RFB954200-01 - Bid Drawings.pdf

PDF 6 MB Posted

Attached to
DOC IMCC Admin Bldg Water Mitigation
Solicitation number
RFB954200-01
Issued by
Jasper County, Iowa

About this file

Summary of RFB954200-01 Bid Drawings

This is a set of bid drawings for a water mitigation project at the Iowa Medical and Classification Center Administration Building in Coralville, Iowa, prepared by the Iowa Department of Administrative Services. The project involves installation of storm sewer systems, foundation drainage improvements, site restoration, and related civil work at the facility located at 2839 Northgate Drive, Iowa City, Iowa 52245. The drawings include cover sheets, existing conditions plans, erosion and sediment control plans, site access and preparation plans, utility plans, construction details, site restoration plans, and grading plans. The project requires installation of approximately 12-inch storm sewer lines, 4-inch perforated drain tile, storm intake structures, and associated appurtenances. The drawings were issued for bid on November 18, 2026, with a project number of 9542.00. No specific contract award date, response deadline, or term length is indicated in the bid drawing documents themselves.

The drawings establish comprehensive requirements for contractor execution including site fencing, erosion and sediment control measures, utility coordination, excavation and backfill specifications, pavement and sidewalk restoration, and grading to finished elevations. The contractor bears responsibility for utility location verification through Iowa One Call at minimum 48 hours before excavation, compliance with all OSHA regulations, daily site cleanup, maintenance of emergency vehicle access, and protection of existing vegetation and structures. All excess excavated material must be disposed of at the owner's on-site dump site. The project requires phased construction to maintain site access and emergency egress, coordination with public safety and parking authorities, and restoration of all disturbed areas to match existing conditions. No specific pricing information, set-asides, incumbent contractor identification, or funding sources are documented in these bid drawings.

View the file

Other files

File Type Posted
RFB954200-01 - Notice to Bidders.pdf PDF
RFB954200-01 - Project Manual.pdf PDF
RFB954200-01 - Bid Form.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT LOCATION

C O

R

AL

R

ID

G E

AV

E

UNIVERSITYPARKWAY

IOWA MEDICAL AND

CLASSIFICATION

CENTER

OWNER'S ON-SITE

EXCESS SOIL

DUMP SITE.

N O

R

TH

G

AT

E D

R

IV

E

IO

W A

C

IT

Y, IO

W A

9.

4.

S H

IV

E-

H

AT

TE

R

Y.

C

O M

A B C D E F HG

A B C D E F HG

Pr in te d:

D R

AW

N

B Y

AP

PR

O

VE

D B

Y

IS

SU

ED

F

O R

IS

SU

E D

AT

E

FI

EL

D B

O O

K

PR

O

JE

C

T N

U M

BE

R

P:

\P ro je ct s\

\2

0\

De liv er ab le s\

Dr aw in gs

\1 _C ivi l\G

0.

dw g

/1

4/

1:

:0

AM

G000

C O

VE

R

S H

EE

T

AS

R

KM

B

BI

D

/1

8/

80 --- C

LI

EN

T

PR

O

JE

C T

N U

M

BE

R : 9

2.

IM

C

C A

D M

IN

B

LD

G

W

AT

ER

M

IT

IG

AT

IO

N

IO

W

A D

EP

AR

M

EN

T O

F

AD

M

IN

IS

TR

AT

IV

E

SE

R

VI

C

ES

C O

R

AL

VI

LL

E, IA

IOWA DEPARTMENT OF ADMINISTRATIVE SERVICES

IMCC ADMIN BLDG WATER MITIGATION

CLIENT PROJECT #9542.00

CORALVILLE, IA

PROJECT LOCATION MAP

1. CONTRACTOR SHALL MINIMIZE THE DISRUPTION OF EMERGENCY

VEHICLE ACCESS THROUGH THE SECURITY GATE. BACKFILL

EXCAVATION AS SOON AS PRACTICAL. PROVIDE TEMPORARY FILL TO

MATCH ADJACENT PAVEMENT IF REPAVING IS NOT COMPLETED

IMMEDIATELY.

2. UTILITY LOCATIONS SHOWN ARE APPROXIMATE AND OTHER

UTILITIES NOT SHOWN ON DRAWINGS MAY EXIST. CONTRACTOR

SHALL HAVE UTILITY LOCATIONS MARKED AND EXCAVATE WITH

CAUTION.

3. SURFACE RESTORATION: REPLACE TOPSOIL TO FINISHED GRADE.

PLACE SUFFICIENT MATERIAL ADJACENT TO BUILDING. PROVIDE

SEED MIX FOR INSTALLATION AND WATERING BY OWNER. OTHER

THAN SEEDING, RETURN DISTURBED AREAS TO CONDITIONS PRIOR

TO CONSTRUCTION, READY FOR SEEDING OR PLANTING BY OWNER.

4. SITE SAFETY AND PEDESTRIAN SAFETY IS OF EXTREME IMPORTANCE.

THE CONTRACTOR IS RESPONSIBLE FOR EXECUTING THE WORK IN A

SAFE MANNER.

5. CONTRACTOR TO COORDINATE WITH PUBLIC SAFETY AND PARKING

THROUGH THE OWNER'S REPRESENTATIVE.

6. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR COMPLIANCE WITH

ALL OSHA REGULATIONS, COMPLIANCE IS MANDATORY.

7. PERFORM SITE CLEANUP ON A DAILY BASIS AT A MINIMUM. KEEP ALL

SURFACES INCLUDING SIDEWALKS, PARKING LOTS, AND ROADWAYS

CLEAN AT ALL TIMES.

8. CONTRACTOR TO ERECT SITE FENCING AND RECEIVE APPROVAL BY

THE OWNER PRIOR TO THE COMMENCEMENT OF WORK.

9. IOWA UTILITIES INFORMATION REQUIRES VERBAL NOTICE TO IOWA

ONE CALL 1-800-292-8989, NOT LESS THAN 48 HOURS BEFORE

EXCAVATING. UTILITY LOCATES SHALL BE KEPT CURRENT PER STATE

REQUIREMENTS.

10. VEHICULAR TRAFFIC OR PARKING OF CONSTRUCTION VEHICLES

UNDER THE DRIP LINES (IN OR OUT OF THE CONSTRUCTION LIMITS)

OF TREES IS STRICTLY PROHIBITED AND VEHICLES MAY BE TOWED.

11. UNFORESEEN CONDITIONS ARE INHERENT TO UNDERGROUND WORK

AND ARE TO BE EXPECTED WITH THIS PROJECT. UPON

ENCOUNTERING UNFORESEEN CONDITIONS, CONTACT OWNER AND

DESIGN PROFESSIONAL FOR DIRECTION ON HOW TO PROCCEED.

12. AT CONTRACTOR'S OPTION, PROVIDE AND PAY FOR STAKING.

STAKING TO BE PERFORMED BY A LICENSED LAND SURVEYOR.

GENERAL INFORMATION

G000 & C SHEETS

27651

Sheet List Table Sheet Number Sheet Title

G000 COVER SHEET

C001 EXISTING CONDITIONS PLAN

C101 EROSION AND SEDIMENT CONTROL PLAN

C201 SITE ACCESS PLAN

C301 SITE PREPARATION AND DEMOLITION PLAN

C401 SITE UTILITY PLAN

C501 CONSTRUCTION DETAILS

C601 SITE RESTORATION PLAN

C701 SITE GRADING PLAN

November 16, 2026November 18, 2026

X

X

X X

X X

X

CP 1

CP 2

CP 4

CP 6

R

AZO

R

W

IR

E

R

AZ

O R

W

IR

E

PCC

PCC

PCC

PC

C

PCC

PCC

PCC

PCC

PCC

PC

C

PC

C

PC

C

PCC

PCC

PCC

GRASS

GRASS

GRASS

GRAVEL

GRASS D

IR

T

GRASS

GRASS

GRASS

GRASS

GRASS

GRAVEL

GRAVEL

G R

AV

EL

GRAVEL

GRASS

E.

N

.F

E.

N

.F

E.N.F.

IMCC

ADMINISTRATION

BUILDING

GROUND ROD

COVERED SEATING AREA

ANTENNA

GROUND ROD

SANITARY MH

809.52 RIM

800.68 IE ±8" VCP (W)

799.22 IE ±10" (N)

799.10 IE ±10" (S)

GROUND ROD

GROUND ROD

2" PVC SUMP PUMP

DISCHARGE INTO ADS TILE.

3" PVC SUMP PUMP

DISCHARGE INTO ADS TILE.

3" PVC COMING OUT OF WALL

1" CONDUIT COMING

OUT OF GROUND

FF THRESHOLD = 804.05

(METAL)

FF = 811.25

(TILE)

FF = 803.89

(CONCRETE)

FF = 811.24

(TILE)

GROUND

ROD

STONE

RETAINING WALL

STONE

RETAINING WALL

STONE RETAINING WALL

SPLIT HEAD

GALVANIZED PIPE

ON WALL

GUARD RAIL

STAIRS

CAMERA POLE AND

JUNCTION BOX.

POLE MOUNTED

MOTION SENSOR.

POLE MOUNTED

MOTION SENSOR.

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X

6" S

T

" S

T

15" ST

8" ST

8" S

T

12" ST

" S

T

" S

T

R

AZ

O R

W

IR

E

R

AZ

O R

W

IR

E R

AZ

O

R W

IR

E

PCC

R

AZ

O R

W

IR

E

R

AZ

O R

W

IR

E

STORM INTAKE

800.09 RIM

797.94 IE 8" DIP (E)

797.79 IE (N)

STORM INTAKE

808.91 RIM

802.40 IE 12" RCP (S)

802.31 IE 12" RCP (N)

6" ADS TILE RUN ON TOP OF

GROUND DIRECTING ROOF

DRAIN DISCHARGE

6" ADS TILE

RUN ON TOP

OF GROUND

DIRECTING

ROOF DRAIN

DISCHARGE

STORM MH

806.64 RIM

799.10 IE 10" VCP (SW)

798.95 IE 12" RCP (W)

798.88 IE 18" RCP (N)

STRUCTURE INACCESSIBLE

UNDER RAZOR WIRE

803.32 IE 4" ADS (SW)

STORM MH

811.92 RIM

STORM INTAKE

801.64 RIM

799.57 IE 4" PVC (S) (PLUGGED WITH ROCK)

799.23 IE 12" VCP (NW)

STORM INTAKE

804.98 RIM

803.48 IE 6" ADS (N)

803.27 BOTTOM

STORM INTAKE

800.31 RIM

798.21 IE 8" DIP (W)

798.16 IE 8" DIP (N)

798.11 IE (E)

STORM MH

811.92 RIM

±804 IE 15" VCP (W)

6" (N)

804.19 BOTTOM

STANDING WATER IN STRUCTURE

803.92 IE 4" PVC (W)

803.90 IE 4" PVC (W)

803.93 IE 4" PVC (W)

SUMP PUMP DISCHARGE

INTO ADS TILE

ENF

6" ADS TILE RUN ON TOP OF

GROUND DIRECTING ROOF

DRAIN DISCHARGE809

POINT #

NORTHING

7956526.25

7956515.59

7956763.16

7956256.05

7956025.32

7956216.48

EASTING

20515354.42

20515516.07

20515516.05

20515410.91

20515506.33

20515515.13

ELEVATION

808.69

810.22

800.95

812.78

807.92

810.65

DESCRIPTION

BRASS MARKER

BRASS MARKER

BRASS MARKER

BRASS MARKER

BRASS MARKER

BRASS MARKER

CONTROL POINT TABLE

IOWA REGIONAL COORDINATE SYSTEM -ZONE 10

NAD83 (2011) NAVD88 GEOID18 US SURVEY FEET

N O

R

TH

G

AT

E D

R

IV

E

IO

W A

C

IT

Y, IO

W A

9.

4.

S H

IV

E-

H

AT

TE

R

Y.

