This document is a Request for Proposals (RFP) issued by North Muskegon Public Schools (the "District") for the purchase and installation of four new boilers with associated pumps and accessories. The District is seeking proposals from qualified contractors for the removal and replacement of the existing boilers. The desired timeline for completion is by November 1, 2024. Proposals are due on September 27, 2024, and the Board of Education will award the contract to the lowest qualified bidder prior to their October board meeting. Non-mandatory walk-throughs can be scheduled during the proposal timeframe. The RFP outlines detailed specifications for the new boilers, pumps, and associated materials that must be included in the proposals.

The RFP requires bidders to complete and submit specific forms, including an Affidavit of Bidder, Iran Economic Sanctions Act Certification, and a Bid Proposal Sheet. Pricing for the project must be included on the Bid Proposal Sheet. The District reserves the right to waive any irregularities in the RFP or bid process. Bidders must agree to indemnify and hold harmless the District for any claims arising from the bid process.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

North Muskegon Public Schools Request for

Proposals

Boiler Replacement 09.10.2024

Mark Mesbergen Fruitport Community Schools 3255 Pontaluna Road Fruitport, MI 49415

Overview North Muskegon Public Schools (the “District”) is seeking proposals from a contractor (each a “Bidder’) for the purchase of four boilers with associated pumps and removal and replacement of those boilers with associated pump and system accessories,. North Muskegon Public Schools is located at 1600 Mills Ave, North Muskegon, MI 49445.

Bids to include the following:

• Refer to Appendix A

• Appendix B has the necessary notes and materials to include

• Appendix C has the specs for the four pieces of equipment that is district has determined to be required for the bid.

Additional Information

Non-Mandatory Walk-Throughs Walk-throughs can be scheduled with Jake Kurtzhal via email jkurtzhal@northmuskegon.org and are recommended.

Desired Installation Time-Line The district’s desired time-line is the four boilers be replaced by November 1, 2024.

Proposal Timeline

1. RFP released on 09/09/2024

2. Non-mandatory walk throughs can happen during this timeframe.

3. Proposals are due on September 27, 2024 at 10:00 am. Bids are to be submitted via mail to: North

Muskegon Public Schools, Attn: Mark Mesbergen, 1600 Mills Ave, North Muskegon, MI 49445 OR via email to mmesbergen@nmps.net with a subject line of “Boilers”.

4. Board of Education will take action on the lowest qualified bidder on or before the October board meeting.

The district will notify the company the following day.

5. This project needs to be completed by November 1, 2024.

Proposal Requirements

1. Proposals shall be prepared in compliance with provisions of this RFP. All provisions and everything a bidder will need is in Appendix A. Failure to comply may result in the disqualification of the proposal.

2. Interested Bidders are strongly encouraged to submit an intent to respond to Mark Mesbergen via mmesbergen@nmps.net to ensure that the Bidder receives all addenda or communications regarding this RFP.

3. Late Proposals will not be accepted.

4. Each Bidder, before submitting a proposal, shall, if it is uncertain of the conditions, requirements, and/or obstacles that might impact the provision of the project, request further information. Failure to make such inquiry or receive an answer shall not relieve the selected Bidder from the obligation to comply, in every detail, with all provisions and requirements of the RFP nor shall it be a basis for any claim whatsoever for alteration in any term or payment required by the eventual contract between the selected Bidder and the District (the “Contract”).

5. If a Bidder discovers any ambiguity, conflict, discrepancy, omission or other error in the RFP, they shall immediately notify the District of such error in writing and request modification or clarification of the document. Modifications will be made by issuing a revision and will be given by written notice to all parties who have submitted an intent to respond. The Bidder is responsible for clarifying any ambiguity, conflict, discrepancy, omission or other error in the RFP prior to submitting the proposal or it shall be deemed waived.

6. All proposals and any accompanying documents become the property of the District and will not be returned.

7. The District reserves the right to waive irregularities in this RFP, the bid process, or the proposals.

Any such waiver shall not modify any remaining RFP requirements or excuse a Bidder from full compliance with the RFP specifications and other Contract requirements if the Bidder is awarded the Contract.

8. Each Bidder who submits a bid, by submitting a bid, agrees to indemnify and hold harmless the District and its employees, board members, and consultants for any claim against the District involving the Bidder and arising out of the bid process. By submitting a bid, each Bidder agrees that it will make not claim against the District regarding this RFP or the bid process.

9. All Bidders, by submitting proposals, agree that they have read and are familiar with all the terms and conditions of the RFP and applicable federal and state laws, rules and regulations and will abide by the terms and conditions thereof.

10. Each Bidder complete Appendix A as the three forms are the proposal bidding documents.

The documents include Affidavit of Bidder, Iran Economic Sanctions Act Certification, and the bid proposal sheet.

APPENDIX A

Proposal:

Please make sure that you have accounted described in Appendix B.

TOTAL PROPOSAL PRICE:

FAMILIAL RELATIONSHIP DISCLOSURE FORM AFFIDAVIT OF BIDDER

The undersigned, the owner or authorized officer of _______________________________(the Bidder), pursuant to the familial disclosure requirements provided in the Advertisement for Bid, hereby represents and warrants, except as provided below, that no familial relationships exist between the owner(s) or any employee of ________________________________________________(the Bidder) and any member of the Board of Education of the School District or the Superintendent of North Muskegon Public Schools.

List and describe any Familial Relationships:

BIDDER: ______________________________

By:____________________________ Its:____________________________

STATE OF MICHIGAN )

) ss.

