RFB922300-02 - CCF Kitchen And Laundry - Drawings (3 of 3).pdf

PDF 16 MB Posted

Attached to
DOC CCF Kitchen & Laundry Addition
Solicitation number
RFB922300-02
Issued by
Page County, Iowa

About this file

The document is a set of drawings for a Request for Bid (RFB) issued by the Iowa Department of Administrative Services for the construction of a new kitchen and laundry facility at the Clarinda Correctional Facility (CCF) located in Clarinda, Iowa. The project scope includes general construction, concrete, masonry, precast, structural steel, EPDM roofing, food service equipment, fire suppression, plumbing, HVAC, electrical, communications, electronic safety/security, earthwork, paving, and utilities. The contract opportunity is specific to Page County, Iowa.

The document does not provide details on pricing terms, set asides, incumbents, funding requirements or sources, or any other salient financial information. It appears to be solely the technical drawings for the construction project and does not contain supplemental contractual details.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MTR

R

DSD

O

AO DO

FM

H

H

AI DI

H

T

T

T

S

1. UNLESS NOTED OTHERWISE, THE SIZE OF EACH BRANCH DUCT TO A TERMINAL AIR BOX

(TAB) SHALL MATCH THE INLET SIZE UNLESS THE BRANCH IS GREATER THAN 6 FEET IN

LENGTH, IN WHICH CASE THE BRANCH DUCT SHALL BE SIZED AT A PRESSURE DROP OF

0.07"W.C. PER 100' OF DUCTWORK.

2. UNLESS NOTED OTHERWISE, THE SIZE OF EACH BRANCH DUCT TO AN AIR TERMINAL SHALL

MATCH THE INLET SIZE.

3. ALIGN TEMPERATURE SENSORS WITH LIGHT SWITCHES AND WHEN IN CLOSE PROXIMITY TO

EACH OTHER.

4. PROVIDE ACCESS DOORS AT ALL DUCT MOUNTED EQUIPMENT.

5. REFER TO 6/M4.1 FOR DUCT BRANCH CONNECTIONS DETAIL.

6. ALL RADIUS ELBOWS SHALL BE TYPE RE1 WITHOUT VANES (CENTER RADIUS R/W=1.0).

EXCEPTION: RADIUS ELBOWS LABELED "RE3" SHALL BE TYPE RE3 WITH VANES (CENTER

RADIUS R/W=0.6). REFER TO SPECIFICATIONS AND DETAIL 6/M4.2 FOR ADDITIONAL

REQUIREMENTS.

7. REFER TO 4/M4.2 FOR FLEX DUCT CONNECTION (STRAIGHT/WRAPPED) DETAIL.

8. REFER TO 5/M4.2 FOR TRAPEZE HANGER DUCT WRAP VAPOR SEAL DETAIL.

VENTILATION GENERAL NOTES:

1. PIPE DRAIN LINES FROM EQUIPMENT TO NEAREST FLOOR DRAIN.

2. INSTALL ALL REFRIGERANT LIQUID AND SUCTION PIPING SIZED PER EQUIPMENT

MANUFACTURER RECOMMENDATIONS.

PIPING GENERAL NOTES:

MECHANICAL GENERAL NOTES:

THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, FIRE PROTECTION, PLUMBING, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE

DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.

DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC.,

AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE

INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING

CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.

2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM

ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR

PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.

3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE

CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO

VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO

VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES

OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING

WITH FABRICATION OR EQUIPMENT ORDERS.

4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE

REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER

ACCESS.

5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO

COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR

EXPENSE TO OTHERS.

6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL

CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF

DESIGN.

7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY

AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING

MOUNTED DEVICES, OTHER THAN SPRINKLERS.

8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS,

FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS

RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND

FINISH.

9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE

DRY WALL CONTRACTOR FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS,

ETC. COORDINATE PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE DRY WALL

CONTRACTOR OF THE REQUIRED ACCESS PANELS PRIOR TO BIDDING.

10. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING,

AND DUCTS PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE

SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER

FOR OUTDOOR USE.

11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL,

PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE

TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS

WITHIN ROOMS.

12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED

OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL

RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.

13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT

MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND

REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS,

PIPING, DUCTWORK, ETC.

14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES.

15. MAINTAIN A MINIMUM WORKING CLEARANCE OF 3’-6” IN FRONT OF ALL ELECTRICAL

EQUIPMENT REQUIRING MAINTENANCE, INSPECTION, AND TESTING INCLUDING BUT NOT

LIMITED TO PANELS, DISTRIBUTION PANELS, SWITCHBOARDS, MOTOR CONTROL CENTERS,

TRANSFORMERS, EQUIPMENT DISCONNECTS AND STARTERS.

16. MAINTAIN THE DEDICATED ELECTRICAL EQUIPMENT SPACE DEFINED BY THE WIDTH / DEPTH

OF ELECTRICAL EQUIPMENT MEASURED FROM THE FLOOR TO A HEIGHT 6’-0” ABOVE THE

EQUIPMENT OR THE STRUCTURAL CEILING, WHICHEVER IS LOWER. SYSTEMS FOREIGN TO

THE ELECTRICAL DISTRIBUTION SYSTEM ARE NOT ALLOWED IN THE DEDICATED

ELECTRICAL SPACE INCLUDING; DUCTWORK, PIPING, ETC.

17. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL

EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT.

18. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER

NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE

CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.

MECHANICAL RENOVATION NOTES:

THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, FIRE PROTECTION, PLUMBING, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD

SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND

REPORT ANY CONFLICTS BEFORE PROCEEDING.

2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS

BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.

3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE

FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD

CONDITIONS.

4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF THEIR WORK AND

SHALL NOTIFY THE ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE

REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO THEIR AREA OF WORK.

5. EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED

WITH THEIR WORK.

6. THIS CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS,

CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK REQUIRED BY

THEIR WORK.

7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH

NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL

EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT

DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL

SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.

8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING

CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT

REMAIN ACTIVE.

9. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY

REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW

SYSTEMS ARE INSTALLED.

10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR

TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND

CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY

DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.

11. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT

THAT HAS BEEN REMOVED.

PITCH PIPE IN DIRECTION

PIPE CAP

PIPE DOWN

PIPE UP OR UP/DOWN

DIRECTION OF FLOW IN PIPE

SHUTOFF VALVE NORMALLY OPEN

REFRIGERANT HOT GASHG

HEATING WATER RETURNHWR

HEATING WATER SUPPLYHWS

REFRIGERANT LIQUIDLIQ

REFRIGERANT SUCTIONSUC

DRAINDPP

STATIC SWITCH

DIFFERENTIAL PRESSURE SENSOR

MECHANICAL SYMBOL LIST

SYMBOL: DESCRIPTION:

NOT ALL SYMBOLS MAY APPLY.

HUMIDISTAT SENSOR

HUMIDISTAT / SENSOR

TEMPERATURE SENSOR WITH WELL

T

THERMOMETER WITH WELL (DIAL TYPE)T

THERMOMETER WITH WELL (FILLED TYPE)

DIRECTION OF AIR FLOW

FLEXIBLE DUCT

MANUAL VOLUME DAMPER

RISE IN DIRECTION OF AIR FLOWR

DUCT CAP

DROP IN DIRECTION OF AIR FLOWD

DUCT DOWN

DUCT UP

SUPPLY/OUTSIDE AIR DUCT SECTION

RETURN AIR DUCT SECTION

EXHAUST/RELIEF AIR DUCT SECTION

4-WAY DIFFUSER WITH BLANKOFF IN ONE DIRECTION

SD-1

6/115

AIR TERMINAL PROPERTIES SYMBOL

NECK SIZE/CFM

### TERMINAL AIR BOX w/REHEAT COIL (REFER TO SCHEDULE)

OPPOSED BLADE DAMPER (REFER TO SCHEDULE)

PARALLEL BLADE DAMPER (REFER TO SCHEDULE)

DIFFERENTIAL PRESSURE SENSOR

PRESSURE SENSOR/MONITORP

PRESSURE SENSOR (DUCT MOUNTED)P

THERMOSTAT/SENSOR TYPE 1 (SENSOR ONLY)S1

TEMPERATURE SENSORT

THERMOSTAT/SENSOR WITH HEAVY DUTY ENCLOSURET

FAN POWERED TERMINAL AIR BOX w/REHEAT COIL

(REFER TO SCHEDULE)

SP

AVERAGING TEMPERATURE

SENSOR

PROBE TEMPERATURE SENSOR

LOW LIMIT TEMPERATURE

SWITCH

FAN

MOTOR

CONTACTOR

PUMP

DUCT SMOKE DETECTOR

ANALOG INPUT

ANALOG OUTPUT

DIGITAL INPUT

DIGITAL OUTPUT

HEATING/ COOLING COIL

FILTER

OPPOSED BLADE DAMPER

PARALLEL BLADE DAMPER

TERMINAL AIR BOX W/ REHEAT

NORMALL CLOSED CONTACT

NORMALLY OPEN CONTACT

MANUAL MOTOR STARTER

W/THERMAL OVERLOAD

OCCUPANCY SENSOR

ACTUATOR

DIFFERENTIAL PRESSURE

SWITCH

CURRENT SWITCH

SENSOR

DUCT FLOW METER

HUMIDITY SENSOR

(DUCT MOUNTED)

HUMIDISTAT SENSOR

HUMIDISTAT / SENSOR

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

DETAIL REFERRED TO BY SECTION CUT

SHEET DETAIL IS LOCATED ON

NAME

VIEW NAME

1/8" = 1'-0"

M101

SIMSIM

INDICATES SIMILAR DETAIL REFERENCED

IN MULTIPLE LOCATIONS

LEVEL NAME

10'-0" HEIGHT ABOVE

PROJECT 0'-0"

1 INDICATES NOTE USED TO DESCRIBE

ADDITIONAL INFORMATION ABOUT

WORK REQUIRED, SPECIFIC TO THE

SHEET AND/OR DETAIL

N

O R HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

LINE TYPE AND TAG KEY:

NEW WORK BY THIS CONTRACTOR (WIDE LINE)

NEW

EXISTING TO BE REMOVED (SHORT DASHED PATTERN)

NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)

EXISTING

EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)

EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

HALFTONING DOES NOT MODIFY SCOPE.

