This is a comprehensive set of architectural and engineering design drawings for the Rehabilitation and Renovation of the Historic Chase Building located at 236 Grand Avenue in Waterbury, Connecticut, issued by the City of Waterbury under RFP #8287. The project encompasses electrical power distribution, lighting controls, technology infrastructure, and associated mechanical and structural systems across a five-story building with basement levels. The electrical scope includes installation of new panelboards, branch circuits, receptacles, and lighting fixtures throughout the facility; replacement of the main switchboard with new distribution sections; installation of lightning protection systems; and integration of emergency power systems including a 1600VA inverter and backup generator connections. Technology infrastructure includes structured cabling for data and voice communications, wireless access points, video conferencing systems, and dedicated IT rooms with network racks and patch panels on the basement and third floors. The project specifications detail conduit sizing, wire gauges, mounting heights, coordination requirements with mechanical and plumbing contractors, and compliance with national electrical codes and industry standards. The contract documents are marked "Not for Construction" and include extensive keynotes, schedules, and cross-references to coordinate work across multiple trades and building systems.

The design establishes 208/120V, three-phase, four-wire electrical service with 3000-ampere main bus capacity distributed through existing and new circuit breakers rated from 15 amperes to 1000 amperes depending on equipment load requirements. Specific major loads include a chiller requiring 1000-ampere feed, multiple HVAC units, water heating systems, and distributed lighting and receptacle circuits organized by floor and zone. Telecommunications cabling utilizes Category 6A unshielded twisted-pair cables routed through conduit to patch panels in dedicated telecommunications rooms, with fiber optic backbone connections between floors. The project requires extensive coordination between electrical, mechanical, plumbing, fire protection, and technology divisions, with notation that existing data room operations must remain functional during construction. Fire-rated wall penetrations, conduit sleeves through floors, proper bonding and grounding connections, and compliance with UL standards for lightning protection and emergency lighting are mandatory. The design accommodates future expansion with spare circuit breaker positions and cable management provisions within equipment racks, and includes provisions for building management system connections and occupancy-based lighting controls throughout the facility.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A T

S A

T S

PL

N G

N G

N G

N G

U C

PL

J

J

A CB D E G H J K L M N P QF

1.1

EX

2.7

2.8

2.9

BUILDING

MECHANICAL ROOM

BUILDING SECURED

VAULT STORAGE

EDUCATIONAL

STORAGE AREA

PASSAGE

005A

WOMEN'S

REGISTRAR OF

VOTERS STORAGE

BUILDING

MAINTENANCE

OFFICE

IT CLOSET

PARKS DEPT.

OUTDOOR

EQUIPMENT

STORAGE

FIELD OFFICE/

SECURITY

SUPERINTENDENTS

STORAGE

026 HRIS STORAGE

FINANCE/ TAX

STORAGE

HR STORAGE

BUILDING ELEC.

BUILDING ELEC.

CORRIDOR

CORRIDOR

PROBATE STORAGE

CLOSET

CLOSET

PARKS DEPT.

STORAGE

EP1.0

EP1.0

PARKS DEPT.

STORAGE

a,GFI a,GFI

PROVIDE NEW PULLBOX FOR

NEW CHILLER FEED, PCHWP-1

FEED, MOTORIZED GATE, AND

RECEPTACLE BRANCH CIRCUITS

MOUNTED BELOW EXISTING TO

REMAIN PULL BOX FOR

GENERATOR FEEDERS

PROVIDE (3) 4" FOR CHILLER, (1) 1" CONDUIT

FOR PCHWP-1, AND 2#10,#10G IN 1"C CONDUIT

FOR RECEPTACLE ROUTED UNDERGROUND

FROM PULL BOX TO CHILLER CH-1. REFER TO

MOTOR CIRCUIT SCHEDULE FOR WIRING

REQUIREMENTS. REFER TO CHILLER CH-1

TRENCHING DETAIL ON E5.1

PROVIDE (3) 4" FOR CHILLER

CH-1 ROUTED FROM EXISTING

SWITCHBOARD TO PULL BOX

TO CHILLER CH-1

DOAS-3DOAS-2

WFU-2 WFU-1

FCU-C

E P

O

EB-D1, ETR

ATS-2, ETR

ATS-1, ETR

WH-2

WH-1

B-1

B-2

PHWP-1

PHWP-2

E B

-2

E T

R

EXISTING SERVICE GROUNDING DISCONNECTED TO

INCOMING WATER SERVICE DURING DEMOLITION

PHASE TO BE RECONNECTED TO NEW WATER SERVICE

IN SAME LOCATION

BUILDING

MECHANICAL ROOM

EP3

ELEVATOR

A

E5.1

ELEVATOR

B

CUSTODIAL

STORAGE

REGISTRAR OF

VOTERS

TEMPORARY

STORAGE

CONNECT NEW LIGHTNING PROTECTION SYSTEM

BUILDING GROUND SYSTEM AT THIS LOCATION

REFER TO ESU1.0 ELECTRICAL SITE PLAN FOR

SITE LIGHTING AND POWER CIRCUITS

ORIGINATING FROM THIS LOCATION. REFER TO

FOUNDATION WALL PENETRATION DETAIL 12/E5.1

REFER TO ESU1.0 ELECTRICAL SITE

PLAN FOR SITE LIGHTING AND POWER

CIRCUITS ORIGINATING FROM THIS

LOCATION. REFER TO FOUNDATION

WALL PENETRATION DETAIL 12/E5.1

MEN'S

FCU-A

8, OSB

UH-A

UH-A

CL

GFI

GFI

GFI GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

BLDG. STOR.

UH-A

UH-A

UH-A

UH-A

UH-A

PROVIDE (2) 1" CONDUIT ROUTED

UNDERGROUND TO MOTORIZED

GATE. (1) CONDUIT WITH 2#10,

#10G FOR POWER, (1) CONDUIT

FOR DATA. REFER TO BRANCH

CIRCUIT TRENCHING DETAIL

PROVIDE (2) 1" CONDUIT ROUTED

UNDERGROUND TO MOTORIZED GATE.

(1) CONDUIT WITH 2#10, #10G FOR

POWER, (1) CONDUIT FOR DATA. REFER

TO BRANCH CIRCUIT TRENCHING DETAIL

STAIR

A

EDUCATION

STORAGE

DOAS EQUIPMENT

ROOM

STAIR

B

NEW CORRIDOR

GFI GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI GFI GFI GFI GFI GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI GFI

GFI GFI

GFI

E5.1

RP-1

2,4, MPB

T4.0

UH-A UH-A

UH-A

UH-A

UH-A

CU-1

DOAS-1

7, GPB

8, GPB

9, GPB

11, GPB

12, GPB

SHWP-1

SHWP-2

10, GPB

SCHWP -1 SCHWP-2

13, GPB

14, GPB

16, GPB

17, GPB

18, GPB

20, GPB

21, GPB

19, GPB

BUILDING ELEC.

7, OSB

9, OSB

10, OSB

EWC

23, GPB

REF REF

24, GPB 25, GPB

22, GPB

UH-A

UH-A

UH-A

UH-A

11, OSB

FCU-C

UH-A

EF-1

EP3

EP6

EP3

EP6

EP3

EP6

EP3

EP6

EP3

EP6

GMU-2

GMU-1

26, GPB

27, GPB

EP3

EP3

EP3

EP3

EP6

EP6

EP6

EP6

17, OSB

16, OSB

EPO

EP7

STORAGE

15, GPB

EP8

EP8

CU-4

CU-5

PROVIDE NEW GROUNDING ELECTRODE BACK TO

BUILDING ELECTRIC SERVICE BUS AT EXISTING

SWITCHGEAR. BONDING CONDUCTOR AND JUMPERS

TO BE SIZED PER NFPA 250.102, AND 250.122

GFI

GFI

GFI

UH-A

UH-A

UH-A

UH-A

D/S: ATS-2

EUH-A

EUH-A

19,21, EB-2, ETR 20,22, EB-2, ETR

G H

UTILITY METER

MSB-1 (SECT. 2)

MSB-1 (SECT. 1)

MSB-1 (MC)

MSB-1 (MAIN)

EXISTING ELECTRICAL

SWITCHBOARD MSB-1. REFER TO

DRAWING E6.1 FOR BREAKERS TO

REMAIN AND NEW BREAKERS TO BE

INSTALLED IN DISTRIBUTION

SECTIONS 1 AND 2.

BUILDING ELEC.

H

2.7

MPB

LPB

GPB

INV-1

MULTI-CIRCUIT EMERGENCY LIGHTING

INVERTER. REFER TO SCHEDULE FOR INV-1

ON E6.2 FOR SPECIFICATION AND WIRING

DIAGRAM ON E5.0 FOR ADDITIONAL

INFORMATION.

GFI

OSB

30, 1W

STORAGE

ELECTRICAL REFERENCE NOTE

1. REFER TO DRAWING E0.0 FOR ELECTRICAL POWER, LIGHTING, AND COORDINATION GENERAL

NOTES.

2. REFER TO DRAWING E0.0 FOR ELECTRICAL ABBREVIATIONS.

3. REFER TO DRAWING E0.0 FOR ELECTRICAL SYMBOL LEGENDS.

4. REFER TO DRAWING E6.0 FOR LIGHTING FIXTURE SCHEDULE.

CONTRACT

DOCUMENTS

NOT FOR CONSTRUCTION

SHEET NO.

PROFESSIONAL SEAL

21 Talcott Notch Road

Farmington, CT 06032 friar.com

860.678.1291

CONSULTANT

DATE:

SCALE

PROJ. #:

DRAWN:

CHECKED:

CES #2025224.00

1/29/2026 3:28:39 PM

As indicated

EP1.0

ELECTRICAL POWER

BASEMENT FLOOR

PLAN

REHABILITATION

AND RENOVATION

OF THE HISTORIC

CHASE BUILDING

CITY OF WATERBURY RFP #8287

236 GRAND AVENUE

WATERBURY, CT 06702

KCM

AJG

2024-108A

2026-0130

1/8" = 1'-0"

ELECTRICAL POWER BASEMENT PLAN - NEW

1/4" = 1'-0"

BASEMENT EXISTING ELECTRICAL ROOM

1/4" = 1'-0"

REMOTE BASEMENT ELECTRICAL ROOM

KEYNOTES - ELECTRICAL

Key Value Keynote Text

EP3 PROVIDE 1" PVC SCHEDULE 40 CONDUIT FROM ABOVE THE ROOF TO BELOW GRADE

EVERY 100" ON AVERAGE ALONG THE PERIMETER OF THE STRUCTURE FOR LIGHTNING

PROTECTION DOWNLEADS. CONDUIT NEVER TO EXCEED AN 8" RADIUS BEND TO

CONFORM TO UL96a. THIS PRECLUDES THE USE OF LB OR JUNCTION BOXES ALONG

THE CONDUIT PATH. PROVIDE CONDUIT AS TIGHT TO INTERIOR WALL AS POSSIBLE.

COORDINATE EXACT LOCATION AND EXECUTION OF WORK WITH ARCHITECT

EP6 PROVIDE 1" PVC SCHEDULE 40 CONDUIT FOR LIGHTNING PROTECTION PENETRATED

THROUGH FOUNDATION AT LEAST 2' BELOW GRADE, AND AT LEAST 2' OFF OF THE

FOUNDATION WALL. CONDUIT NEVER TO EXCEED AN 8" RADIUS BEND TO CONFORM TO

UL96a. THIS PRECLUDES THE USE OF LB OR JUNCTION BOXES ALONG THE CONDUIT

PATH. PROVIDE CONDUIT AS TIGHT TO INTERIOR WALL AS POSSIBLE. COORDINATE

EXACT LOCATION AND EXEXCUTION OF WORK WITH THE ARCHITECT

EP7 PROVIDE CONTACTOR FOR BOILER ROOM GAS AND ELECTRIC SHUTOFF. REFER TO

DETAIL 8/E5.2

EP8 PROVIDE 20A, 120V, 1-PHASE HARDWIRED CONNECTION TO BMS PANEL. COORDINATE

EXACT LOCATION AND MOUNTING HEIGHT WITH MECHANICAL CONTRACTOR PRIOR TO

ROUGH-IN. REFER TO MECHANICAL PIPING PLANS FOR ADDITIONAL INFORMATION.