C

O M

A B C D E F HG

A B C D E F HG

Pr in te d:

D R

AW

N

B Y

AP

PR

O

VE

D B

Y

IS

SU

ED

F

O R

IS

SU

E D

AT

E

FI

EL

D B

O O

K

PR

O

JE

C

T N

U M

BE

R

P:

\P ro je ct s\

\2

0\

De liv er ab le s\

Dr aw in gs

\1 _C ivi l\C

1.

dw g

/1

4/

1:

:4

AM

C001

EX

IS

TI

N

G C

O N

D

IT

IO

N

S

PL

AN

AS

R

KM

B

BI

D

/1

8/

80 --- C

LI

EN

T

PR

O

JE

C T

N U

M

BE

R : 9

2.

IM

C

C A

D M

IN

B

LD

G

W

AT

ER

M

IT

IG

AT

IO

N

IO

W

A D

EP

AR

M

EN

T O

F

AD

M

IN

IS

TR

AT

IV

E

SE

R

VI

C

ES

C O

R

AL

VI

LL

E, IA

EXISTING CONDITIONS PLAN

ABBREVIATIONS

RESTRAINED JOINT

DUCTILE IRON PIPE

NOTES

ASPHALTACC

ABAN

DIA

DIP

DW

FO

IE

LF

LPS

MH

ABANDONED

DIAMETER

DUCTILE IRON PIPE

DOMESTIC WATER

FIBER OPTIC

INVERT ELEVATION

LINEAR FEET

LOW PRESSURE STEAM

MANHOLE

OE

PCC

PVC

RCP

RE'D/REQ'D

RGS

RJ

DIP

SAN

SMH

ST

TELU

TEMP

UE

WAT/W

OVERHEAD ELECTRIC

PORTLAND CEMENT CONCRETE

POLYVINYL CHLORIDE PIPE

REINFORCED CONCRETE PIPE

REQUIRED

RIGID STEEL

SANITARY SEWER

SANITARY MANHOLE

STORM SEWER

TELECOMMUNICATIONS

TEMPORARY

UNDERGROUND ELECTRIC

WATER MAIN

PL PROPERTY LINE

1. UTILITIES SHOWN ARE BASED ON TOPOGRAPHICAL SURVEY COMPLETED

09-04-2026 BY SHIVE-HATTERY. SURVEY UTILITY INFORMATION IS PROVIDED BY

THE OPERATING AUTHORITY OF EACH UTILITY, SURFACE FEATURES, AND

AVAILABLE RECORD DRAWINGS. NO SUBSURFACE INVESTIGATION HAS BEEN MADE

TO DETERMINE ACCURACY OF THE INFORMATION. IT IS THE CONTRACTOR'S

RESPONSIBILITY TO DETERMINE THE EXACT LOCATION OF UNDERGROUND

UTILITIES. CALL IOWA ONE-CALL (1-800-292-8989) FOR UTILITY LOCATES PRIOR TO

CONSTRUCTION. UTILITY LOCATES SHALL BE KEPT CURRENT PER STATE

REQUIREMENTS.

2. PLAN AND EXECUTE ALL NEW CONSTRUCTION THAT IS WITHIN CLOSE PROXIMITY

TO EXISTING OR NEW UTILITIES CAREFULLY SO THAT UTILITIES ARE NOT

DAMAGED. PHYSICALLY VERIFY THE LOCATION OF ALL UTILITIES PRIOR TO

COMMENCING WORK. REPAIR ANY DAMAGES TO EXISTING OR NEW UTILITIES.

1. PROTECT STAKING CONTROL POINTS THROUGHOUT THE PROJECT.

2. STAKING AND LAYOUT FOR THIS PROJECT IS THE RESPONSIBILITY OF THE

CONTRACTOR.

3. NO STAKING COORDINATES WILL BE PROVIDED FOR THE WORK SHOWN ON THE

C-SERIES SHEETS. ELECTRONIC AUTOCAD FILES WILL BE PROVIDED AND IT IS THE

CONTRACTOR'S RESPONSIBILITY TO PROVIDE STAKING AND LAYOUT BASED ON

ELECTRONIC DRAWING DATA.

4. UNLESS OTHERWISE APPROVED, IT IS EXPECTED THE CONTRACTOR CAREFULLY

OBTAINS ELEVATIONS FROM THE PLANS, AND THAT UTILITIES WILL BE INSTALLED

AS CLOSE TO PRECISE PROFILE ELEVATIONS AS CONSTRUCTION METHODS WILL

REASONABLY ALLOW.

STAKING/LAYOUT NOTES

GENERAL SITE

EXISTING STRUCTURE

PLAN MARK DESCRIPTION

LEGEND

GUARD POST/ BOLLARD

SHRUB

DECIDUOUS TREE

CONIFEROUS TREE

SINGLE POLE SIGN

HANDHOLE

UTILITY POLE

LIGHT POST

FIRE HYDRANT

VALVE

UTILITY END CAP

CLEANOUT

DRAINAGE MANHOLE

ELECTRICAL MANHOLE

TELEPHONE PEDESTAL

SANITARY MANHOLE

TELEPHONE MANHOLE

INTAKE - CIRCLE

INTAKE - RECTANGLE

CHAIN LINK FENCE

620 MAJOR CONTOUR

MINOR CONTOUR

SURVEY CONTROL POINT

ELECTRIC OUTLET JUNCTION BOX

CP-1

RD BUILDING ROOF DRAIN

BUSH LIMITS

UTILITY LINES

LINE TYPE DESCRIPTION

OVERHEAD ELEC.

UNDERGROUND ELEC.

GAS MAIN

WATER MAIN

SANITARY SEWER

STORM SEWER

UNDERGROUND TELE.

UNDERGROUND

STEAM

DUCTBANK

FIBER OPTICS

SITE LIGHTING

LEGEND

X

X

X

X

X X

X

X X

X X

X

R

AZO

R

W

IR

E

R

AZ

O R

W

IR

E

PCC

PCC

PCC

PC

C

PCC

PCC

PCC

PCC

PCC

PC

C

PC

C

PC

C

PCC

PCC

PCC

GRASS

GRASS

GRASS

GRAVEL

GRASS D

IR

T

GRASS

GRASS

GRASS

GRASS

GRASS

GRAVEL

GRAVEL

G R

AV

EL

GRAVEL

GRASS

E.

N

.F

E.

N

.F

E.N.F.

IMCC

ADMINISTRATION

BUILDING

GROUND ROD

COVERED SEATING AREA

ANTENNA

GROUND ROD

GROUND ROD

GROUND ROD

2" PVC SUMP PUMP

DISCHARGE INTO ADS TILE.

3" PVC SUMP PUMP

DISCHARGE INTO ADS TILE.

3" PVC COMING OUT OF WALL

1" CONDUIT COMING

OUT OF GROUND

FF THRESHOLD = 804.05

(METAL)

FF = 811.25

(TILE)

FF = 803.89

(CONCRETE)

FF = 811.24

(TILE)

GROUND

ROD

STONE

RETAINING WALL

STONE

RETAINING WALL

STONE RETAINING WALL

SPLIT HEAD

GALVANIZED PIPE

ON WALL

GUARD RAIL

STAIRS

CAMERA POLE AND

JUNCTION BOX.

POLE MOUNTED

MOTION SENSOR.

POLE MOUNTED

MOTION SENSOR.

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X

6" S

T

" S

T

15" ST

8" ST

8" S

T

12" ST

" S

T

" S

T

R

AZ

O R

W

IR

E

R

AZ

O R

W

IR

E R

AZ

O

R W

IR

E

PCC

R

AZ

O R

W

IR

E

R

AZ

O R

W

IR

E

STORM INTAKE

800.09 RIM

797.94 IE 8" DIP (E)

797.79 IE (N)

STORM INTAKE

808.91 RIM

802.40 IE 12" RCP (S)

802.31 IE 12" RCP (N)

6" ADS TILE RUN ON TOP OF

GROUND DIRECTING ROOF

DRAIN DISCHARGE

6" ADS TILE

RUN ON TOP

OF GROUND

DIRECTING

ROOF DRAIN

DISCHARGE

STORM MH

806.64 RIM

799.10 IE 10" VCP (SW)

798.95 IE 12" RCP (W)

798.88 IE 18" RCP (N)

STRUCTURE INACCESSIBLE

UNDER RAZOR WIRE

803.32 IE 4" ADS (SW)

STORM MH

811.92 RIM

STORM INTAKE

801.64 RIM

799.57 IE 4" PVC (S) (PLUGGED WITH ROCK)

799.23 IE 12" VCP (NW)

STORM INTAKE

804.98 RIM

803.48 IE 6" ADS (N)

803.27 BOTTOM

STORM INTAKE

800.31 RIM

798.21 IE 8" DIP (W)

798.16 IE 8" DIP (N)

798.11 IE (E)

STORM MH

811.92 RIM

±804 IE 15" VCP (W)

6" (N)

804.19 BOTTOM

STANDING WATER IN STRUCTURE

803.92 IE 4" PVC (W)

803.90 IE 4" PVC (W)

803.93 IE 4" PVC (W)

SUMP PUMP DISCHARGE

INTO ADS TILE

ENF

6" ADS TILE RUN ON TOP OF

GROUND DIRECTING ROOF

DRAIN DISCHARGE80

EXISTING ACCESS ROAD, TYP

EXISTING GRADE CONTOUR, TYP

EXISTING STORM SEWER AND INTAKE, TYP

0.

0.

0.

0.

0.

2.

11.53%

CLEANUP OF DIRT AND DEBRIS IS REQUIRED.

CONTRACTOR SHALL USE ALL METHODS

NECESSARY TO PREVENT TRACKING OFF-SITE

AT ALL TIMES AND AS REQUIRED BY THE

OWNER. CONTRACTOR SHALL ANTICIPATE

THE USE OF DUST CONTROL MEASURES.

CONTRACTOR TO DETERMINE

PREFERRED LOCATION DURING EACH

PHASE OF CONSTRUCTION, TYP

ANTICIPATED CONTRACTOR STAGING AREA,

COORDINATE FINAL LOCATION WITH OWNER, TYP.

SURFACE APPLIED INTAKE PROTECTION, TYP

CLEANUP OF DIRT AND DEBRIS IS REQUIRED.

CONTRACTOR SHALL USE ALL METHODS

NECESSARY TO PREVENT TRACKING OFF-SITE

AT ALL TIMES AND AS REQUIRED BY THE

OWNER. CONTRACTOR SHALL ANTICIPATE

THE USE OF DUST CONTROL MEASURES.

MAINTAIN STABILIZED CONSTRUCTION

ENTRANCE/EXIT (SUDAS 9040.120). DRESS

WITH STONE AS REQUIRED TO PREVENT

TRACKING OFF-SITE. INSTALL GEOTEXTILE

FILTER FABRIC BELOW STONE.

X

X

X

X

X

X

R

AZO

R

W

IR

E

PCC

PCC

PCC

PC

C

PCC

PCC

PCC

PCC

PCC

PC

C

PC

C

PC

C

PCC

PCC

PCC

GRASS

GRASS

GRASS

GRAVEL

GRASS D

IR

T

GRASS

GRASS

GRASS

GRASS

GRASSGRAVEL

GRASS

E.

N

.F

E.

N

.F

E.N.F.

IMCC

ADMINISTRATION

BUILDING

GROUND ROD

COVERED SEATING AREA

ANTENNA

GROUND ROD

GROUND ROD

GROUND ROD

2" PVC SUMP PUMP

DISCHARGE INTO ADS TILE.

3" PVC SUMP PUMP

DISCHARGE INTO ADS TILE.