'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING

TAG UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL

INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST

INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL

INDICATES A PLUMBING CONNECTION TO A FOOD SERVICE EQUIPMENT.

REFERENCE FOOD SERVICE DRAWINGS FOR ADDITIONAL INFORMATION IN

REGARDS TO TYPE OF EQUIPMENT, ROUGH-IN SIZES, AND ADDITIONAL

COMMENTS.

T101

BUILDING CODE: IBC 2015 EDITION

FIRE CODE: IFC 2015 EDITION

PLUMBING CODE: UPC 2021 EDITION

MECHANICAL CODE: IMC 2021 EDITION

ELECTRICAL CODE: NFPA 70 (NEC) 2020 EDITION

LIFE SAFETY CODE: NFPA 101 2012 EDITION

ENERGY CONSERVATION CODE: IECC 2012

HEALTH DEPARTMENT CODE: CURRENT EDITION

LOCAL BUILDING CODE: CURRENT EDITION

APPLICABLE CODES

CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.

TEMPERATURE CONTROLS CONTRACTORT.C.C.

SECURITY CONTRACTORS.C.

CIVIL CONTRACTORC.C.

FIRE PROTECTION CONTRACTORF.P.C.

PLUMBING CONTRACTORP.C.

MECHANICAL CONTRACTORM.C.

ELECTRICAL CONTRACTORE.C.

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

TECHNOLOGY CONTRACTORT.C.

CONSTRUCTION MANAGERC.M.

FOOD SERVICE EQUIPMENT CONTRACTORFSEC

CONTACT PERSONS:

PROJECT MANAGER

MECHANICAL

ELECTRICAL

TECHNOLOGY

MIKE MCCARTY

MIKE MCCARTY

KRISTEN SPINA

MIKE MCCARTY

DESCRIPTION: PERSON:

MECHANICAL ABBREVIATION KEY

ABBR: DESCRIPTION:

DIFFERENTIAL PRESSURE GAUGE (RANGE)DPG (0-2")

DIFFERENTIAL PRESSURE SWITCHDPS

AD ACCESS DOOR

ABOVE FINISHED FLOORAFF

NOT IN CONTRACTNIC

CFSD CONTROL/FIRE/SMOKE DAMPER

EA EXHAUST/RELIEF AIR

FD FIRE DAMPER

FOB FLAT ON BOTTOM

FOT FLAT ON TOP

FSD FIRE/SMOKE DAMPER

MA MIXED AIR

OA OUTSIDE AIR

RA RETURN AIR

SA SUPPLY AIR

SD SMOKE DAMPER

TRANSFER DUCTTD

UC-1 DOOR UNDERCUT BY OTHERS (1" TYPICAL)

ECFSD EXISTING CONTROL FIRE SMOKE DAMPER

EFD EXISTING FIRE DAMPER

EFSD EXISTING FIRE SMOKE DAMPER

ESD EXISTING SMOKE DAMPER

TERMINAL AIR BOXTAB

TYPICALTYP

UON UNLESS OTHERWISE NOTES

NORMALLY CLOSEDN.C.

NORMALLY OPENN.O.

PRESSURE SWITCHPS

MIXING VALVEMV

ELECTRICAL TO PNEUMATIC VALVEEP

CO CLEANOUT

C COMMON

SCCR SHORT CIRCUIT CURRENT RATING

MECHANICAL DESIGN CONDITIONS:

SUMMER:

WINTER:

DESIGN CONDITIONS:

TYPICAL ROOM SETPOINTS:

BASED ON WEATHER DATA FOR: {CLARINDA, IA}

KITCHEN SUMMER DESIGN: 80°F DRY BULB, 60% RELATIVE HUMIDITY

LAUNDRY, OFFICES, STORAGE SUMMER DESIGN: 72°F DRY BULB, 60% RELATIVE HUMIDITY

WINTER DESIGN: 68°F DRY BULB, NO HUMIDITY REQUIREMENT

91°F DRY BULB, 73°F WET BULB

-10°F DRY BULB

1. REFER TO EQUIPMENT SCHEDULES TO CROSS REFERENCE WHICH CONTROL DIAGRAMS

APPLY TO WHICH ITEMS OF EQUIPMENT. REFER TO TERMINAL AIR BOX (TAB) SCHEDULES

FOR TEMP SENSOR REQUIREMENTS FOR EACH TAB.

2. EACH D.I., D.O., A.I. AND A.O. POINT SHOWN FOR ALL CONTROL DIAGRAMS SHALL BE

DISCRETE FROM ALL OTHER POINTS EXCEPT AS SPECIFICALLY NOTED.

3. ALL WIRING, CONTROL COMPONENTS, DEVICES AND PROGRAMMING SHOWN ON THESE

CONTROL DRAWINGS SHALL BE PROVIDED BY THE TCC UNLESS SPECIFICALLY NOTED

OTHERWISE.

4. TEMPERATURE CONTROL CABLING, CONDUIT, BOXES, IDENTIFICATION: REFER TO THE

SPECIFICATIONS FOR A COMPLETE LIST OF REQUIREMENTS. THE FOLLOWING SCHEDULE IS

PROVIDED AS A CONVENIENCE. REFER TO SECTION 23 09 00 AND DIV 26 FOR ADDITIONAL

DETAILED REQUIREMENTS.

A. CABLE/WIRE JACKET COLOR: BLUE

B. CONDUIT BOX COLOR ABOVE FINISHED CEILINGS AND UNFINISHED SPACES WITHOUT

CEILINGS: BLUE

C. CONDUIT BOX COLOR IN SPACES WITH EXPOSED FINISHED STRUCTURE: BLUE

D. CABLE/WIRE INSTALLATION: IN CONDUIT WHEN CONCEALED IN WALLS AND OTHER

ASSEMBLIES. PLENUM-RATED CABLE SHALL BE USED ABOVE FINISHED ACCESSIBLE

CEILINGS, INDEPENDENTLY SUPPORTED FROM OTHER SYSTEM CABLING/WIRE EVERY 4

FT WITH BRIDAL RINGS AND CABLE SADDLES. ALL CABLING SHALL BE IN CONDUIT IN

SPACES WITH EXPOSED FINISHED STRUCTURE.

5. ALL ACTUATORS SHALL BE OF THE ELECTRICAL TYPE FOR THIS PROJECT UNLESS AN

ACTUATOR IS SPECIFICALLY INDICATED ON THE DRAWINGS OR SPECIFICATIONS TO BE

PNEUMATIC.

6. ALL MODULATING DAMPER AND VALVE ACTUATORS SHOWN WITH POSITION FEEDBACK

SHALL HAVE THE VALVE POSITION DISPLAYED ON GRAPHICAL SCREEN ADJACENT TO THE

DAMPER/VALVE COMMAND SIGNAL. DISPLAYED VALVE POSITION SHALL BE FROM THE

FEEDBACK DEVICE/CIRCUIT (OUTPUT SIGNAL FROM THE FMCS TO THE ACTUATOR IS NOT

ACCEPTABLE)

7. MODULATING SIGNALS SHALL BE DISPLAYED AS % OPEN (SIGNALS DISPLAYED AS %

CLOSED ARE NOT ACCEPTABLE).

8. PRESSURE TRANSMITTERS WHOSE SIGNAL IS UTILIZED FOR MAINTAINING DUCT STATIC

PRESSURE SHALL BE WIRED DIRECTLY TO THE CONTROLLER THAT MODULATES FAN

SPEED. SIGNAL SHALL BE COMPLETELY INDEPENDENT OF THE FMCS NETWORK.

9. ALL CONTROL COMPONENTS SUCH AS RELAYS, SWITCHES, DDC CONTROLLERS, ETC.

SHALL BE MOUNTED IN STEEL ENCLOSURES WITH STEEL MOUNTING BACKPLATES PER

SPECIFICATION 23 09 00.

10. EACH CONTROL PANEL SHALL HAVE A LAMINATED COPY OF THE APPLICABLE SEQUENCE OF

OPERATION AND CONTROL DIAGRAM INDICATING THE POINTS, COMPONENTS AND

OPERATION OF EQUIPMENT ASSOCIATED WITH EACH PANEL. REFER TO SECTION 23 09 00

FOR ADDITIONAL REQUIREMENTS.