COUNTY OF )

The instrument was acknowledged before me on the _____ day of _____________, 2024, by , Notary Public ______________________ County, Michigan

My Commission Expires: __________________

Acting in the County of: __________________

AFFIDAVIT OF COMPLIANCE – IRAN ECONOMIC SANCTIONS ACT

Michigan Public Act No. 517 of 2012

The undersigned, the owner or authorized officer of the below-named applicant (the “Applicant”), pursuant to the compliance certification requirement provided in the North Muskegon Public Schools (the “School District”) Request For Proposals (the “RFP”), hereby certified, represents and warrants that the Applicant *(including its officers, directors and employees) is not an “Iran linked business” within the meaning of the Iran Economic Sanctions Act, Michigan Public Act No. 517 of 2012 (the “Act”), and that in the event Applicant is awarded a contract as a result of the aforementioned RFP, the Applicant will not become an “Iran linked business” at any time during the course of performing any services under the contract.

The Contract further acknowledges that any person who is found to have submitted a false certification is responsible for a civil penalty of not more than $250,000.00 or 2 time the amount of the contract or proposed contract for which the false certification was made, whichever is greater, the cost of the School District’s investigation, and reasonable attorney fees, in addition to the fine.

Moreover, any person who submitted a false certification shall be ineligible to bid on a request for proposal for three (3) years from the date that it is determined that the person has submitted the false certification.

APPLICANT: ___________________________________

Name of Applicant By:________________________________ Title:________________________________ Date:______________________________

STATE OF MICHIGAN )

) ss.

COUNTY OF _________ )

The instrument was acknowledged before me on the _____ day of ________, 2024, by____________________.

Notary Public _____________________ County, Michigan

Acting in the County of: ____________ __

My Commission Expires: ______________

APPENDIX B

• Removal and disposal of the (4) existing heating boilers including associated materials. Remove all existing combustion air intake ductwork from boilers to combustion air intake louver.

• Provide and install all necessary steel piping, fittings, and gas regulators for installation of gas piping to new boilers and for installation of 4” heating supply and return piping along with Victaulic butterfly valves. Install pressure gages upstream and downstream of each gas regulator.

• Provide and install all necessary vent piping and accessories from new boilers through the roof with Metal-Fab AL29-4C vent piping and stainless-steel outer jacket. Terminate above roof at or above height of existing boiler vents with velocity cone.

• Provide and install all necessary intake air piping from new boilers through the roof using pvc.

• Roof patching is included in this proposal for patching holes through roof for combustion air intake and vent piping.

• Provide and install all necessary hangers, brackets and supports for all new piping.

• Electrical is included in this proposal for disconnecting existing boilers and associated boiler pumps, and making connections to new boilers and associated boiler pumps. Reuse existing circuits and disconnect devices.

• Provide temporary insulation on all new piping as part of this proposal.

• Provide (4) new Viessmann Vitocrossal 300 CA3B, 2500 MBH, 96% boilers including condensate neutralization tanks with removable top lids, boiler air intake kits, boiler low water cut-off with manual reset/test, hi-limit temperature control with manual reset, and BACnet interfaces.

• Provide (4) new Bell & Gossett Ecocirc XL 45-375 pumps, 150gpm, 25ft.hd., 0% Glycol, 460v/3ph, with external temperature sensor accessories and BACnet interfaces.

• Install (4) new Viessmann Vitocrossall 300 CA3B, 2500 MBH boilers, including condensate neutralization tanks, air intake kits, pressure relief valves, Ecocirc XL boiler pumps and associated accessories, pump inlet strainers, pump check valves, and balancing valves for flow measurement.

Provide PVC condensate piping routed to nearest floor drain.

• Modify and extend existing boiler concrete house keeping pads to meet boiler manufacturer’s installation requirements.

• Coordinate chemical treatment with owner’s water treatment provider.

• Factory-authorized service representatives to inspect, startup, and test new boilers and pumps upon completion. Report results in writing.

• Cleanup and removal of all work associated debris

• Permits and inspections are included in this proposal

• Include cost of owner's HVAC Controls representative W.J. O'Neil to modify the existing Johnson

Controls N2 system for the new boilers.

A Practical Approach To Innovation

VITOCROSSAL 300, CA3B

Gas condensing boiler with fully-modulating pre-mix cylinder burner for commercial, multi-family, and light industrial applications.

2500 to 6000 MBH

G A S C O N D E N S I N G B O I L E R

Appendix C

G A S C O N D E N S I N G B O I L E R

With its unique synthesis of proven technology and innovative With its unique synthesis of proven technology and innovative features, the Vitocrossal 300, CA3B takes a bold step forward while features, the Vitocrossal 300, CA3B takes a bold step forward while retaining the superior Viessmann quality you know and trust. retaining the superior Viessmann quality you know and trust.

The Vitocrossal 300, CA3B offers gas-fired condensing technology with fully-modulating pre-mix cylinder burner.

Viessmann technology from top to bottom Our fully-modulating pre-mix cylinder burners feature a wide modulation and combined burner turndown ratio of up to 15:1. This matches the load to provide clean, quiet and environmentally friendly operation. The burners come fully assembled and installed for ease of commissioning.

The SA240 stainless steel Inox-Lamellar heat exchanger surface provides maximum heat extraction while maintaining a compact size. Its smooth, corrosion resistant surfaces allow condensate to simply run off, creating a “self-cleaning” process that ensures continuous condensing efficiency, reduced maintenance costs, and longevity. The 160 psi pressure rating allows for this unit to be installed in almost any building.

With the Vitocrossal 300, CA3B, Viessmann offers outstanding thermal efficiencies over 96% and delivers exceptional performance and reliability at an attractive price.

Progressive design features The Vitocrossal 300, CA3B can operate with a low inlet gas pressure of only 4 inches of water column (NG), eliminating the need for gas boosters. With low water pressure drop, the heat exchangers are ideal for variable primary systems and eliminate the need for a dedicated boiler pump. The boiler’s large water content reduces wasteful burner cycling, thereby increasing system efficiency and overall durability.