3" PVC COMING OUT OF WALL

1" CONDUIT COMING

OUT OF GROUND

FF THRESHOLD = 804.05

(METAL)

FF = 811.25

(TILE)

FF = 803.89

(CONCRETE)

FF = 811.24

(TILE)

GROUND

ROD

STONE

RETAINING WALL

STONE

RETAINING WALL

STONE RETAINING WALL

SPLIT HEAD

GALVANIZED PIPE

ON WALL

GUARD RAIL

STAIRS

CAMERA POLE AND

JUNCTION BOX.

POLE MOUNTED

MOTION SENSOR.

POLE MOUNTED

MOTION SENSOR.

6" S

T

" S

T

15" ST

8" ST

12" ST

" S

T

" S

T

STORM MH

806.64 RIM

799.10 IE 10" VCP (SW)

798.95 IE 12" RCP (W)

798.88 IE 18" RCP (N)

STRUCTURE INACCESSIBLE

UNDER RAZOR WIRE

803.32 IE 4" ADS (SW)

STORM MH

811.92 RIM

STORM INTAKE

801.64 RIM

799.57 IE 4" PVC (S) (PLUGGED WITH ROCK)

799.23 IE 12" VCP (NW)

STORM INTAKE

804.98 RIM

803.48 IE 6" ADS (N)

803.27 BOTTOM

STORM INTAKE

800.31 RIM

798.21 IE 8" DIP (W)

798.16 IE 8" DIP (N)

798.11 IE (E)

STORM MH

811.92 RIM

±804 IE 15" VCP (W)

6" (N)

804.19 BOTTOM

STANDING WATER IN STRUCTURE

803.92 IE 4" PVC (W)

803.90 IE 4" PVC (W)

803.93 IE 4" PVC (W)

SUMP PUMP DISCHARGE

INTO ADS TILE

ENF

6" ADS TILE RUN ON TOP OF

GROUND DIRECTING ROOF

DRAIN DISCHARGE80

4" S

T 4"

S T

X X

X

X X

X

X X

X X

X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X

EXISTING ACCESS ROAD, TYP

EXISTING GRADE CONTOUR, TYP

ADDITIONAL SURFACE

APPLIED INTAKE PROTECTION.

THIS CONTROL TO REMAIN

UNTIL THE SITE HAS BEEN

STABILIZED AND APPROVED

BY THE OWNER'S

REPRESENTATIVE, TYP.

PROPOSED PAVEMENT, TYP

FINISHED GRADE CONTOUR, TYP

STORM SEWER AND INTAKE, TYP

PERFORATED DRAIN TILE, TYP

8" FILTER SOCK ALONG EDGE OF

PAVEMENT. THIS CONTROL TO

REMAIN UNTIL THE SITE HAS BEEN

STABILIZED AND APPROVED BY

THE OWNER'S REPRESENTATIVE.

ONCE REMOVED, 8" FILTER SOCK

TO BE DISCARDED AND

PERMANENT SEEDING, FERTILIZER

AND MULCHING TO BE APPLIED TO

THE BARE SPOT, TYP.

SURFACE APPLIED INTAKE PROTECTION

TO REMAIN UNTIL THE SITE HAS BEEN

STABILIZED AND APPROVED BY THE

OWNER'S REPRESENTATIVE, TYP

EXISTING STORM SEWER AND INTAKE, TYP

5.3 2%

8.22%

6.82%

8.20%

5.

N O

R

TH

G

AT

E D

R

IV

E

IO

W A

C

IT

Y, IO

W A

9.

4.

S H

IV

E-

H

AT

TE

R

Y.

C

O M

A B C D E F HG

A B C D E F HG

Pr in te d:

D R

AW

N

B Y

AP

PR

O

VE

D B

Y

IS

SU

ED

F

O R

IS

SU

E D

AT

E

FI

EL

D B

O O

K

PR

O

JE

C

T N

U M

BE

R

P:

\P ro je ct s\

\2

0\

De liv er ab le s\

Dr aw in gs

\1 _C ivi l\C

1.

dw g

/1

4/

1:

:5

AM

C101

ER

O

SI

O

N A

N D

SE

D

IM

EN

T C

O N

TR

O

L

PL

AN

C M

B

KM

B

BI

D

/1

8/

80 --- C

LI

EN

T

PR

O

JE

C T

N U

M

BE

R : 9

2.

IM

C

C A

D M

IN

B

LD

G

W

AT

ER

M

IT

IG

AT

IO

N

IO

W

A D

EP

AR

M

EN

T O

F

AD

M

IN

IS

TR

AT

IV

E

SE

R

VI

C

ES

C O

R

AL

VI

LL

E, IA

EROSION AND SEDIMENT CONTROL PLAN - PRE-DURING - CONSTRUCTION EROSION AND SEDIMENT CONTROL PLAN - POST - CONSTRUCTION

EROSION AND SEDIMENT CONTROL NOTES

CONTRACTOR STAGING AREA FOR

PORTABLE RESTROOM FACILITIES,

TEMPORARY FUEL TANKS, WASTE

CONTAINERS AND OTHER

HAZARDOUS CHEMICALS. RELOCATE

AS REQUIRED FOR CONSTRUCTION.

PROJECT SITE/DISTURBED AREA

LEGEND

SPILL KIT TO BE INSTALLED AND

RELOCATED AS REQUIRED FOR

CONSTRUCTION

CONCRETE, PAINT, AND GROUT

WASHOUT AREA PER SUDAS

SECT 11,050. CONTRACTOR TO

HAUL OFF WASTE MATERIAL.

SUGGESTED LOCATION.

RELOCATE AS REQUIRED FOR

CONSTRUCTION.

PORTABLE RESTROOM

FACILITY LOCATION

EXISTING/PROPOSED GRADE

DIRECTION OF DRAINAGE

4.0%

8" FILTER SOCK (SUDAS 9040.102).

SHALL HAVE 'J' HOOKS AT MAXIMUM

25' INCREMENTS.

1. EROSION/SEDIMENT CONTROL MEASURES SHOULD BE

INSTALLED BEFORE EARTH DISTURBING ACTIVITIES BEGIN AND

ARE REQUIRED REGARDLESS OF THE TIME OF YEAR. THIS

PLAN MUST BE IMPLEMENTED DURING WINTER MONTHS AS

WELL.

2. IT IS THE CONTRACTOR'S RESPONSIBILITY TO CONTROL

EROSION/SEDIMENT ON THE SITE AT ALL TIMES. THE CONTROL

MEASURES SHOWN ON THE PLAN ARE A MINIMUM. THE

CONTRACTOR SHALL PROVIDE ADDITIONAL

EROSION/SEDIMENT CONTROL MEASURES AS NECESSARY TO

FULFILL THIS REQUIREMENT. CONTRACTOR TO INCORPORATE

ALL TEMPORARY STABILIZING AND PERMANENT

EROSION/SEDIMENT CONTROL FEATURES AT THE EARLIEST

TIME PRACTICABLE.

3. THE CONTRACTOR IS REQUIRED TO USE STABILIZATION

CONTROLS ON ALL DISTURBED AREAS OF THE SITE

REGARDLESS OF THE TIME PERIOD BEFORE THEY WILL BE

DISTURBED AGAIN.

4. THE CONTRACTOR SHALL RESTORE DISTURBED AREAS AS

SOON AS WORK IS COMPLETED AS INDICATED ON THE PLANS.

5. THE CONTRACTOR SHALL USE CONTROL MEASURES AS

REQUIRED TO KEEP SOILS FROM LEAVING THE SITE.

6. CONTRACTOR SHALL IMPLEMENT SITE SPECIFIC BEST

MANAGEMENT PRACTICES (BMPS) AS SHOWN AND REQUIRED

BY THE EROSION AND SEDIMENT CONTROL PLAN. ADDITIONAL

BEST MANAGEMENT PRACTICES SHALL BE IMPLEMENTED BY

THE CONTRACTOR AS DICTATED BY SITE CONDITIONS OR THE

PROJECT GOVERNING AUTHORITIES AT NO ADDITIONAL COST

TO THE OWNER THROUGHOUT ALL PHASES OF

CONSTRUCTION.

7. IF AFTER REPEATED FAILURE ON THE PART OF THE

CONTRACTOR TO PROPERLY CONTROL SOIL EROSION,

SEDIMENT AND/OR POLLUTION FROM THE PROJECT SITE, THE

GOVERNING AUTHORITIES RESERVE THE RIGHT TO EFFECT

NECESSARY CORRECTIVE MEASURES AND CHARGE ANY

COSTS TO THE CONTRACTOR.

8. ALL BMPS AND CONTROLS SHALL CONFORM TO THE

APPLICABLE FEDERAL OR STATE REQUIREMENTS, STANDARDS,

AND SPECIFICATIONS OR MANUAL OF PRACTICE.

9. IN THE EVENT THAT SOILS LEAVE THE SITE, CLEANUP OF ALL

SURROUNDING ROADS, DRIVES, AND PARKING LOTS SHALL BE

PERFORMED ON A DAILY BASIS AT A MINIMUM AND UPON

REQUEST BY OWNER'S REPRESENTATIVE AT NO ADDITIONAL

COST. PAVEMENT IS TO BE SCRAPED OF DEBRIS AND MUD AND

BROOMED CLEAN. MUD TRACKS ARE TO BE REMOVED AS THEY

ARE CREATED.

10. IF DURING CONSTRUCTION OPERATIONS ANY LOOSE

MATERIALS ARE DEPOSITED IN THE FLOW LINE OF GUTTERS,

DRAINAGE STRUCTURES, OR DITCHES SUCH THAT THE

NATURAL FLOW LINE OF WATER IS OBSTRUCTED, THIS LOOSE

MATERIAL SHALL BE REMOVED.

11. ALL SEDIMENT SHALL BE PREVENTED FROM ENTERING ANY

EXISTING STORM DRAINAGE SYSTEMS BY THE USE OF INLET

PROTECTION OR OTHER APPROVED FUNCTIONAL METHODS.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING

SEDIMENT RESULTING FROM CONSTRUCTION ACTIVITIES

ASSOCIATED WITH THIS PROJECT.

12. CONSTRUCTION ACCESS POINTS TO THE SITE SHALL BE

PROTECTED IN SUCH A WAY AS TO PREVENT TRACKING OF

MUD OR SOIL ONTO PUBLIC THOROUGHFARES. ALL SEDIMENT

SPILLED, DROPPED, WASHED OR TRACKED ONTO PUBLIC

RIGHTS-OF-WAY MUST BE REMOVED IMMEDIATELY BY THE

CONTRACTOR.

13. CLEAN SILT FROM FILTER SOCKS ON A REGULAR BASIS AS PER

THE STANDARD SPECIFICATIONS. FILTER SOCKS MUST BE

CLEANED OUT WHEN THEY ARE 33% FULL.

14. CONTRACTOR TO LOCATE/ RELOCATE FILTER SOCKS AS

NECESSARY THROUGHOUT THE PROJECT TO CONTROL

EROSION/SEDIMENT. FILTER SOCK INSTALLATION IS TO

FOLLOW SUDAS 9040.102.

15. REMOVE ALL TEMPORARY EROSION/SEDIMENT CONTROLS,

NOT CALLED OUT TO REMAIN, AFTER SITE HAS BEEN

STABILIZED AND APPROVED BY THE OWNER'S

REPRESENTATIVE.

16. WHERE WATER IS PUMPED FROM EXCAVATIONS ON SITE,

PROVISIONS SHALL BE MADE TO REMOVE SEDIMENT FROM

THE WATER BEFORE IT IS RELEASED. REFER TO SUDAS 3010

SECT 3.04 FOR DEWATERING GUIDANCE.

17. WHERE WATER IS RELEASED FROM A DEWATERING SYSTEM,

PRECAUTIONS SHALL BE TAKEN TO ENSURE THAT EROSION

GULLIES DO NOT FORM. WATER MUST BE FILTERED THROUGH

AN APPROPRIATE FILTER DEVICE BEFORE DISCHARGING.