REVISIONS

NO. DATE DESCRIPTION

PL

PT

PL

PL

PL

E

PT

PL

PL

PL

PL

PL

PL

PL

PL

PL PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PT

PL

PL

PL

PL

PL

PL

PL

PL

PLPL PL

PL

PL

PLPLPL

PL

PL

PL

FFFF

PL

FFFF

PL

E

PL

PT

PL

PE

B

B

B

B

A CB D E G H J K L M N P QF

1.1

EX

2.7

2.8

2.9

ACADEMIC LANG.

ARTS

STORAGE

106A

ACADEMIC SS &

SCIENCE

ACADEMIC MATH &

TEACHING

ACADEMIC R&T

PASSAGE

103A

OFFICE

103B

STORAGE

103C

ENTRY

STORAGE

110B

CLOSET

110D

COMMUNICATIONS

ENTRY

OFFICE

120A

SHARED

KITCHENETTE

ACADEMIC

MULTILINGUAL

ACADEMIC

MULTILINGUAL

ASS. SUPER

VACANT

OFFICE

ASSISTANT SUPER

ENTRY

154 OFFICE

SUPERINTENDENT

SUITE

CONFERENCE

158A

OFFICE

158B

OFFICE

158C

OFFICE

TOILET

157F

CLOSET

157E

OFFICE

157A

PASSAGE

157BTOILET

157C

SUPERINTENDENT

OFFICE

157D

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

ACADEMIC ART &

GYM

STORAGE

164A

STAIR

A

ENTRY

LOBBY

CORRIDOR

102W

CORRIDOR

102EENTRY

MAIL ROOM

MEN'S

1W 1E a,GFI a,GFI

EP1 EP1

EP2

a,GFI a,GFI

COPY

a,GFI

WM1 WM1

WM1

WM1

WM1WM1WM1WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

VC

VC

FCU-G

FCU-B

FCU-A

FCU-B

FCU-C FCU-C

FCU-E FCU-C

FCU-C

FCU-C

FCU-E

FCU-D

FCU-D

FCU-C

FCU-CFCU-C

OFFICE

110G

REGISTRAR

110A

OFFICE

110F

KITCHENETTE

110E

VAULT

110C

EP3

1, 1W

3, 1W

2, 1W

4, 1W

5, 1W

6, 1W 7, 1W

8, 1W

9, 1W

10, 1W

11, 1W

12, 1W

13, 1W

15, 1W

14, 1W

16, 1W

17, 1W

18, 1W

WOMENS

19, 1W

20, 1W 21, 1W

22, 1W

23, 1W

1, 1E

2, 1E

3, 1E

4, 1E

5, 1E 6, 1E

7, 1E

8, 1E

9, 1E

10, 1E

11, 1E

12, 1E

13, 1E

14, 1E

15, 1E

16, 1E

18, 1E

19, 1E

21, 1E

20, 1E

22, 1E

23, 1E

17, 1E

FCU-C

WM1

WM1

WM1

9, OS2W

10, OS2W

5, OS2W

WM1

1, OS2W

2, OS2E

3, OS2E

9, OS2E

6, OS2E

FCU-C

CL

CL

CL

CL

CL

CL

CL

CL

CL

CL CL CL CL CL CL

CL CL

CL

CL

CL

CL

CL

CL

CL

CL

CLCLCL

CL

CL

25, 1W

24, 1W 26, 1W

27, 1W

WM1

WM1

WM1 WM1

WM1

WM1

WM1

WM1

WM1

WM1 WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1 WM1

WM1

WM1

WM1 WM1

WM1 WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

a

28, 1W

GRAND STAIR

G

STAIR

B

WM1

VC

7'AFF

VC

7'AFF7'AFF

EP3

EP3

EP3

EP3

EP3

EP3

EP3

EP3

VC

25, 1E

27, 1E

18, OSB

19, OSB

20, OSB

21, OSB

REF

a,GFI a,GFI

29, 1W

REUSE EXISTING POWER BACKBOX

MOUNTED IN WALL ALONG FLOOR

AT THIS LOCATION FOR NEW

POWER TO DESK

35, 1W

ELECTRICAL REFERENCE NOTE

1. REFER TO DRAWING E0.0 FOR ELECTRICAL POWER, LIGHTING, AND COORDINATION GENERAL

NOTES.

2. REFER TO DRAWING E0.0 FOR ELECTRICAL ABBREVIATIONS.

3. REFER TO DRAWING E0.0 FOR ELECTRICAL SYMBOL LEGENDS.

4. REFER TO DRAWING E6.0 FOR LIGHTING FIXTURE SCHEDULE.

CONTRACT

DOCUMENTS

NOT FOR CONSTRUCTION

SHEET NO.

PROFESSIONAL SEAL

21 Talcott Notch Road

Farmington, CT 06032 friar.com

860.678.1291

CONSULTANT

DATE:

SCALE

PROJ. #:

DRAWN:

CHECKED:

CES #2025224.00

1/29/2026 3:39:40 PM

As indicated

EP1.1

ELECTRICAL POWER

FIRST FLOOR PLAN

REHABILITATION

AND RENOVATION

OF THE HISTORIC

CHASE BUILDING

CITY OF WATERBURY RFP #8287

236 GRAND AVENUE

WATERBURY, CT 06702

KCM

AJG

2024-108A

2026-0130

1/8" = 1'-0"

ELECTRICAL POWER FIRST FLOOR PLAN - NEW

REVISIONS

NO. DATE DESCRIPTION

KEYNOTES - ELECTRICAL

Key Value Keynote Text

EP1 PROVIDE NEW 60A, 42 POLE, RECESSED PANELBOARD.

EP2 PROVIDE DIVIDED SURFACE MOUNTED RACEWAY FOR INTERIOR POWER AND DATA

CIRCUITS

EP3 PROVIDE 1" PVC SCHEDULE 40 CONDUIT FROM ABOVE THE ROOF TO BELOW GRADE

EVERY 100" ON AVERAGE ALONG THE PERIMETER OF THE STRUCTURE FOR LIGHTNING

PROTECTION DOWNLEADS. CONDUIT NEVER TO EXCEED AN 8" RADIUS BEND TO

CONFORM TO UL96a. THIS PRECLUDES THE USE OF LB OR JUNCTION BOXES ALONG

THE CONDUIT PATH. PROVIDE CONDUIT AS TIGHT TO INTERIOR WALL AS POSSIBLE.

COORDINATE EXACT LOCATION AND EXECUTION OF WORK WITH ARCHITECT

E

PT

PL

PL

PLPL

PL PL

PT

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PT

PT

FF

PL

PL

PL

E

PL PL

E

E

PL

PT PT

PL

PL

PL

PL PL

B

B B

B

J

A CB D E G H J K L M N P QF

1.1

EX

2.7

2.8

2.9

STAIR

A

SHARED

KITCHENETTE

ENTITLEMENT

GRANTS SUITE

OFFICE

HR PUBLIC ENTRY

HR RECEPTIONISTS

HR COPY

203A

HR FILE VAULT

203B

HR SHARED OFFICE

HR MEETING

PASSAGE

OFFICE

OFFICE

HR CONFERENCE

TOILET

208A

PASS.

FILE STORAGE

204A

MEN'S

OFFICE

OFFICE

PASS.

OFFICE

212A

OFFICE

212B

LOBBY

CORRIDOR

201W

CORRIDOR

201E

CONFERENCE

ROOM

275 SPED OFFICE

COMP. GRANTS

OFFICE

COMP. GRANTS

OFFICE

SPED OFFICE

SPED OFFICE

OFFICE

SPED OFFICE

SPED OFFICE

SPED OFFICE

TOILET

267A

TOILET

268A

KITCHENETTE/

MEETING

250F

OFFICE

250G

OFFICE

250C

CLOSET

250D

CLOSET

250E

OFFICE

250A

TOILET

210A

2W 2E a,GFI a,GFI

TYPICAL OPEN OFFICE RECEPTACLE

POWER AND FIRE ALARM LAYOUT

EP1

EP1

EP2

WM1

WM1

WM1

WM1

WM1

a,GFI

OFFICE

WOMEN'S

WM1

WM1

WM1 WM1

WM1 WM1 WM1 WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1WM1

WM1

WM1WM1WM1WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

VC

VC

FCU-B

FCU-B

FCU-F

FCU-F

FCU-G

FCU-F

FCU-B

FCU-C

FCU-B

FCU-B

FCU-A

FCU-C FCU-E

EP3

EP3

FCU-F

1, 2W 2, 2W

3, 2W 4, 2W

5, 2W6, 2W

7, 2W

8, 2W

9, 2W

10, 2W

11, 2W

13, 2W

14, 2W

15, 2W

16, 2W 17, 2W

18, 2W

19, 2W

20, 2W

21, 2W

22, 2W

23, 2W

24, 2W

25, 2W

1, 2E

2, 2E

5, 2E

5, 2E

6, 2E

9, 2E

WM1

26, 2W

27, 2W

10, 2E

11, 2E

12, 2E

14, 2E

13, 2E

15, 2E

16, 2E

18, 2E

17, 2E

19, 2E

20, 2E

2, OS2W

FCU-B

4, OS2W

10, OS2E

7, OS2E

4, OS2E

CL

CL

CL

CL

CL

CL

CL

CL CL

CL

CL

CL

CL CL

CL

CL

CL

CL CL

CL CL

CL

CL

FCU-B

CL

CL

CL

CL

CL

21, 2E

22, 2E

FF

23, 2E

24, 2E

FF

26, 2E

25, 2E

29, 2W

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1 WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1

LP2W

OS2W

OS2E LP2E

a,GFI a,GFI

4, 2E

STORAGE

a,GFI

WM1

COPY

a,GFI a,GFI

CL

A A

CL

27, 2E

WM1

B

8, 2E

STAIR

B

28, 1W

REFER TO STORAGE

219 LOWER LEVEL

FOR CONTINUATION

OF CIRCUIT

WM1

WM1

12, 2W

GRAND STAIR

G

VC

7, 2E

28, 2W

WM1

WM1

FCU-B

6,11, OS2W

11, OS2W

EP3

EP3

EP3

EP3

EP3

EP3

EP3

EP3

15, OS2W

16, OS2W

17, OS2W 12, OS2E

13, OS2E

CORRIDOR

EP8

G H

2.7

REFER TO STORAGE 219

UPPER LEVEL FOR

CONTINUATION OF CIRCUIT

ELECTRICAL REFERENCE NOTE

1. REFER TO DRAWING E0.0 FOR ELECTRICAL POWER, LIGHTING, AND COORDINATION GENERAL

NOTES.

2. REFER TO DRAWING E0.0 FOR ELECTRICAL ABBREVIATIONS.

3. REFER TO DRAWING E0.0 FOR ELECTRICAL SYMBOL LEGENDS.

4. REFER TO DRAWING E6.0 FOR LIGHTING FIXTURE SCHEDULE.

CONTRACT

DOCUMENTS

NOT FOR CONSTRUCTION

SHEET NO.

PROFESSIONAL SEAL

21 Talcott Notch Road

Farmington, CT 06032 friar.com

860.678.1291

CONSULTANT

DATE:

SCALE

PROJ. #:

DRAWN:

CHECKED:

CES #2025224.00

1/29/2026 3:28:47 PM

As indicated

EP1.2

ELECTRICAL POWER

SECOND FLOOR

PLAN

REHABILITATION

AND RENOVATION

OF THE HISTORIC

CHASE BUILDING

CITY OF WATERBURY RFP #8287

236 GRAND AVENUE

WATERBURY, CT 06702

KCM

AJG

2024-108A

2026-0130

1/8" = 1'-0"

ELECTRICAL POWER SECOND FLOOR PLAN - NEW

REVISIONS

NO. DATE DESCRIPTION

1/4" = 1'-0"

ELECTRICAL POWER STORAGE 219 LOWER LEVEL - NEW

KEYNOTES - ELECTRICAL

Key Value Keynote Text

EP1 PROVIDE NEW 60A, 42 POLE, RECESSED PANELBOARD.