A versatile solution The Vitocrossal 300, CA3B offers a solution for almost every ap-plication, such as multiple venting options and seamless integra-tion into building management systems (BMS). The Vitocrossal 300, CA3B comes fully assembled, which makes it easy to ins-tall, even older buildings with narrow entrances or small mecha-nical rooms. Suitable for high altitude operation of up to 10,000 feet, the sky‘s the limit for the Vitocrossal 300, CA3B.

Dual fuel: Switch from natural gas (NG) to LP Dual fuel is a feature that maintains normal operation in critical care applications, such as nursing homes, hospitals, educational institutions, industrial operations, and more. The Vitocrossal 300, CA3B provides the ability to easily switch from natural gas (NG) to LP at the simple turn of a key (must be pre-ordered).

B E N E F I T S AT A G L A N C E

+ Low emissions and quiet operation from fully-modulating Viessmann pre-mix cylinder burners (up to 3)

+ Total burner modulation turndown ratio of up to 15:1 precisely matches load per boiler

+ The fully assembled boiler simplifies installation and commissioning

+ Flexibility for venting through the sidewall or chimney applications up to 100 ft. (equivalent length) and combustion air options of sealed combustion or room dependent

+ Common venting up to four boilers* + Gas fuel flexibility (NG/LPG/Dual Fuel**) + Low inlet gas pressure capability as low as 4” W.C. (NG) for compatibility with a range of supply pressures + Large water content extends burner run time and reduces cycling + No dedicated boiler pump required due to low water pressure drop through heat exchanger + Vitotronic 300 GW6C can be used as a single boiler control or as a cascade primary/secondary control system + Seamless integration with building management systems + 0-10 VDC temperature setpoint input

S P E C I F I C AT I O N S

+ Certified BTS 2000 >96% + Single inputs from 250 up to 6,000 MBH + Cascade system inputs up to 48,000 MBH with external

Vitocontrol-S + ASME CSD-1 compliant

User-friendly control system The Vitotronic 300, GW6C control system is an advanced digital boiler and system control with outdoor reset function that ensures reliable, efficient performance of the entire heating system. The Vitotronic 300, GW6C will modulate stages and rotate burners to meet the heating system‘s load. The standard control package will regulate supply water temperature for one high temperature circuit, two mixing valve circuits, and one DHW circuit.

Multiple-boiler systems The built-in Vitotronic 300, GW6C cascade control system is simple to use, as it automatically stages burners and rotates boilers to match heating loads up to 12,000 MBH. For larger systems, Viessmann also offers custom boiler controls with virtually unlimited capacities and additional options such as real time system loading, VFD pump outputs, BTU metering, and efficiency trending.

Vitotronic 300, GW6C control system

Low-emission fully-modulating pre-mix cylinder burner

Vitotronic 300, GW6C control system

Fully-modulating pre-mix cylinder burner

Inox-Lamellar heat exchanger surfaces

Highly effective thermal insulation

Wide water passageways with low pressure drop

VITOCROSSAL 300

2 5 0 0 - 6 0 0 0 M B H

A Practical Approach To Innovation

Viessmann Manufacturing Company Inc.

Warwick, RI, 02886 1-800-288-0667 viessmann-us.com

Model CA3B CA3B 2.5 CA3B 3.0 CA3B 3.5 CA3B 4.0 CA3B 5.0 CA3B 6.0

Maximum Input MBH 2500 3000 3500 4000 4000 6000

Minimum Input MBH 250 300 300 400 300 400

Net AHRI Rating MBH 2089 2506 2924 3342 4178 5013

Combustion Efficiency % 94.1* 94.1* 94.1* 94.1* 94.1* 94.1*

Thermal Efficiency % 96.1* 96.1* 96.1* 96.1* 96.1* 96.1*

Output* MBH 2400 2880 3360 3840 4800 5760

Overall Dimensions (Including insulation & jacketing)

Width inches 34 34 39.5 39.5 39.5 39.5

Height (Does not include boiler pad or seismic brackets) inches 78.75 78.75 84 84 84 84

Depth (Length) inches 88.75 88.75 99.5 99.5 136 136

Weight (Including burners, controls, insulation & jacketing) lbs 4233 4233 4696 4806 6261 6894

Boiler Water Content USG 108 108 151 143 227 218

Minimum Heat Exchanger Surface ft.² 142.7 142.7 170.2 193.5 244.1 288.8

Maximum Operating Pressure PSI 160 160 160 160 160 160

Fixed Water Temperature Limit ºF 210 210 210 210 210 210

Adjustable Water Temperature Limit ºF 203 203 203 203 203 203

Boiler Water Supply/Return ANSI Flanges ø inches 4 4 4 4 4 6

Gas Supply Connection (NG) ø inches 2.5 2.5 2.5 2.5 3 3

Flue Gas Outlet Size ID ø inches 10 10 12 12 16 16

Combustion Air Supply Size ID ø inches 10 10 12 12 16 16

Power Supply V / PH / Hz 120 / 1 / 160 120 / 1 / 160 120 / 1 / 160 120 / 1 / 160 208 / 3 / 60 208 / 3 / 60

Power Consumption At Max. Input NG Amp 20 20 20 20 20 20

* Tested to ANSI/AHRI standard 1500 Performance Rating of Commercial Space Heating Boilers / DOE Test Procedure 81 FR 89276 / U.S. Standards ANSI Z21.13/CSA 4.9 / AHRI, BTS-2000 Testing Standard Method to determine the efficiency of Commercial Heating Boilers.

Technical information subject to change without notice.

