PUMP Schedule

Max HP Volts Diameter RPM

P-1 650 100 25 480 3 1750 Base 6" Suction

6"Discharge Double Suction

Type

P-2 650 100 25 480 3 1750 Base 6" Suction

6"Discharge Double Suction

Type

O.A.T. AWS

18 200 30 170 60 140

Equipment Capabilities

Converter: To heat 650 GPM from 180 degrees farenheit to 200 degrees Farenheit with 7459 Pounds 125 PSI Steam.

Minimum tube surface 129 Sq. Feet Maximum Tube velocity 4.8 FPS.

Maximum water pressure Drop 1.0 Ft. Maximum Scale Factor .002

ServiceMOTORHead FT H2O Capacity

GPM

Plan Mark Mounting Notes

Sheet1