EP2 PROVIDE DIVIDED SURFACE MOUNTED RACEWAY FOR INTERIOR POWER AND DATA

CIRCUITS

EP3 PROVIDE 1" PVC SCHEDULE 40 CONDUIT FROM ABOVE THE ROOF TO BELOW GRADE

EVERY 100" ON AVERAGE ALONG THE PERIMETER OF THE STRUCTURE FOR LIGHTNING

PROTECTION DOWNLEADS. CONDUIT NEVER TO EXCEED AN 8" RADIUS BEND TO

CONFORM TO UL96a. THIS PRECLUDES THE USE OF LB OR JUNCTION BOXES ALONG

THE CONDUIT PATH. PROVIDE CONDUIT AS TIGHT TO INTERIOR WALL AS POSSIBLE.

COORDINATE EXACT LOCATION AND EXECUTION OF WORK WITH ARCHITECT

EP8 PROVIDE 20A, 120V, 1-PHASE HARDWIRED CONNECTION TO BMS PANEL. COORDINATE

EXACT LOCATION AND MOUNTING HEIGHT WITH MECHANICAL CONTRACTOR PRIOR TO

ROUGH-IN. REFER TO MECHANICAL PIPING PLANS FOR ADDITIONAL INFORMATION.

PT

PL

PT

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PLPL

PL

PL

PL

PL

PL

PL

PT

PL

PT

PL

FF

PL

PL PL

PL

PT

FF FF

PE

B

B

B

B

J

A CB D E G H J K L M N P QF

1.1

EX

2.7

2.8

2.9

STAIR

A

OFFICE

SECURITY OFFICE

SHARED

OFFICE

ONBOARDING

OFFICE

VAULT

307A

CONFERENCE

OPEN OFFICE

OFFICE

328A

SHARED

KITCHENETTE

SCHOOL

INSPECTOR

WOMEN'S

LOBBY

CORRIDOR

301E

MEN'S

CORRIDOR

301W

VAULT

310N

OFFICE

310M

OFFICE

310L

OFFICE

310J

OFFICE

310G

OFFICE

310F

OFFICE

310E

OFFICE

310D

OFFICE

310B

TEL. ROOM

KITCHENETTE

OFFICE

OFFICE

OFFICE

OPEN OFFICE

STORAGE

OFFICE

BOT IT SHARED

OFFICE

OFFICE

VAULT

360D

VAULT

343A

OFFICE

360A

CONFERENCE/

STORAGE

360C

IT TRAINING

3W 3E

T4.0 a,GFI

EP1 EP1

EP2

EXISTING DATA ROOM AND ALL SERVICES

MUST REMAIN OPERATIONAL DURING

CONSTRUCTION.

COPY

a,GFI a,GFI a,GFI bc bc

CONFERENCE

310C

WM1

WM1

WM1

WM1

WM1

WM1

WM1

WM1 WM1 WM1

WM1 WM1 WM1 WM1

WM1

WM1

WM1

WM1WM1WM1

WM1

WM1WM1

WM1WM1WM1WM1

WM1

WM1

WM1

WM1

WM1

E3-4 E3-2E3-3

CRAC-2 CRAC-1

VC

VC

B

VC

VC

VC

FCU-G

FCU-F

AC-3

FCU-G

EP3

IT OFFICE

FCU-A

FCU-D

FCU-A

1, 3W

OFFICE

310H

2, 3W

3, 3W

4, 3W

5, 3W

6, 3W

8, 3W

7, 3W

9, 3W

10, 3W

11, 3W

KITCHENETTE

310K

12, 3W

CORRIDOR

310A

13, 3W

14, 3W

15, 3W

16, 3W

3, OS2W 18, 3W

19, 3W

20, 3W

21, 3W

22, 3W 23, 3W

24, 3W

25, 3W

26, 3W 27, 3W

28, 3W

29, 3W

30, 3W

31, 3W

2, 3E

3, 3E

4, 3E

5, 3E

6, 3E

7, 3E

8, 3E

9, 3E

10, 3E

11, 3E

12, 3E

13, 3E

14, 3E

15, 3E

16, 3E

17, 3E

18, 3E

FCU-A

8, OS2E

1, OS2E

CL CL

CL

CL

CL

CL

CL

CL

CL

CL

CL

CL

CL

CL

CL

CL

CL

CL CL CL

CL CL CL CL

CL

CL CL

CL CL

CL

CL

CL

19, 3E

20, 3E

32, 3W

33, 3W

REFa,GFI a,GFI

41, 3W 39, 3W

37, 3W

AC-2

WM1

WM1

WM1

WM1

WM1

25, 3E a

WM1

STAIR

B

1, 3E

35, 3W a

COPY

34, 3W

T4.0

BOE IT SHARED

OFFICE

FCU-G

PLP-1,ETRPLP-2,ETR

WM1

WM1

VC

WM1WM1

7'AFF

7'AFF

36, 3W

7'AFF

7'AFF

7'AFF

VC

MON

7'AFF

7'AFF VC

13, OS2W

FCU-A

3, OS2W

FCU-D

11, OS2E

FCU-F

FCU-C

7, OS2W

FCU-A

FCU-C

FCU-B

FCU-D

8, OS2W

12, OS2W

EP3

EP3

EP3

EP3

EP3

EP3

EP3

EP3

5, OS2E

21, 3E 22, 3E

23, 3E

VC

38, 3W

14, OS2W

18, OS2W

19, OS2W

14, OS2E

15, OS2E

REF

WM1a,GFI a,GFI

24, 3E

EP8

B

DATA ROOM

360B

ELECTRICAL REFERENCE NOTE

1. REFER TO DRAWING E0.0 FOR ELECTRICAL POWER, LIGHTING, AND COORDINATION GENERAL

NOTES.

2. REFER TO DRAWING E0.0 FOR ELECTRICAL ABBREVIATIONS.

3. REFER TO DRAWING E0.0 FOR ELECTRICAL SYMBOL LEGENDS.

4. REFER TO DRAWING E6.0 FOR LIGHTING FIXTURE SCHEDULE.

CONTRACT

DOCUMENTS

NOT FOR CONSTRUCTION

SHEET NO.

PROFESSIONAL SEAL

21 Talcott Notch Road

Farmington, CT 06032 friar.com

860.678.1291

CONSULTANT

DATE:

SCALE

PROJ. #:

DRAWN:

CHECKED:

CES #2025224.00

1/29/2026 3:28:51 PM

As indicated

EP1.3

ELECTRICAL POWER

THIRD FLOOR PLAN

REHABILITATION

AND RENOVATION

OF THE HISTORIC

CHASE BUILDING

CITY OF WATERBURY RFP #8287

236 GRAND AVENUE

WATERBURY, CT 06702

KCM

AJG

2024-108A

2026-0130

1/8" = 1'-0"

ELECTRICAL POWER THIRD FLOOR PLAN - NEW

REVISIONS

NO. DATE DESCRIPTION

KEYNOTES - ELECTRICAL

Key Value Keynote Text

EP1 PROVIDE NEW 60A, 42 POLE, RECESSED PANELBOARD.

EP2 PROVIDE DIVIDED SURFACE MOUNTED RACEWAY FOR INTERIOR POWER AND DATA

CIRCUITS

EP3 PROVIDE 1" PVC SCHEDULE 40 CONDUIT FROM ABOVE THE ROOF TO BELOW GRADE

EVERY 100" ON AVERAGE ALONG THE PERIMETER OF THE STRUCTURE FOR LIGHTNING

PROTECTION DOWNLEADS. CONDUIT NEVER TO EXCEED AN 8" RADIUS BEND TO

CONFORM TO UL96a. THIS PRECLUDES THE USE OF LB OR JUNCTION BOXES ALONG

THE CONDUIT PATH. PROVIDE CONDUIT AS TIGHT TO INTERIOR WALL AS POSSIBLE.

COORDINATE EXACT LOCATION AND EXECUTION OF WORK WITH ARCHITECT

EP5 CONNECT NEW CRAC UNIT TO FEEDER PRESERVED DURING DEMOLITION PHASE

EP8 PROVIDE 20A, 120V, 1-PHASE HARDWIRED CONNECTION TO BMS PANEL. COORDINATE

EXACT LOCATION AND MOUNTING HEIGHT WITH MECHANICAL CONTRACTOR PRIOR TO

ROUGH-IN. REFER TO MECHANICAL PIPING PLANS FOR ADDITIONAL INFORMATION.

PL

PL

PT

PL

PL

PL

PL

PL

PL

PL

PL PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PT

PT PT

PL

PL PL

PL

PL

B B

A CB D E G H J K L M N P QF

1.1

EX

2.7

2.8

2.9

STAIR

A

FIRE DEPT. CONF.

RM.

LOBBY

FIRE DEPT. OFFICE

MEN'S

WOMENS

ACCESS

BUSINESS OPEN

OFFICE

FIRE DEPT. OFFICE

FIRE DEPT. OFFICE

FIRE DEPT. IT

405A

OFFICE

430B

SHARED OFFICE

430A

OFFICE

430E

OFFICE

430F

DEPUTY FIRE CHIEF

OFFICE

405E

FIRE DEPT. ADMIN.

405F

FIRE CHIEF OFFICE

405G

VAULT

405D a,GFI

COPY

a,GFI

CONFERENCE

ROOM

430D

WM1

WM1 WM1 WM1 WM1 WM1

WM1WM1WM1

WM1

WM1

WM1

WM1

WM1 WM1

VC

FCU-C

FCU-D

FCU-D

FCU-C

FCU-A

EP3

E5.1

ELEVATOR

B

ELEVATOR

A

FCU-E

KITCHENETTE

405C

OFFICE

405B

FCU-B

FCU-D

22, GP423, GP4 13, GP4

4, GP4

12, GP4

33, GP4

31, GP4

5, GP4

28, GP4

10, GP4

WM1

8, GP4

29, GP4

3, OSFDP

WM1

2, OSFDP

WM1

1, OSFDP

25, GP4 16, GP4

27, GP4

32, GP4

30, GP4

6, GP4

17, GP4

24, GP4

19, GP4

3, GP4

FCU-F

3, OS4CL

CL

CL

CL

CL

CL

CL

CL

CL

CLCL

KITCHENETTE

430C

WM1

CL

26, GP4

CL

CL CL

FF FF

1, GP4

20, GP4

15, GP4

2, GP4

CP-A

WM1

OSFDP

GP4LP4OS4

a,GFI a

14, GP4

a,GFI a,GFI

21, GP4 REF

9, GP4

WM1 WM1

B

E5.1

STAIR

B1, OS4

4, OS4

FCU-C

5'AFF

POWER FOR EXISTING AV

RACK. COORDINATE EXACT

LOCATION IN FIELD.

O S

F D

P

5'AFF

EP3

EP3

EP3

EP3

APPROXIMATE LOCATION

OF EXISTING GROUND

ROD ELECTRODE SYSTEM

CONNECTED TO WATER

SERVICE IN BASEMENT

EP3

EP3

EP3

EP3

EP3

5, OS4

6, OS4

REF

11, GP4

G H J K

2.7

UH-A

UH-A

GFI

7, GP4

ELEVATOR B

PENTHOUSE

2, OS4

ELECTRICAL REFERENCE NOTE

1. REFER TO DRAWING E0.0 FOR ELECTRICAL POWER, LIGHTING, AND COORDINATION GENERAL

NOTES.

2. REFER TO DRAWING E0.0 FOR ELECTRICAL ABBREVIATIONS.

3. REFER TO DRAWING E0.0 FOR ELECTRICAL SYMBOL LEGENDS.

4. REFER TO DRAWING E6.0 FOR LIGHTING FIXTURE SCHEDULE.

CONTRACT

DOCUMENTS

NOT FOR CONSTRUCTION

SHEET NO.