9442732 10/2020 Printed in USA

L E G E N D A Supply header

B Return header

C Vitotronic 300 GW6C

D Common supply water temperature limit switch 210°F (99°C)

E Common flue gas temperature limit switch

F Boiler section automatic motorized isolation valve

G Flue gas collector cleanout and inspection port

H Air vent

I Viessmann cylinder burner (1 per section)

J 160 psi maximum operating pressure

K Boiler drains

L Low water cutoff

M Pressure and temperature gauge

N Pressure relief valve

O Boiler heat exchanger https://www.viessmann-us.com/ https://www.viessmann-us.com/

SUBMITTAL

A-429H

JOB: REPRESENTATIVE:

UNIT TAG: ORDER NUMBER: DATE:

ENGINEER: SUBMITTED BY: DATE:

CONTRACTOR: APPROVED BY: DATE:

CAST IRON BODY STAINLESS STEEL BODY RATED MOTOR CHARACTERISTICS

MODEL NUMBER PART NUMBER MODEL NUMBER PART NUMBER HP* VOLTAGE PHASE Hz WATTS RANGE AMP RANGE ecocirc XL 20-35 104300 ecocirc XL N 20-35 104450LF 1/12 115 1 50/60 6 - 85 0.1 - 1.3 ecocirc XL 36-45 104301 ecocirc XL N 36-45 104451LF 1/6 115 1 50/60 20 - 200 0.1 - 3.0 ecocirc XL 36-45 104302 ecocirc XL N 36-45 104452LF 1/6 208-230 1 50/60 20 - 200 0.1 - 1.5 ecocirc XL 15-75 104303 ecocirc XL N 15-75 104453LF 1/6 115 1 50/60 30 - 150 0.1 - 2.3 ecocirc XL 15-75 104304 ecocirc XL N 15-75 104454LF 1/6 208-230 1 50/60 30 - 150 0.1 - 1.1 ecocirc XL 55-45 104306 ecocirc XL N 55-45 104456LF 1/2 208-230 1 50/60 30 - 500 0.2 - 2.0 ecocirc XL 20-140 104308 ecocirc XL N 20-140 104458LF 1/2 208-230 1 50/60 35 - 470 0.2 - 2.0 ecocirc XL 65-130 104309 ecocirc XL N 65-130 104459LF 1 208-230 1 50/60 45 - 825 0.5 - 3.5 ecocirc XL 40-200 104312 ecocirc XL N 40-200 104462LF 1 208-230 1 50/60 45 - 825 0.5 - 3.5 ecocirc XL 70-145 104315 ecocirc XL N 70-145 104465LF 2 208-230 1 50/60 55 - 1400 0.6 - 6.0 ecocirc XL 40-275 104318 ecocirc XL N 40-275 104468LF 2 208-230 1 50/60 50 - 1400 0.5 - 6.0 ecocirc XL 65-130 104310 ecocirc XL N 65-130 104460LF 1 208-230/400-460 3 50/60 50 - 800 0.5 - 2.8/2.0 ecocirc XL 40-200 104313 ecocirc XL N 40-200 104463LF 1 208-230/400-460 3 50/60 50 - 800 0.5 - 2.8/2.0 ecocirc XL 95-160 104321 ecocirc XL N 95-160 104471LF 2 208-230/400-460 3 50/60 50 - 1250 0.5 - 4.4/2.0 ecocirc XL 27-320 104323 ecocirc XL N 27-320 104473LF 2 208-230/400-460 3 50/60 50 - 1500 0.5 - 4.4/3.0 ecocirc XL 110-180 104326 ecocirc XL N 110-180 104476LF 3 400-460 3 50/60 50 - 2000 0.5 - 3.7 ecocirc XL 45-375 104328 ecocirc XL N 45-375 104478LF 3 400-460 3 50/60 50 - 2150 0.5 - 4.0

SUBMITTAL

A-429G

JOB: REPRESENTATIVE:

UNIT TAG: ORDER NO. DATE:

ENGINEER: SUBMITTED BY: DATE:

CONTRACTOR: APPROVED BY: DATE:

ecocirc® XL High Efficiency Large Wet Rotor Circulator with Electronically Commutated Motor (ECM)

DESCRIPTION

The ecocirc® XL circulator is designed with a highly efficient electronically commutated permanent magnet motor (ECM Technology). Cast Iron model is designed for closed loop hydronic heating and cooling systems, and Stainless Steel body pump for plumbing systems or open loop heating and cooling systems.

CONSTRUCTION MATERIALS

Pump Body: Cast Iron or Stainless Steel Impeller: Poly-phenylene Sulfide or Stainless Steel Shaft: AISI 420 Stainless Steel Rotor: Permanent Magnet Bearing: Carbon Sleeve Gasket/O-Ring: EPDM All Other Wetted Parts: AISI 304 Stainless Steel Motor Type: Electronically Commutated Permanent Magnet Motor Insulation Class: F

SPECIFICATIONS

OPERATING DATA

Maximum Working Pressure: 175 psi (12 Bar) Minimum Working Temperature: 14°F (-10°C) Maximum Working Temperature: 230°F (110°C) Ambient Temperature Range: 32°F - 104°F (0°C - 40°C)

MODEL NO.

