This is an equipment specification document prepared by Dane County, Wisconsin, detailing the current Renewable Natural Gas (RNG) facility equipment inventory at 7242 Maahic Way, Madison, Wisconsin. The document, created by Alex Thomas and reviewed by the RNG Operations Team under the direction of County Executive Melissa Agard and Director John Welch, provides comprehensive specifications and replacement priorities for the facility's nitrogen and carbon removal units and supporting infrastructure. The equipment list includes three 60 HP blowers (3,000 scfm capacity), two National Turbine blowers (125 HP each, 2,200 scfm each), a Guntner LFG chilling unit, two Temperature Swing Adsorption (TSA) systems with CarboTech vessels, two Pressure Swing Adsorption (PSA) systems in separate phases, a Regenerative Thermal Oxidizer, compression equipment including Ariel and GE compressors, and associated buffer vessels and recirculation equipment. Replacement priorities are designated as high, low, or dependent on downstream and upstream equipment needs, reflecting the interdependency of system components.

The current PSA system was originally commissioned in 2019 and has reached the end of its useful life, prompting the county's procurement initiative to replace the nitrogen and carbon removal units with more efficient current technology while increasing landfill gas processing capacity. The equipment inventory reflects a sophisticated multi-stage biogas upgrading process, with various components supplied by manufacturers including John Zink, National Turbine, Guntner US LLC, Norit, CarboTech, Busch, TECON, Hoffman Lamson, R&R Engineering, VPT Kompressoren GmbH, Ariel, GE, Basset Manufacturing, and Thermatech. The facility currently operates two trains of adsorber vessels with maximum capacities of 6,250 cubic meters per hour and minimum capacities of 1,100 cubic meters per hour, with operating temperatures capped at 55°C and operating pressures between 20 and 35 mbar.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

County Executive Melissa Agard Director John Welch, PE

1919 Alliant Energy Center Way Madison, Wisconsin 53713

Attachment C: RNG Equipment List

Current RNG Equipment Make/Model Specifications and Capacity Priority for Replacement Three 60 HP Blowers

1,000 scfm (each) -60" w.c. with 4 psig outlet

Supplied by John Zink.

3,000 scfm capacity

5 HP with 0.5 psi pressure drop 184F/110F inlet/outlet

Provided through John Zink 3,000 scfm

82 MMBtu/hour ZEF 12" x 35' Supplied by John Zink.

Designed for 3,000 scfm Two vessels at 12 ft dia x 30 ft height

Operating in series

National Turbine Two National Turbine blowers NT88207 125 HP, 2,200 scfm (each)

LFG Chilling Unit Guntner US LLC Vshape Glycol Cooler 232 PSI Rated Pressure Low

500 HP.

Maximum of 2,345 scfm

(each) at 11.6 psig inlet and 160 psig discharge.

Two vessels at 5 ft dia. x 11 ft 6” S/S operating in series.

Norit ROZ3 activated carbon.

Custom Fabrication The TSA consists of two vessels at 5’ dia. x

11’6” S/S operating in parallel Carbon Activated media

CarboTech Vessels

Two trains, each six 5’10” dia. x 8’ S/S adsorber vessels with four Busch

RA1600B426 vacuum pumps (with a -

13.26 psig vacuum)

50 HP

Unknown media responsible for CO2, O2, and N2 removal 6,250 cubic meters/hour capacity maximum 1,100 cubic meters/hour capacity minimum

Maximum operating temperature 55°C

Operating Pressure of 20 mbar, 35mbar maximum

One train, six 5’10” dia. x 8’ S/S adsorber vessels with four Busch

RA1600B426 vacuum pumps (with a -

13.26 psig vacuum).

50 HP

Proprietary Media Unknown media responsible for N2 removal and recirculation 6,250 cubic meters/hour capacity maximum 1,100 cubic meters/hour capacity minimum

Maximum operating temperature 55°C

Operating Pressure of 20 mbar, 35mbar maximum

R&R Engineering

H-60-10

John Zinc

Custom Fabrication

VPT 500-160 WCV

TECON Biogas Storage Bladder

26-AF20

73206-GDGI

Hoffman Lamson Blowers

CarboTech Vessels

Proprietary Media

Custom Fabrication

Norit BG1 Activated Carbon Media

TECON Biogas Storage Bladder

26-AF20

VPT Kompressoren GmbH

National Turbine

Wellfield Vacuum Blowers

Wellfield Vacuum Blower Cooler

Flare

Bulk H2S Removal Towers

LFG Booster Blowers (2)

H2S Polishing Towers

Temperature Swing Adsorption System (TSA)

Pressure Swing Adsorption System (Phase 1)

Pressure Swing Adsorption System (Phase 2)

LFG Compression

Pressure Swing Adsorption (Phase

1) Discharge Buffer Bladder

Pressure Swing Adsorption (Phase

2) Recirculation Buffer Bladder

Pressure Swing Adsorption (Phase

1) Discharge Buffer Blowers (2)

Low

Low

Low

Low

Dependent on Downstream Equipment Need

Dependent on Downstream Equipment Need

Dependent on Downstream Equipment Need

High

High

High

Dependent on Upstream Equipment Need

Dependent on Upstream Equipment Need

Two National Turbine blowers Dependent on Upstream

Equipment Need NT55207 Capacity of 1,500 scfm (each)

One Ariel JGQ/2, 250 HP, 1,300 scfm

70/135 psig inlet to 975 psig discharge

JGQ/2

9.8 MMBtu/hr

200 HP combustion air fan 30,000 scfm

Created by: Alex Thomas Checked by: RNG Operations Team

Regenerative Thermal Oxidizer

Tann

(1) Ariel

Thermal Oxidizer

Product Gas Compression

Pressure Swing Adsorption (Phase

2) Recirculation Blower

Dependent on Upstream Equipment Need

Dependent on Upstream Equipment Need

National Turbine blower Dependent on Upstream

Equipment Need NT55207 Capacity of 1,500 scfm

100/125 psig inlet to 985 psig discharge compressors

Two GE A352, 250 HP, 1,251scfm (each)(2) Cobey Energy

GE A352

National Turbine

PSA Intermediate Product Vessel (Between Phase 1 and 2)

Product Buffer Vessel Dependent on Upstream

Equipment Need

Dependent on Upstream Equipment Need

Basset Manufacturing

Thermatech Pressure Vessel

Basset Manufacturing

Thermatech Pressure Vessel

Design temperature 200°F

Max Pressure of 165 psi

Design temperature 200°F

Max Pressure of 165 psi