PROFESSIONAL SEAL

21 Talcott Notch Road

Farmington, CT 06032 friar.com

860.678.1291

CONSULTANT

DATE:

SCALE

PROJ. #:

DRAWN:

CHECKED:

CES #2025224.00

1/29/2026 3:28:55 PM

As indicated

EP1.4

ELECTRICAL POWER

FOURTH FLOOR

PLAN

REHABILITATION

AND RENOVATION

OF THE HISTORIC

CHASE BUILDING

CITY OF WATERBURY RFP #8287

236 GRAND AVENUE

WATERBURY, CT 06702

KCM

AJG

2024-108A

2026-0130

1/8" = 1'-0"

ELECTRICAL POWER FOURTH FLOOR PLAN - NEW

1/8" = 1'-0"

ELECTRICAL POWER PENTHOUSE PLAN - NEW

REVISIONS

NO. DATE DESCRIPTION

KEYNOTES - ELECTRICAL

Key Value Keynote Text

EP3 PROVIDE 1" PVC SCHEDULE 40 CONDUIT FROM ABOVE THE ROOF TO BELOW GRADE

EVERY 100" ON AVERAGE ALONG THE PERIMETER OF THE STRUCTURE FOR LIGHTNING

PROTECTION DOWNLEADS. CONDUIT NEVER TO EXCEED AN 8" RADIUS BEND TO

CONFORM TO UL96a. THIS PRECLUDES THE USE OF LB OR JUNCTION BOXES ALONG

THE CONDUIT PATH. PROVIDE CONDUIT AS TIGHT TO INTERIOR WALL AS POSSIBLE.

COORDINATE EXACT LOCATION AND EXECUTION OF WORK WITH ARCHITECT

A CB D E G H J K L M N P QF

1.1

EX

2.7

2.8

2.9A CB D E G H J K L M N P QF

A.5

2.7

2.8

2.9

1.1

CU-2

CU-3

CRAC-CU-2 CRAC-CU-1

WP,GFI WP,GFI

WP,GFI

18, GP4

EF-2

WP,GFIWP,GFI

WP,GFIWP,GFI

WP,GFI

34, GP4

EP3

EP3

EP3

EP3

EP3

EP3

EP3

EP3

EP3

CONTRACT

DOCUMENTS

NOT FOR CONSTRUCTION

SHEET NO.

PROFESSIONAL SEAL

21 Talcott Notch Road

Farmington, CT 06032 friar.com

860.678.1291

CONSULTANT

DATE:

SCALE

PROJ. #:

DRAWN:

CHECKED:

CES #2025224.00

1/29/2026 3:27:50 PM

1/8" = 1'-0"

E2.1

ELECTRICAL ROOF

PLAN

REHABILITATION

AND RENOVATION

OF THE HISTORIC

CHASE BUILDING

CITY OF WATERBURY RFP #8287

236 GRAND AVENUE

WATERBURY, CT 06702

KCM

AJG

2024-108A

2026-0130

REVISIONS

NO. DATE DESCRIPTION

1/8" = 1'-0"

ELECTRICAL ROOF PLAN - NEW

KEYNOTES - ELECTRICAL

Key Value Keynote Text

EP3 PROVIDE 1" PVC SCHEDULE 40 CONDUIT FROM ABOVE THE ROOF TO BELOW GRADE EVERY 100" ON AVERAGE ALONG THE PERIMETER OF THE STRUCTURE FOR LIGHTNING PROTECTION DOWNLEADS. CONDUIT NEVER TO EXCEED AN 8" RADIUS BEND TO CONFORM TO UL96a. THIS PRECLUDES THE USE OF LB OR JUNCTION BOXES ALONG THE CONDUIT PATH. PROVIDE CONDUIT AS TIGHT TO INTERIOR WALL AS POSSIBLE. COORDINATE EXACT

LOCATION AND EXECUTION OF WORK WITH ARCHITECT

NORMAL

DIMMING LOAD

NORMAL

CONTROLLER

SEE NOTE 1

NLC

NETWORK

BRIDGE MODULE

SEE NOTE 6

PC

CEILING MOUNTED PHOTOCELL

(WHERE APPLICABLE)

CEILING

OCCUPANCY

SENSOR

SYMBOL: OS

CEILING

VACANCY

SENSOR

SYMBOL: VS

QUANTITY AND LOCATION OF SENSORS PER PLANS

ON

OFF

ON

OFF

TO ADDITIONAL

NETWORK DEVICES

CABLE LEGEND

DATA LINE OR CONTROL

CABLING PER MFR. REQ'S

(SEE NOTE 1)

SWITCHED AND 0-10V

DIMMING WIRING

2#12+1#12G & 2#18 AWG

3 NORMAL 120/277VAC POWER

SOURCE - REFER TO FLOOR

PLANS FOR CIRCUITING

GENERAL NOTES:

1. DETAIL IS MANUFACTURER-AGNOSTIC. REFER TO SPECIFICATIONS

FOR BASIS OF DESIGN LIGHTING CONTROL SYSTEM MANUFACTURER.

SYSTEM TOPOLOGY AND ARCHITECTURE IS SHOWN

DIAGRAMMATICALLY ON THIS DETAIL. FINAL CONNECTIONS, WIRING

SCHEME, WIRE TYPE AND STYLE, AND OTHER SYSTEM COMPONENT

CONFIGURATIONS SHALL BE AS REQUIRED BY APPROVED LIGHTING

CONTROL MANUFACTURER. PROVIDE ADAPTERS, CONVERTERS AND

OTHER SYSTEM COMPONENTS REQUIRED BY MANUFACTURER.

SUBMIT FOR APPROVAL BY ENGINEER A WIRING DIAGRAM

INDICATING ALL COMPONENTS AND CONNECTIONS.

2. PROVIDE FACTORY COMMISSIONING OF ALL SENSORS, PHOTOCELLS

AND CONTROLS.

3. REFER TO FLOOR PLANS FOR EXACT LIGHTING FIXTURES ON EACH

ZONE, AND QUANTITY AND LOCATION OF ALL DEVICES.

4. FINISHES AND COLORS OF ALL LIGHTING CONTROL DEVICES AND

SWITCH PLATES SHALL BE SELECTED BY ARCHITECT

5. OCCUPANCY AND VACANCY SENSORS SHALL BE PROVIDED WITH

AUXILIARY RELAY OPTION FOR CONNECTION TO BUILDING

MANAGEMENT SYSTEM BY DIVISION 23 CONTRACTOR. IF SUBMITTED

SENSORS DO NOT HAVE THIS ABILITY, PROVIDE ADDITIONAL

INPUT/OUTPUT MODULES CAPABLE OF SUPPORTING RELAYED

OUTPUT TO BMS.

6. SYSTEM SHALL BE PROVIDED WITH NETWORKED CONNECTIONS

BETWEEN EACH CONTROLLER IN PROJECT, SO THAT EACH ROOM

CAN BE SET UP AND CONFIGURED FROM A CENTRALLY OPERATED

SYSTEM. PROVIDE BRIDGE MODULES AS REQUIRED BY

MANUFACTURER TO SUPPORT THIS NETWORKING CAPABILITY.

SEQUENCE OF OPERATIONS:

1. ROOM OCCUPANCY SENSORS SHALL BE SET FOR AUTO ON, AUTO

OFF OPERATION. TIMEOUT AFTER 20 MINUTES.

2. ROOM VACANCY SENSORS SHALL BE SET FOR MANUAL ON, AUTO

OFF OPERATION. TIMEOUT AFTER 20 MINUTES.

3. 4-BUTTON "LVD" KEYPAD(S) SHALL PROVIDE MANUAL CONTROL OF

FIXTURES AS FOLLOWS:

• BUTTON 1: "ON": TURN ALL LIGHTS ON

• BUTTON 2: "▲": PRESS TO RAISE ALL LIGHTS

• BUTTON 3: "▼": PRESS TO LOWER ALL LIGHTS

• BUTTON 4: "OFF": TURN ALL LIGHTS OFF

4. 2-BUTTON "LV" KEYPAD(S) SHALL PROVIDE MANUAL CONTROL OF

FIXTURES AS FOLLOWS:

• BUTTON 1: "ON": TOGGLE ALL LIGHTS ON

• BUTTON 2: "OFF": TOGGLE ALL LIGHTS OFF

5. WHERE PHOTOCELL IS INDICATED ON PLANS, ZONE SHALL HAVE

AUTOMATIC DIMMING VIA PHOTOCELL AND SHALL CAP MAXIMUM

LIGHT LEVEL OF 40 FOOT-CANDLES IN THIS ZONE.

WALL

OCCUPANCY

SENSOR

WALL

VACANCY

SENSOR

SYMBOL: OS SYMBOL: VS

SYMBOL: SYMBOL:

QUANTITY AND LOCATION OF LOW-VOLTAGE

SWITCHES PER PLANS

$ LV $ LVD

FRONT

OFF

ON

OFF

BACK

OFF

* PRIMARY ZONE: PHOTOCELL SHALL PROVIDE AUTOMATIC DIMMING

AND SHALL CAP MAXIMUM LIGHT LEVEL OF 50 F.C. IN THIS ZONE.

** SECONDARY ZONE: PHOTOCELL SHALL PROVIDE AUTOMATIC DIMMING

AND SHALL CAP MAXIMUM LIGHT LEVEL OF 50 F.C. IN THIS ZONE.

NORMAL

DIMMING LOAD*

ZONE "a"

TEACHING WALL

PRIMARY DAYLIGHT

NORMAL

CONTROLLER

SEE NOTE 1

NLC

NORMAL

DIMMING LOAD

NORMAL

CONTROLLER

SEE NOTE 1

NORMAL

DIMMING LOAD

NORMAL

CONTROLLER

SEE NOTE 1

NORMAL

DIMMING LOAD

NORMAL

CONTROLLER

SEE NOTE 1

NORMAL

DIMMING LOAD

NORMAL

CONTROLLER

SEE NOTE 1

NORMAL

DIMMING LOAD

NORMAL

CONTROLLER

SEE NOTE 1

ZONE "b"

TEACHING WALL

SECOND DAYLIGHT

ZONE "c"

TEACHING WALL

NO DAYLIGHT

ZONE "d"

BACK OF ROOM

PRIMARY DAYLIGHT

ZONE "e"

BACK OF ROOM

SECOND DAYLIGHT

ZONE "f"

BACK OF ROOM

NO DAYLIGHT

a,b,c,d,e,f SEE NOTE 7

CEILING

OCCUPANCY

SENSOR

SYMBOL: OS

CEILING

VACANCY

SENSOR

SYMBOL: VS

QUANTITY AND LOCATION OF SENSORS PER PLANS

WALL

OCCUPANCY

SENSOR

WALL

VACANCY

SENSOR

SYMBOL: OS SYMBOL: VS

PC

CEILING MOUNTED PHOTOCELL

(WHERE APPLICABLE)

NETWORK

BRIDGE MODULE

SEE NOTE 6

TO ADDITIONAL

NETWORK DEVICES

GENERAL NOTES:

1. DETAIL IS MANUFACTURER-AGNOSTIC. REFER TO SPECIFICATIONS

FOR BASIS OF DESIGN LIGHTING CONTROL SYSTEM MANUFACTURER.

SYSTEM TOPOLOGY AND ARCHITECTURE IS SHOWN

DIAGRAMMATICALLY ON THIS DETAIL. FINAL CONNECTIONS, WIRING

SCHEME, WIRE TYPE AND STYLE, AND OTHER SYSTEM COMPONENT

CONFIGURATIONS SHALL BE AS REQUIRED BY APPROVED LIGHTING

CONTROL MANUFACTURER. PROVIDE ADAPTERS, CONVERTERS AND

OTHER SYSTEM COMPONENTS REQUIRED BY MANUFACTURER.

SUBMIT FOR APPROVAL BY ENGINEER A WIRING DIAGRAM

INDICATING ALL COMPONENTS AND CONNECTIONS.

2. PROVIDE FACTORY COMMISSIONING OF ALL SENSORS, PHOTOCELLS

AND CONTROLS.

3. REFER TO FLOOR PLANS FOR EXACT LIGHTING FIXTURES ON EACH

ZONE, AND QUANTITY AND LOCATION OF ALL DEVICES.

4. FINISHES AND COLORS OF ALL LIGHTING CONTROL DEVICES AND

SWITCH PLATES SHALL BE SELECTED BY ARCHITECT

5. OCCUPANCY AND VACANCY SENSORS SHALL BE PROVIDED WITH

AUXILIARY RELAY OPTION FOR CONNECTION TO BUILDING

MANAGEMENT SYSTEM BY DIVISION 23 CONTRACTOR. IF SUBMITTED

SENSORS DO NOT HAVE THIS ABILITY, PROVIDE ADDITIONAL

INPUT/OUTPUT MODULES CAPABLE OF SUPPORTING RELAYED

OUTPUT TO BMS.

