S-619JS_ADDENDUM_2.docx
DOCX document 25 KB Posted
- Attached to
- HVAC Water Treatment Services and Products
- Solicitation number
- S-619JS (Expires 02/01/19)
- Issued by
- Florida
About this file
This is an addendum to a competitive invitation for bid issued by the School District of Volusia County, Florida for HVAC Water Treatment Service and Products (Bid No. S-619JS). The addendum addresses questions and clarifications that arose during a pre-bid conference held on May 3, 2016, with attendance from vendor representatives including Bryce Water Services, Inc., Chem-Aqua, and Kroff, along with district purchasing and facilities staff. The scope of work encompasses water treatment services for cooling towers and chilled water loops throughout the district's HVAC systems. Bidders are required to conduct bi-annual testing and treatment visits on condenser and chilled water loops, perform quarterly or semi-annual visits at closed loop sites, and install corrosion coupon racks as part of equipment requirements. The bid submission deadline is May 24, 2016 at 2:00 p.m., with late proposals not accepted. Site inspections should be conducted after school hours, defined as after 3:00 p.m. for elementary and high schools and after 4:00 p.m. for middle schools. During summer months when the district operates on a four-day, ten-hour schedule, inspections should occur as soon as school lets out during regular school year hours.
All water treatment products must be in solid form for cooling tower treatment, with liquid chemicals prohibited except as temporary corrective action when deemed necessary by the district. Bidders should base proposals on solid chemistry exclusively, with the exception of closed loop chemical treatment. The oxidizing biocide may be manually dosed during service visits rather than requiring a third automated feeder. Proposals should include provisions for achieving three to four cycles of concentration or higher, with the district currently responsible for purchasing and providing softeners and salt for pre-treatment systems. Contact for questions and concerns should be directed first to Dave Biletto and second to Tony Gutierrez. The district indicated that vendor presentations may be scheduled after committee evaluation if additional information is needed. Acknowledgment of receipt and understanding of this addendum must be returned with the bid submission by the deadline.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S-619JS_-_Board_Approval_Docs.pdf | ||
| S-619JS_HVAC_Water_Treatment_Services_TAB-BOARD_STAMP_APPROVED.pdf | ||
| S-619JS_ADDENDUM_1.doc | DOC document | |
| S-619JS_Hvac_Water_Treatment_Services_and_Products.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
| THE SCHOOL DISTRICT OF VOLUSIA COUNTY | BID NO.: S-619JS |
| 3750 OLSON DRIVE | DATE: MAY 11, 2016 |
DAYTONA BEACH, FL 32124 Page 2 of 3
NOTICE
ADDENDUM #2 TO BID NO.: S-619JS – HVAC Water Treatment Service & Products
OPENING DATE & TIME: MAY 24, 2016 @ 2:00 P.M.
LATE PROPOSALS WILL NOT BE CONSIDERED
Pre-Bid Conference held May 3, 2016 attendees:
| Vendors: | VSCB Representatives: | ||||
| Jay Hoggard – Bryce Water Services, Inc. | Tony Gutierrez – Environmental Specialist | ||||
| Paul Bryant – Bryce Water Services, Inc. | Gary Hopkins – Purchasing Supervisor | ||||
| Jason Woodall – Chem-Aqua | Jacqueta Scott- Buyer, Purchasing Dept. | ||||
| Mike Grossman – Chem-Aqua | Laura Daulton- Buyer, Purchasing Dept. | ||||
| Andria Zambito – Kroff | Antoinette Shaffer - Office Specialist II (Recorder) | ||||
| Jeannie Beck - Office Specialist III (Recorder) |
Listed below you will find answers to questions regarding the ITB for HVAC Water Treatment Service and Products that were brought up at the Pre-Bid Conference and any additional questions received.
Q: Jacqueta Scott asked: Who should be contacted for questions or concerns?
A: Tony Gutierrez answered: First contact is Dave Biletto, and second contact is Tony Gutierrez second.
Q: Jacqueta Scott asked: When is the best time to perform inspections.