18. THE CONTRACTOR IS REQUIRED TO INSTALL STABILIZATION

CONTROLS ON ALL DISTURBED AREAS OF THE SITE

IMMEDIATELY FOLLOWING COMPLETION OF GRADING

ACTIVITIES. REFER TO SUDAS 9040 FOR REQUIRED

STABILIZATION CONTROLS NOT SHOWN ON THIS PLAN.

19. ALL EXISTING AND PROPOSED STORM INTAKES, WITHIN AND

ADJACENT TO THE PROJECT AREA, MUST BE PROTECTED

THROUGHOUT THE DURATION OF THE PROJECT AS IDENTIFIED

ON THE DRAWINGS. INTAKES SHALL BE FREE OF DIRT, DEBRIS

AND ROCK AT COMPLETION OF WORK.

20. SANITARY WASTE DISPOSAL: ALL LOCATIONS OF PORTABLE

RESTROOM FACILITIES MUST BE IDENTIFIED ON THE PLAN. IN

THE EVENT THAT PORTABLE RESTROOM FACILITIES ARE USED

ON-SITE, THE CONTRACTOR IS REQUIRED TO INSTALL AN 8"

FILTER SOCK AROUND THE FACILITY TO MINIMIZE THE RADIUS

OF THE AFFECTED ZONE IN THE EVENT OF A SPILL. WASTES

SHALL BE COLLECTED AND DISPOSED OF IN COMPLETE

COMPLIANCE WITH LOCAL, STATE AND FEDERAL

REGULATIONS. PORTABLE RESTROOM FACILITIES MUST NOT

BE LOCATED NEAR DRAINAGE WAYS. RELOCATE AS REQUIRED

FOR CONSTRUCTION.

21. POLLUTION AND SPILL PREVENTION PLANNING: POTENTIALLY

HAZARDOUS MATERIALS ON THE CONSTRUCTION SITE

INCLUDE FUEL, LUBRICANTS, CURING COMPOUNDS,

FERTILIZERS, GREASE AND CLEANING SOLVENTS. THE

CONTRACTOR STAGING AREA FOR PORTABLE RESTROOM

FACILITIES, TEMPORARY FUEL TANKS, WASTE CONTAINERS

AND OTHER HAZARDOUS CHEMICALS MUST BE PROTECTED BY

AN 8" FILTER SOCK AT ALL TIMES. ALL REASONABLE

PRECAUTIONS WILL BE TAKEN TO PREVENT SPILLS. ANY

SPILLED MATERIAL WILL IMMEDIATELY BE DIRECTED AWAY

FROM STORMWATER INTAKES, DETENTION BASINS, OR

DRAINAGE WAYS. SPILLED MATERIALS WILL BE CLEANED AND,

IF NECESSARY, SOIL REMEDIATION PRACTICES WILL BE USED.

A RECORD OF SPILLS WILL BE MAINTAINED BY THE PRIME

CONTRACTOR. RELOCATE AS REQUIRED FOR CONSTRUCTION.

22. CONCRETE, PAINT AND GROUT WASHOUT AREA: THE

WASHOUT AREA SHOULD BE AN APPROVED CONCRETE

WASHOUT CONTAINER, COLLECTION BAG, OR WASHOUT BOX

PER SUDAS 11,050. PROTECT WITH AN EROSION CONTROL

DEVICE (IF USING FILTER SOCKS, STACK TWO (2) TALL).

CONTRACTOR TO HAUL OFF ALL WASTE MATERIAL. ALL

LOCATIONS OF CONCRETE, PAINT AND GROUT WASHOUT

AREAS MUST BE PROVIDED BY THE CONTRACTOR AND

IDENTIFIED ON THE PLAN (RELOCATE AS REQUIRED FOR

CONSTRUCTION). THE CONTRACTOR IS REQUIRED TO INSTALL

A SIGN THAT DESIGNATES THE WASHOUT AREA.

23. CONCRETE SLURRY AND DUST FROM SAWCUTTING ACTIVITIES

IS PROHIBITED FROM ENTERING THE STORM SEWER SYSTEM.

ALL STORM INTAKES LOCATED NEAR SAWCUTTING ACTIVITIES

ARE REQUIRED TO BE PROTECTED. SAWCUT SLURRY AND

DUST MUST BE CONTAINED, CLEANED UP, AND DISPOSED OF

OFF-SITE.

24. SPILL KIT: THE LOCATION OF THE SPILL KIT MUST BE

IDENTIFIED ON THE PLAN. THE SPILL KIT SHALL CONTAIN, BUT

NOT BE LIMITED TO THE FOLLOWING ITEMS: A GARBAGE CAN,

GLOVES, SAFETY GOGGLES, BROOM AND DUST PAN AND OIL

ABSORBENT CLAY CHIPS OR PADS. THE SPILL KIT SHALL BE

RESTOCKED AS SUPPLIES ARE USED. THE CONTRACTOR

SHALL INSTALL A SIGN THAT DESIGNATES THE SPILL KIT.

RELOCATE AS REQUIRED FOR CONSTRUCTION. THE SPILL KIT

SHOULD BE DESIGNED TO DEAL WITH ANY HAZARDOUS

MATERIALS ON-SITE.

25. DUST CONTROL: THE CONTRACTOR SHALL IMPLEMENT DUST

CONTROL MEASURES WHERE DUST IS GENERATED. FREQUENT

WATERING OF THE SITE, SPRINKLED, VEGETATIVE COVER,

MULCH, WINDBREAKS, TILLAGE, STONE AND SPRAY-ON

CHEMICAL SOIL TREATMENTS (PALLIATIVES) ARE POSSIBLE

DUST CONTROL MEASURES. IF THE DUST CONTROL IS NOT

ACCEPTABLE IT SHALL BE CHANGED AS DIRECTED BY THE

OWNER'S REPRESENTATIVE.

26. STOCKPILED MATERIALS: CONTRACTOR TO IDENTIFY ALL

LOCATIONS OF STOCKPILED MATERIALS ON THE STORMWATER

POLLUTION PREVENTION PLAN. CONTRACTOR SHALL PROVIDE

ALL EROSION/SEDIMENT CONTROLS AS REQUIRED TO CONTAIN

MATERIALS ON-SITE. AT A MINIMUM, THE CONTRACTOR IS

REQUIRED TO PROVIDE SILT FENCE/FILTER SOCKS AROUND

STOCKPILED SOILS BEFORE STOCKPILE IS RE-SPREAD.

27. THE CONTRACTOR SHALL AMEND THE EROSION AND

SEDIMENT CONTROL PLAN WHENEVER THERE IS A CHANGE IN

DESIGN, CONSTRUCTION, OPERATION OR MAINTENANCE OF A

STORMWATER BMP.

SEQUENCING AND PHASING NOTES

PROPOSED PAVEMENT. SEE SHEET

C601 FOR MORE INFORMATION.

SURFACE APPLIED INTAKE

PROTECTION (NOTE: FILTER

SOCKS ARE NOT AN ALLOWABLE

INTAKE PROTECTION DEVICE).

SEE SUDAS 9040 SECT 2.19.

1. THIS PROJECT MAY BE CONSTRUCTED OVER

SEVERAL PHASES. EROSION/SEDIMENT CONTROL

DEVICES IDENTIFIED ON THE PLAN WILL BE

IMPLEMENTED ON A PER PHASE BASIS.

2. INSTALL INTAKE PROTECTION AND DOWN SLOPE

AND SIDE SLOPE PERIMETER CONTROLS BEFORE

LAND DISTURBING ACTIVITY OCCURS.

3. STRIP TOPSOIL TO A DEPTH OF 6" AND STOCKPILE.

DO NOT MIX TOPSOIL WITH SUBSOIL.

4. GRADE SUBSOIL TO CONFORM WITH THE GRADES,

CONTOURS AND LEVELS IDENTIFIED ON THE

DRAWINGS.

5. ROUGH GRADE FOR ROADWAY, WALKS, CURBS,

GUTTERS, AND LANDSCAPED AREAS.

6. COVER OR STABILIZE DISTURBED AREAS AS SOON

AS POSSIBLE.

7. SCARIFY AREAS TO RECEIVE TOPSOIL TO A DEPTH

OF 4". REMOVE ALL STONES, WOOD AND OTHER

DEBRIS LARGER THAN 1" FROM AREAS TO RECEIVE

TOPSOIL. DO NOT COMPACT TOPSOIL.

8. REFER TO SHEET C601 FOR SITE RESTORATION

INFORMATION.

9. UPON COMPLETION OF EACH PHASE AND APPROVAL

BY THE OWNER'S REPRESENTATIVE,

EROSION/SEDIMENT CONTROL DEVICES MAY BE

REMOVED/RELOCATED.

C O

R

AL

R

ID

G E

AV

E

IOWA MEDICAL AND

CLASSIFICATION

CENTER

UNIVERSITY

PKWY

CONTRACTOR ACCESS ROUTE.

MAINTAIN ACCESS TO EASTERN

LOADING DOCK DOOR DURING

CONSTRUCTION, TYP.

MATERIALS AND EQUIPMENT SHALL

BE SECURED AT THE END OF EACH

DAY. REFER TO OWNER'S PROJECT

REQUIREMENTS FOR SECURITY

STANDARDS, TYP.

CONTRACTOR WORK AREA.

MAINTAIN ACCESS TO

EGRESS DOOR AND FIRE

DEPARTMENT CONNECTION.

SECURED ACCESS GATE.

COORDINATE WITH

OWNER FOR ACCESS.

SITE ACCESS

GATE, TYP.

COORDINATE WITH OWNER 1-WEEK

PRIOR TO LOADING DOCK CLOSURE

SO OWNER CAN REVISE DELIVERY

SCHEDULE. CONTRACTOR MAY BEGIN

WORK AFTER THE DELIVERY IS

COMPLETED ON MONDAY MORNING

AND LOADING DOCK MUST BE OPENED

PRIOR TO THE FOLLOWING MONDAY.

COORDINATE WITH OWNER FOR

REMOVAL OF PORTION OF EXTERIOR

PERIMETER FENCE AND INSTALLATION

OF SECURE ACCESS GATE TO INSTALL

BARRIER CURB. REMOVAL OF FENCE

AND INSTALLATION OF SECURE GATE

TO BE BY OWNER. SEE PHOTO 1/C201.

5'-6" WIDE X 8'-0" TALL ACCESS GATE FOR

WORK IN BETWEEN PERIMETER FENCES.

COORDINATE WITH OWNER FOR ACCESS

THROUGH SECURE GATES, TYP.

CONSTRUCTION AREA

ROADWAY VEHICLE TRAFFIC FLOW ARROW

PEDESTRIAN ROUTE

CHAIN LINK CONSTRUCTION FENCE

CONTRACTOR ACCESS ROUTE

N O

R

TH

G

AT

E D

R

IV

E

IO

W A

C

IT

Y, IO

W A

9.

4.

S H

IV

E-

H

AT

TE

R

Y.

C

O M

A B C D E F HG

A B C D E F HG

Pr in te d:

D R

AW

N

B Y

AP

PR

O

VE

D B

Y

IS

SU

ED

F

O R

IS

SU

E D

AT

E

FI

EL

D B

O O

K

PR

O

JE

C

T N

U M

BE

R

P:

\P ro je ct s\

\2

0\

De liv er ab le s\

Dr aw in gs

\1 _C ivi l\C

1.

dw g

/1

4/

1:

:0

AM

C201

SI

TE

A C

C

ES

S

PL

AN

AS

R

KM

B

BI

D

/1

8/

80 --- C

LI

EN

T

PR

O

JE

C T

N U

M

BE

R : 9

2.

IM

C

C A

D M

IN

B

LD

G

W

AT

ER

M

IT

IG

AT

IO

N

IO

W

A D

EP

AR

M

EN

T O

F

AD

M

IN

IS

TR

AT

IV

E

SE

R

VI

C

ES

C O

R

AL

VI

LL

E, IA

SITE ACCESS PLAN

PHASING/TRAFFIC CONTROL NOTES

1. PHASING DRAWINGS ARE PROVIDED TO DESCRIBE THE REQUIRED SCHEDULING OF THE WORK IN THIS PROJECT TO

ACCOMMODATE VEHICLE AND PEDESTRIAN ACCESS ON SITE.