FLOW HEAD

HP RPM

VOLTAGE CYCLE PHASE

SPECIALS

SCHEDULE

CAST IRON BODY STAINLESS STEEL BODY RATED MOTOR CHARACTERISTICS

MODEL NUMBER PART NUMBER MODEL NUMBER PART NUMBER HP* VOLTAGE PHASE Hz WATTS RANGE AMP RANGE ecocirc XL 20-35 104300 ecocirc XL N 20-35 104450LF 1/12 115 1 50/60 6 - 85 0.1 - 1.3 ecocirc XL 36-45 104301 ecocirc XL N 36-45 104451LF 1/6 115 1 50/60 20 - 200 0.1 - 3.0 ecocirc XL 36-45 104302 ecocirc XL N 36-45 104452LF 1/6 208-230 1 50/60 20 - 200 0.1 - 1.5 ecocirc XL 15-75 104303 ecocirc XL N 15-75 104453LF 1/6 115 1 50/60 30 - 150 0.1 - 2.3 ecocirc XL 15-75 104304 ecocirc XL N 15-75 104454LF 1/6 208-230 1 50/60 30 - 150 0.1 - 1.1 ecocirc XL 55-45 104306 ecocirc XL N 55-45 104456LF 1/2 208-230 1 50/60 30 - 500 0.2 - 2.0 ecocirc XL 20-140 104308 ecocirc XL N 20-140 104458LF 1/2 208-230 1 50/60 35 - 470 0.2 - 2.0 ecocirc XL 65-130 104309 ecocirc XL N 65-130 104459LF 1 208-230 1 50/60 45 - 825 0.5 - 3.5 ecocirc XL 40-200 104312 ecocirc XL N 40-200 104462LF 1 208-230 1 50/60 45 - 825 0.5 - 3.5 ecocirc XL 70-145 104315 ecocirc XL N 70-145 104465LF 2 208-230 1 50/60 55 - 1400 0.6 - 6.0 ecocirc XL 40-275 104318 ecocirc XL N 40-275 104468LF 2 208-230 1 50/60 50 - 1400 0.5 - 6.0 ecocirc XL 65-130 104310 ecocirc XL N 65-130 104460LF 1 208-230/400-460 3 50/60 50 - 800 0.5 - 2.8/2.0 ecocirc XL 40-200 104313 ecocirc XL N 40-200 104463LF 1 208-230/400-460 3 50/60 50 - 800 0.5 - 2.8/2.0 ecocirc XL 95-160 104321 ecocirc XL N 95-160 104471LF 2 208-230/400-460 3 50/60 50 - 1250 0.5 - 4.4/2.0 ecocirc XL 27-320 104323 ecocirc XL N 27-320 104473LF 2 208-230/400-460 3 50/60 50 - 1500 0.5 - 4.4/3.0 ecocirc XL 110-180 104326 ecocirc XL N 110-180 104476LF 3 400-460 3 50/60 50 - 2000 0.5 - 3.7 ecocirc XL 45-375 104328 ecocirc XL N 45-375 104478LF 3 400-460 3 50/60 50 - 2150 0.5 - 4.0

Note: Where potable water is pumped, use a stainless steel booster. ecocirc XL pumps are recommended for indoor use only.

* Nominal HP

Note: Where potable water is pumped, use a stainless steel booster. ecocirc XL pumps are recommended for indoor use only.

* Nominal HP

SCHEDULE

ecocirc XL A-429F

DIMENSIONS AND WEIGHTS

MODEL NO Nominal Motor HP DIMENSIONS - INCHES (mm) APPROX. SHIPPING WEIGHT LBS. (KG) A B C D E F Cast Iron Stainless Steel ecocirc XL 20-35 1/12 9.94 (252) 6.38 (162) 8.20 (208) 4.19 (106) 7.20 (183) 4.72 (120) 19.8 (9) 22 (10) ecocirc XL 36-45 1/6 9.94 (252) 6.38 (162) 8.20 (208) 4.19 (106) 7.20 (183) 4.72 (120) 19.8 (9) 22 (10) ecocirc XL 15-75 1/6 11.04 (280) 8.5 (216) 8.39 (213) 5.19 (132) 7.57 (192) 4.72 (120) 26.4 (12) 28.6 (13) ecocirc XL 55-45 1/2 11.89 (302) 6.38 (162) 10.18 (258) 4.19 (106) 8.12 (206) 5.02 (127) 26.4 (12) 28.6 (13) ecocirc XL 20-140 1/2 13.39 (340) 11.5 (292) 10.41 (264) 5.19 (132) 8.20 (208) 5.02 (127) 35.2 (16) 39.6 (18) ecocirc XL 65-130 1 14.84 (377) 11.5 (292) 11.80 (299) 4.62 (117) 9.53 (242) 5.77 (146) 39.6 (18) 44 (20) ecocirc XL 40-200 1 15.17 (385) 11.5 (292) 11.80 (299) 5.19 (132) 9.53 (242) 5.77 (146) 41.8 (19) 46.2 (21) ecocirc XL 70-145 2 14.84 (377) 11.5 (292) 11.80 (299) 4.62 (117) 9.53 (242) 5.77 (146) 38.4 (17.4) 44 (20) ecocirc XL 40-275 2 16.04 (407) 12.0 (305) 12.57 (319) 6.00 (152) 10.07 (256) 5.77 (146) 49.6 (22.5) 55 (25) ecocirc XL 65-130 1 14.96 (380) 11.5 (292) 11.85 (301) 2.87 (73) 10.43 (265) 5.31 (135) 39.6 (18) 44 (20) ecocirc XL 40-200 1 15.23 (387) 11.5 (292) 11.85 (301) 5.19 (132) 10.43 (265) 5.31 (135) 35.2 (16) 39.6 (18) ecocirc XL 95-160 2 14.44 (367) 11.5 (292) 11.37 (289) 2.87 (73) 10.43 (265) 5.31 (135) 39.6 (18) 44 (20) ecocirc XL 27-320 2 15.27 (388) 14.17 (360) 11.81 (300) 6.00 (152) 10.43 (265) 5.31 (135) 49.6 (22.5) 55 (25) ecocirc XL 110-180 3 14.44 (367) 11.5 (292) 11.37 (289) 2.87 (73) 10.43 (265) 5.31 (135) 38.4 (17.4) 44 (20) ecocirc XL 45-375 3 16.14 (410) 14.17 (360) 12.67 (321) 6.00 (152) 10.43 (265) 5.31 (135) 49.6 (22.5) 55 (25)