11. TCC SHALL EXTEND CONTROL SIGNAL FROM ADDRESSABLE RELAY DEVICE SERVING EACH

AIR HANDLING UNIT. REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS. TCC SHALL

EXTEND AND TERMINATE WIRING AS REQUIRED FOR EQUIPMENT SHUTDOWN.

12. TCC SHALL PROVIDE POWER SUPPLIES FOR ALL 24VAC POWER REQUIREMENTS TO

INCLUDE, BUT NOT LIMITED TO, APPLICATION SPECIFIC, TERMINAL AIR BOX CONTROLLERS,

DAMPER AND VALVE ACTUATORS, BUILDING PRESSURE SENSORS, AND OTHER CONTROL

COMPONENTS AND DEVICES. REFER TO CONTROLS SPECIFICATIONS FOR POWER SUPPLY

REQUIREMENTS. REFER TO MECHANICAL FLOOR PLANS FOR POWER SUPPLY LOCATIONS.

PROVIDE LOW VOLTAGE WIRING FROM POWER SUPPLIES TO ALL CONTROLLERS,

MONITORS, COMPONENTS AND DEVICES REQUIRING 24 VAC POWER. ADDITIONAL POWER

SUPPLIES NOT SHOWN AND REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM

SHALL BE PROVIDED BY THE TEMPERATURE CONTROL CONTRACTOR. THE TEMPERATURE

CONTROL CONTRACTOR SHALL PROVIDE FINANCIAL PROVISIONS WITHIN THEIR BID FOR

THE ELECTRICAL CONTRACTOR TO PROVIDE BRANCH POWER TO THE ADDITIONAL POWER

SUPPLIES. COORDINATE THE LOCATION OF ADDITIONAL POWER SUPPLY CABINET WITH THE

ELECTRICAL CONTRACTOR.

13. TCC SHALL PROVIDE CONDUIT RUNS AS REQUIRED FOR OUTDOOR EQUIPMENT AND FOR

EQUIPMENT INSTALLED REMOTELY FROM THE MAIN BUILDING THAT IS BEING MONITORED

OR CONTROLLED BY THE FMCS.

14. ELEMENT LENGTHS FOR BOTH MIXED AIR TEMP SENSORS AND LOW LIMIT TEMP SWITCHES

SHALL BE MINIMUM 1 LINEAR FOOT PER SQUARE FOOT OF COIL SURFACE AREA. PROVIDE

MULTIPLE SENSORS AND SWITCHES AS NEEDED TO ACHIEVE REQUIRED ELEMENT

LENGTHS. LOCATE RESET SWITCHES MAX. 6'-6" ABOVE ADJACENT STANDING SURFACE (E.G.

ROOF, PLATFORM OR FLOOR) SO THE RESET SWITCH CAN BE CYCLED WITHOUT THE NEED

FOR A LADDER.

15. TO PREVENT GENERATOR OVERLOADING, TCC SHALL PROGRAM A STAGGERED START TIME

FOR ALL MECHANICAL EQUIPMENT THAT IS CONTROLLED BY FMCS TO INCLUDE, BUT NOT

LIMITED TO, AIR HANDLERS, CONDENSING UNITS AND, EXHAUST FANS. THE FIRST

EQUIPMENT SHALL START 2 MINUTES (ADJ.) FROM THE TIME THE FMCS RECEIVES THE

SIGNAL THAT THE TRANSFER SWITCH CHANGED TO EMERGENCY POWER SOURCE WITH

ALL EQUIPMENT BEING ENERGIZED WITHIN A 20 MINUTE (ADJ.) TIME SPAN. COORDINATE

ORDER OF EQUIPMENT STAGING WITH OWNER'S REPRESENTATIVE.

16. CONTROL DIAGRAMS ARE SCHEMATIC IN NATURE AND DO NOT SHOW ALL REQUIRED

CONTROL DEVICES AND COMPONENTS. REFER TO FLOOR PLANS, FLOW DIAGRAMS AND

DETAILS FOR ADDITIONAL CONTROL DEVICES, COMPONENTS AND REQUIREMENTS NOT

SHOWN ON THESE CONTROL DRAWINGS.

17. TCC SHALL PROVIDE ALL CONTROL COMPONENTS AND ACCESSORIES AS REQUIRED FOR

EQUIPMENT TO BE CONTROLLED AS DESCRIBED IN THE SEQUENCE OF OPERATION

REGARDLESS OF WHETHER ALL CONTROL COMPONENTS OR POINTS ARE SHOWN IN THE

ASSOCIATED CONTROL DIAGRAM.

18. COORDINATE DDC CONTROL PANEL EMERGENCY POWER SUPPLY REQUIREMENT WITH

ELECTRICAL CONTRACTOR. ALL CONTROLS ASSOCIATED WITH MECHANICAL SYSTEM

REQUIRING EMERGENCY POWER SHALL BE CONNECTED TO THE EMERGENCY POWER

SYSTEM.

TEMPERATURE CONTROL GENERAL NOTES:

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

RFB922300-02

/2

/2

:0 :0

P

M M0.0

MECHANICAL

COVERSHEET

MIKMCC

DAVING

0240202.00

CLARINDA

CORRECTIONAL

FACILITY - KITCHEN &

LAUNDRY ADDITION

STATE OF IOWA - DEPARTMENT

OF CORRECTIONS

2000 N 16TH ST, CLARINDA, IA

51632

02/09/2024

MIKMCC

BID SETMECHANICAL SHEET INDEX

M0.0 MECHANICAL COVERSHEET

MD1.1 LEVEL 01 DEMOLITION PLAN - MECHANICAL

M1.1 LEVEL 01 PLAN - AREA A - MECHANICAL

M1.2 LEVEL 01 PLAN - AREA B - MECHANICAL

M1.3 LEVEL 02 PLAN - AREA A - MECHANICAL

M1.4 LEVEL 02 PLAN - AREA B - MECHANICAL

M3.0 ENLARGED PLAN - MECHANICAL

M4.1 MECHANICAL DETAILS

M4.2 MECHANICAL DETAILS

M4.3 MECHANICAL DETAILS

M5.1 CONTROL DIAGRAMS

M5.2 CONTROL DIAGRAMS

M5.3 CONTROL DIAGRAMS

M6.1 MECHANICAL SCHEDULES

M6.2 MECHANICAL SCHEDULES

GRAND TOTAL: 15

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2024 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

PROJECT #21007688.00

D

E

F

1 2 3 4 5 6 7 8 9

P4 P3

/4

"H W

S

REMOVE EXISTING FIN TUBE RADIATOR

AND PREPARE FOR INSTALLATION OF

NEW ON OPPOSITE WALL.

EXISTING SHUTOFF VALVES, CONTROL VALVE AND

TEMPERATURE SENSOR TO REMAIN FOR REUSE.

/4

"H W

R

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

RFB922300-02

/2

/2

:0 :0

P

M MD1.1

LEVEL 01

DEMOLITION PLAN -

MECHANICAL

MIKMCC

DAVING

0240202.00

CLARINDA

CORRECTIONAL

FACILITY - KITCHEN &

LAUNDRY ADDITION

STATE OF IOWA - DEPARTMENT

OF CORRECTIONS

2000 N 16TH ST, CLARINDA, IA

51632

02/09/2024

MIKMCC

BID SET

N O R

HT

1/8" = 1'-0"

LEVEL 01 DEMOLITION PLAN - MECHANICAL1

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2024 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

PROJECT #21007688.00

S1

S

S1

D

E

F

1 2 3 4 5 6 7 8 9

PA

PB

PC

P5 P4 P3

AA

AB

A1 A2 A3

HALL

DISHROOM

CHEMICAL

STORAGE

ELEC.

LAUNDRY

CORRIDOR

FOLDING

OFFENDER

RR

PASSAGE

VISITOR

ENTRANCE

RECEPTION

TOILET

TOILET

OFFICER

HALL

PERSONNEL

ENTRANCE

ADMINISTRATION

TOILET

OFFICE

TOILET

TOILET

MUSTER

ANTEROOM

SEGREGATION

A/C

1046RELEASE

SHAKEDOWN

PEDESTRIAN

SALLYPORT

FAMILY

WAITING

SEARCH

SEARCH

CONTACT

VISIT

VISITOR

TOILET

INMATE

TOILET

INMATE

SEARCH

PHONE

CONTACT

PHONE

CONTACT

PHONE

CONTACT

PHONE

CONTACT

PHONE

CONTACT

NON-CONTACT

VISIT

TOILET

EVIDENCE

CAPTAIN'S

OFFICE

OFFICE

OFFICE

HALL

CORRIDOR

DRYER

CHASE

OPEN

BREAKROOM/

STORAGE

1062A

OFFICE

1062B

M1.1

FTAB-1TAB-2

TAB-1

EG-1

6x6/75 x S

A x1

SA

14x12 SA x S

A

OAL-5

OAL-4

MOD-4

MOD-5

TAB-2

TAB-1

FTAB-1

x S

A

20x16 SA

32x16 SA

EG-2

10x10/435

(TYP.3)

16x16 EA UP TO 12x12 EA

THRU ROOF.