2. SITE PHASING DRAWINGS DO NOT SHOW THE FULL EXTENT OF WORK IN EACH PHASE, BUT RATHER A GENERAL WORK AREA

AND SITE ACCESS REQUIREMENTS. REFER TO OTHER DRAWINGS FOR FULL SCOPE OF WORK.

3. CONTRACTOR MAY SUBMIT ALTERNATE TRAFFIC CONTROL AND PHASING OPTIONS FOR OWNER APPROVAL PRIOR TO

CONSTRUCTION.

4. NO CONTRACTOR VEHICLE PARKING WILL BE ALLOWED ON SIDEWALKS, DRIVES, GRASS, OR STREETS OUTSIDE OF CONSTRUCTION LIMITS. VEHICLES PARKED OUTSIDE CONSTRUCTION LIMITS WILL BE TOWED AT THE EXPENSE OF THE VEHICLE OWNER. SEE OWNER'S PROJECT REQUIREMENTS FOR ADDITIONAL INFORMATION ON PARKING AND SITE ACCESS.

5. FENCING SHOWN ON THE PLANS IS A MINIMUM. CONTRACTOR IS RESPONSIBLE FOR PROVIDING FENCING TO MAINTAIN A SECURE SITE AT ALL TIMES, AND TO ACCOMMODATE ACTUAL WORK LIMITS AND PHASING LIMITS. PROVIDE CONSTRUCTION

FENCE FOR ALL WORK EXTENDING BEYOND MAIN SITE FENCE.

6. REPAIR OR REPLACE DAMAGED CONSTRUCTION FENCE ON THE SAME DAY AS IT IS DAMAGED, MAINTAINING A SECURE SITE AT

ALL TIMES. REPAIR OR PATCH ANY DISTURBED AREAS DUE TO FENCING INSTALLATION.

7. PROVIDE PERMANENT OR TEMPORARY PEDESTRIAN DETOUR ROUTES TO MEET SITE ACCESS AND CURRENT ADA STANDARDS FOR ACCESSIBLE DESIGN. COORDINATE LOCATIONS WITH THE OWNER'S REPRESENTATIVE. PLAN AND COORDINATE

TEMPORARY WALKS FOR SITE ACCESS WITH CONSTRUCTION ACTIVITIES.

8. NO ROAD OR LANE CLOSURES PERMITTED FOR STAGING OF DELIVERY TRUCKS.

9. FURNISH, ERECT, AND MAINTAIN ALL SIGNAGE DURING THE PROJECT. REMOVE ALL DEVICES AT THE END OF THE PROJECT.

10. PROVIDE AND INSTALL TEMPORARY CONSTRUCTION PROJECT SIGNAGE AND MAINTAIN SIGNAGE THROUGHOUT CONSTRUCTION. SIGNS MAY BE INSTALLED ON THE PROJECT FENCING OR SUPPORTED INDEPENDENTLY DEPENDING ON SITE

CONDITIONS.

11. ALL VEHICULAR AND PEDESTRIAN CONTROL SIGNAGE SHALL CONFORM TO THE STANDARDS IN THE MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES (MUTCD) LATEST EDITION. SIDEWALK CLOSURES AND DETOURS SHALL BE IOWA DOT TYPE II BARRICADES AND SHALL BE WHITE WITH BLACK LETTERING, EXCEPT THE S1-1 AND R1-6A SIGNS. TRAFFIC CONTROL AND TRAFFIC DETOUR SIGNAGE SHALL BE ORANGE WITH BLACK LETTERING. ALL SIGNAGE SHOULD BE COORDINATED WITH ALL

OTHER TRAFFIC CONTROL PLANS IN THE AREA.

12. RESTORE ACCESS TO SIDEWALKS AND BUILDING ENTRANCES AS SOON AS POSSIBLE.

BARRIER CURB WORK AREA1

LEGEND

OWNER TO REMOVE PORTION OF EXTERIOR

PERIMETER FENCE AND INSTALL 7'-6" WIDE X 7'-10"

TALL ACCESS GATE. CONTRACTOR TO COORDINATE

WITH OWNER FOR TIMING OF GATE INSTALLATION

FOR ACCESS TO INSTALL BARRIER CURB.

X

X X

X X

X

R

AZO

R

W

IR

E

R

AZ

O R

W

IR

E

PCC

PCC

PCC

PC

C

PCC

PCC

PCC

PCC

PCC

PC

C

PC

C

PC

C

PCC

PCC

PCC

GRASS

GRASS

GRASS

GRAVEL

GRASS D

IR

T

GRASS

GRASS

GRASS

GRASS

GRASS

GRAVEL

GRAVEL

G R

AV

EL

GRAVEL

GRASS

E.

N

.F

E.

N

.F

E.N.F.

IMCC

ADMINISTRATION

BUILDING

GROUND ROD

COVERED SEATING AREA

ANTENNA

GROUND ROD

SANITARY MH

809.52 RIM

800.68 IE ±8" VCP (W)

799.22 IE ±10" (N)

799.10 IE ±10" (S)

GROUND ROD

GROUND ROD

2" PVC SUMP PUMP

DISCHARGE INTO ADS TILE.

3" PVC SUMP PUMP

DISCHARGE INTO ADS TILE.

3" PVC COMING OUT OF WALL

1" CONDUIT COMING

OUT OF GROUND

FF THRESHOLD = 804.05

(METAL)

FF = 811.25

(TILE)

FF = 803.89

(CONCRETE)

FF = 811.24

(TILE)

GROUND

ROD

STONE

RETAINING WALL

STONE

RETAINING WALL

STONE RETAINING WALL

SPLIT HEAD

GALVANIZED PIPE

ON WALL

GUARD RAIL

STAIRS

CAMERA POLE AND

JUNCTION BOX.

POLE MOUNTED

MOTION SENSOR.

POLE MOUNTED

MOTION SENSOR.

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X

6" S

T

" S

T

15" ST

8" ST

8" S

T

12" ST

" S

T

" S

T

R

AZ

O R

W

IR

E

R

AZ

O R

W

IR

E R

AZ

O

R W

IR

E

PCC

R

AZ

O R

W

IR

E

R

AZ

O R

W

IR

E

STORM INTAKE

800.09 RIM

797.94 IE 8" DIP (E)

797.79 IE (N)

STORM INTAKE

808.91 RIM

802.40 IE 12" RCP (S)

802.31 IE 12" RCP (N)

6" ADS TILE RUN ON TOP OF

GROUND DIRECTING ROOF

DRAIN DISCHARGE

6" ADS TILE

RUN ON TOP

OF GROUND

DIRECTING

ROOF DRAIN

DISCHARGE

STORM MH

806.64 RIM

799.10 IE 10" VCP (SW)

798.95 IE 12" RCP (W)

798.88 IE 18" RCP (N)

STRUCTURE INACCESSIBLE

UNDER RAZOR WIRE

803.32 IE 4" ADS (SW)

STORM MH

811.92 RIM

STORM INTAKE

801.64 RIM

799.57 IE 4" PVC (S) (PLUGGED WITH ROCK)

799.23 IE 12" VCP (NW)

STORM INTAKE

804.98 RIM

803.48 IE 6" ADS (N)

803.27 BOTTOM

STORM INTAKE

800.31 RIM

798.21 IE 8" DIP (W)

798.16 IE 8" DIP (N)

798.11 IE (E)

STORM MH

811.92 RIM

±804 IE 15" VCP (W)

6" (N)

804.19 BOTTOM

STANDING WATER IN STRUCTURE

803.92 IE 4" PVC (W)

803.90 IE 4" PVC (W)

803.93 IE 4" PVC (W)

SUMP PUMP DISCHARGE

INTO ADS TILE

ENF

6" ADS TILE RUN ON TOP OF

GROUND DIRECTING ROOF

DRAIN DISCHARGE

.2

12'

REMOVE PAVEMENT.

REMOVE STORM INTAKE.

CONTRACTOR TO REMOVE AND

DISPOSE OF GROUND LEVEL RAZOR

WIRE STACKED IN 3-2-1 CONFIGURATION

AS REQUIRED TO INSTALL STORM

SEWER, TYP. SEE PHOTOS 1 AND 2/C301.

REMOVE PAVEMENT AS

REQUIRED TO REMOVE

EXISTING STORM

INTAKE AND INSTALL

NEW STORM SEWER.

REMOVE STORM INTAKE.

EXCAVATE AND EXPOSE NORTHERN

WALL FACE AND ABANDONED STORM

SEWER ON NORTH END OF TUNNEL.

FILL STORM SEWER TO THE NORTH

AND SOUTH WITH LOW STRENGTH

FLOWABLE FILL AND CAP, TYP.

REMOVE STORM SEWER AS

REQUIRED FOR NEW FOUNDATION

DRAIN TILE CONNECTION, TYP.

REMOVE ABANDONED

CONCRETE FENCE

FOOTING.

REMOVE ABANDONED

CONCRETE FENCE FOOTING

AS REQUIRED FOR

EXPLORATORY EXCAVATION

TO LOCATE STORM SEWER

AND INSTALL LIQUID

APPLIED WATERPROOFING

ON BUILDING FACE. REMOVE DAMAGED PCC CONCRETE.

PROTECT ADJACENT FENCE POSTS.

REMOVE STORM SEWER. REMOVE AND STORE ABOVE

GRADE DRAIN TILE FOR

REINSTALLATION, TYP.

REMOVE AND STORE ABOVE

GRADE DRAIN TILE FOR

REINSTALLATION, TYP.

2'

STRIP, SALVAGE, AND STORE

GRAVEL SURFACING AS

REQUIRED FOR STORM SEWER

INSTALLATION, TYP.

REMOVE PCC PAVEMENT

REMOVE SURFACE FEATURE

REMOVE AND DISPOSE OF UTILITY

PRESSURE GROUT AND ABANDON UTILITY

LEGEND

STRIP, SALVAGE, AND STORE GRAVEL

N O

R

TH

G

AT

E D

R

IV

E

IO

W A

C

IT

Y, IO

W A

9.

4.

S H

IV

E-

H

AT

TE

R

Y.

C

O M

A B C D E F HG

A B C D E F HG

Pr in te d:

D R

AW

N

B Y

AP

PR

O

VE

D B

Y

IS

SU

ED

F

O R

IS

SU

E D

AT

E

FI

EL

D B

O O

K

PR

O

JE

C

T N

U M

BE

R

P:

\P ro je ct s\

\2

0\

De liv er ab le s\

Dr aw in gs

\1 _C ivi l\C

1.

dw g

/1

4/

1:

:0

AM

C301

SI

TE

PR

EP

AR

AT

IO

N

AN

D

D

EM

O

LI

TI

O

N

PL

AN

AS

R

KM

B

BI

D

/1

8/

80 --- C

LI

EN

T

PR

O

JE

C T

N U

M

BE

R : 9

2.

IM

C

C A

D M

IN

B

LD

G

W

AT

ER

M

IT

IG

AT

IO

N

IO

W

A D

EP

AR

M

EN

T O

F

AD

M

IN

IS

TR

AT

IV

E

SE

R

VI

C

ES

C O

R

AL

VI

LL

E, IA

SITE PREPARATION AND DEMOLITION PLAN

SITE PREPARATION AND DEMOLITION NOTES

1. CONSTRUCTION FENCE IS REQUIRED AROUND CONSTRUCTION AREAS AND ALL UNATTENDED OPEN EXCAVATIONS. CONSTRUCT FENCE AS SHOWN ON THE

PLAN AND MAINTAIN IN AN UPRIGHT POSITION AT ALL TIMES. PROVIDE ORANGE CONSTRUCTION FENCE TO SECURE ALL WORK OUTSIDE OF THE CHAIN LINK

FENCE. SEE DETAIL 1/C501.