MODEL NO FLANGE SIZE INCHES - NPT # of Bolts DIMENSIONS - INCHES (mm) B&G COMPANION FLANGE (Set of 2)

G H J K CAST IRON PN STAINLESS STEEL PN

ecocirc XL 20-35 3/4, 1, 1-1/4, 1-1/2 2 4.19 (106) 3.16 (80) 2.62 (66) 0.47 (12) 101201 - 101204 101208LF - 101211LF ecocirc XL 36-45 3/4, 1, 1-1/4, 1-1/2 2 4.19 (106) 3.16 (80) 2.62 (66) 0.47 (12) 101201 - 101204 101208LF - 101211LF ecocirc XL 15-75 2 4 5.18 (132) 4.06 (103) - 0.56 (14) 101215 101216LF ecocirc XL 55-45 3/4, 1, 1-1/4, 1-1/2 2 4.19 (106) 3.16 (80) 2.62 (66) 0.47 (12) 101201 - 101204 101208LF - 101211LF ecocirc XL 20-140 2 4 5.19 (132) 4.06 (103) - 0.56 (14) 101215 101216LF ecocirc XL 65-130 1, 1-1/4, 1-1/2 2 4.62 (117) 3.44 (87) 2.86 (73) 0.47 (12) 101205 - 101207 101212LF - 101214LF ecocirc XL 40-200 2 4 5.19 (132) 4.06 (103) - 0.56 (14) 101215 101216LF ecocirc XL 70-145 1, 1-1/4, 1-1/2 2 4.62 (117) 3.44 (87) 2.86 (73) 0.47 (12) 101205-101207 101212LF-101214LF ecocirc XL 40-275 3 4 6.00 (152) 5.06 (129) - 0.53 (13) 101217 101218LF ecocirc XL 65-130 1, 1-1/4, 1-1/2 2 4.62 (117) 3.44 (87) 2.86 (73) 0.47 (12) 101205 - 101207 101212LF - 101214LF ecocirc XL 40-200 2 4 5.19 (132) 4.06 (103) - 0.56 (14) 101215 101216LF ecocirc XL 95-160 1, 1-1/4, 1-1/2 2 4.62 (117) 3.44 (87) 2.86 (73) 0.47 (12) 101205 - 101207 101212LF - 101214LF ecocirc XL 27-320 3 4 6.00 (152) 5.06 (129) - 0.53 (13) 101217 101218LF ecocirc XL 110-180 1, 1-1/4, 1-1/2 2 4.62 (117) 3.44 (87) 2.86 (73) 0.47 (12) 101205-101207 101212LF-101214LF ecocirc XL 45-375 3 4 6.00 (152) 5.06 (129)) - 0.53 (13) 101217 101218LF

1-1/2" is the diameter of the suction and discharge for the 2-bolt models.

SINGLE PHASE PUMP DIMENSIONS THREE PHASE PUMP DIMENSIONS

MODEL NO Nominal Motor HP DIMENSIONS - INCHES (mm) APPROX. SHIPPING WEIGHT

LBS. (KG)

A B C D E F Cast Iron Stainless Steel ecocirc XL 20-35 1/12 9.94 (252) 6.38 (162) 8.20 (208) 4.19 (106) 7.20 (183) 4.72 (120) 19.8 (9) 22 (10) ecocirc XL 36-45 1/6 9.94 (252) 6.38 (162) 8.20 (208) 4.19 (106) 7.20 (183) 4.72 (120) 19.8 (9) 22 (10) ecocirc XL 15-75 1/6 11.04 (280) 8.5 (216) 8.39 (213) 5.19 (132) 7.57 (192) 4.72 (120) 26.4 (12) 28.6 (13) ecocirc XL 55-45 1/2 11.89 (302) 6.38 (162) 10.18 (258) 4.19 (106) 8.12 (206) 5.02 (127) 26.4 (12) 28.6 (13) ecocirc XL 20-140 1/2 13.39 (340) 11.5 (292) 10.41 (264) 5.19 (132) 8.20 (208) 5.02 (127) 35.2 (16) 39.6 (18) ecocirc XL 65-130 1 14.84 (377) 11.5 (292) 11.80 (299) 4.62 (117) 9.53 (242) 5.77 (146) 39.6 (18) 44 (20) ecocirc XL 40-200 1 15.17 (385) 11.5 (292) 11.80 (299) 5.19 (132) 9.53 (242) 5.77 (146) 41.8 (19) 46.2 (21) ecocirc XL 70-145 2 14.84 (377) 11.5 (292) 11.80 (299) 4.62 (117) 9.53 (242) 5.77 (146) 38.4 (17.4) 44 (20) ecocirc XL 40-275 2 16.04 (407) 12.0 (305) 12.57 (319) 6.00 (152) 10.07 (256) 5.77 (146) 49.6 (22.5) 55 (25) ecocirc XL 65-130 1 14.96 (380) 11.5 (292) 11.85 (301) 2.87 (73) 10.43 (265) 5.31 (135) 39.6 (18) 44 (20) ecocirc XL 40-200 1 15.23 (387) 11.5 (292) 11.85 (301) 5.19 (132) 10.43 (265) 5.31 (135) 35.2 (16) 39.6 (18) ecocirc XL 95-160 2 14.44 (367) 11.5 (292) 11.37 (289) 2.87 (73) 10.43 (265) 5.31 (135) 39.6 (18) 44 (20) ecocirc XL 27-320 2 15.27 (388) 14.17 (360) 11.81 (300) 6.00 (152) 10.43 (265) 5.31 (135) 49.6 (22.5) 55 (25) ecocirc XL 110-180 3 14.44 (367) 11.5 (292) 11.37 (289) 2.87 (73) 10.43 (265) 5.31 (135) 38.4 (17.4) 44 (20) ecocirc XL 45-375 3 16.14 (410) 14.17 (360) 12.67 (321) 6.00 (152) 10.43 (265) 5.31 (135) 49.6 (22.5) 55 (25)

MODEL NO FLANGE SIZE INCHES - NPT # of Bolts DIMENSIONS - INCHES (mm) B&G COMPANION FLANGE (Set of 2)

G H J K CAST IRON PN STAINLESS STEEL PN

ecocirc XL 20-35 3/4, 1, 1-1/4, 1-1/2 2 4.19 (106) 3.16 (80) 2.62 (66) 0.47 (12) 101201 - 101204 101501LF-101504LF ecocirc XL 36-45 3/4, 1, 1-1/4, 1-1/2 2 4.19 (106) 3.16 (80) 2.62 (66) 0.47 (12) 101201 - 101204 101501LF-101504LF ecocirc XL 15-75 2 4 5.18 (132) 4.06 (103) - 0.56 (14) 101215 101508LF ecocirc XL 55-45 3/4, 1, 1-1/4, 1-1/2 2 4.19 (106) 3.16 (80) 2.62 (66) 0.47 (12) 101201 - 101204 101501LF-101504LF ecocirc XL 20-140 2 4 5.19 (132) 4.06 (103) - 0.56 (14) 101215 101508LF ecocirc XL 65-130 1, 1-1/4, 1-1/2 2 4.62 (117) 3.44 (87) 2.86 (73) 0.47 (12) 101205 - 101207 101505LF-101507LF ecocirc XL 40-200 2 4 5.19 (132) 4.06 (103) - 0.56 (14) 101215 101508LF ecocirc XL 70-145 1, 1-1/4, 1-1/2 2 4.62 (117) 3.44 (87) 2.86 (73) 0.47 (12) 101205-101207 101505LF-101507LF ecocirc XL 40-275 3 4 6.00 (152) 5.06 (129) - 0.53 (13) 101217 101509LF ecocirc XL 65-130 1, 1-1/4, 1-1/2 2 4.62 (117) 3.44 (87) 2.86 (73) 0.47 (12) 101205 - 101207 101505LF-101507LF ecocirc XL 40-200 2 4 5.19 (132) 4.06 (103) - 0.56 (14) 101215 101508LF ecocirc XL 95-160 1, 1-1/4, 1-1/2 2 4.62 (117) 3.44 (87) 2.86 (73) 0.47 (12) 101205 - 101207 101505LF-101507LF ecocirc XL 27-320 3 4 6.00 (152) 5.06 (129) - 0.53 (13) 101217 101509LF ecocirc XL 110-180 1, 1-1/4, 1-1/2 2 4.62 (117) 3.44 (87) 2.86 (73) 0.47 (12) 101205-101207 101505LF-101507LF ecocirc XL 45-375 3 4 6.00 (152) 5.06 (129)) - 0.53 (13) 101217 101509LF

1-1/2" is the diameter of the suction and discharge for the 2-bolt models.

DIMENSIONS AND WEIGHTS

ecocirc XL A-429H

ONBOARD USER INTERFACE

SAFETY STANDARDS AND PROTECTION

� Enclosure: Class 2, IP44 (equivalent to NEMA Type 2) � UL Listed to UL 778; UL 1004-1, 1004-7; and UL 60730-1 � cUL Listed to C22.2 #108 � Electronically Thermally Protected (Integrated Motor Protection) � Motor Insulation Class: F � Stainless steel models are CSA Certified for NSF/ANSI 61 that product contains less than 0.25% lead content by weight on wetted surface. certified.

STANDARD OPERATING MODES

CONSTANT SPEED

The pump maintains a constant speed at any flow rate. The desired speed is set on the interface panel of the pump.

CONSTANT PRESSURE (Δp-c)

The pump maintains a constant differential pressure at any flow demand until the maximum speed is reached. The desired head of the pump can be set via user interface. Recommended for use in systems with small or constant pressure losses.

PROPORTIONAL PRESSURE (Δp-v)

The differential pressure continuously increases or deceases based on the flow demand. The set point head can be set on the pump user interface. Use for systems with large pressure losses.

NIGHT MODE

The pump will automatically reduce speed when there is an abrupt change in fluid temperature. The change in fluid temperature is from a boiler operating in night time setback mode. The built-in temperature sensor is used. (Fixed Speed, Constant Pressure, Proportional Pressure)

TEMPERATURE DEPENDENT OPERATING MODES

SET POINT TEMPERATURE (Δp-T)

The nominal differential pressure set point is modified based on the fluid temperature.Uses the built-in temperature sensor.

SET POINT TEMPERTURE (T)

The pump maintains a constant temperature in a system, such as domestic hot water system or a single temperature heating system.

Uses the built-in temperature sensor.

DIFFERENTIAL TEMPERTURE (ΔT)

The pump maintains a constant differential temperature between the built-in and external temperature sensors.

INPUT SIGNALS

� One 0-10V (Analog): Speed Control by external controller � One 4-20mA (Analog): Connection with an external differential pressure sensor for pressure control mode (two differential pressure sensor ranges: 0-15 and 0-30 PSIG) on single phase models.

● Two absolute pressure sensors 4-20mA (Analog) input for three phase models.

� One external temperature sensor input for Differential Temp operating mode.

Sensor Type: KTY82, P/N: 104502

� One built-in temperature sensor for Set Point Temp and Differential-Temp operating mode.