FTR-1

SG-1

24x12/960

(TYP.2)

SD-1

10/260

(TYP.5)

SD-1

8/125

SD-1

8/120

RG-2

12x12/505

(TYP.2)

SD-1

10/255

(TYP.5)

SD-1

10/250

(TYP.2)

SD-1

10/250

(TYP.2)

RG-2

18x18/985

(TYP.2)

SD-1

8/120

SG-1

8x6/200 x E

A

12x10 SA

14x12 SA

20x16 RA

16x12 SA

14x14 RA

RG-2 RG-2

15x15 RA

/4

"H W

S /4

"H W

R

INSTALL NEW RADIANT FIN

TUBE HEATER. ROUTE

PIPING EXPOSED ON WALL

SIMILAR TO EXISTING AND

PROVIDE PVC JACKETING.

EXTEND EXISTING HEATING

WATER SUPPLY AND RETURN

PIPING TO NEW RADIANT FIN

TUBE HEATER. EXISTING

SHUTOFF VALVES, CONTROL

VALVE, AND TEMPERATURE

SENSOR TO REMAIN.

3/4"HWS

3/4"HWR

CAB-1

SG-2

16x8/0

(TYP.2)

RG-1

36x14/1920

25x17 RA

6x6 EA

18⌀ EA SERVING DRYER

UP THRU ROOF TO

GOOSENECK. (TYP.6)

28x16 RA

REFER TO 3/M4.1 FOR

LOUVER INSTALLATION

DETAIL. (TYP.)

AREA 'A'

AREA 'B'

HALL

DISHROOM

CHEMICAL

STORAGE

ELEC.

LAUNDRY

CORRIDOR

FOLDING

OFFENDER

RR

PASSAGE

VISITOR

ENTRANCE

RECEPTION

TOILET

TOILET

OFFICER

HALL

PERSONNEL

ENTRANCE

ADMINISTRATION

TOILET

OFFICE

TOILET

TOILET

MUSTER

ANTEROOM

SEGREGATION

A/C

1046RELEASE

SHAKEDOWN

PEDESTRIAN

SALLYPORT

FAMILY

WAITING

SEARCH

SEARCH

CONTACT

VISIT

VISITOR

TOILET

INMATE

TOILET

INMATE

SEARCH

PHONE

CONTACT

PHONE

CONTACT

PHONE

CONTACT

PHONE

CONTACT

PHONE

CONTACT

NON-CONTACT

VISIT

TOILET

EVIDENCE

CAPTAIN'S

OFFICE

OFFICE

OFFICE

HALL

CORRIDOR

DRYER

CHASE

OPEN

BREAKROOM/

STORAGE

1062A

OFFICE

1062B

LEVEL 01

0"

EXTEND AND CAP DRYER EXHAUST

DUCT BELOW INSULATED CEILING

FOR BASE BID. FOR ADD

ALTERNATE, EXTEND AND

CONNECT DUCT TO DRYERS.

(TYP.6)

18ø EA (TYP.6)

DRYER

OAL-4

MOD-4

INSTALL DUCT INSPECTION DOOR.

CONFIRM LOCATION WITH DRYER

MANUFACTURER

RECOMMENDATIONS

CONFIRM DISTANCE

ABOVE ROOF WITH

DRYER MANUFACTURER

RECOMMENDATIONS

LEVEL 02

16'-6"

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

RFB922300-02

/2

/2

:0 :1

P

M M1.1

LEVEL 01 PLAN -

AREA A -

MECHANICAL

MIKMCC

DAVING

0240202.00

CLARINDA

CORRECTIONAL

FACILITY - KITCHEN &

LAUNDRY ADDITION

STATE OF IOWA - DEPARTMENT

OF CORRECTIONS

2000 N 16TH ST, CLARINDA, IA

51632

02/09/2024

MIKMCC

BID SET

N O R

HT

1/8" = 1'-0"

LEVEL 01 PLAN - AREA A - MECHANICAL1

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2024 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

PROJECT #21007688.00

1/4" = 1'-0"

SECTION - LEVEL 01 PLAN2

KEYNOTES:

1. BALANCE DIFFUSER/GRILLE TO LISTED CFM WHEN THE

ASSOCIATED FAN POWERED TAB IS AT THE MAXIMUM

SCHEDULED HEATING PRIMARY AIRFLOW PLUS TAB

FAN CFM.

2. CONNECT COOLER/FREEZER REFRIGERATION SYSTEM

TO FMCS FOR MONITORING PER CONTROL DIAGRAM

11/M5.1. CONFIRM FINAL LOCATION WITH FMCS.

3. INSTALL ONE SUPPLY GRILLE HIGH AND ONE SUPPLY

GRILLE LOW TO ALLOW CIRCULATION OF AIR IN

PLUMBING CHASE ON OUTSIDE WALL. COORDINATE

GRILLE LOCATION WITH CMU BLOCKS. BOTTOM GRILLE

SHALL BE INSTALLED WITH CENTER AT 12" AFF AND

TOP GRILLE SHALL BE INSTALLED WITH CENTER AT 92"

AFF. COORDINATE GRILLE LOCATIONS WITH ALL WALL

MOUNTED ITEMS.

4. REFER TO 1/M4.1 FOR TERMINAL AIR BOX - SINGLE

DUCT - WRAPPED DETAIL. (TYP.)

5. REFER TO 2/M4.1 FOR TERMINAL AIR BOX - FAN

POWERED SERIES - WRAPPED.

S

S

S1

S1

S

S

H

PD

PE

P5

P4 P3

AB

AC

AD

AE

AF

AG

AH

A1 A2 A4 A5A3

HOT PRO &

ASSEMBLY

DISHROOM

P O

T

P A

N W

A S

H

POT & PAN

STOR

LNDRY &

CHEM

STOR

STAFF BREAK

RM

DIRECTOR

OFF

STAFF

RR

CART

WASH

1221A

OFFENDER

BREAK

SUPERVISOR

OFF.

OFFENDER

RR

C A

R T

P A

R K

IN

G

BAKERY

FREEZER

TEMPERING

MEAT & DAIRY

REF.

PRODUCE

REF

INGR & DRY

GOOD ISSUE

DRY STORAGE

RECEIVING

BAKERY

FRZR

BAKERY

REF

INGREDIENT

ASSEMBLY

CORRIDOR

MECH

COLD PRO &

ASSEMBLY

PASSAGE

PRODUCE

ISSUE

MEAT &

DAIRY

ISSUE

FRZR

ISSUE

STOR

JAN

TOOL

CONTROL

EG-1

6x6/75

TAB-3FTAB-2

EG-1

6x6/75

FTAB-3

EG-2

10x10/385

TAB-460x28 SA

FTAB-4

x S

A

20x12 EA

4x31 EA

16x16 EA

6x6 EA

18x16 EA

32x16 EA

24x16 EA

32x16 EA

PANT-LEG WYE FITTING

TO 32x32 EA UP

12x12 EA (TYP.2)

EG-1

6x6/50

EG-2

8x8/200

EG-2

8x8/200

EG-2

8x8/200

EG-2

8x8/200

16x12 SA x S

A

32x16 SA x S

A

TAB-3

FTAB-2

TAB-4

14x12 SA

10x10 SA

FTAB-4

FTAB-3

x E

A

10x10 EA

10x8 EA

12x12 SA

EG-2

8x8/200

10x10 EA

16x14 EA UP TO 12x12 EA

THRU ROOF.

16x12 SA

12x12 RA 10x10 RA x R

A

24x12 RA

40x16 RA x R

A

4ø EA

SD-1

10/220

SD-1

10/220

SD-1

8/110

SD-1

10/230

SD-1

10/235

SD-1

10/230

SD-1

8/120

SD-1

10/245

(TYP.6)

RG-2

10x10/445

RG-2

8x8/210

RG-2

8x8/220

SD-1

10/220

SD-1

10/235

(TYP.2)

RG-2

15x15/700

RG-2

8x8/225 x S

A

48x24 RA

RG-2

10x10/350

(TYP.2)

x S

A

SD-1

12/400

RG-2

8x8/270

RG-2

15x15/680

(TYP.2)

RG-2

8x8/340

RG-2

6x6/110

RG-2

6x6/85

10x10 SA

8x8 SA

20x16 RA

SD-1

10/220

(TYP.8)

SD-1

10/220

(TYP.12)

SD-2

10/300

(TYP.13)

SD-2

12/500

(TYP.13)

SD-1

10/220

(TYP.9)

RG-2

18x18/1000

(TYP.11)

x R

A x R

A

20x20 RA

12x12 EA

SD-1

10/220

RG-2

SD-1

8/165

RG-2

10x10 RA

RG-2

RG-2

x S

A x S

A

36x28 SA

30x12 SA x S

A x S

A

14x14 SA

SD-1

10/230

CONNECT MUFFIN MONSTER/SEWAGE

GRINDER TO FMCS FOR MONITORING

PER CONTROL DIAGRAM 10/M5.1.

REFER TO CIVIL PLAN C401 FOR

LOCATION.

CONNECT GENERATOR TO FMCS FOR

MONITORING PER CONTROL DIAGRAM

9/M5.1. REFER TO E0.2 FOR LOCATION.

CAB-2 CAB-3

15x12 EA (TYP.4)

12x12 EA

12x12 EA

12x12 EA

12x12 EA

44x20 SA

44x16 SA

40x16 RA

UH-1

DS-2

x S

A x S

A

10x12 SA

UH-1

DOAS-1

DS-1

x R

A

8x8 EA x E

A x E

A

8 SG-2

16x8/0

(TYP.2)

SG-2

16x8/0

(TYP.2)

SG-2

16x8/0

(TYP.2)

SG-2

16x8/0

(TYP.2)

SG-2

16x8/0

(TYP.2)

10x12 SA x R

A

7 7 7

7 7

20x14 RA

25x17 RA

12x12 RA

17x15 RA

AREA 'A'

AREA 'B'

HOT PRO &

ASSEMBLY

DISHROOM

P O

T

P A

N W

A S

H

POT & PAN

STOR

LNDRY &

CHEM

STOR

STAFF BREAK

RM

DIRECTOR

OFF

STAFF

RR

CART

WASH

1221A

OFFENDER

BREAK

SUPERVISOR

OFF.

OFFENDER

RR

C A

R T

P A

R K

IN

G

BAKERY

FREEZER

TEMPERING

MEAT & DAIRY

REF.

PRODUCE

REF

INGR & DRY

GOOD ISSUE

DRY STORAGE

RECEIVING

BAKERY

FRZR

BAKERY

REF

INGREDIENT

ASSEMBLY

CORRIDOR

MECH

COLD PRO &

ASSEMBLY

PASSAGE

PRODUCE

ISSUE

MEAT &

DAIRY

ISSUE

FRZR

ISSUE

STOR

JAN

TOOL

CONTROL

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

RFB922300-02

/2

/2

:0 :2

P

M M1.2

LEVEL 01 PLAN -

AREA B -

MECHANICAL

MIKMCC

DAVING

0240202.00

CLARINDA

CORRECTIONAL

FACILITY - KITCHEN &

LAUNDRY ADDITION

STATE OF IOWA - DEPARTMENT

OF CORRECTIONS

2000 N 16TH ST, CLARINDA, IA

51632

02/09/2024

MIKMCC

BID SET

N O R

HT

1/8" = 1'-0"

LEVEL 01 PLAN - AREA B - MECHANICAL1

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2024 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

PROJECT #21007688.00

KEYNOTES:

1. CONNECT 8"⌀ EXHAUST DUCT TO ROTATING

RACK OVEN AND ROUTE UP TO EXHAUST FAN

ON ROOF ABOVE.

2. 12"x12" EA DN TO KITCHEN HOOD RISER.

3. CONNECT EXHAUST DUCT TO DISHWASHER

DUCT RISER.

4. CONNECT EXHAUST DUCT TO DISHWASHER

EXHAUST HOOD RISER.

5. ROUTE 4" ALUMINUM DRYER EXHAUST DUCT

FROM DRYER UP TO ROOF. TERMINATE WITH

DRYER VENT PER DETAIL 5/M4.1.

6. TYPICAL DIFFUSERS REFERS TO ALL

DIFFUSERS SHOWN NORTH TO SOUTH IN

COLUMN.

7. BALANCE DIFFUSER(S)/GRILLE(S) TO LISTED

CFM WHEN THE ASSOCIATED FAN POWERED

TAB IS AT THE MAXIMUM SCHEDULED HEATING

PRIMARY AIRFLOW PLUS TAB FAN CFM.

8. INSTALL ONE SUPPLY GRILLE HIGH AND ONE

SUPPLY GRILLE LOW TO ALLOW CIRCULATION

OF AIR IN PLUMBING CHASE ON OUTSIDE

WALL. COORDINATE GRILLE LOCATION WITH

CMU BLOCKS. BOTTOM GRILLE SHALL BE

INSTALLED WITH CENTER AT 12" AFF AND TOP

GRILLE SHALL BE INSTALLED WITH CENTER AT

92" AFF. COORDINATE GRILLE LOCATIONS

WITH ALL WALL MOUNTED ITEMS.

D

E

F

1 2 3 4 5 6 7 8 9

PA

PB

PC

P5 P4 P3

AA

AB

A1 A2 A3

MECHANICAL

FUTURE

EXPANSION

VESTIBULE

MECHANICAL

OFFICE

M1.1

AHU-A1

B-1E

B-2E B-3E B-4E B-5E

EPO EPO

6"HWR

6"HWS

6"HWS6"HWS

"H

W S

"H

W R

AIR SEPARATOR

5'x4.5' OAL

6"HWR

6"HWR

LOCATION OF EXISTING HEAD END

CONTROLS. EXTEND NEW CONTROLLERS

BACK TO EXISTING HEAD END.

CONNECT PRESSURE BOOSTER SYSTEM

AND WATER SOFTENER SYSTEMS TO

FMCS FOR MONITORING PER CONTROL

DIAGRAM 10/M5.1.

REFER TO 3/M4.2 FOR

ROOF SUPPORT - FAN

CURB DETAIL (TYP.)

18" ALUMINUM DRYER EXHAUST DUCT

TERMINATED WITH GOOSE NECK (TYP. 6).

EF-1

AREA 'A'

AREA 'B'

MECHANICAL

FUTURE

EXPANSION

VESTIBULE

MECHANICAL

OFFICE

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

RFB922300-02

/2

/2

:0 :3

P

M M1.3

LEVEL 02 PLAN -

AREA A -

MECHANICAL

MIKMCC

DAVING

0240202.00

CLARINDA

CORRECTIONAL

FACILITY - KITCHEN &

LAUNDRY ADDITION

STATE OF IOWA - DEPARTMENT

OF CORRECTIONS

2000 N 16TH ST, CLARINDA, IA

51632

02/09/2024

MIKMCC

BID SET

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2024 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

PROJECT #21007688.00

N O R

HT

1/8" = 1'-0"

LEVEL 02 PLAN - AREA A - MECHANICAL1

KEYNOTES:

1. LOCATE FAN 10FT MINIMUM FROM ROOF EDGE

SO RAILING IS NOT REQUIRED.

PD

PE

P5

P4 P3

AB

AC

AD

AE

AF

AG

AH

A1 A2 A4 A5A3

MECH

M3.0

EF-2

EF-3

EF-9

EF-5

EF-6

EF-7

EF-8

INSTALL CONDENSING UNIT PER

CONDENSING UNIT SUPPORT

DETAIL 1/M4.2 (TYP.).

4"⌀ DRYER VENT DN.

REFER TO 5/M4.1 FOR

DRYER VENT DETAIL.

EF-4

CU-2

CU-1A

CU-1B

REFER TO 2/M4.2 FOR

KITCHEN GREASE EXHAUST

FAN DETAIL (TYP.)

LIQ (TYP.2)

SUC (TYP.2)

LIQ (TYP.2)

SUC (TYP.2)

LIQ (TYP.2)

SUC (TYP.2)

AREA 'A'

AREA 'B'

MECH

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

RFB922300-02

/2

/2

:0 :3

P

M M1.4

LEVEL 02 PLAN -

AREA B -

MECHANICAL

MIKMCC

DAVING

0240202.00

CLARINDA

CORRECTIONAL

FACILITY - KITCHEN &

LAUNDRY ADDITION

STATE OF IOWA - DEPARTMENT

OF CORRECTIONS

2000 N 16TH ST, CLARINDA, IA

51632

02/09/2024

MIKMCC

BID SET

N O R

HT

1/8" = 1'-0"

LEVEL 02 PLAN - AREA B - MECHANICAL1

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2024 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

PROJECT #21007688.00

KEYNOTES:

1. LOCATE FAN 10FT MINIMUM FROM ROOF EDGE

SO RAILING IS NOT REQUIRED.

P5

AE

AF

A2 A4A3

MECH

OAL-1

98x28 RA REFER TO 3/M4.1 FOR

LOUVER INSTALLATION

DETAIL (TYP.)

OAL-2

AHU-1 DDC CONTROL

PANEL

DOAS-1 DDC

CONTROL PANEL

40x16 RAAHU-1

DOAS-1

M3.0

M3.0

LOCATE GLOBAL REFERENCE

POINTS FOR FMCS ON NORTH

FACE OF PENTHOUSE

60x28 SA

98x28 OA

30x30 OA

72x72 OA

UH-2

48x24 RA

RAL-1

72x48 EA

168x72 OA

UH-2

LIQ (TYP.2)

SUC (TYP.2)

LIQ (TYP.2)

SUC (TYP.2)

LIQ (TYP.2)

SUC (TYP.2)

x O

A

GV-1

40"X20" OA DUCT DN

TO OPEN AT 1' AFF.

MECH

44x20 SA

72x30 EA

LEVEL 02

16'-6"

A2

ROOF

31'-2"

28x60 SA

28x98 RA

DOAS-1

28x98 OA

OAL-1

72x168 OA

24x48 RA

REFER TO 1/M4.3 FOR

DOAS-1 DETAIL.

3'-0"

10⌀ FLUE

(TYP.2)

A2 A4E-1A3

A2

A3 A4

A2

A3 A4

LEVEL 02

16'-6"

A2

ROOF

31'-2"

RAL-1

16x40 RA x R

A

AHU-1

REFER TO 2/M4.3 FOR

AHU-1 DETAIL.

ALLOW FOR 3'-0"

CLEARANCE TO ACCESS

OPPOSITE SIDE OF AHU.

12x86 SA

20x44 SA

6⌀ FLUE

86x12 RA

CONNECTION

86x18 EA

CONNECTION

86x18 OA

CONNECTION

A2 A3

A2

A3

A2

A3

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

RFB922300-02

/2

/2

:0 :4

P

M M3.0

ENLARGED PLAN -

MECHANICAL

MIKMCC

DAVING

0240202.00

CLARINDA

CORRECTIONAL

FACILITY - KITCHEN &

LAUNDRY ADDITION

STATE OF IOWA - DEPARTMENT

OF CORRECTIONS

2000 N 16TH ST, CLARINDA, IA

51632

02/09/2024

MIKMCC

BID SET

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2024 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

PROJECT #21007688.00

N O R

HT

1/4" = 1'-0"

LEVEL 02 PLAN - AREA B - MECHANICAL ENLARGED PLAN1

1/4" = 1'-0"

SECTION - DOAS-12

1/4" = 1'-0"

SECTION - AHU-13

KEYNOTES:

1. MAINTAIN A 36"X80" MINIMUM CLEAR PATHWAY

BETWEEN LOUVER AND VERTICAL DUCT AT

DOAS-1.

2. INSTALL AHU-1 AND DOAS-1 ON A 4"

HOUSEKEEPING PAD.

3. ROUTE REFRIGERANT PIPING FROM AIR

HANDLING UNIT/DOAS TO CONDENSING UNIT

PER MANUFACTURER RECOMMENDATIONS.

4. INSTALL OUTSIDE AIR FLOW MEASURING

STATION IN STRAIGHT SECTION OF DUCTWORK.

5. CONTRACTOR TO FIT ALL EQUIPMENT AND

SHIPPING SPLITS THROUGH EITHER THE MAIN

MECHANICAL ROOM DOORS OR OAL-1

OPENING. FOR THE LOUVER OPENING SIZE,

REFER TO THE ARCHITECTURAL PLANS.

6. MAINTAIN 36"X80" MINIMUM CLEAR PATHWAY

BETWEEN RETURN DUCT AND FLOOR.

7. GV-1 TO BE LOCATED ON ROOF OF

MECHANICAL PENTHOUSE. REFER TO 3/M4.2

FOR ROOF SUPPORT - FAN/HOOD CURB DETAIL.

8. 6"⌀ FLUE VENT UP THRU ROOF TO

MANUFACTURER'S VENT KIT. REFER TO 4/M4.1

FOR GAS VENT THRU ROOF DETAIL.

9. 10"⌀ FLUE VENT UP THRU ROOF TO

MANUFACTURER'S VENT KIT. REFER TO 4/M4.1

FOR GAS VENT THRU ROOF DETAIL. (TYP.2)

ELBOW WITH 1" LINER

ATTACHED TO NECK OF

FAN POWERED TERMINAL

AIR BOX. (SEE DRAWING

FOR DUCT SIZE.)

SUPPORT DUCTWORK

FROM STRUCTURE

ABOVE, NOT FROM TAB.

X

X

INSULATED ROUND, RIGID SPIRAL

DUCT. MATCH TAB INLET DIAMETER.

MINIMUM 2XINLET DIAMETER. (TYP.)

TYPE B - 1" MERV 4

FILTER AND FILTER

ACCESS FROM BELOW.

NYLON TIE WRAP, TWO REQUIRED

FOR EACH END OF FLEXIBLE DUCT

(TOTAL 4). INSTALL ONE TIE WRAP

TO SECURE THE INNER LINER AND

ONE TO SECURE THE OUTER SHELL. (TYP.)

PRE-MANUFACTURED CONICAL

TAKE-OFF WITH SELF-ADHESIVE

NEOPRENE GASKET (EQUAL TO

SHEET METAL CONNECTORS

CONICAL E-Z TAP)

FASTEN WITH SELF-TAPPING

SHEETMETAL SCREWS (MIN. 4)

CUT DUCT OPENING TO MATCH

LARGER TAKEOFF DIAMETER

INSULATED GALVANIZED DUCT

CUT HELIX AND INNER FABRIC HERE. SECURE

WITH NYLON TIE. OVERLAP FLEX DUCT

MINIMUM OF 2" ONTO RIGID DUCT. PROVIDE

DUCT SEALER AT CONNECTION BETWEEN

FLEX DUCT AND RIGID DUCT.

INSULATED FLEX DUCT

3' MAX.

6" MIN.

. D

DUCT TO RETURN

GRILLES (SEE DRAWING

FOR DUCT SIZE)

-6

V

N O

M

IN

A L

OR 30" MIN.

WIDTH OF EQUIPMENT

FAN

FAN POWERED

TERMINAL AIR BOX.

S.A.

REHEAT COIL 3

-6

V

N O

M

IN

A L

OR 30" MIN.

WIDTH OF EQUIPMENT

FLEX CONNECTOR

CLIP ANGLE AROUND ENTIRE PERIMETER OF LOUVER.

BIRD SCREEN

WALL CONSTRUCTION

EXTERIOR DUCT INSULATION

AS SPECIFIED ON ALL

OUTSIDE AIR DUCTWORK.

SEAL ALL INTERIOR LOWER

SHEET METAL JOINTS

WATERTIGHT WITH MASTIC.

CAULK

20 GAUGE SHEET METAL BLANKOFF ATTACHED TO

ALL UNUSED AREAS OF LOUVER. BACK WITH 2" RIGID

3# DENSITY FIBERGLASS BOARD INSULATION WITH

FOIL SCRIM FACING THE ROOM. SEAL WATERTIGHT.

EXTENDED DRIP SILL BY

OTHERS. SEE

ARCHITECTURAL DRAWINGS

FOR DETAILS OF

INSTALLATION.

20 GAUGE SHEET METAL

ANGLE. BENT TO MATCH

DUCT AND LOUVER.

ANGLE MAY BE

FABRICATED AS PART OF

THE BLANKOFF.

FASTENERS ON

12" STAGGERED

CENTERS.

CAULK ALL

AROUND (TYP.)

18X18

GASKETED

ACCESS

DOOR

CUT OFF LOWER BIRD

SCREEN AND FRAMING. FORM

A MINIMUM 1" ANGLED BEND

OUT OF THE ENTIRE LENGTH

OF RAW BIRD SCREEN EDGE

TO REST ON INSIDE BOTTOM

OF DUCT. FASTEN LOUVER TO CLIP ANGLES ON 18" MINIMUM CENTERS.

MOUNT FACE OF

LOUVER FLUSH

WITH EXTERIOR

FINISH UNLESS

OTHERWISE NOTED.

° (M

IN

IM

U M

(MINIMUM)

24".

NOTES:

1. SEAL ALL JOINTS ON BOTTOM INTERIOR SURFACE OF DUCT WITHIN 6'-0" OF

THE LOUVER WATER TIGHT.

2. MOUNT BOTTOM OF INTAKE LOUVERS AT LEAST 40" ABOVE GRADE OR ROOF

ELEVATION TO MINIMIZE CHANCES OF SNOW DRIFTING INTO THE LOUVER.

3. CAULK SHEETMETAL SCREWS WHERE THEY PENETRATE METAL.

SEAL WATER TIGHT

STORM COLLAR

ROOF DECK

SIZE AS INDICATED

ON PLAN

SEAL AROUND

FLASHING BY

OTHERS.

ROOFING AND

INSULATION

BY OTHERS

TALL CONE FLASHING

BIRD PROOF TOP

36" MINIMUM ABOVE

ROOF. 24" MINIMUM

ABOVE ANY WALL

WITHIN 10'-0" RADIUS

CAP HEIGHT 24"

ABOVE ROOF DECK

STORM COLLAR

TALL CONE ROOF FLASHING.

VENT PIPE DOWN TO DRYER.

MOP WITH TAR AROUND

BASE OF CONE.

RUN ROOFING UP UNDER

FLASHING CONE.

BIRD-PROOF

RAIN CAP

CAP HEIGHT 24"

ABOVE

FINISHED ROOF

D1>D2

45 DEGREE

BUTT FLANGE

STRAIGHT TAP

ENTRY Θ 45°

45 DEGREE CONICAL

CLINCH LOCK

CORNER FILLER

PIECE OR USE

GASKET (TYP.)

45 DEGREE LEAD IN

DOVETAIL JOINT

LINED DUCT CONNECTION

(NO EXPOSED LINER EDGES)

DUCT LINER

FLANGED

NOTE:STRAIGHT TAP WITH BUTT

FLANGE FOR BRANCH AND TEE

CONNECTION IN RECTANGULAR DUCTS

UNDER 1" PRESSURE CLASS ONLY.

ENTRY Θ 45°

D

W

L

Θ

D

(L = 4" OR W/4; WHICHEVER IS LARGER)

NOTES:

1. DO NOT USE CONNECTIONS WITH SCOOPS.

2. FIT ALL CONNECTIONS TO AVOID VISIBLE OPENINGS AND

SECURE THEM SUITABLY FOR THE PRESSURE CLASS.

3. ADDITIONAL MECHANICAL FASTENERS ARE REQUIRED FOR

4"W.G. AND OVER.

4. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

NOTES:

1. THIS DETAIL APPLIES ONLY TO TAPS OFF WRAPPED DUCTS.

2. THIS DETAIL APPLIES TO TERMINAL AIR BOXES WITH ROUND INLETS AND

RECTANGULAR OUTLETS.

3. DUCT LEADING TO TAB INLET MUST BE STRAIGHT FOR 1.5 DIAMETER

UPSTREAM.

4. MAINTAIN VAPOR BARRIER FROM MAIN TO BRANCH DUCT.

NYLON TIE WRAP, TWO REQUIRED

FOR EACH END OF FLEXIBLE DUCT

(TOTAL 4). INSTALL ONE TIE WRAP

TO SECURE THE INNER LINER AND

ONE TO SECURE THE OUTER SHELL. (TYP.)

PRE-MANUFACTURED CONICAL

TAKE-OFF WITH SELF-ADHESIVE

NEOPRENE GASKET (EQUAL TO

SHEET METAL CONNECTORS

CONICAL E-Z TAP)

FASTEN WITH SELF-TAPPING

SHEETMETAL SCREWS (MIN. 4)

CUT DUCT OPENING TO MATCH

LARGER TAKEOFF DIAMETER

INSULATED GALVANIZED DUCT

CUT HELIX AND INNER FABRIC HERE. SECURE

WITH NYLON TIE. OVERLAP FLEX DUCT

MINIMUM OF 2" ONTO RIGID DUCT. PROVIDE

DUCT SEALER AT CONNECTION BETWEEN

FLEX DUCT AND RIGID DUCT.

AIR FLOWTERMINAL AIR BOX

RECTANGULAR INSULATED DUCT

INSULATED FLEX DUCT

INSULATED TRANSITION

REHEAT COIL (IF SCHEDULED),

INSULATE PER SPECIFICATIONS.

3' MAX.

6" MIN.

. D

MAINTAIN MINIMUM WORKING

CLEARANCE TO ELECTRICAL

CONNECTIONS AS REQUIRED BY NFPA

70 (NATIONAL ELECTRIC CODE)

-6

V

N O

M

IN

A L

OR 30" MIN

WIDTH OF EQUIPMENT

INSULATED ROUND, RIGID SPIRAL

DUCT. MATCH TAB INLET DIAMETER.

MINIMUM 2XINLET DIAMETER. (TYP.)

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

RFB922300-02

/2

/2

:0 :4

P

M M4.1

MECHANICAL

DETAILS

MIKMCC

DAVING

0240202.00

CLARINDA

CORRECTIONAL

FACILITY - KITCHEN &

LAUNDRY ADDITION

STATE OF IOWA - DEPARTMENT

OF CORRECTIONS

2000 N 16TH ST, CLARINDA, IA

51632

02/09/2024

MIKMCC

BID SET

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2024 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

PROJECT #21007688.00

NO SCALE

TERMINAL AIR BOX - FAN POWERED SERIES - WRAPPED2

NO SCALE

LOUVER INSTALLATION DETAIL3 NO SCALE

GAS VENT THRU ROOF (MEMBRANE ROOF)4

NO SCALE

DRYER VENT DETAIL5 NO SCALE

BRANCH CONNECTIONS6

NO SCALE

TERMINAL AIR BOX - SINGLE DUCT - WRAPPED1

ELASTOMERIC FLASHING

LAP SEALANT

GREASE TRAP

HINGED COVER

TWO (2) HOUR

FIRE PROTECTION

PREFABRICATED ROOF

CURB FURNISHED

WITH FAN. (WITH

WOOD NAILER AND

INSULATED LINER.)

SINGLE MEMBRANE

ROOFING

SPLICING CEMENT

UNDER FLASHING

FASTENER STRIP

ANCHOR TO CURB

WITH SHEET METAL

SCREWS.

SUBSTRATE ADHESIVE

BETWEEN FLASHING

AND CURB.

AREA TO REMAIN OPEN

TO VENTILATE SHAFT.

RANGE HOOD DUCTWORK

FRAME, ROOF, &

ROOFING BY

OTHERS.

VENT CURB EXTENSION

DISCHARGE HEIGHT

MINIMUM 40" ABOVE ROOF

DECK

NEMA 3R DISCONNECT

WIRED FROM MOTOR TO

DISCONNECT THRU

THE BREATHER TUBE

RANGE HOOD

EXHAUST FAN

NOTES:

1. ALL ROOF FLASHING SHALL BE PER ROOFING

MANUFACTURERS RECOMMENDATIONS.

ATTACH FAN TO CURB

WITH CADMIUM PLATED

LAG SCREWS PER

MANUFACTURERS

RECOMMENDATIONS

FAN OR INTAKE HOOD

FACTORY SUPPLIED

BACKDRAFT DAMPER.

MOTORIZED OR GRAVITY AS

SCHEDULED. DUCTWORK

FLASH ROOF MEMBRANE

TO CURB. (NOTE 1)

PREFABRICATED ROOFCURB

FURN. WITH FAN. (WITH WOOD

NAILER AND INSULATED LINER.)

CADMIUM PLATED LAG SCREWS.

PER MANUFACTURERS

RECOMMENDATIONS

FRAME, ROOF, & ROOFING BY

OTHERS. REFER TO

ARCHITECTURAL PLANS.

EXHAUST FAN CURB HEIGHT 24"

ABOVE ROOF DECK

INTAKE HOOD CURB HEIGHT 36"

ABOVE ROOF DECK.

NOTES:

1. ALL ROOF FLASHING SHALL BE PER ROOFING MANUFACTURERS RECOMMENDATIONS.

NYLON TIE WRAP, TWO REQUIRED

ON ENDS OF FLEXIBLE DUCT.

INSTALL ONE TIE WRAP TO SECURE

THE INNER LINER AND ONE TO

SECURE THE OUTER SHELL. (TYP.)

FOLD UNDER END OF JACKET SO IT

FITS NEATLY UP TO RECTANGULAR

DUCT.

PROVIDE DUCT SEALER ON DUCTS

ABOVE 2" PRESSURE CLASS.

CUT INSIDE CARRIER

DUCT AT THIS POINT.

NYLON TIE WRAP

SEAL INSULATION JOINT WITH A

BEAD OF CAULK TO MAKE AIR

TIGHT SEAL.

FASTEN WITH SELF-TAPPING

SHEETMETAL SCREWS (MIN.4)

PRE-MANUFACTURED TAKE-OFF

WITH SELF-ADHESIVE NEOPRENE

GASKET AND MANUAL BALANCING

DAMPER (EQUAL TO SHEET METAL

CONNECTORS E-Z TAP)

PROVIDE EXTENDED HANDLE FOR

USE WITH 1 1/2" INSULATION. FIT

FLEX DUCT JACKET AROUND

DAMPER OPERATOR AND TAPE AS

REQUIRED FOR NEAT INSTALLATION.

1/2 OF DUCT DIAMETER MINIMUM SO

DAMPER DOES NOT CUT FLEX OR

OBSTRUCT FLOW IN MAIN. (NOTE 2)

CUT DUCT OPENING TO

MATCH

TAKEOFF DIAMETER

EXTERIOR INSULATION

(REFER TO

SPECIFICATION SECTION

23 31 00 - DUCTWORK)

INSULATED FLEX DUCT

GALVANIZED SHEET METAL DUCT

FLANGE

NOTES:

1. THIS DETAIL APPLIES ONLY TO TAPS OFF UNLINED DUCTS.

2. MANUFACTURED TAP/DAMPER COMBINATIONS WITH LESS THAN 1/2 DUCT DIAMETER SPACING BETWEEN THE MAIN

DUCT AND THE DAMPER SHAFT ARE ACCEPTABLE ONLY IF THE DAMPER SHAFT IS INSTALLED PARALLEL TO THE AIR

FLOW IN THE MAIN DUCT.

FLEXIBLE DUCT WRAP WITH VAPOR BARRIER.

SEE SPECIFICATION SECTION 23 07 13 -

DUCTWORK INSULATION)

RIGID INSULATION WITH VAPOR BARRIER.

SEE SPECIFICATION SECTION 23 07 13 -

DUCTWORK INSULATION)

VAPOR SEAL TAPE

VAPOR SEAL TAPE

SECTION

ELEVATION

STRUT SUPPORT

HANGER

RIGID INSULATION VAPOR

BARRIER. SEE SPECIFICATION

SECTION 23 07 13 - DUCTWORK

INSULATION

VAPOR SEAL TAPE

HANGER RODS

ROUND DUCT CLAMP

RIGID INSULATION VAPOR

BARRIER. SEE SPECIFICATION

SECTION 23 07 13 - DUCTWORK

INSULATIONSECTION

ELEVATION

NOTES:

1. DETAIL FOR USE WHERE DUCTS REQUIRE TRAPEZE OR DOUBLE ROD HANGERS (36" DIA. OR EQUIVALENT)

RECTANGULAR

MITERED ELBOW

WITH VANES

TYPE RE2

RECTANGULAR

MITERED ELBOW

TYPE RE6

USE ONLY AS PART OF OFFSETS

AND TRANSITIONS PER FIGURE 4-7

TYPE 2 OR AS SHOWN ON

DRAWINGS. OFFSETS ABOVE 30°

SHALL BE TYPE RE1.