2. USE CAUTION WHILE INSTALLING FENCE NOT TO DAMAGE UNDERGROUND UTILITIES.

3. FENCING, BARRICADES AND SIGNAGE MUST BE USED TO DIVERT TRAFFIC AROUND THE CONSTRUCTION ACTIVITY.

4. SEE SITE ACCESS PLAN FOR ADDITIONAL CONSTRUCTION FENCE LOCATIONS.

5. KEEP ALL DRIVES OPEN AT ALL TIMES EXCEPT FOR THOSE INDICATED. PERFORM THE WORK IN A MANNER THAT WILL MAINTAIN UNINTERRUPTED VEHICULAR

AND PEDESTRIAN TRAFFIC. MAINTAIN ROADS FREE OF RUTS.

6. MAINTAIN POSITIVE DRAINAGE ON THE SITE THROUGHOUT THE DURATION OF THE PROJECT.

7. INSTALL EROSION CONTROL MEASURES ON SITE PRIOR TO PERFORMING SOIL DISTURBING ACTIVITIES.

8. THIS PROJECT DISTURBS LESS THAN ONE ACRE AND DOES NOT REQUIRE A SWPPP. HOWEVER, THE CONTRACTOR IS STILL REQUIRED TO CONTROL SEDIMENT

AND PREVENT IT FROM LEAVING THE SITE OR ENTERING DRAINAGE SYSTEMS.

9. CONTACT THE OWNER IMMEDIATELY AND SUSPEND WORK IF SUSPECT CONTAMINATED SOIL IS ENCOUNTERED.

10. CONTACT THE OWNER'S REPRESENTATIVE TO COORDINATE ANY TREE PRUNING REQUIRED FOR WORK. ALL PRUNING OF TREES SHOWN TO REMAIN SHALL BE

COMPLETED BY OWNER. USE CAUTION NOT TO DAMAGE TREES NOT SHOWN TO BE REMOVED.

11. STRIP TOPSOIL WITHIN DISTURBED AREA. ALL EXISTING TOPSOIL THAT IS ACCEPTABLE TO THE OWNER MAY BE REUSED. ALL OTHER TOPSOIL SHALL BE

DISPOSED OF AT OWNER'S ON-SITE DUMP SITE.

12. DISPOSE OF ALL EXCESS EXCAVATED MATERIAL THAT WILL NOT BE USED ON SITE AT OWNER'S ON-SITE DUMP SITE OR STOCKPILED OFF SITE AT LOCATION(S)

SECURED BY THE CONTRACTOR.

13. IMMEDIATELY PROVIDE A TEMPORARY SPLICE IN THE EVENT THAT LIGHTING CIRCUITS ARE DISRUPTED INTENTIONALLY OR UNINTENTIONALLY TO REESTABLISH THE CIRCUIT. CONTACT THE OWNER'S REPRESENTATIVE PRIOR TO MAKING ANY PERMANENT ELECTRICAL CONNECTIONS. PROVIDE PERMANENT

CONNECTIONS AT NO ADDITIONAL COST TO THE OWNER.

14. REMOVE EXISTING PAVEMENT IN FULL PANELS OR AS NOTED ON DRAWINGS. DOUBLE SAW CUTTING SHALL BE AT THE CONTRACTOR'S DISCRETION. IF THE EDGES OF EXISTING PANELS ARE DAMAGED DURING CONSTRUCTION, REPLACE THOSE PANELS AT NO ADDITIONAL COST TO THE OWNER.

15. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE THE ACTUAL PAVEMENT REMOVAL LIMITS AND ACCOUNT FOR THOSE IN THE BID PRICE. NO ADDITIONAL COMPENSATION WILL BE GIVEN FOR PAVEMENT REMOVAL IN ADDITION TO WHAT IS SHOWN IN THE DRAWINGS. THE LIMITS OF ROADWAY AND

SIDEWALK REMOVAL SHOWN ARE A MINIMUM.

16. REPLACE AT NO COST TO THE OWNER ALL DAMAGED STREET SIGNS, PAVEMENT MARKINGS, SIDEWALK LAMPS, SIDEWALKS, STEPS, LANDSCAPE STRUCTURES, CURB AND GUTTER, STREETS, DRIVES AND ALL OTHER SURFACE STRUCTURES NOT SCHEDULED TO BE REMOVED DURING THE COURSE OF THE WORK.

17. REPLACE ANY PROPERTY MONUMENTS REMOVED OR DESTROYED BY CONSTRUCTION. MONUMENTS SHALL BE SET BY A LAND SURVEYOR REGISTERED TO

PRACTICE IN THE STATE OF IOWA.

18. WHERE A SECTION OF PAVEMENT, CURB AND GUTTER, OR SIDEWALK IS CUT OR OTHERWISE DAMAGED BY THE CONTRACTOR, REMOVE AND REPLACE THE ENTIRE SECTION AT NO COST TO THE OWNER. REMOVE PAVEMENT, CURBS, GUTTERS, AND SIDEWALKS TO THE NEAREST JOINT A MINIMUM OF TWO FEET BEYOND THE EDGE OF ALL EXCAVATIONS. DOCUMENT (OR PHOTO) ALL CRACKED PCC PAVEMENT OR DAMAGED ASPHALT PAVEMENT PRIOR TO CONSTRUCTION. IF NEW CRACKS IN PCC PAVEMENT DEVELOP OR ASPHALT PAVEMENT IS DAMAGED DUE TO CONSTRUCTION TRAFFIC (EXTENDS BEYOND

CONSTRUCTION LIMITS), REPLACE DAMAGED AREA AT NO ADDITIONAL COST TO THE OWNER.

19. REMOVE AND REPLACE ALL LANDSCAPING INCLUDING TREES, SHRUBS, BUSHES AND GRASS OR TURF NOT CALLED OUT TO BE REMOVED ON THE DRAWINGS WHERE DAMAGED DURING CONSTRUCTION AT NO COST TO THE OWNER. WHERE TREES, BUSHES AND SHRUBS CANNOT BE OR ARE NOT PROTECTED, OR ARE OTHERWISE DESTROYED OR DAMAGED BY CONTRACTOR, REPLACE THE TREES, BUSHES AND SHRUBS WITH NEW PLANTS OF THE SAME VARIETY AND SIZE AS THE PLANT DAMAGED OR DESTROYED. RESTORE GRASS OR TURF WHERE DESTROYED OR DAMAGED DURING CONSTRUCTION, TO THE CONDITION THAT

EXISTED PRIOR TO CONSTRUCTION.

20. TREAT THE ON SITE SOILS AND PROVIDE ROCK SURFACING AS NEEDED TO MAINTAIN A SUITABLE WORKING SURFACE DURING CONSTRUCTION.

UTILITY DEMOLITION NOTES

1. CAREFULLY COORDINATE ALL UTILITY DEMOLITION WITH PHASING REQUIREMENTS OF THE PROJECT.

2. PLUG ALL PREVIOUSLY ABANDONED UTILITY LINES DISCOVERED DURING CONSTRUCTION THAT ARE CUT DURING EXCAVATION WITH 3' OF CONCRETE AND WITNESSED BY OWNER OR OWNER'S THIRD PARTY INSPECTOR. VERIFY WITH OWNER THAT LINES ARE ABANDONED PRIOR TO PLUGGING.

3. PRESSURE GROUT AND CAP ALL UTILITIES TO BE ABANDONED IN PLACE.

4. CONTACT THE OWNER OF EACH UTILITY PRIOR TO DEMOLITION OR ABANDONMENT TO VERIFY THAT UTILITY HAS BEEN ABANDONED.

5. DISPOSE OF ALL DEMOLITION ITEMS SHOWN TO BE REMOVED AND NOT RETAINED BY THE OWNER OFF-SITE BY IN ACCORDANCE WITH ALL APPLICABLE STATE

AND LOCAL LAWS AND REGULATIONS.

COILED RAZOR WIRE REMOVAL (SOUTH)1

CONTRACTOR TO REMOVE AND

DISPOSE OF GROUND LEVEL RAZOR

WIRE STACKED IN 3-2-1 CONFIGURATION

AS REQUIRED TO INSTALL STORM

SEWER, TYP. SEE PHOTOS 1 AND 2/C301.

PROTECT CAMERA POLE AND

JUNCTION BOX DURING STORM

SEWER INSTALLATION.

PROTECT POLE MOUNTED

MOTION SENSOR DURING

STORM SEWER INSTALLATION.

COILED RAZOR WIRE REMOVAL (NORTH)2

CONTRACTOR TO REMOVE AND

DISPOSE OF GROUND LEVEL RAZOR

WIRE STACKED IN 3-2-1 CONFIGURATION

AS REQUIRED TO INSTALL STORM

SEWER, TYP. SEE PHOTOS 1 AND 2/C301.

R

AZO

R

W

IR

E

PCC

PCC

PCC

PC

C

PCC

PCC

PCC

PCC

PCC

PC

C

PC

C

PC

C

PCC

PCC

PCC

GRASS

GRASS

GRASS

GRAVEL

GRASS D

IR

T

GRASS

GRASS

GRASS

GRASS

GRASSGRAVEL

GRASS

E.

N

.F

E.

N

.F

E.N.F.

IMCC

ADMINISTRATION

BUILDING

GROUND ROD

COVERED SEATING AREA

ANTENNA

GROUND ROD

SANITARY MH

809.52 RIM

800.68 IE ±8" VCP (W)

799.22 IE ±10" (N)

799.10 IE ±10" (S)

GROUND ROD

GROUND ROD

2" PVC SUMP PUMP

DISCHARGE INTO ADS TILE.

3" PVC SUMP PUMP

DISCHARGE INTO ADS TILE.

3" PVC COMING OUT OF WALL

1" CONDUIT COMING

OUT OF GROUND

FF THRESHOLD = 804.05

(METAL)

FF = 811.25

(TILE)

FF = 803.89

(CONCRETE)

FF = 811.24

(TILE)

GROUND

ROD

STONE

RETAINING WALL

STONE

RETAINING WALL

STONE RETAINING WALL

SPLIT HEAD

GALVANIZED PIPE

ON WALL

GUARD RAIL

STAIRS

CAMERA POLE AND

JUNCTION BOX.

POLE MOUNTED

MOTION SENSOR.

POLE MOUNTED

MOTION SENSOR.

6" S

T

" S

T

15" ST

8" ST

12" ST

" S

T

" S

T

STORM MH

806.64 RIM

799.10 IE 10" VCP (SW)

798.95 IE 12" RCP (W)

798.88 IE 18" RCP (N)

STRUCTURE INACCESSIBLE

UNDER RAZOR WIRE

803.32 IE 4" ADS (SW)

STORM MH

811.92 RIM

STORM INTAKE

801.64 RIM

799.57 IE 4" PVC (S) (PLUGGED WITH ROCK)

799.23 IE 12" VCP (NW)

STORM INTAKE

804.98 RIM

803.48 IE 6" ADS (N)

803.27 BOTTOM

STORM INTAKE

800.31 RIM

798.21 IE 8" DIP (W)

798.16 IE 8" DIP (N)

798.11 IE (E)

STORM MH

811.92 RIM

±804 IE 15" VCP (W)

6" (N)

804.19 BOTTOM

STANDING WATER IN STRUCTURE

803.92 IE 4" PVC (W)

803.90 IE 4" PVC (W)

803.93 IE 4" PVC (W)

SUMP PUMP DISCHARGE

INTO ADS TILE

ENF

6" ADS TILE RUN ON TOP OF

GROUND DIRECTING ROOF

DRAIN DISCHARGE

X X

X

X X

X

X X

X X

X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X

4" S

T

+0

+0

+2

15"ST

4" S

T

+0

+0

+0

+4

" S

T

STORM INT 1.0

SW-401 (48") WITH TYPE 4B GRATE

STORM INT 3.0

SW-401 (48") WITH TYPE 4B GRATE

INSTALL STORM SEWER MANHOLE

AND CONNECT TO EXISTING PIPES.

