022 POP End: 05-14-2023
0019 36.00 EA ________________
Recertification of room; As needed Contract Period: Base POP Begin: 05-15-2022 POP End: 05-14-2023
0020 4.00 EA ________________
Service Call; As needed Contract Period: Base POP Begin: 05-15-2022 POP End: 05-14-2023
1001 18.00 EA ________________
In-Ceiling HEPA Filter Test Contract Period: Option 1 POP Begin: 05-15-2022 POP End: 05-14-2023
1002 18.00 EA ________________
Cleanroom Certification Contract Period: Option 1 POP Begin: 05-15-2023 POP End: 05-14-2024
1003 12.00 EA ________________
Room Certification Contract Period: Option 1 POP Begin: 05-15-2023 POP End: 05-14-2024
1004 10.00 EA ________________
Cleanroom Non-viable Count Contract Period: Option 1 POP Begin: 05-15-2023 POP End: 05-14-2024
1005 146.00 EA ________________
Cleanroom/Hoods Viable Air and Surface Sampling Contract Period: Option 1 POP Begin: 05-15-2023 POP End: 05-14-2024
1006 6.00 EA ________________
Pass through testing of HEPA filter Contract Period: Option 1 POP Begin: 05-15-2023 POP End: 05-14-2024
1007 6.00 EA ________________
Mid wall Air Exhaust Contract Period: Option 1 POP Begin: 05-15-2023 POP End: 05-14-2024
1008 6.00 EA ________________
Horizontal Laminar Airflow Workstation Contract Period: Option 1 POP Begin: 05-15-2023 POP End: 05-14-2024
1009 6.00 EA ________________
LabGard ES AIR 4-foot Class II, Type A2 Contract Period: Option 1 POP Begin: 05-15-2023 POP End: 05-14-2024
1010 4.00 EA ________________
LabGard 4 foot Bench Top Containment Ventilated Enclosure Contract Period: Option 1 POP Begin: 05-15-2023 POP End: 05-14-2024
1011 2.00 EA ________________
Pharmacy NuAire, CACI (semi-annual) Contract Period: Option 1 POP Begin: 05-15-2023 POP End: 05-14-2024
1012 1.00 EA ________________
NuAire NU – 425- 400, Class II Type A/B3, Biological Safety Cabinet (annual) Contract Period: Option 1 POP Begin: 05-15-2023 POP End: 05-14-2024
1013 1.00 EA ________________
LabGard ES 4 foot, Class II Type A2, Biological Safety Cabinet (annual) Contract Period: Option 1 POP Begin: 05-15-2023 POP End: 05-14-2024
1014 20.00 EA ________________
Resampling due to failures; As needed Contract Period: Option 1 POP Begin: 05-15-2023 POP End: 05-14-2024
1015 12.00 HR ________________
USP 797/795/800 troubleshoot consulting; As needed Contract Period: Option 1 POP Begin: 05-15-2023 POP End: 05-14-2024
1016 24.00 EA ________________
Recertification of hood; As needed Contract Period: Option 1 POP Begin: 05-15-2023 POP End: 05-14-2024
1017 36.00 EA ________________ ________________
Recertification of room; As needed Contract Period: Option 1 POP Begin: 05-15-2023 POP End: 05-14-2024
1018 4.00 EA ________________
Service Call; As needed Contract Period: Option 1 POP Begin: 05-15-2023 POP End: 05-14-2024
2001 18.00 EA ________________
In-Ceiling HEPA Filter Test Contract Period: Option 2 POP Begin: 05-15-2024 POP End: 05-14-2025
2002 18.00 EA ________________
Cleanroom Certification Contract Period: Option 2 POP Begin: 05-15-2024 POP End: 05-14-2025
2003 12.00 EA ________________
Room Certification Contract Period: Option 2 POP Begin: 05-15-2024 POP End: 05-14-2025
2004 10.00 EA ________________
Cleanroom Non-viable Count Contract Period: Option 2 POP Begin: 05-15-2024 POP End: 05-14-2025
2005 146.00 EA ________________
Cleanroom/Hoods Viable Air and Surface Sampling Contract Period: Option 2 POP Begin: 05-15-2024 POP End: 05-14-2025
