QUESTIONS AND ANSWERS FOR SOLICITATION # 19N10219Q0011 – SUPPLY OF LOW VOLTAGE AUTOMATIC VOLTAGE REGULATOR (AVR) FOR AMERICAN EMBASSY RESIDENCES

S/N
QUESTIONS
ANSWERS
1
What is the required Input & Output Voltage?
240/415v
2
What is the required output regulation? With a +20-20% input, we would be looking at

+/- 5-6%, size dependent AVR must be able to handle input voltages within the range of +20% to -20% of 415v while maintaining a steady output of 415v.

3
Do you accept materials made in Singapore like (Ashley Edison)
Yes
4
How long could it take to receive the payment after delivering the requirements?
Net 30 Days
5
Is there an estimated Amount for this contract
Not Relevant, Information Provided In The Solicitation Is Sufficient. This is a request for the supply of goods not services. (See Block 14 in the SF1449 Form of the Solicitation, Page 3)
6
What is the maximum period to deliver the requirements after signing the contract?
Provided In The Solicitation (See Section B Page 6 of the Solicitation)
7
This request for quote is for Automatic Voltage Regulators for use in a US Embassy in Nigeria, why then is CE a requirement? Equipment is not being used in a European country and also being used in a US property, so why is a European standard being applied which effectively precludes US companies from bidding
Voltage Regulators Will Be Used At Residential Properties Leased By The US Embassy And Are Manufactured To Local Standards And Nigeria Uses The European Standards.
8
Is the CE marking in paragraph 1.1.1 an absolute requirement?
Yes
9
Item 6 states ‘100kVA’ however item 2 is also 100kVA. Is item 6 meant to be 1000kVA?
Yes, it is 1000KVA, Check The Amended Solicitation Package Posted on FBO August 21, 2019
10
The AVRs have been specified to require IP54 enclosure, even though they are indoor AVRs. Is this to help protect servo/mechanical type AVRs from dust and help with their maintenance programmes?
No, AVR Needs To Be Rated For Outdoor Use. See Sections 1.1.1 & 1.1.3, Page 5 of the Solicitation
11
Are you intending on procuring all 18 AVRs mentioned, or only a selection of the 18 AVRs?
Yes All 18 AVRs
12
If our company will be awarded, is there possibility to submit the cargo through the Department of state European Logistics support office ( ELSO) in Antwerp Belgium to ship to you or not, pls. advise
The Ship To Address Is Provided In The Solicitation (See Section A Page 6 of the Solicitation), But If You Offer An Alternative Ship To Address That Provides Some Advantage To Government, It May Be Considered (See Evaluation of Options Page 25 of the Solicitation)
13
Will the bypass need to be internal or wrap around?
Whatever is applicable to the product being offered.
14
What type of communication are you looking for (contact closures, Ethernet, etc) ?
By USB or Ethernet