VERIFY PIPE SIZES AND IE'S PRIOR

TO ORDERING STRUCTURE.

CONNECT TO EXISTING STORM

SEWER PIPING WITH WYE OR

INSERT-A-TEE CONNECTION.

CLEANOUT, TYP.

SEE DETAIL 8/C501.

INSTALL STORM SEWER

MANHOLE OVER EXISTING

STORM SEWER AND CONNECT

TO EXISTING PIPES. VERIFY

PIPE SIZES AND IE'S PRIOR TO

ORDERING STRUCTURE, TYP.

STORM INT 1.1

SW-401 (48")

WITH TYPE 3B GRATE

INSTALL 4"

PERFORATED

DRAIN TILE. SEE

DETAIL 5/C501.

INSTALL NEW 12"

STORM SEWER.

INSTALL 4" PERFORATED DRAIN

TILE AND CONNECT TO EXISTING

DRAIN TILE WITH WYE

CONNECTION AND REINSTALL

CLEANOUT, SEE DETAIL 5/C501.

INSTALL NEW 12"

STORM SEWER.

STORM INT 2.0

SW-401 (48")

WITH TYPE 3B GRATE

" S

T

CONNECT NEW 12" STORM SEWER

TO EXISTING STORM MANHOLE.

INSTALL 4" PERFORATED

DRAIN TILE. SEE DETAIL 5/C501.

INSTALL LIQUID APPLIED WATER PROOFING ON

EXPOSED PORTIONS OF BELOW GRADE STRUCTURE

EXTERIOR WALL PER MANUFACTURER'S

INSTRUCTIONS. BACKFILL WITH 12" OF BENTONITE

MIXED SOIL AGAINST BUILDING, TYP.

ANTICIPATED SHORING LIMITS.

CONTRACTOR SHALL UTILIZE

STABILIZATION METHODS TO

PROTECT FROM UNDERMINING

EXISTING FENCE FOOTINGS

AND ANTENNA TOWER, TYP.

INSTALL 4" PERFORATED DRAIN TILE AS FAR

NORTH AS POSSIBLE USING NARROW EXCAVATION

METHODS SUCH AS HYDRO EXCAVATION NORTH

OF ANTENNA STRUCTURE DUE TO RESTRICTED

WORKING AREA. APPLY AS MUCH LIQUID APPLIED

WATER PROOFING ON EXPOSED PORTIONS OF

BELOW GRADE STRUCTURE EXTERIOR WALL PER

MANUFACTURER'S INSTRUCTIONS AS FEASIBLE.

PROTECT EXISTING SIDEWALK AND

FENCE FOUNDATIONS DURING STORM

SEWER INSTALLATION.

10+00

0.

0.

0.

0.

11+00

9.

11+20

9.

1 PROFILE - STORM SEWER - SOUTH

EXISTING

GRADE, TYP.

EXISTING

GRADE, TYP.

12"ST @ 0.5%

ST

O

R M

IN

T

1.

R

IM

SE

E G

R

AD

IN

G

P

LA

N

2.

IE

2"

N

2.

IE

5"

E)

2.

IE

5"

W

EXISTING BUILDING.

ST

O

R M

IN

T

1.

R

IM

SE

E G

R

AD

IN

G

P

LA

N

2.

IE

2"

S)

2.

IE

N

INSTALL LIQUID WATER PROOFING ON

EXPOSED PORTIONS OF BELOW GRADE

STRUCTURE EXTERIOR WALL PER

MANUFACTURER'S INSTRUCTIONS.

BACKFILL WITH 12" OF BENTONITE

MIXED SOIL AGAINST BUILDING, TYP.

(E

XI

ST

PROPOSED

GRADE, TYP.

9.

9.

9.

9.

9.

PROPOSED

GRADE, TYP.

(E

XI

ST

(N

EW

20+00

0.

0.

0.

21+00

0.

0.

9.

8.

22+00

7.

6.

22+40

4.

12"ST @ 0.5%

2 PROFILE - STORM SEWER - NORTH

EXISTING

GRADE, TYP.

EXISTING

GRADE, TYP.

INSTALL LIQUID WATER PROOFING ON

EXPOSED PORTIONS OF BELOW GRADE

STRUCTURE EXTERIOR WALL PER

MANUFACTURER'S INSTRUCTIONS.

BACKFILL WITH 12" OF BENTONITE

MIXED SOIL AGAINST BUILDING, TYP.

EX

IS

TI

N

G M

AN

H

O

LE

R

IM

SE

E G

R

AD

IN

G

P

LA

N

1.

IE

2"

S)

9.

IE

0"

SW

8.

IE

2"

W

8.

IE

8"

N E)

ST

O

R M

IN

T

2.

R

IM

SE

E G

R

AD

IN

G

P

LA

N

2.

IE

(S

2.

IE

2"

N

(E

XI

ST

PROPOSED

GRADE, TYP.

PROPOSED

GRADE, TYP.

0.

0.

0.

0.

0.

9.

8.

7.

6.

(N

EW

(E

XI

ST

(E

XI

ST

N O

R

TH

G

AT

E D

R

IV

E

IO

W A

C

IT

Y, IO

W A

9.

4.

S H

IV

E-

H

AT

TE

R

Y.

C

O M

A B C D E F HG

A B C D E F HG

Pr in te d:

D R

AW

N

B Y

AP

PR

O

VE

D B

Y

IS

SU

ED

F

O R

IS

SU

E D

AT

E

FI

EL

D B

O O

K

PR

O

JE

C

T N

U M

BE

R

P:

\P ro je ct s\

\2

0\

De liv er ab le s\

Dr aw in gs

\1 _C ivi l\C

1.

dw g

/1

4/

1:

:4

AM

C401

SI

TE

U

TI

LI

TY

PL

AN

AS

R

KM

B

BI

D

/1

8/

80 --- C

LI

EN

T

PR

O

JE

C T

N U

M

BE

R : 9

2.

IM

C

C A

D M

IN

B

LD

G

W

AT

ER

M

IT

IG

AT

IO

N

IO

W

A D

EP

AR

M

EN

T O

F

AD

M

IN

IS

TR

AT

IV

E

SE

R

VI

C

ES

C O

R

AL

VI

LL

E, IA

SITE UTILITY PLAN

UTILITY CONSTRUCTION NOTES

1. THE MEANS OF THE WORK AND THE SAFETY OF THE CONTRACTOR'S EMPLOYEES ARE SOLELY THE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR HAS A

CONTRACTUAL OBLIGATION TO COMPLY WITH ALL APPLICABLE LAWS AND REGULATIONS INCLUDING THOSE OF OSHA. AT NO TIME WILL EITHER THE OWNER OR THE ENGINEER TAKE RESPONSIBILITY FOR EITHER THE MEANS OF THE WORK OR THE SAFETY OF THE CONTRACTOR'S EMPLOYEES.

2. FIELD-VERIFY THE INVERT ELEVATIONS AT ALL TIE-IN LOCATIONS PRIOR TO THE START OF GRAVITY SEWER LINE INSTALLATION. REPORT ANY DISCREPANCIES BETWEEN THE VERIFIED ELEVATIONS AND THE PLAN ELEVATIONS TO THE ENGINEER IMMEDIATELY. NO GRAVITY SEWER LINE INSTALLATION SHALL PROCEED UNTIL VERIFICATION IS

COMPLETE AND ANY NECESSARY ADJUSTMENTS ARE APPROVED.

3. FOR THE PURPOSES OF GENERAL SAFETY, CONSTRUCT FENCE AROUND CONSTRUCTION AREAS AT ALL UNATTENDED OPEN EXCAVATIONS. SEE SHEET C501 FOR FENCE TYPE

AND DETAIL. MAINTAIN ALL FENCES IN AN UPRIGHT POSITION AT ALL TIMES.

4. LOCATION, SIZE, AND DEPTH OF BURIED UTILITIES ARE ILLUSTRATED BASED ON AVAILABLE RECORDS FROM THE UTILITY OPERATING AUTHORITY. RECORD LOCATIONS ARE FIELD VERIFIED BASED ON OBSERVABLE SURFACE FEATURES SUCH AS MANHOLES, VALVE BOXES, EVIDENCE OF TRENCHES, ETC. OR FIELD MARKING BY THE OPERATING AUTHORITY WHEREVER POSSIBLE. EXCAVATIONS HAVE NOT BEEN MADE TO VERIFY LOCATIONS OR DEPTH OF BURIED UTILITIES. EXACT LOCATION AND ELEVATION OF ALL

UTILITIES MUST BE DETERMINED BY THE CONTRACTOR.

5. CONTACT EACH UTILITY'S OPERATING AUTHORITY AND SCHEDULE JOINT MEET LOCATES. VERIFY WITH EACH UTILITY'S OPERATING AUTHORITY THAT LOCATES HAVE BEEN PERFORMED. IOWA ONE CALL SYSTEM: 1-800-292-8989. IT IS THE ESSENCE OF THIS CONTRACT TO PROTECT ALL EXISTING UTILITIES. WORK TO EXPLORE AND VERIFY THE LOCATION AND ELEVATION OF ALL UTILITIES AT LEAST 100 FEET IN ADVANCE OF THE EXCAVATION WORK. IN THE EVENT THAT A UTILITY IS DISCOVERED THAT WAS NOT SHOWN ON THE DRAWINGS OR A SUBSTANTIAL DEVIATION IN LOCATION OR ELEVATION OF A KNOWN UTILITY EXISTS, REPORT IT TO THE OWNER'S REPRESENTATIVE AS SOON AS

DISCOVERED.

6. PROTECT ALL UTILITIES AND VAULTS FROM DAMAGE DUE TO OPERATION OF HEAVY EQUIPMENT. HAND EXCAVATION WILL BE REQUIRED WHEN EXPOSING EXISTING UTILITIES.

7. USE EXTREME CAUTION WHILE EXCAVATING AND WORKING OVER EXISTING TUNNELS AND UNDERGROUND VAULTS TO PROTECT STRUCTURE AND WATERPROOFING SYSTEM.

HAND EXCAVATION WILL BE REQUIRED. IF WATERPROOFING SYSTEM IS DAMAGED, CONTACT THE OWNER FOR REPAIR INSTRUCTION.

8. SHORE/SUPPORT ALL UTILITIES CROSSING THROUGH EXCAVATION TRENCH TO PROTECT THE UTILITY. SOME NON-REINFORCED DUCTBANKS MAY EXIST ON SITE THAT WILL REQUIRE SPECIAL SUPPORT/SHORING. ALL SHORING/SUPPORT SYSTEMS ARE SUBJECT TO APPROVAL BY THE OWNER. REPAIR ALL DAMAGE TO UTILITIES CAUSED BY

CONSTRUCTION ACTIVITIES AT NO COST TO THE OWNER.

9. UNDERGROUND TUNNELS AND VAULTS ARE PRESENT ON SITE. SHORE/SUPPORT EXISTING UNDERGROUND TUNNELS AND VAULTS TO SUPPORT CONSTRUCTION ACTIVITIES THAT ARE CROSSING OR ADJACENT TO EXISTING STRUCTURES PRIOR TO COMMENCING WORK. SUBMIT METHOD OF SHORING TO OWNER AND DESIGN PROFESSIONAL FOR REVIEW PRIOR TO INSTALLATION. NO ADDITIONAL COMPENSATION WILL BE PROVIDED FOR SHORING. DURING THE CONSTRUCTION PROCESS, IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO MAINTAIN THE INTEGRITY OF THE EXISTING STRUCTURE AND PROTECT IT FROM DAMAGE.