2006 6.00 EA ________________
Pass through testing of HEPA filter Contract Period: Option 2 POP Begin: 05-15-2024
POP End: 05-14-2025
2007 6.00 EA ________________
Mid wall Air Exhaust Contract Period: Option 2 POP Begin: 05-15-2024 POP End: 05-14-2025
2008 6.00 EA ________________
Horizontal Laminar Airflow Workstation Contract Period: Option 2 POP Begin: 05-15-2024 POP End: 05-14-2025
2009 6.00 EA ________________
LabGard ES AIR 4-foot Class II, Type A2 Contract Period: Option 2 POP Begin: 05-15-2024 POP End: 05-14-2025
2010 4.00 EA ________________
LabGard 4 foot Bench Top Containment Ventilated Enclosure Contract Period: Option 2 POP Begin: 05-15-2024 POP End: 05-14-2025
2011 2.00 EA ________________
Pharmacy NuAire, CACI (semi-annual) Contract Period: Option 2 POP Begin: 05-15-2024 POP End: 05-14-2025
2012 1.00 EA ________________
NuAire NU – 425- 400, Class II Type A/B3, Biological Safety Cabinet (annual) Contract Period: Option 2 POP Begin: 05-15-2024 POP End: 05-14-2025
2013 1.00 EA ________________
LabGard ES 4 foot, Class II Type A2, Biological Safety Cabinet (annual) Contract Period: Option 2 POP Begin: 05-15-2024 POP End: 05-14-2025
2014 20.00 EA ________________
Resampling due to failures; As needed Contract Period: Option 2 POP Begin: 05-15-2024 POP End: 05-14-2025
2015 12.00 HR ________________
USP 797/795/800 troubleshoot consulting; As needed Contract Period: Option 2 POP Begin: 05-15-2024 POP End: 05-14-2025
2016 24.00 EA ________________
Recertification of hood; As needed Contract Period: Option 2 POP Begin: 05-15-2024 POP End: 05-14-2025
2017 36.00 EA ________________
Recertification of room; As needed Contract Period: Option 2 POP Begin: 05-15-2024 POP End: 05-14-2025
2018 4.00 EA ________________
Service Call; As needed Contract Period: Option 2 POP Begin: 05-15-2024 POP End: 05-14-2025
3001 18.00 EA ________________
In-Ceiling HEPA Filter Test Contract Period: Option 3 POP Begin: 05-15-2025 POP End: 05-14-2026
3002 18.00 EA ________________
Cleanroom Certification Contract Period: Option 3 POP Begin: 05-15-2025 POP End: 05-14-2026
3003 12.00 EA ________________
Room Certification Contract Period: Option 3
POP Begin: 05-15-2025 POP End: 05-14-2026
3004 10.00 EA ________________
Cleanroom Non-viable Count Contract Period: Option 3 POP Begin: 05-15-2025 POP End: 05-14-2026
3005 146.00 EA ________________
Cleanroom/Hoods Viable Air and Surface Sampling Contract Period: Option 3 POP Begin: 05-15-2025 POP End: 05-14-2026
3006 6.00 EA ________________
Pass through testing of HEPA filter Contract Period: Option 3 POP Begin: 05-15-2025 POP End: 05-14-2026
3007 6.00 EA ________________
Mid wall Air Exhaust Contract Period: Option 3 POP Begin: 05-15-2025 POP End: 05-14-2026
3008 6.00 EA ________________
Horizontal Laminar Airflow Workstation Contract Period: Option 3 POP Begin: 05-15-2025 POP End: 05-14-2026
3009 6.00 EA ________________
LabGard ES AIR 4-foot Class II, Type A2 Contract Period: Option 3 POP Begin: 05-15-2025 POP End: 05-14-2026
3010 4.00 EA ________________
LabGard 4 foot Bench Top Containment Ventilated Enclosure Contract Period: Option 3 POP Begin: 05-15-2025 POP End: 05-14-2026
3011 2.00 EA ________________ ________________
Pharmacy NuAire, CACI (semi-annual) Contract Period: Option 3 POP Begin: 05-15-2025 POP End: 05-14-2026
3012 1.00 EA ________________