6. SYSTEM SHALL BE PROVIDED WITH NETWORKED CONNECTIONS

BETWEEN EACH CONTROLLER IN PROJECT, SO THAT EACH ROOM

CAN BE SET UP AND CONFIGURED FROM A CENTRALLY OPERATED

SYSTEM. PROVIDE BRIDGE MODULES AS REQUIRED BY

MANUFACTURER TO SUPPORT THIS NETWORKING CAPABILITY.

7. NUMBER OF ZONES APPLICABLE TO A GIVEN ROOM IS INDICATED ON

PLANS VIA ZONE TAGGING ON "NLC" AND "ELC" CONTROL SYMBOLS.

DETAIL INDICATES A TYPICAL ROOM WITH ALL APPLICABLE ZONES.

ROOMS WITHOUT A PARTICULAR ZONE WILL NOT HAVE THIS ZONE

LETTER TAG ON "NLC" AND "ELC" SYMBOL.

SEQUENCE OF OPERATIONS:

1. SUGGESTED LABELING SHOWN. SUBMIT TO OWNER FOR APPROVAL

PRIOR TO ORDERING.

2. ROOM OCCUPANCY SENSORS SHALL BE SET FOR AUTO ON, AUTO

OFF OPERATION. TIMEOUT AFTER 20 MINUTES.

3. ROOM VACANCY SENSORS SHALL BE SET FOR MANUAL ON, AUTO

OFF OPERATION. TIMEOUT AFTER 20 MINUTES.

4. "LK1" STATION SHALL CONSIST OF ONE KEYPAD TO PROVIDE

MANUAL CONTROL OF LIGHTING:

• "ON" = TURN ON ALL LIGHTING IN ROOM

• "OFF" = TURN OFF ALL LIGHTING IN ROOM

5. "LK2" STATION SHALL CONSIST OF TWO KEYPADS TO PROVIDE

MANUAL CONTROL OF LIGHTING:

• KEYPAD #1 : "FRONT": ON/OFF/RAISE/LOWER CONTROL OF

ZONES "a", "b", AND "c" SIMULTANEOUSLY

• KEYPAD #2 : "BACK" : ON/OFF/RAISE/LOWER CONTROL OF ZONES

"d", "e" AND "f" SIMULTANEOUSLY

TYP.

SYMBOL: SYMBOL:

QUANTITY AND LOCATION OF LOW-VOLTAGE

SWITCHES PER PLANS

$ LK1 $ LK2

CABLE LEGEND

DATA LINE OR CONTROL

CABLING PER MFR. REQ'S

(SEE NOTE 1)

SWITCHED AND 0-10V

DIMMING WIRING

2#12+1#12G & 2#18 AWG

3 NORMAL 120/277VAC POWER

SOURCE - REFER TO FLOOR

PLANS FOR CIRCUITING

NORMAL

SWITCHED LOAD

NORMAL

CONTROLLER

SEE NOTE 1

NLC

2S

GENERAL NOTES:

1. DETAIL IS MANUFACTURER-AGNOSTIC. REFER TO

SPECIFICATIONS FOR BASIS OF DESIGN LIGHTING CONTROL

SYSTEM MANUFACTURER. SYSTEM TOPOLOGY AND

ARCHITECTURE IS SHOWN DIAGRAMMATICALLY ON THIS

DETAIL. FINAL CONNECTIONS, WIRING SCHEME, WIRE TYPE

AND STYLE, AND OTHER SYSTEM COMPONENT

CONFIGURATIONS SHALL BE AS REQUIRED BY APPROVED

LIGHTING CONTROL MANUFACTURER. PROVIDE ADAPTERS,

CONVERTERS AND OTHER SYSTEM COMPONENTS REQUIRED

BY MANUFACTURER. SUBMIT FOR APPROVAL BY ENGINEER A

WIRING DIAGRAM INDICATING ALL COMPONENTS AND

CONNECTIONS.

2. PROVIDE FACTORY COMMISSIONING OF ALL SENSORS,

PHOTOCELLS AND CONTROLS.

3. REFER TO FLOOR PLANS FOR EXACT LIGHTING FIXTURES ON

EACH ZONE, AND QUANTITY AND LOCATION OF ALL DEVICES.

4. FINISHES AND COLORS OF ALL LIGHTING CONTROL DEVICES

AND SWITCH PLATES SHALL BE SELECTED BY ARCHITECT

PLUG LOAD

CONTROLLER

SEE NOTE 1

PL

TO SWITCHED

RECEPTACLES PER PLUG

LOAD CONTROL DETAIL

SYMBOL: $ LVSSYMBOL: $ LOS

CABLE LEGEND

DATA LINE OR CONTROL

CABLING PER MFR. REQ'S

(SEE NOTE 1)

2S

SWITCHED WIRING

2#12+1#12G & 2#18 AWG

3 NORMAL 120/277VAC POWER

SOURCE - REFER TO FLOOR

PLANS FOR CIRCUITING

2D

SWITCHED AND 0-10V

DIMMING WIRING

2#12+1#12G & 2#18 AWG

TYP.

NORMAL

DIMMING LOAD

NORMAL

CONTROLLER

SEE NOTE 1

NLC

2D

PLUG LOAD

CONTROLLER

SEE NOTE 1

PL

TO SWITCHED

RECEPTACLES PER PLUG

LOAD CONTROL DETAIL

SYMBOL: $ LVSDSYMBOL: $ LOSD

TYP.

SEQUENCE OF OPERATIONS:

1. LOW VOLTAGE OCCUPANCY SENSOR SWITCHES

(TAGGED "LOS" AND "LOSD") SHALL BE SET FOR AUTO

ON, AUTO OFF OPERATION. TIMEOUT AFTER 20

MINUTES.

2. LOW VOLTAGE VACANCY SENSOR SWITCHES (TAGGED

"LVS" AND "LVSD") SHALL BE SET FOR MANUAL ON,

AUTO OFF OPERATION. TIMEOUT AFTER 20 MINUTES.

3. "LOS" AND "LVS" SWITCHES SHALL PROVIDE MANUAL

ON/OFF CONTROL OF ALL LIGHTS IN ROOM

SIMULTANEOUSLY.

4. "LOSD" AND "LVSD" SWITCHES SHALL PROVIDE

MANUAL ON/OFF/RAISE/LOWER CONTROL OF ALL

LIGHTS IN ROOM SIMULTANEOUSLY.

OS

VS

TYPICAL WALL SENSOR SWITCH

NEUTRAL

LIGHTING

LOAD

HOT SWITCHED

HOT

NEUTRAL

HOT

NEUTRAL

0-10V VIOLET/GRAY

(WALL DIMMERS ONLY)

OR $

OSD

OR $

VSD

NOTES:

1. REFER TO MANUFACTURERS WIRING DIAGRAM FOR EXACT WIRING DETAIL.

2. WIRE IN SERIES WITH THREE-WAY SWITCH, WHERE INDICATED ON PLANS.

3. PROVIDE 0-10V WIRING FROM WALL DIMMERS, WHERE INDICATED ON PLANS.

TYPICAL SPECIFICATIONS:

4. LIGHTING SHALL TIME OUT AFTER 20 MINUTES.

1. "OS" OCCUPANCY SENSOR SWITCH:

(SET TO AUTO-ON, AUTO-OFF MODE)

2. "OSD" OCCUPANCY SENSOR 0-10V DIMMER:

(SET TO AUTO-ON, AUTO-OFF MODE)

3. "VS" VACANCY SENSOR SWITCH:

(SET TO MANUAL-ON, AUTO-OFF MODE)

4. "VSD" VACANCY SENSOR 0-10V DIMMER:

(SET TO MANUAL-ON, AUTO-OFF MODE)

5. REFER TO LIGHTING CONTROL SPECIFICATION FOR ADDITIONAL INFORMATION.

PLUG LOAD

CONTROLLER

SEE NOTE 1

PL

NORMAL

CONTROLLER

SEE NOTE 1

NLC

W H

IT

E

(N E

U T

R A

L

B L A

C K

(1 V

WHITE NEUTRAL

BLACK HOT

RED SWITCHED

HOT

SYMBOL:

C O

N T

R O

L L

E D

C O

N T

R O

L L

E D

SYMBOL:

120V BRANCH CIRCUIT

PER POWER PLANS

#12 AWG (TYP.)

GENERAL NOTES:

1. DETAIL IS MANUFACTURER-AGNOSTIC. REFER TO SPECIFICATIONS

FOR BASIS OF DESIGN LIGHTING CONTROL SYSTEM MANUFACTURER.

SYSTEM TOPOLOGY AND ARCHITECTURE IS SHOWN

DIAGRAMMATICALLY ON THIS DETAIL. FINAL CONNECTIONS, WIRING

SCHEME, WIRE TYPE AND STYLE, AND OTHER SYSTEM COMPONENT

CONFIGURATIONS SHALL BE AS REQUIRED BY APPROVED LIGHTING

CONTROL MANUFACTURER. PROVIDE ADAPTERS, CONVERTERS AND

OTHER SYSTEM COMPONENTS REQUIRED BY MANUFACTURER.

SUBMIT FOR APPROVAL BY ENGINEER A WIRING DIAGRAM

INDICATING ALL COMPONENTS AND CONNECTIONS.

2. "PL" PLUG LOAD CONTROLLER SYMBOLS ARE SHOWN ON

ELECTRICAL POWER FLOOR PLANS. PROVIDE MULTIPLE

CONNECTIONS WHERE MULTIPLE SYMBOLS ARE SHOWN.

3. REFER TO TYPICAL CONTROLLED RECEPTACLE WIRING DIAGRAM ON

ELECTRICAL DETAILS DRAWINGS FOR ADDITIONAL REQUIREMENTS.

SEQUENCE OF OPERATIONS:

1. ROOM OCCUPANCY SENSORS SHALL SWITCH LIGHTING USING AUTO

ON, AUTO OFF OPERATION. TIMEOUT AFTER 20 MINUTES.

2. ROOM VACANCY SENSORS SHALL SWITCH LIGHTING USING MANUAL

ON, AUTO OFF OPERATION. TIMEOUT AFTER 20 MINUTES.

3. PLUG LOAD CONTROLLER SHALL DE-ENERGIZE CONTROLLED

RECEPTACLES UPON TIMEOUT SIGNAL FROM OCCUPANCY OR

VACANCY SENSORS IN ROOM.

4. PLUG LOAD CONTROLLER SHALL NOT DE-ENERGIZE CONTROLLED

RECEPTACLES UPON MANUAL-OFF SIGNAL TO LIGHT FIXTURES.

5. PROGRAM LIGHTING WITHIN THE SPACE TO TURN OFF (3) MINUTES

PRIOR TO RECEPTACLE SHUTOFF IN ORDER FOR STILL OCCUPANTS

TO RE-ESTABLISH OCCUPANCY IN THE SPACE.

TO LIGHT FIXTURES, SENSORS

AND SWITCHES PER LIGHTING

CONTROL DETAILS

NOTE 2

DATA LINE OR CONTROL

CABLING PER MFR. REQ'S

(SEE NOTE 1)

R

R

R

1600 VA

INVERTER

INPUT

INVERTER

OUTPUT BUS

NORMAL

CIRCUIT

SWITCH OR

CONTROL DEVICE

SWITCH OR

CONTROL DEVICE

TYPICAL BYPASS RELAY

INVERTER OUTPUT

NORMALLY ON CIRCUIT

BREAKER (TYP.)

NOTES

1. REFER TO SCHEDULE FOR INV-1 ON E6.2 FOR INVERTER SPECIFICATION.

LIGHTING

LOAD

LIGHTING

LOAD

LIGHTING

LOAD

LIGHTING

LOAD

20A-1P

SWITCH OR

CONTROL DEVICE

NORMAL

CIRCUIT

NORMAL

CIRCUIT

EMERGENCY

LIGHTING

PANELBOARD

UL1008 LISTED RELAY

BODINE GTD20A OR EQUAL

EMERGENCY LIGHTING

FIXTURES: QUANTITY AS SHOWN

ON FLOOR PLANS

LIGHTING CONTROL PANEL, LOCAL POWER

PACK, OR OTHER CONTROL CONTACTS

WHERE APPLICABLE. REFER TO ASSOCIATED

LIGHTING CONTROL DETAILS FOR

ADDITIONAL INFORMATION.