10. SHORING OF EXISTING OR NEW UTILITIES AND OTHER SITE FEATURES IS NOT NECESSARILY SHOWN ON THE PLANS. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ASCERTAIN IF SHORING IS NEEDED IN ADDITION TO WHAT IS SHOWN ON THE DRAWINGS BASED ON THE OWNER'S REQUIREMENTS FOR VEGETATION/STRUCTURE/PAVING PROTECTION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PLAN AND DESIGN ALL SHORING. SHORING DESIGN TO BE PERFORMED BY A LICENSED ENGINEER LICENSED TO PERFORM WORK IN THE STATE OF IOWA. SUBMIT DESIGN OF SHORING TO OWNER AND DESIGN PROFESSIONAL FOR REVIEW PRIOR TO INSTALLATION. NO ADDITIONAL COMPENSATION WILL BE

PROVIDED FOR SHORING.

11. IF HAZARDOUS MATERIALS ARE ENCOUNTERED DURING CONSTRUCTION OPERATIONS, STOP WORK IN THAT AREA AND CONTACT THE OWNER FOR DIRECTION. DO NOT REMOVE CONTAMINATED MATERIALS FROM THE SITE UNTIL RECEIVING DISPOSAL DIRECTION FROM THE OWNER. REFER TO SPECIFICATION FOR INSTRUCTIONS. COMPLY WITH APPLICABLE REGULATIONS, LAWS AND ORDINANCES CONCERNING REMOVAL, HANDLING AND PROTECTION AGAINST EXPOSURE OR ENVIRONMENTAL POLLUTION

12. PHASE WORK TO MEET UTILITY OUTAGE AND PROJECT SCHEDULE REQUIREMENTS.

13. STAGING AREAS ARE LIMITED. IT IS ANTICIPATED THAT SOME AREAS WILL REQUIRE THAT ALL EXCAVATED MATERIALS WILL BE HAULED TO OWNER'S ON-SITE DUMP SITE AND NEW BACKFILL MATERIALS HAULED IN. HAUL OFF AND IMPORT OF MATERIALS SHALL BE AT NO ADDITIONAL COST TO THE OWNER.

14. UTILITIES AND OTHER SITE FEATURES SCHEDULED FOR DEMOLITION ARE NOT SHOWN ON THE SITE UTILITY PLAN. REFER TO THE UTILITY DEMOLITION PLAN ON SHEET C301.

15. COORDINATE ALL UTILITY OUTAGES WITH COMPANY OF UTILITY.

16. THE OWNER SHALL OPERATE ALL VALVES AND HYDRANTS.

17. ALL UTILITY SHUT DOWNS REQUIRE WRITTEN NOTIFICATION TO THE OWNER A MINIMUM OF 1 WEEK IN ADVANCE. SHUT DOWN MAY HAVE A DURATION NO MORE THAN 8 HOURS.

18. THE ALIGNMENT OF UTILITIES AND OTHER WORK IN THIS CONTRACT HAS BEEN CAREFULLY LAID OUT. THE CONTRACTOR IS NOT PERMITTED TO INSTALL UTILITIES AT SIGNIFICANT DEVIATION FROM ALIGNMENT AND PROFILES PROVIDED WITHOUT FIRST RECEIVING APPROVAL FROM THE OWNER'S REPRESENTATIVE AND DESIGN

PROFESSIONAL.

19. TEMPORARILY CAP ALL PIPES OVERNIGHT WITH WATER TIGHT FITTINGS AND PRIOR TO LEAVING SITE.

20. SEE SHEETS C501 FOR TYPICAL UTILITY TRENCH AND EMBEDMENT DETAILS.

21. BACKFILL THE TRENCH WITH SUITABLE MATERIALS THAT MEET COMPACTION REQUIREMENTS. THE COST TO HAUL OUT EXISTING MATERIALS AND BRING IN NEW MATERIALS IS INCIDENTAL TO THE PROJECT AT NO ADDITIONAL COSTS TO THE OWNER. THE COST TO HAUL IN ADDITIONAL MATERIAL WHEN NATIVE MATERIAL IS BEING COMPACTED TIGHTER THAN THE IN-SITU CONDITION IS INCIDENTAL TO THE PROJECT AT NO ADDITIONAL COSTS TO THE OWNER.

22. DEWATERING IS INCIDENTAL TO THE PROJECT. THE USE OF DEWATERING EQUIPMENT WILL BE DONE AT THE CONTRACTOR'S OPTION.

23. IF WET SOILS ARE ENCOUNTERED, THE CONTRACTOR IS NOT REQUIRED TO INSTALL WELL POINTS TO DEWATER AREAS IN ADVANCE OF EXCAVATING THE TRENCH. EXCAVATE THE TRENCH, REMOVE UNSUITABLE MATERIAL AS REQUIRED, AND KEEP THE TRENCH DEWATERED AS REQUIRED TO INSTALL THE PIPE.

24. IF UNSUITABLE SOILS FOR UTILITY BEDDING ARE ENCOUNTERED, CONTACT THE OWNER. REPLACE ALL UNSUITABLE SOILS WITH SPECIFIED COMPACTED BACKFILL AT THE OWNER'S APPROVAL. INSTALL GEOTEXTILE FABRIC WHEN SUBBASE CAN NOT BE STABILIZED WITH ROCK ALONE. INSTALL GEOTEXTILE FABRIC AS PER MANUFACTURER'S

RECOMMENDATION AND AT THE OWNER'S APPROVAL.

25. INSTALL NEW ROADWAY SUBDRAIN WHEN EXCAVATING THROUGH STREETS FOR UTILITY INSTALLATION. CONNECT NEW SUBDRAIN TO EXISTING SUBDRAIN.

26. REPLACE ALL DISRUPTED LIGHT CIRCUITS COMPLETELY FROM THE NEAREST HANDHOLE OR SOURCE NOT DISTURBED.

27. THE CONTRACTOR IS REQUIRED TO KEEP ACCURATE CONSTRUCTION RECORD DOCUMENTS INCLUDING ELEVATIONS FOR UTILITIES AT EACH CHANGE IN PROFILE OR ALIGNMENT. CONTRACTOR TO UTILIZE GPS EQUIPMENT TO OBTAIN AS-BUILT COORDINATES PRIOR TO BACKFILL.

28. ADJUST ALL NEW AND EXISTING CASTINGS TO MATCH THE FINISHED ELEVATIONS INDICATED ON THE PLANS. ADJUST ALL RIM ELEVATIONS WITHIN PAVED SURFACES TO MATCH

FINISHED PAVING. ALL ADJUSTMENT RINGS FOR MANHOLES OR INTAKES SHALL BE CONCRETE.

N O

R

TH

G

AT

E D

R

IV

E

IO

W A

C

IT

Y, IO

W A

9.

4.

S H

IV

E-

H

AT

TE

R

Y.

C

O M

A B C D E F HG

A B C D E F HG

Pr in te d:

D R

AW

N

B Y

AP

PR

O

VE

D B

Y

IS

SU

ED

F

O R

IS

SU

E D

AT

E

FI

EL

D B

O O

K

PR

O

JE

C

T N

U M

BE

R

P:

\P ro je ct s\

\2

0\

De liv er ab le s\

Dr aw in gs

\1 _C ivi l\C

1.

dw g

/1

4/

1:

:5

AM

C501

C O

N

ST

R U

C

TI

O N

D

ET

AI

LS

AS

R

KM

B

BI

D

/1

8/

80 --- C

LI

EN

T

PR

O

JE

C T

N U

M

BE

R : 9

2.

IM

C

C A

D M

IN

B

LD

G

W

AT

ER

M

IT

IG

AT

IO

N

IO

W

A D

EP

AR

M

EN

T O

F

AD

M

IN

IS

TR

AT

IV

E

SE

R

VI

C

ES

C O

R

AL

VI

LL

E, IA

6' -0

MOVEABLE CHAINLINK FENCE SHALL BE INSTALLED AROUND CONSTRUCTION

SITE PERIMETER.

NOTES:

GRADE

MOVEABLE PANELS SHALL BE SECURELY FASTENED DOWN TO PREVENT

MOVEMENT, OVERTURNING, OR WIND PROBLEMS.

TEMPORARY CHAIN LINK CONSTRUCTION FENCE 1

1.

2.

MOVEABLE GALVANIZED STEEL

CHAIN LINK FENCING, POSTS & RAILS

BASE PLATE WITH SAND BAGS

TO PREVENT OVERTURNING

PROVIDE BEIGE PVC PRIVACY SLATS WITH BOTTOM LOCK SLAT ON FENCE EXCEPT

AT CONSTRUCTION GATES AND TO ALLOW FOR SITE DISTANCE AT DRIVE

ENTRANCES.

3.

DT

2 PIPE EXCAVATION & BEDDING FOR STORM SEWERS

NOTE:

SUBGRADE SHALL BE EXCAVATED OR OVEREXCAVATED, IF

NECESSARY, SO A UNIFORM FOUNDATION FREE OF

PROTRUDING ROCKS MAY BE PROVIDED.

PROVIDE TOPSOIL OR PAVING AS PER

PLANS AND SPECIFICATIONS.

ACTUAL TRENCH SIDE SLOPE TO BE

DETERMINED BY CONTRACTOR IN

ACCORDANCE WITH OSHA STANDARDS

IN LANDSCAPE AREAS, BACKFILL SHALL BE

SUITABLE NATIVE OR IMPORTED SUITABLE FILL

COMPACTED TO 95% STANDARD PROCTOR

DENSITY. IN PAVED AREAS, BACKFILL SHALL BE

IOWA DOT GRADATION 11 CLASS 'A' ROADSTONE

COMPACTED TO 98% STANDARD PROCTOR

DENSITY.

HAND TAMPED BACKFILL SEE NOTE

FOR MATERIAL

D/4, 4" MIN

12" MIN

PIPING SHALL HAVE SUDAS

CLASS 1 (IOWA DOT GRAD. 3)

BEDDING AND ENVELOPE

UNDISTURBED SOIL

2.0'

WARNING TAPE 12"-18"

ABOVE UTILITY

PCC PAVEMENT4

NOTES:

1. ALL NEW PAVEMENT SHALL BE DOWELED INTO EXISTING.

2. ALL PAVEMENT SHALL BE JOINTED TO MEET IOWA DOT STANDARD ROAD PLAN PV-101

AND ACCORDING TO SUDAS SECTION 5G

FINISH PER

SPECIFICATIONS.

SEE GRADING PLAN

FOR CROSS-SLOPES,

TYP.

PROVIDE 6" OF IOWA DOT GRADATION 14 SUBBASE. SEE

SPECIFICATION FOR COMPACTION REQUIREMENTS

SUBGRADE TO BE SCARIFIED TO A DEPTH OF 12" AND RECOMPACTED

TO 98% STANDARD PROCTOR DENSITY

PCC PAVEMENT. SEE PLAN FOR

LOCATION AND THICKNESS.

EXPANSION JOINT6

SLOPE

1"

1/

2"

3/4" BUILDING OR STRUCTURE FACE, 1/2" ELSEWHERE

BUILDING FACE OR ABUTTING PAVEMENT

JOINT SEALANT

CLOSED CELL POLYETHYLENE FOAM BACKER ROD

EXPANSION JT. MATERIAL

ABUTTING PAVEMENT

7 GRAVEL SURFACE SECTION

6"

SUBGRADE TO BE

SCARIFIED TO A

DEPTH OF 12" AND

RECOMPACTED TO

98% STANDARD

PROCTOR DENSITY.

2" NOMINAL DIAMETER

ROCK SURFACING.

WEED BARRIER

PCC SIDEWALK3

NOTES:

1. SPACE 1/2" EXPANSION JOINTS AT MAX 100' INTERVALS.

2. PROVIDE MEDIUM BROOM FINISH PERPENDICULAR TO THE DIRECTION OF TRAVEL.

SEE GRADING PLAN FOR

CROSS-SLOPE, TYP.

EXISTING SIDEWALK

PROVIDE 4" OF IOWA DOT…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .