PUMP Schedule
Max HP Volts Diameter RPM
P-1 650 100 25 480 3 1750 Base 6" Suction
6"Discharge Double Suction
Type
P-2 650 100 25 480 3 1750 Base 6" Suction
6"Discharge Double Suction
Type
O.A.T. AWS
18 200 30 170 60 140
Equipment Capabilities
Converter: To heat 650 GPM from 180 degrees farenheit to 200 degrees Farenheit with 7459 Pounds 125 PSI Steam.
Minimum tube surface 129 Sq. Feet Maximum Tube velocity 4.8 FPS.
Maximum water pressure Drop 1.0 Ft. Maximum Scale Factor .002
ServiceMOTORHead FT H2O Capacity
GPM
Plan Mark Mounting Notes
Sheet1