SYMBOL: R

1 2 3 4 5 6 7 1 2 3 4 5 6 7

TERMINAL

BLOCK #2

TERMINAL

BLOCK #1

EM. HOT

EM. NEUTRAL

NORMAL

LIGHTING PANEL

HOT

NEUTRAL

NEUTRAL

HOT $

NOTES:

1. UL1008 RELAY LOCATIONS ARE SHOWN DIAGRAMMATICALLY ON FLOOR PLANS.

LOCATE IN SAME ELECTRICAL ROOM AS ASSOCIATED NORMAL AND EMERGENCY

PANELBOARDS. CIRCUITS TO BOTH NORMAL AND EMERGENCY PANELBOARDS ARE

SHOWN FROM RELAY ON FLOOR PLANS.

2. FIXTURES CONNECTED TO UL 1008 TRANSFER RELAY SHALL BE POWERED VIA THE

NORMAL LIGHTING CIRCUIT UPON STANDARD CONDITIONS. UPON POWER FAILURE,

RELAY SHALL TRANSFER POWER TO EMERGENCY LIGHTING CIRCUIT SHOWN ON

FLOOR PLANS.

3. REFER TO SUBMITTED MANUFACTURER'S WIRING SCHEMATIC FOR EXACT

CONNECTIONS.

NOTE 1

LOCAL WALL SWITCH, WHERE APPLICABLE.

REFER TO FLOOR PLANS FOR LOCATIONS.

TYPICAL STANDALONE OCCUPANCY SENSOR DETAIL

N.T.S.

NORMAL

LOAD

POWER PACK

CEILING OCCUPANCY SENSOR

WITH AUXILIARY RELAY

OS OS

RELAY

EMERGENCY SOURCE

(PER PLANS)

SENSING FEED

EMERG.

LOAD

SEQUENCE OF OPERATIONS:

1. AUTO-ON WHEN OCCUPANCY IS DETECTED BY CEILING

SENSOR(S). REFER TO FLOOR PLANS FOR QUANTITY

AND LOCATIONS.

2. AUTO-OFF AFTER 20 MINUTES OF UNOCCUPIED SPACE.

3. MANUAL ON-OFF CONTROL OF ALL FIXTURES BY KEY

SWITCHES, WHERE INDICATED ON PLANS.

4. REFER TO LIGHTING CONTROL SPECIFICATION FOR

ADDITIONAL INFORMATION.

$K

UL924 BYPASS RELAY.

REFER TO RELAY WIRING

DETAIL FOR ADDITIONAL

SPECIFICATIONS.

RED (+24VDC @ 150mA)

BLACK (COMMON)

BLUE (CONTROL)

GROUND

NEUTRAL

HOT

RED

RED

BLACK

WHITE

PP

CONTRACT

DOCUMENTS

NOT FOR CONSTRUCTION

SHEET NO.

PROFESSIONAL SEAL

21 Talcott Notch Road

Farmington, CT 06032 friar.com

860.678.1291

CONSULTANT

DATE:

SCALE

PROJ. #:

DRAWN:

CHECKED:

CES #2025224.00

1/29/2026 3:27:51 PM

NTS

E5.0

ELECTRICAL DETAILS

REHABILITATION

AND RENOVATION

OF THE HISTORIC

CHASE BUILDING

CITY OF WATERBURY RFP #8287

236 GRAND AVENUE

WATERBURY, CT 06702

KCM

AJG

2024-108A

2026-0130

NTS

TYPICAL 1-ZONE LIGHTING CONTROL DETAIL

NTS

TYPICAL MULTI-ZONE ROOM CONTROL DETAIL W/ PRIMARY & SECONDARY DAYLIGHT

NTS

TYPICAL LOW VOLTAGE SENSOR SWITCH DETAIL

NTS

TYPICAL LINE VOLTAGE SENSOR SWITCH DETAIL

NTS

TYPICAL PLUG LOAD CONTROL DETAIL

REVISIONS

NO. DATE DESCRIPTION

NTS

LIGHTING INVERTER WIRING DIAGRAM

NTS

UL 1008 TRANSFER RELAY DETAIL

NTS

TYPICAL STANDALONE OCCUPANCY SENSOR DETAIL

S

H

CM

MM

S

H

J

CM

CM

CM

S

H

CM

MM

CM

CM

CM

J

S

H

18"MIN.

24" MIN.

BELOW

GRADE

12"

SAND

BEDDING 6" MINIMUM

COVER ON ALL SIDES

COMPACTED BACKFILL

IN 6" LIFTS

SEE NOTE 3 (TYP)

EXISTING BITUMINOUS

PAVEMENT IF GRASS IS ENCOUNTERED, REGRADE, REPAIR,

AND RESEED TO MATCH SURROUNDINGS.

SAW CUT AND REMOVE BITUMINOUS PAVEMENT.

PATCH TO MATCH EXISTING SURROUNDING

PAVEMENT CONSTRUCTION AFTER INSTALLATION

OF FEEDER, CONDUIT OR DUCTBANK.

PLASTIC WARNING TAPE

TO READ "CAUTION BURIED

UTILITY LINE BELOW".

(3) 4" SCHEDULE 40 PVC

CONDUIT. SEE NOTE 4.

7 1/2"

(2) 1" CONDUITS. (1) FOR

PCHWP-1 FEEDER, (1) FOR

RECEPTACLE CIRCUIT.

PROVIDE 2" SPACERS

NOTES:

1. TYPICAL CONDUITS AND QUANTITIES SHOWN, REFER TO DRAWINGS FOR QUANTITIES AND

SIZES.

2. COORDINATE AND GROUP CONDUITS IN COMMON TRENCH. SINGLE ROW SHOWN, MULTIPLE

ROW DUCT BANKS ARE ACCEPTABLE, MAINTAINING SEPARATION DISTANCE REQUIREMENTS.

3. PROVIDE SUITABLE SEPARATORS AND CHAIRS 4 FT. MAX. ON CENTER, SET TO COMPACTED

TRENCH BOTTOM AND BAND CONDUITS TOGETHER PRIOR TO BACKFILL OR PLACING CONCRETE.

4. REFER TO CONCRETE ENCASEMENT DETAIL WHERE CONCRETE ENCASEMENT IS REQUIRED.

USE 'TYPE EB' SCHEDULE 40 PVC CONDUIT.

C

TO GAS-FIRED EQUIPMENT BURNERS

(REFER TO PLANS FOR LOCATIONS)

SQUARE D CLASS 8903 SERIES

MECHANICALLY HELD CONTACTOR

WITH 2-WIRE CONTROL INTERFACE

OR APPROVED EQUAL

NOTES:

1. PROVIDE CONTACTOR WITH QUANTITY OF POLES REQUIRED TO SHUT POWER DOWN TO EQUIPMENT

LISTED PLUS (2) SPARE POLES. COORDINATE LOCATION IN EQUIPMENT ROOM IN FIELD.

2. COORDINATE CONNECTIONS TO EQUIPMENT/ CONTROL PANELS IN FIELD

3. STI MODEL #SS202-4-PO-EN PUSHBUTTON, QUANTITY SHOWN ON PLANS:

A. WITH (1) N.O. AND (1) N.C. CONTACT COMPATIBLE WITH CONTACTOR

B. RED COLOR WITH "EMERGENCY POWER OFF" LEGEND

C. NON-ALARMED FLIP UP FLUSHED COVER

D. MOMENTARY OPERATION

4. POWER VIA LOCAL 120VAC RECEPTACLE CIRCUIT IN EQUIPMENT ROOM.

5. NORMALLY OPEN, 120VAC SOLENOID VALVE FOR GAS LINE TO EQUIPMENT SHALL BE FURNISHED AND

INSTALLED BY PLUMBING CONTRACTOR.

6. PROVIDE DEDICATED 120VAC, 20A-1P CIRCUIT TO SOLENOID VALVE. POWER VIA LOCAL 120/240V (OR

120/208V) PANELBOARD SERVING RECEPTACLE CIRCUITS IN EQUIPMENT ROOM.

REFER TO MOTOR CIRCUIT

SCHEDULE FOR EQUIPMENT TO

BE POWERED VIA CONTACTOR

SEE NOTE 3

(TYP)

L

EPO

SEE NOTE 4

N

L NNOTE 6

NOTE 5

SPECIFICATIONS:

1. ELEVATOR DISCONNECT SWITCH SHALL BE EATON BUSSMANN SERIES

QUIK-SPEC POWER MODULE SWITCH OR APPROVED EQUAL

2. AMPERAGE RATING AND FUSE SIZE AS INDICATED ON ELECTRICAL

RISER DIAGRAM AND/OR FLOOR PLANS

3. INTEGRAL 24VDC SHUNT-TRIP CAPABILITY

4. FIRE ALARM MONITORING RELAY

5. TWO(2) SETS OF N.O./N.C. AUXILIARY CONTACTS

6. GREEN PILOT LIGHT

7. INTEGRAL CONTROL TRANSFORMER

PROVIDE FUSED ELEVATOR

DISCONNECT SWITCH PER

SPECIFICATIONS BELOW

MAIN POWER FEEDERS

PER RISER DIAGRAM

C

SHUNT

TRIP

FS

F.A.

SHUTOFF

FM

F.A.

MONITOR

AUX

AUX

CONTACT

INTEGRAL

CONTROL

TRANSFORMER

CMSHUNT TRIP SIGNAL FROM

FIRE ALARM SYSTEM

MM

FIRE ALARM VOLTAGE

MONITORING SIGNAL

FM

FM

AUX

FM

SIGNAL TO BATTERY

LOWERING SYSTEM PER

ELEVATOR MANUFACTURER'S

REQUIREMENTS

MAIN POWER FEEDERS

PER RISER DIAGRAM

GENERAL NOTES:

1. ALL CONTROL WIRING SHALL BE #14 AWG UNLESS OTHERWISE NOTED

2. PROVIDE WITH (3) DUAL-ELEMENT TIME DELAY FUSES

3. GC AND EC SHALL COORDINATE EXACT LOCATION OF DISCONNECT

SWITCH WITH ELEVATOR MANUFACTURER AND LOCAL AHJ PRIOR TO

ROUGH-IN. ALL DEVICES AND CONNECTIONS SHALL BE MADE IN

LOCATIONS ACCEPTABLE TO ELEVATOR MANUFACTURER AND AHJ.

CHANGES IN LOCATIONS AS A RESULT OF THIS COORDINATION SHALL

BE MADE AT NO ADDITIONAL COST TO OWNER.

18"MIN.

1 1/4" SCHEDULE 40 PVC

CONDUIT

24"

BELOW

GRADE

12"

NOTES:

1. TYPICAL CONDUITS AND QUANTITIES SHOWN, REFER TO DRAWINGS FOR QUANTITIES AND

SIZES.

EXISTING BITUMINOUS

PAVEMENT

IF GRASS IS ENCOUNTERED, REGRADE, REPAIR,

AND RESEED TO MATCH SURROUNDINGS.

SAW CUT AND REMOVE BITUMINOUS PAVEMENT.

PATCH TO MATCH EXISTING SURROUNDING

PAVEMENT CONSTRUCTION AFTER INSTALLATION

OF FEEDER, CONDUIT OR DUCTBANK.

SAND

BEDDING 6" MINIMUM

COVER ON ALL SIDES

COMPACTED BACKFILL

IN 6" LIFTS

PLASTIC WARNING TAPE

TO READ "CAUTION BURIED

ELECTRIC LINE BELOW"

G H

2.7

E

WP,GFI

NOTE 5

NOTE 6

NOTE 10

(TYPICAL)

NOTE 8

E

E

WP

NOTE 9

NOTE 2

17, LPB

37, GPB

G

NOTE 5

NOTE 6

NOTE 10

NOTE 11

E

E

E

GFI NOTE 1

NOTE 3

NOTE 2

NOTE 7

WP

5, LP4

37, GP4

1" PVC CONDUITS SEE

SITE PLAN

CAST IN PLACE CONCRETE

BASE 18" DIAMETER

TYPE SL1A OR SL1B FIXTURE.

SEE E6.00 FOR FIXTURE

SCHEDULE AND ESU1.00 FOR

QUANTITY AND LOCATIONS

STANCHION BASE SET

IN CONCRETE

3-1/2"

10"

10"

PROVIDE WIREMOLD 4000 SERIES

TWO-PIECE STEEL RACEWAY FOR

DATA/VOIP CABLING AND POWER.