A: Tony Gutierrez answered: It is best after school hours.
Q: Jacqueta Scott asked: Starting the second week of June, for the summer months, the district will be working four (4), ten (10) hour days; Monday through Thursday. What would you consider after school hours at that time?
A: Tony Gutierrez answered: As soon as school lets out during the regular school year: Elementary-after 3PM, Middle-after 4PM, and High-after 3PM.
Q: Paul Bryant asked: If we do end up going to another bid, hopefully we are going to still be using, rather than a liquid chemical, preferably a powdered chemical. Hopefully get personnel training for any changes in equipment.
A: Jason Woodall answered: Powder is the chemical referenced.
Jacqueta Scott stated: You have until this Friday to ask additional questions via email. Monday, May 09, 2016 we will post an addendum on Vendorlink with the questions and answers discussed during this Pre Bid Conference.
Q: Adria Zambito asked: Does the scope include pre-treatment? Is it included or separate from the scope as far as softeners and filtrations on the systems?
A: Tony Gutierrez answered: Currently we purchase the softeners and we provide the salt. We take care of the pretreatment. The scope pertains to towers and chillers, loop treatment.
Q: Adria Zambito asked: Is there a minimum requirement regarding the number of cycles you want to achieve?
A: Tony Gutierrez answered: Three (3) or four (4) cycles. No problem submitting more.
Jacqueta Scott reminded everyone that the bid due date is May 24th at 2PM.
Gary Hopkins stated that we only read the name of those who submitted bids, no prices are disclosed.
Q: Andria Zambito asked: Is there going to be an opportunity for presentations after the committee decision?
A: Jacqueta Scott answered: Possibly after the evaluation, if more information is needed. Submit what you like, as long as you have the minimum requirements.
Additional questions received via email:
Q: Are closed loop sites to be visited quarterly or semiannually?
A: Testing and treatment shall be made bi-annually on condenser and chilled water loops.
Q: There is contradicting info about type of chemicals to be used. In some areas it talks about liquid chemicals for tower sites and other areas it indicates solid chemicals are to be used for tower systems?
A: All products shall be in SOLID FORM, with the exception of the closed loop chemical. In no event shall liquid chemicals be used for the cooling tower treatment program.
Q: During the site visits, I noticed both solid and liquid chemistry was being used throughout the sites. The bid states that solid chemistry is preferred. Should we build our programs based on solid chemistry only? Or should we offer liquid at the sites that currently have liquid chemical in addition to solids to the remaining sites?
A: The bid should be based on solids, the only time we would introduce the liquid is if we deemed it necessary as part of corrective action. The liquid is used as a temporary treatment only when required.
Q: Corrosion coupons were stated as required in the bid, however during site visit I noted that not all systems had a coupon rack in place. Are we to include this as a part of the equipment requirements and add to the list?
A: Yes, coupon racks should be part of the bid.
Q: The bid also states it is required to have 3 chemicals feeding the system, scale & corrosion inhibitor, oxidizing biocide & a non-oxidizing biocide. This is definitely best practices, however it was noted during our site visit that only two chemical feeders were seen at most sites. In order to comply with three chemical feed stations a third feeder and chemical pump will need to be purchased. Should this be included in the bid under equipment as well or is the oxidizing biocide being hand dosed during service visits?
A: Yes, the oxidizer is being manually introduced.
ACKNOWLEDGEMENT
This addendum to BID number S-619JS HVAC Water Treatment Service & Products has been received and fully understood.
Vendor: ___________________________________________ Date: ___________________
Address: __________________________________________ Zip Code: ________________
Phone: ____________________________________________ Fax: ____________________
Signature: __________________________________________________________________
PLEASE RETURN THIS ACKNOWLEDGEMENT WITH BID BY 2:00 P.M., 5/24/2016
| The School District of Volusia County | Phone: 386-734-7190, ext. 50853 | |
| Jacqueta Scott, Buyer | Fax: 386-506-5056 |
Purchasing Department 3750 Olson Drive Facilities/Maintenance Building Daytona Beach, FL 32124