DHS CHMHI Cherokee Voldeng Building Remodel
Solicitation number
RFB928300-02
Issued by
Cherokee County, Iowa

About this file

This document is an addendum to a Request for Bid (RFB) for the remodeling of the Cherokee Mental Health Institute Voldeng Building in Iowa. The project includes an elevator addition, exterior security fencing, and parking lot work. The addendum provides clarifications on the project schedule, revisions to the drawings and specifications, and answers to various questions from potential bidders. Key details include maintaining the May 22, 2025 owner occupancy date, acceptable manufacturers for HVAC and other equipment, and acceptable substitutes for certain materials and systems. The contract opportunity is being solicited by the Iowa Department of Administrative Services.

The addendum also confirms that the owner will provide telecom equipment and be responsible for the access control and security camera systems, with the contractor providing the supporting infrastructure. Pricing information, set-asides, or funding sources are not provided. The contract duration and any renewal options are not specified.

View the file

Other files

File Type Posted
RFB928300-02 - Bid Form.pdf PDF
RFB928300-02 - Addendum #01.pdf PDF
RFB928300-02 - Notice.pdf PDF
RFB928300-02 - Specifications.pdf PDF
RFB928300-02 - Addendum #03.pdf PDF
RFB928300-02 - Drawings.pdf PDF
1220811-event.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Name: DHS CHMHI Voldeng Building Remodel

DAS RFB #: 928300-02

DAS Project #: 9283.00

Date: 4/16/2024

Addendum 2:

• Cover Page – Clarifications, Questions, & Answers (2 Pages)

1 CLARIFICATIONS

1.1 Schedule - We will conduct a pull plan meeting with all trades following contract award to work through manpower availability, sequencing, and schedule detail. If individual floor completion dates or other milestone dates need to shift due to crew availability, it is the intent that we would work to accommodate this through the pull plan process. The duration, sequence, and dates provided in the preliminary schedule for tasks between Mobilization and Owner Occupancy are for example and will be adjusted as needed through the pull plan process. It is the intent that the milestone date for Owner Occupancy on May 22nd, 2025, be maintained.

2 REVISIONS

2.1 DELETE, the note on Sheet S100A, that reads as follows: “COORDINATE REBAR PLACEMENT AND

LAYOUT WITH PROMELT ELECTRIC SNOW-MELT SYSTEM EMBEDDED INTO CONCRETE SLAB –

REFER TO MECHANICAL.”

2.2 ADD, Note 2 to the Condensing Unit Schedule on Sheet M201 “Acceptable Manufacturers to include Daikin, Mitsubishi, Toshiba, Gree or equivalent.

2.3 ADD, Note 3 to the Mini Split Air Conditioner Schedule on Sheet M201 “Acceptable Manufacturers to include Daikin, Mitsubishi, Toshiba, Gree or equivalent.

2.4 ADD, Note 8 to the Fin-Tube Schedule on Sheet M201 “Acceptable Manufacturers to include Slant Fin, Vulcan, Zehnder Rittling or equivalent.

2.5 ADD Specification Section 01 1200 1.09.A.2.i to read “Code required signage will be provided by the Owner and installed by Bid Package #01. Include an allowance of $5,000 for this scope of work. Final cost will be negotiated through change order once scope of signage is determined.”

3 QUESTIONS & ANSWERS

3.1 Telecom Equipment: It appears all telecom equipment is Owner provided. Aside from providing two racks, all switches, servers, wireless access points, and etc is OFOI or existing. Just want to confirm that is the intent.

3.1.1 Yes. The contractor will provide the racks, raceway, mounting infrastructure, and peripheral devices (card readers, cameras, door contacts, etc.). The owner will be providing all switches, UPS’s, servers. Wireless Access points were not discussed.

3.2 Access Controls and Security Cameras: It looks like we are tying into existing systems and head-end software for both of these systems. I haven't run across what the existing systems are but this information would be helpful for potential bidders.

3.2.1 There is no existing camera or access control system at Voldeng. The owner utilizes a Genetec Server, and Genetec Archiver for door controls, and camera recording at other buildings. They would like to utilize these same head end pieces of equipment, and software systems, but these systems work with other manufacturers.

3.3 Can all the light types be Cooper equals to the Acuity fixture types?

3.3.1 Yes, the contractor can bid Cooper as an equal to the Acuity fixture types. However, all fixture types will need to be reviewed and approved during shop drawings to verify all requirements of the Acuity fixture are met with the submitted Cooper fixtures.

3.4 We are currently having a hard time finding 32” razor ribbon and were wondering if 30” or 36” could be used instead?

3.4.1 30” razor ribbon is acceptable to use in lieu of the 32” that was called out. If you cannot find the 30” either, then 36” will also be acceptable.

3.5 Does the security fence need to have top, bottom, and middle rails?

3.5.1 Yes, unless the fence manufacturer recommends something different.

3.6 Are aluminum fence ties ok to use on the line post and rails?

3.6.1 Yes, they are.

3.7 As far as the gates go will they all have key fobs per the specifications or just the gates at the sally port entrances?

3.7.1 Yes, just the sally port entrances.

3.8 Is Vetrotech Keralite Laminated fire-rated clear safety glass an acceptable substitute?

3.8.1 They are an acceptable substitute.

3.9 Is NW Specialty Hardware an acceptable substitute for the Detention Toilet / Washroom Accessories?

3.9.1 Yes, they are an acceptable substitute for the grab bars (security bars) only.

3.10 Is Avant Guards Manufacturing an acceptable manufacturer for the Level 6 - Aluminum Security Screens?

3.10.1 Yes, they are an acceptable manufacturer.

3.11 The range hood schedule on sheet M901 states the cfm as 500. The Greenheck IOM states for recirculating fan the cfm should be 300. Please clarify?

3.11.1 The range hood cfm shall be 300 for recirculating per the IOM.

3.12 Is Kidde Commercial an acceptable manufacturer for the Addressable Fire-Alarm System?

3.12.1 Yes, they are an acceptable manufacturer.

3.13 Is Captive Aire an acceptable manufacturer for the Commercial Kitchen Hood?

3.13.1 No, they are an acceptable manufacturer.

END OF ADDENDUM 2