PROVIDE WIREMOLD V401DFO

DIVDED ENTRANCE END FITTING AT

TOP OF RACE WAY.

PROVIDE WIREMOLD V4046H-2 TAP

OF FITTING W/ FOUR CONENCTRIC

KOs FOR POWER AND DATA FEED

TO MODULAR FURNITURE.

FFSYMBOL ON PLANS:

FLEXIBLE WHIP CONDUIT FOR

TELEPHONE AND DATA WIRING

FURNISHED WITH FURNITURE

AND INSTALLED BY EC.

PROVIDE FINAL CONNECTIONS TO

FURNITURE WITH WHIP

DIVIDED RACEWAY AT BASE OF

FURNITURE (COORDINATE EXACT

POINT OF CONNECTION WITH

FURNITURE IN FIELD)

FLEXIBLE WHIP CONDUIT FOR

POWER WIRING FURNISHED

WITH FURNITURE AND

INSTALLED BY EC.

J K

2.7

NOTE 10

E E E

NOTE 5

NOTE 6

WP

NOTE 2

WP,GFI

NOTE 8

ELEV B CONTROL

ROOM

NOTE 9

19, LPB

39, GPB

J

NOTE 7

NOTE 2

NOTE 1

NOTE 11

GFI

NOTE 3

NOTE 5

NOTE 6

NOTE 10

EE

E

WP

6, LP435, GP4

CAST METAL SINGLE GANG

NEMA 3R JUNCTION BOX

WITH THREADED HUBS

SECTION

RIGID STEEL CONDUIT

FOR SUPPORT

RIGID STEEL

CONDUIT FOR WIRING

M A

X

WEATHERPROOF

IN-USE COVER

ELEVATION

1" PVC CONDUITS SEE

SITE PLAN

CAST IN PLACE CONCRETE

BASE 18" DIAMETER

STANCHION BASE

SET IN CONCRETE 3-1/2"

10"

10"

CONDUIT SLEEVE

CONDUIT

GROUND

MASTIC COATING

ON WALL AND

CONDUIT

LINK SEAL

NOTES:

1. FOR EXTERIOR, BELOW GRADE WALL

APPLICATIONS.

ESCUTCHEON PLATE

POURED CONCRETE OR C.M.U. WALL.

VERIFY CONSTRUCTION TYPE AND

MATERIAL WITH ARCHITECT.

WATER STOP AND ANCHOR COLLAR,

CONTINUOUSLY WELDED ALL

AROUND TO SLEEVE, MINIMUM 1".

CONTRACT

DOCUMENTS

NOT FOR CONSTRUCTION

SHEET NO.

PROFESSIONAL SEAL

21 Talcott Notch Road

Farmington, CT 06032 friar.com

860.678.1291

CONSULTANT

DATE:

SCALE

PROJ. #:

DRAWN:

CHECKED:

CES #2025224.00

1/29/2026 3:27:54 PM

As indicated

E5.1

ELECTRICAL DETAILS

REHABILITATION

AND RENOVATION

OF THE HISTORIC

CHASE BUILDING

CITY OF WATERBURY RFP #8287

236 GRAND AVENUE

WATERBURY, CT 06702

KCM

AJG

2024-108A

2026-0130

NTS

TRENCHING DETAIL - CHILLER CH-1

NTS

BOILER ROOM EPO DETAIL (MANUAL ONLY)

NTS

ELEVATOR DISCONNECT SWITCH DETAIL

NTS

TYPICAL SITE BRANCH CIRCUIT TRENCHING DETAIL

1/2" = 1'-0"

ELECTRICAL ELEVATOR SHAFT A PIT - PART PLAN

MACHINE ROOMLESS ELEVATOR NOTES:

1. PROVIDE 3/4"C. WITH (2) POTS PHONE LINES TO LOCAL I.T.

ROOM FOR ELEVATOR COMMUNICATIONS. PROVIDE FINAL

CONNECTIONS TO ELEVATOR CONTROLLER. COORDINATE

EXACT POINT OF CONNECTION WITH ELEVATOR

CONTRACTOR.

2. ELEVATOR MAIN POWER FEED. PROVIDE WIRING AND

CONDUIT PER ELECTRICAL RISER DIAGRAM. PROVIDE POWER

FROM SPECIALTY SHUNT-TRIP ELEVATOR DISCONNECT

SWITCH IN LOCAL ELECTRICAL ROOM (PER PLANS) TO A

SECOND DISCONNECT SWITCH LOCATED IN ELEVATOR

SHAFT - IN A LOCATION APPROVED BY BOTH AHJ AND

ELEVATOR INSTALLER. THE DISCONNECT SWITCH WITHIN

SHAFT SHALL BE THE SAME AMPERAGE AS THE SPECIALTY

SHUNT-TRIP DISCONNECT SWITCH, AND NON-FUSED. PROVIDE

FINAL CONNECTIONS FROM THE DISCONNECT SWITCH TO THE

ELEVATOR CONTROLLER, EXACT LOCATION SHALL BE

COORDINATED WITH ELEVATOR INSTALLER.

3. ELEVATOR CAB LIGHTING CIRCUIT. PROVIDE 2#12+1#12G,

3/4"C. FROM INDICATED CIRCUIT TO A 30A/2P DISCONNECT

SWITCH, FUSED AT 20A LOCATED IN THE ELEVATOR SHAFT - IN

A LOCATION APPROVED BY BOTH AHJ AND ELEVATOR

INSTALLER. PROVIDE FINAL CONNECTIONS FROM THE

DISCONNECT SWITCH TO THE ELEVATOR CONTROLLER,

EXACT LOCATION SHALL BE COORDINATED WITH ELEVATOR

INSTALLER.

4. ELEVATOR CONTROLLER LOCATED AT TOP OF SHAFT.

CONTROLLER PROVIDED WITH CONDUIT ENTRY PROVISIONS,

COMMUNCIATIONS AND CODE REQUIRED ELEVATOR

CONTROLS. COORDINATE CONDUIT ENTRY, WIRING

REQUIREMENTS AND ALL REQUIRED TERMINATIONS WITH

ELEVATOR INSTALLER.

5. SMOKE DETECTOR TO COMMUNICATE WITH ELEVATOR

RECALL FUNCTIONALITY - PER FIRE ALARM RISER DIAGRAM.

6. HEAT DETECTOR (COMBINATION FIXED TEMPERATURE/ RATE

OF RISE STYLE), TO COMMUNICATE WITH ELEVATOR SHUNT-

TRIP DISCONNECT SWITCH - PER FIRE ALARM RISER DIAGRAM.

INSTALL WITHIN 24" OF SPRINKLER HEAD.

7. FIRE ALARM CONTROL MODULES TO COMMUNICATE WITH

ELEVATOR CONTROLLER. PROVIDE QUANTITY AS REQUIRED

BY ELEVATOR MANUFACTURER. PROVIDE FINAL

CONNECTIONS TO CONTROLLER.

8. PROVIDE WEATHERPROOF, GFCI-TYPE DUPLEX RECEPTACLE.

COORDINATE LOCATION WITH ELEVATOR INSTALLER. PROVIDE

DEDICATED 120V, 20A BRANCH CIRCUIT USING 2#12+1#12G,

3/4"C.

9. PROVIDE FIRE ALARM CONTROL AND MONITOR MODULES FOR

ELEVATOR SHUNT TRIP AND VOLTAGE MONITORING

FUNCTIONALITY, CONNECTED PER ELEVATOR DISCONNECT

SWITCH DETAIL.

10. PROVIDE WEATHERPROOF PILOT LIGHT SWITCH AND LIGHT

FIXTURES AS SPECIFIED PER LIGHTING FIXTURE SCHEDULE.

LIGHT FIXTURES SHALL BE PROVIDED WITH WIREGUARD

ACCESSORY. INSTALL LIGHT FIXTURES IN ELEVATOR PIT AND

TOP OF SHAFT AT LOCATIONS COORDINATED WITH THE

ELEVATOR INSTALLER AND INSPECTOR, AS REQUIRED TO

ACHIEVE A MINIMUM OF 19 FOOTCANDLES. CONTRACTOR

SHALL TAKE LIGHT MEASUREMENTS PRIOR TO FINAL

INSTALLATION OF THESE LIGHT FIXTURES TO ENSURE

REQUIRED ILLUMINATION LEVELS ARE BEING ACHIEVED.

COORDINATE LIGHT FIXTURE LOCATION WITH ELEVATOR

EQUIPMENT AND ALL ASSOCIATED APPURTENANCES.

11. PROVIDE GFCI-TYPE DUPLEX RECEPTACLE ADJACENT TO THE

ELEVATOR CONTROLLER. PROVIDE DEDICATED 120V, 20A

BRANCH CIRCUIT USING 2#12+1#12G, 3/4"C.

1/2" = 1'-0"

ELECTRICAL ELEVATOR TOP OF SHAFT A - PART PLAN

NTS

STANCHION MOUNTED FLOODLIGHT DETAIL

REVISIONS

NO. DATE DESCRIPTION

NTS

POWER & DATA MODULAR FURNITURE CONNECTIONS DETAIL - SURFACE RACEWAY

1/2" = 1'-0"

ELECTRICAL ELEVATOR SHAFT B PIT - PART PLAN

1/2" = 1'-0"

ELECTRICAL ELEVATOR TOP OF SHAFT B - PART PLAN

NTS

STANCHION MOUNTED RECEPTACLE DETAIL

NTS

FOUNDATION WALL PENETRATION DETAIL

GENERAL NOTES:

1. AIR TERMINAL SPACING SHALL CONFORM TO NFPA 780 & UL 96A REQUIREMENTS.

2. MATERIAL COMPATIBILITY SHALL CONFORM TO NFPA 780 & 96A REQUIREMENTS.

3. MATERIAL CLASS SHALL CONFORM TO NFPA 780 & UL 96A REQUIREMENTS.

4. AIR TERMINALS SHALL BE UL LISTED.

LIGHTNING PROTECTION CONDUCTORS:

CLASS 1/2 - STRANDED BASKET-WEAVE

COPPER CONDUCTOR

FOR SURFACES NOT COMPATIBLE WITH COPPER:

CLASS 1/2 - STRANDED BASKET-WEAVE

ALUMINUM CONDUCTOR

FASTEN COPPER CONDUCTORS WITH ADHESIVE

COPPER CABLE HOLDERS. FASTEN ALUMINUM

CONDUCTORS WITH ADHESIVE ALUMINUM CABLE

HOLDERS. LIGHTNING PROTECTION CONDUCTORS

SHALL BE FASTENED AT INTERVALS NOT MORE THAN

36" ON CENTER.

MOUNT ADHESIVE FITTINGS WITH ROOF SYSTEM

MANUFACTURER APPROVED ADHESIVE. ALL REQUIRED

SLIP SHEETS, BATTEN STRIPS, PAVERS, AND SPECIAL

REQUIREMENTS OF THE ROOFING SYSTEM

MANUFACTURER SHALL BE FURNISHED AND INSTALLED

BY THE ROOFING CONTRACTOR.

ADHESIVE COPPER AIR TERMINAL BASE.

FOR SURFACES NOT COMPATIBLE WITH COPPER USE

ADHESIVE ALUMINUM AIR TERMINAL BASE.

AIR TERMINAL:

CLASS 1 - 3/8" DIAMETER SOLID COPPER

CLASS 2 - 1/2" DIAMETER SOLID COPPER

FOR SURFACES NOT COMPATIBLE WITH COPPER:

CLASS 1 - 1/2" DIAMETER SOLID ALUMINUM

CLASS 2 - 5/8" DIAMETER SOLID ALUMINUM

GENERAL NOTES:

1. AIR TERMINAL SPACING SHALL CONFORM TO NFPA 780 & UL 96A REQUIREMENTS.

2. MATERIAL COMPATIBILITY SHALL CONFORM TO NFPA 780 & 96A REQUIREMENTS.

3. MATERIAL CLASS SHALL CONFORM TO NFPA 780 & UL 96A REQUIREMNTS.

4. AIR TERMINALS SHALL BE UL LISTED.

LIGHTNING PROTECTION CONDUCTORS:

CLASS 1/2 - STRANDED BASKET-WEAVE

COPPER CONDUCTOR

FOR SURFACES NOT COMPATIBLE WITH COPPER:

CLASS 1/2 - STRANDED BASKET-WEAVE

ALUMINUM CONDUCTOR

FASTEN COPPER CONDUCTORS WITH COPPER

CABLE LOOPS. FASTEN ALUMINUM CONDUCTORS

WITH ALUMINUM CABLE LOOPS. LIGHTNING

PROTECTION CONDUCTORS SHALL BE FASTENED

AT INTERVALS NOT MORE THAN 36" ON CENTER.