REMOTE BUILDING MANAGEMENT SYSTEM CAPABILITIES

� The pump can be monitored or controlled by a signal from BMS (Building Management System). Built-in protocols are BACnet and Modbus. Direct connection to a PC is available.

� An optional wireless module can be added to create a short range wireless field for remote connection to the pump. An internet browser can be used to program the advanced settings. Module P/N: 104500

START/STOP CONNECTIONS: Connect to external dry contact relay or use with a thermostat.

OUTPUT RELAY(single phase): Normally Open Dry Contact Relay for Fault Mode indication.

OUTPUT RELAYS (three phase): Two Normally Open Dry Contact Relays for Fault Mode and Run indication.

1. Control mode button

2. Control mode indicators

3. Parameter button

4. Parameter indicators

5. Setting buttons

6. Numeric display

7. Power indicator

8. Status / Fault indicator

9. Remote control indicator

Xylem Inc.

8200 N. Austin Avenue Morton Grove, IL 60053 Phone: (847)966-3700 Fax: (847)965-8379 www.xylem.com/bellgossett Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries.

© 2021 Xylem Inc.

ecocirc XL A-429H ecocirc XL High Head Performance Range ecocirc XL High Flow Performance Range

Q [GPM]

15-75

20-140

40-200

40-275

27-320

45-375 ecocirc XL High Flow Performance Range Curve

25 50 75 100 125 150 175 200 225 250 275 300 325 350

H [P

I]

Q [GPM]

20-35

36-45

55-45 65-130

70-145

95-160 110-180 ecocirc XL High Head Performance Range Curve

20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170

H [P

I]

Xylem Inc.

8200 N. Austin Avenue

Morton Grove, IL 60053

Tel: (847) 966–3700 Fax: (847) 965–8379 www.xylem.com/bellgossett

Xylem and Bell & Gossett are registered trademarks of Xylem Inc. or one of its subsidiaries. All other trademarks or registered trademarks are property of their respective owners.

© 2024 Xylem A-429H June 2024

ONBOARD USER INTERFACE

SAFETY STANDARDS AND PROTECTION

� Enclosure: Class 2, IP44 (equivalent to NEMA Type 2) � UL Listed to UL 778; UL 1004-1, 1004-7; and UL 60730-1 � cUL Listed to C22.2 #108 � Electronically Thermally Protected (Integrated Motor Protection) � Motor Insulation Class: F � Stainless steel models are CSA Certified for NSF/ANSI 61 that product contains less than 0.25% lead content by weight on wetted surface. certified.

STANDARD OPERATING MODES

CONSTANT SPEED

The pump maintains a constant speed at any flow rate. The desired speed is set on the interface panel of the pump.

CONSTANT PRESSURE (Δp-c)

The pump maintains a constant differential pressure at any flow demand until the maximum speed is reached. The desired head of the pump can be set via user interface. Recommended for use in systems with small or constant pressure losses.

PROPORTIONAL PRESSURE (Δp-v)

The differential pressure continuously increases or deceases based on the flow demand. The set point head can be set on the pump user interface. Use for systems with large pressure losses.

NIGHT MODE

The pump will automatically reduce speed when there is an abrupt change in fluid temperature. The change in fluid temperature is from a boiler operating in night time setback mode. The built-in temperature sensor is used. (Fixed Speed, Constant Pressure, Proportional Pressure)

TEMPERATURE DEPENDENT OPERATING MODES

SET POINT TEMPERATURE (Δp-T)

The nominal differential pressure set point is modified based on the fluid temperature.Uses the built-in temperature sensor.

SET POINT TEMPERTURE (T)

The pump maintains a constant temperature in a system, such as domestic hot water system or a single temperature heating system.

Uses the built-in temperature sensor.

DIFFERENTIAL TEMPERTURE (ΔT)

The pump maintains a constant differential temperature between the built-in and external temperature sensors.

INPUT SIGNALS

� One 0-10V (Analog): Speed Control by external controller � One 4-20mA (Analog): Connection with an external differential pressure sensor for pressure control mode (two differential pressure sensor ranges: 0-15 and 0-30 PSIG) on single phase models.

● Two absolute pressure sensors 4-20mA (Analog) input for three phase models.

� One external temperature sensor input for Differential Temp operating mode.

Sensor Type: KTY82, P/N: 104502

� One built-in temperature sensor for Set Point Temp and Differential-Temp operating mode.

REMOTE BUILDING MANAGEMENT SYSTEM CAPABILITIES

� The pump can be monitored or controlled by a signal from BMS (Building Management System). Built-in protocols are BACnet and Modbus. Direct connection to a PC is available.

� An optional wireless module can be added to create a short range wireless field for remote connection to the pump. An internet browser can be used to program the advanced settings. Module P/N: 104500

START/STOP CONNECTIONS: Connect to external dry contact relay or use with a thermostat.

OUTPUT RELAY(single phase): Normally Open Dry Contact Relay for Fault Mode indication.

OUTPUT RELAYS (three phase): Two Normally Open Dry Contact Relays for Fault Mode and Run indication.

1. Control mode button

2. Control mode indicators

3. Parameter button

4. Parameter indicators

5. Setting buttons

6. Numeric display

7. Power indicator

8. Status / Fault indicator

9. Remote control indicator

Xylem Inc.

8200 N. Austin Avenue Morton Grove, IL 60053 Phone: (847)966-3700 Fax: (847)965-8379 www.xylem.com/bellgossett Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries.

© 2021 Xylem Inc.

ecocirc XL A-429H

Overview
Bids to include the following:
Additional Information
Non-Mandatory Walk-Throughs
Desired Installation Time-Line
Proposal Timeline
Proposal Requirements