NuAire NU – 425- 400, Class II Type A/B3, Biological Safety Cabinet (annual) Contract Period: Option 3 POP Begin: 05-15-2025 POP End: 05-14-2026
3013 1.00 EA ________________
LabGard ES 4 foot, Class II Type A2, Biological Safety Cabinet (annual) Contract Period: Option 3 POP Begin: 05-15-2025 POP End: 05-14-2026
3014 20.00 EA ________________
Resampling due to failures; As needed Contract Period: Option 3 POP Begin: 05-15-2025 POP End: 05-14-2026
3015 12.00 HR ________________
USP 797/795/800 troubleshoot consulting; As needed Contract Period: Option 3 POP Begin: 05-15-2025 POP End: 05-14-2026
3016 24.00 EA ________________
Recertification of hood; As needed Contract Period: Option 3 POP Begin: 05-15-2025 POP End: 05-14-2026
3017 36.00 EA ________________
Recertification of room; As needed Contract Period: Option 3 POP Begin: 05-15-2025 POP End: 05-14-2026
3018 4.00 EA ________________
Service Call; As needed
Contract Period: Option 3 POP Begin: 05-15-2025 POP End: 05-14-2026
4001 18.00 EA ________________
In-Ceiling HEPA Filter Test Contract Period: Option 4 POP Begin: 05-15-2026 POP End: 05-14-2027
4002 18.00 EA ________________
Cleanroom Certification Contract Period: Option 4 POP Begin: 05-15-2026 POP End: 05-14-2027
4003 12.00 EA ________________
Room Certification Contract Period: Option 4 POP Begin: 05-15-2026 POP End: 05-14-2027
4004 10.00 EA ________________
Cleanroom Non-viable Count Contract Period: Option 4 POP Begin: 05-15-2026 POP End: 05-14-2027
4005 146.00 EA ________________
Cleanroom/Hoods Viable Air and Surface Sampling Contract Period: Option 4 POP Begin: 05-15-2026 POP End: 05-14-2027
4006 6.00 EA ________________
Pass through testing of HEPA filter Contract Period: Option 4 POP Begin: 05-15-2026 POP End: 05-14-2027
4007 6.00 EA ________________
Mid wall Air Exhaust Contract Period: Option 4 POP Begin: 05-15-2026 POP End: 05-14-2027
4008 6.00 EA ________________
Horizontal Laminar Airflow Workstation Contract Period: Option 4 POP Begin: 05-15-2026 POP End: 05-14-2027
4009 6.00 EA ________________
LabGard ES AIR 4-foot Class II, Type A2 Contract Period: Option 4 POP Begin: 05-15-2026 POP End: 05-14-2027
4010 4.00 EA ________________
LabGard 4 foot Bench Top Containment Ventilated Enclosure Contract Period: Option 4 POP Begin: 05-15-2026 POP End: 05-14-2027
4011 2.00 EA ________________
Pharmacy NuAire, CACI (semi-annual) Contract Period: Option 4 POP Begin: 05-15-2026 POP End: 05-14-2027
4012 1.00 EA ________________
NuAire NU – 425- 400, Class II Type A/B3, Biological Safety Cabinet (annual) Contract Period: Option 4 POP Begin: 05-15-2026 POP End: 05-14-2027
4013 1.00 EA ________________
LabGard ES 4 foot, Class II Type A2, Biological Safety Cabinet (annual) Contract Period: Option 4 POP Begin: 05-15-2026 POP End: 05-14-2027
4014 20.00 EA ________________
Resampling due to failures; As needed Contract Period: Option 4 POP Begin: 05-15-2026 POP End: 05-14-2027
4015 12.00 HR ________________
USP 797/795/800 troubleshoot consulting; As needed Contract Period: Option 4 POP Begin: 05-15-2026 POP End: 05-14-2027
4016 24.00 EA ________________
Recertification of hood; As needed Contract Period: Option 4 POP Begin: 05-15-2026 POP End: 05-14-2027
4017 36.00 EA ________________
Recertification of room; As needed Contract Period: Option 4 POP Begin: 05-15-2026 POP End: 05-14-2027
4018 4.00 EA ________________
Service Call; As needed Contract Period: Option 4 POP Begin: 05-15-2026 POP End: 05-14-2027