MOUNT AIR TERMINAL BASE WITH SELF TAPPING

STAINLESS STEEL SCREWS.

COPPER SIDE MOUNT AIR TERMINAL BASE. FOR

SURFACES NOT COMPATIBLE WITH COPPER USE

ALUMINUM SIDE MOUNT AIR TERMINAL BASE

AIR TERMINAL:

CLASS 1 - 3/8" DIAMETER SOLID COPPER

CLASS 2 - 1/2" DIAMETER SOLID COPPER

FOR SURFACES NOT COMPATIBLE WITH COPPER:

CLASS 1 - 1/2" DIAMETER SOLID ALUMINUM

CLASS 2 - 5/8" DIAMETER SOLID ALUMINUM

10" MAX.

2'0" MAX.

GENERAL NOTES:

1. AIR TERMINAL SPACING SHALL CONFORM TO

NFPA 780 & UL 96A REQUIREMENTS.

2. MATERIAL COMPATIBILITY SHALL CONFORM

TO NFPA 780 & 96A REQUIREMENTS.

3. MATERIAL CLASS SHALL CONFORM TO NFPA

780 & UL 96A REQUIREMENTS.

4. AIR TERMINALS SHALL BE UL LISTED.

EXTRUDED PARALLEL CABLE SPLICER:

• PROVIDE COPPER FOR COPPER

CONDUCTORS.

• PROVIDE ALUMINUM FOR ALUMINUM

CONDUCTORS.

LIGHTNING PROTECTION CONDUCTORS:

CLASS 1/2 - STRANDED BASKET-WEAVE

COPPER CONDUCTOR

FOR SURFACES NOT COMPATIBLE WITH COPPER:

CLASS 1/2 - STRANDED BASKET-WEAVE

ALUMINUM CONDUCTOR

FASTEN COPPER CONDUCTORS WITH

COPPER CABLE LOOPS. FASTEN ALUMINUM

CONDUCTORS WITH ALUMINUM CABLE

LOOPS. LIGHTNING PROTECTION

CONDUCTORS SHALL BE FASTENED AT

INTERVALS NOT MORE THAN 36" ON

CENTER.

COPPER AIR TERMINAL BASE. FOR

SURFACES NOT COMPATIBLE WITH COPPER

USE ALUMINUM AIR TERMINAL BASE.

SECURE WITH ADHESIVE BACKING AS

APPROVED BY ROOFTOP UNIT

MANUFACTURER.

AIR TERMINAL:

CLASS 1 - 3/8" DIAMETER SOLID COPPER

CLASS 2 - 1/2" DIAMETER SOLID COPPER

FOR SURFACES NOT COMPATIBLE WITH COPPER:

CLASS 1 - 1/2" DIAMETER SOLID ALUMINUM

CLASS 2 - 5/8" DIAMETER SOLID ALUMINUM

20' M

AX.

24"

MAX.

GENERAL NOTES:

1. AIR TERMINAL SPACING SHALL CONFORM TO NFPA 780 & UL 96A REQUIREMENTS.

2. MATERIAL COMPATIBILITY SHALL CONFORM TO NFPA 780 & 96A REQUIREMENTS.

3. MATERIAL CLASS SHALL CONFORM TO NFPA 780 & UL 96A REQUIREMENTS.

4. AIR TERMINALS SHALL BE UL LISTED.

FASTEN COPPER CONDUCTORS WITH COPPER STANDING SEAM METAL ROOF

FASTENER. FASTEN ALUMINUM CONDUCTORS WITH ALUMINUM STANDING

SEAM METAL ROOF FASTENER. LIGHTNING PROTECTION CONDUCTORS

SHALL BE FASTENED AT INTERVALS NOT MORE THAN 36" ON CENTER.

EXTRUDED COPPER STANDING SEAM METAL ROOF AIR

TERMINAL BASE. FOR SURFACES NOT COMPATIBLE

WITH COPPER USE EXTRUDED ALUMINUM STANDING

SEAM METAL ROOF AIR TERMINAL BASE.

AIR TERMINAL:

CLASS 1 - 3/8" DIAMETER SOLID COPPER

CLASS 2 - 1/2" DIAMETER SOLID COPPER

FOR SURFACES NOT COMPATIBLE WITH COPPER:

CLASS 1 - 1/2" DIAMETER SOLID ALUMINUM

CLASS 2 - 5/8" DIAMETER SOLID ALUMINUM

LIGHTNING PROTECTION CONDUCTORS:

CLASS 1/2 - STRANDED BASKET-WEAVE

COPPER CONDUCTOR

FOR SURFACES NOT COMPATIBLE WITH COPPER:

CLASS 1/2 - STRANDED BASKET-WEAVE

ALUMINUM CONDUCTOR

3/4" X 10 COPPER-CLAD GROUND ROD. THE

CONNECTION TO THE GROUND ROD SHALL BE MADE

AT A POINT NOT LESS THAN 18" BELOW GRADE AND

A MINIMUM OF 24" AWAY FROM FOOTINGS OR

FOUNDATION WALLS.

COPPER HIGH COMPRESSION CONNECTOR (WHERE

GROUND LOOP IS USED).

CLASS 1 GROUND LOOP CONDUCTOR (WHERE SHOWN).

COPPER HIGH COMPRESSION CONNECTOR.

1" SCH 40 PVC SLEEVE THROUGH FLOOR FOR

CONNECTION OF PERIMETER STEEL COLUMN GROUND.

SEAL SLEEVE AS REQUIRED AFTER INSTALLATION OF

GROUND CONDUCTOR. ALL SEALING AND SLEEVES

SHALL BE FURNISHED AND INSTALLED BY THE

GENERAL CONTRACTOR

CLASS 1 COPPER GROUND CONDUCTOR

FASTEN BOND PLATE TO CLEANED BARE METAL

SURFACE OF STEEL COLUMN WITH STAINLESS STEEL

SELF TAPPING SCREWS.

CAST BRONZE 8 SQUARE INCH BONDING PLATE.

PERIMETER STEEL COLUMN. THE PERIMETER STEEL

COLUMNS SHALL BE PROVIDED WITH A GROUND

CONNECTION AT INTERVALS NOT TO EXCEED 60' 0" ON

CENTER.

24"

DOWN CONDUCTOR TO CONNECTION WITH GROUND

SYSTEM.

SLEEVE AND SEAL AS REQUIRED (FURNISHED AND

INSTALLED BY GENERAL CONTRACTOR)

CLASS 1 OR 2 COPPER DOWN CONDUCTOR

1" SCH 40 PVC CONDUIT. CONDUIT SHALL BE

FURNISHED AND INSTALLED BY THE ELECTRICAL

CONTRACTOR WITH PULL TAPE AND CAPS AT EACH

END.

EXTERIOR WALL

SEAL ROOF PENETRATION AS REQUIRED (FURNISHED

AND INSTALLED BY THE ROOFING CONTRACTOR).

THROUGH ROOF CABLE CONNECTOR.

PARAPET

FLASHING

SECONDARY BOND TO FLASHING (SEE BONDING DETAILS).

CONDUCTOR TO ROOF LIGHTNING PROTECTION SYSTEM

CAST METAL SINGLE GANG

NEMA 3R JUNCTION BOX

WITH THREADED HUBS

SECTION

ROOF

RIGID STEEL CONDUIT

FOR SUPPORT

RIGID STEEL

CONDUIT FOR WIRING

M A

X

WEATHERPROOF

IN-USE COVER

PITCH POCKET

GALVANIZED

STEEL STRUT

BEAM CLAMP

WITH U-BOLT

BUILDING STEEL

CONDUIT CLAMP

ELEVATION

NOTES:

1. WHERE APPLICABLE MOUNT ROOF RECEPTACLE TO MECHANICAL

EQUIPMENT ENCLOSURES.

2. COORDINATE WITH ROOFING CONTRACTOR FOR ALL ROOF

PENETRATIONS AND SEALING TO MAINTAIN ROOF WARRANTY.

RESET MUTE

Heat Detector

Fire Alarm

Power

Gas On

EM Stop

MERLIN GAS SAFETY SYSTEM

UTILITY CONTROL PANEL FOR GAS AND ELECTRIC

SHUTOFF WITH (4) ZONE DETECTION: BASIS OF DESIGN:

AGS MERLIN GDP4 GAS DETECTION SYSTEM.

NOTES:

1. REFER TO FLOOR PLANS FOR LOCATIONS OF CONTROLLER, EPO SHUTDOWN BUTTONS AND SOLENOIDS.

COORDINATE BETWEEN ELECTRICAL AND PLUMBING DRAWINGS.

2. UNLESS NOTED OTHERWISE, ALL EQUIPMENT, WIRING, ELECTRICAL CONNECTIONS AND TESTING BY DIV. 26.

COORDINATE SOLENOID VALVE CABINET LOCATION(S) AND FIELD WIRING WITH DIV. 22.

3. STI MODEL #SS2021PO-EN PUSHBUTTON, QUANTITY SHOWN ON PLANS, WIRED IN PARALLEL:

A. WITH (1) N.O. AND (1) N.C. CONTACT COMPATIBLE WITH CONTROL PANEL INPUT

B. RED COLOR WITH "EMERGENCY POWER OFF" LEGEND

C. NON-ALARMED FLIP UP FLUSHED COVER

D. TURN-TO-RESET, MAINTAINED OPERATION

4. FIRE ALARM CONTROL MODULE WIRED IN PARALLEL WITH EMERGENCY SHUTOFF (EPO) BUTTON INPUT(S).

5. SQUARE D CLASS 8903 SERIES MECHANICALLY HELD CONTACTOR WITH 2-WIRE CONTROL INTERFACE OR

APPROVED EQUAL. PROVIDE CONTACTOR WITH QUANTITY OF POLES REQUIRED TO SHUT POWER DOWN TO EQUIPMENT LISTED PLUS (3) SPARE POLES. COORDINATE LOCATION IN EQUIPMENT ROOM IN FIELD.

6. POWER VIA 2#12+1#12G, 3/4"C. TO LOCAL UNSWITCHED RECEPTACLE CIRCUIT NOT CONTROLLED VIA

ELECTRICAL CONTACTOR.

7. NATURAL GAS DETECTOR: MODEL AGSNGXS. MOUNT TO A SINGLE GANG BOX ON WALL OR ON BOILER SUPPORT AT 5'-6" AFF. PROVIDE ONE PER BOILER AND MOUNT DIRECTLY ABOVE GAS CONNECTION TO BOILER WHERE DETECTORS ARE NOT SHOWN ON PLANS. COORDINATE LOCATION IN EQUIPMENT ROOM IN FIELD.

8. DRY CONTACT OUTPUT TO FIRE ALARM MONITORING MODULE TO REPORT TO FIRE ALARM SYSTEM UPON GAS

DETECTION.

120V AC FROM

CONTROL OUTPUT

Dimensions 10inx7inx3in approx.

2#12+1#12G, 3/4"C.

GAS LINE IN

(BY DIV. 22)

GAS LINE OUT

(BY DIV. 22)

120VAC NORMALLY CLOSED

SOLENOID VALVE AND

ENCLOSURE FURNISHED BY

DIV.22, INSTALLED BY DIV.22,

WIRED BY DIV.26.

2#12+1#12G, 3/4"C.

NOTE 3

NOTE 3

NOTE 4 CM

EPO

EPO

2#18-1/2"C TO

AUXILIARY PANIC INPUT

2#18-1/2"C TO

AUXILIARY PANIC INPUT

2#18-1/2"C TO

AUXILIARY PANIC INPUT

UC

EMERGENCY SHUT OFF SWITCH

3.22"

4.86"

EMERGENCY

2"

MOUNTING

HEIGHT TO BE

DETERMINED

BY ARCHITECT

TO SHUT OFF GAS AND ELECTRICITY

IN BOILER…