RECTANGULAR

RADIUS ELBOW

TYPE RE1

R/W = 1.0 (MINIMUM)

R/W < 1.0 SHALL BE TYPE

RE3

RECTANGULAR

RADIUS ELBOW WITH VANES

TYPE RE3

REFER TO SMACNA HVAC SYSTEMS DUCT DESIGN MANUAL,

FOURTH EDITION, SECTION 5.14 "SPLITTER VANES" AND SMACNA

HVAC DUCT CONSTRUCTION STANDARDS, THIRD EDITION,

FIGURES 4-2 AND 4-9 AND CHARTS 4-1 AND 4-1M. ELBOW SHALL

HAVE THREE SPLITTER VANES AND r/W = 0.10 (R/W = 0.60) UNLESS

NOTED OTHERWISE.

RECTANGULAR

RADIUS ELBOW WITH

SQUARE THROAT

NOT ALLOWED

RECTANGULAR / OVAL / ROUND

MITERED ELBOW

WITHOUT VANES

TYPE RE4

NOT ALLOWED

OVAL / ROUND

RADIUS ELBOW

SMOOTH OR 5 GORE (MINIMUM)

R/W = 1.5 (MINIMUM)

W W

R

R

W r R 1 R

R R

W

W

E X

C E

E D

N O

T T

O

W

W

90 90

W

W

NOTES:

1. BEAD, CROSSBREAK, AND REINFORCE FLAT SURFACES AS IN

STRAIGHT DUCT.

2. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

3. DEFAULT ELBOW SHALL BE TYPE "RE1".

4. ELBOW TYPES SHALL BE INSTALLED AS SHOWN AND NOT BE

SUBSTITUTED WITHOUT PERMISSION. EXCEPTION: RE1 OR RE3

MAY BE SUBSTITUTED FOR RE2.

LEG OF CONDENSING UNIT.

COUNTER FLASHING.

RESTRAINED VIBRATION ISOLATORS.

LAG SCREW ISOLATOR

INTO WOOD NAILER

PREFAB CURB WITH NAILER.

CURB TO EXTEND 12"

BEYOND UNIT ON BOTH ENDS.

FRAMING, ROOF, & ROOFING

BY OTHERS. REFER TO

ARCHITECTURAL DRAWINGS.

CURB HEIGHT 18"

ABOVE ROOF

DECK

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

RFB922300-02

/2

/2

:0 :4

P

M M4.2

MECHANICAL

DETAILS

MIKMCC

DAVING

0240202.00

CLARINDA

CORRECTIONAL

FACILITY - KITCHEN &

LAUNDRY ADDITION

STATE OF IOWA - DEPARTMENT

OF CORRECTIONS

2000 N 16TH ST, CLARINDA, IA

51632

02/09/2024

MIKMCC

BID SET

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2024 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

PROJECT #21007688.00

NO SCALE

FAN - KITCHEN GREASE EXHAUST FAN2

NO SCALE

ROOF SUPPORT - FAN/HOOD CURB3

NO SCALE

FLEX DUCT CONNECTION (STRAIGHT/WRAPPED)4

NO SCALE

TRAPEZE HANGER DUCT WRAP VAPOR SEAL5

NO SCALE

ELBOW CONSTRUCTION6

NO SCALE

CONDENSING UNIT SUPPORT

(MEMBRANE

ROOF)1

262 45 8

TOP VIEW

PROFILE VIEW

98x26 RETURN AIR

DAMPER AND OPENING

98x26 OUTSIDE AIR

DAMPER AND OPENING

98x26 RETURN AIR

DAMPER AND OPENING

98x26 OUTSIDE AIR

DAMPER AND OPENING

8 2 4

3 10

12 6 5 8

18 18

108x24 SUPPLY AIR

OPENING

108x24 SUPPLY AIR

OPENING

VFD

VFD

TOP VIEW

PROFILE VIEW

SPLIT SPLIT

SPLIT

SPLIT

SPLIT

SPLIT SPLIT

6 19 20

21 22 19 8

86x18 OUTDOOR AIR

DAMPER AND OPENING

86x18 OUTDOOR AIR

DAMPER AND OPENING

86x18 EXHAUST AIR

DAMPER AND OPENING

86x18 EXHAUST AIR

DAMPER AND OPENING

86x12 RETURN AIR OPENING

86x12 RETURN AIR OPENING

86x12 SUPPLY AIR OPENING

86x12 SUPPLY AIR OPENING

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

RFB922300-02

/2

/2

:0 :4

P

M M4.3

MECHANICAL

DETAILS

MIKMCC

DAVING

0240202.00

CLARINDA

CORRECTIONAL

FACILITY - KITCHEN &

LAUNDRY ADDITION

STATE OF IOWA - DEPARTMENT

OF CORRECTIONS

2000 N 16TH ST, CLARINDA, IA

51632

02/09/2024

MIKMCC

BID SET

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2024 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

PROJECT #21007688.00

NO SCALE

DOAS-1 DETAIL1 NO SCALE

AHU-1 DETAIL2

KEYNOTES:

1. 8" BASERAIL.

2. DX COOLING COIL.

3. INDIRECT FIRED NATURAL GAS HEATING COIL.

4. CENTRIFUGAL PLENUM SUPPLY FAN.

5. ACCESS DOOR, MINIMUM WIDTH OF 12".

6. ACCESS DOOR, MINIMUM WIDTH OF 16".

7. ACCESS DOOR, MINIMUM WIDTH OF 24".

8. ACCESS DOOR, MINIMUM WIDTH OF 30" OR LARGER IF REQUIRED FOR FAN

ACCESS AND MOTOR REMOVAL.

9. MIXING BOX WITH ANGLED FILTER SECTION, MERV 8 FILTERS.

10. DISCHARGE PLENUM.

11. DAMPERS OVER THE SINGLE STAGE HEATING COIL SECTIONS (QUANTITY: 3).

NO COIL OVER MODULATING COIL.

12. ACCESS DOOR, MINIMUM WIDTH OF 28" OR LARGER IF REQUIRED FOR FILTER

REMOVAL.

13. VERTICAL ECONOMIZER SECTION.

14. CENTRIFUGAL PLENUM RETURN FAN.

15. MERV 8 FILTER RACK.

16. 6"⌀ STAINLESS STEEL FLUE.

17. 10"⌀ STAINLESS STEEL FLUE.

18. MODULE TO CONTAIN LED MARINE LIGHTS.

19. ACCESS DOOR, MINIMUM WIDTH OF 14".

20. ACCESS DOOR, MINIMUM WIDTH OF 28" OR LARGER IF REQUIRED FOR FAN

ACCESS AND MOTOR REMOVAL.

21. ACCESS DOOR, MINIMUM WIDTH OF 18" OR LARGER IF REQUIRED FOR FILTER

REMOVAL.

22. ACCESS DOOR, MINIMUM WIDTH OF 10".

23. ACCESS DOOR, MINIMUM WIDTH OF 20".

DI

DO

DI

AI AI

AI

AI

AO

AO

AI

T

DO

AI

T

AI

AIAO

AI

AO

T

T

DO

DI

DO

DI

DO

DI

DI

DI DI DI DI AI

AI AIAI DI

AI DO

DIDI

DIDIDIDI DI DI

DISHWASHER

EXHAUST

EXHAUST

FAN

CS

FAN

STATUS

DISHWASHER

REMOTE FAN

CONTROL

CONTACTS

ACT

START/

STOP

SEQUENCE OF OPERATION:

FMCS SHALL MONITOR CONTACTS THAT ARE PART OF THE DISHWASHER

CONTROLS TO DETERMINE WHEN THE DISHWASHER CONTROLS ARE CALLING FOR

REMOTE EXHAUST FAN START/STOP COMMANDS.

WHEN THE DISHWASHER CONTROLS CALL FOR REMOTE FAN START, FMCS SHALL

ENERGIZE DISHWASHER EXHAUST FAN. WHEN DISHWASHER CONTROLS CALL FOR

REMOTE FAN STOP, FMCS SHALL DE-ENERGIZE DISHWASHER EXHAUST FAN AFTER

30 MINUTES (ADJ.) TO ALLOW DUCTWORK TO DRY.

2-POSITION DAMPER SHALL FULLY OPEN WHEN FAN IS ENERGIZED. WHEN FAN IS

DE-ENERGIZED, 2-POSITION DAMPER SHALL FULLY CLOSE.

EXHAUST FAN MAY ALSO BE ENABLED/DISABLE PER DOAS-1 CONTROL SEQUENCE.

COMMAND FROM DOAS-1 SEQUENCE MAY NOT DISABLE FAN IF DISHWASHER

CONTROLS ARE CALLING FOR FAN TO RUN.

ALARMS, INTERLOCKS AND SAFETIES:

AN ALARM SHALL BE GENERATED AT THE FMCS OPERATOR WORKSTATION IN THE

EVENT THE FMCS COMMANDS THE EXHAUST FAN TO OPERATE AND THE CURRENT

SENSING RELAY DETECTS INSUFFICIENT CURRENT DRAW.

SEQUENCE OF OPERATION:

PROVIDE GLOBAL O.A. DRY-BULB TEMPERATURE, OUTSIDE AIR REFERENCE

PRESSURE, AND RELATIVE HUMIDITY TRANSMITTERS.

OUTSIDE AIR PRESSURE SHALL BE INSTALLED ON ALL FOUR SIDES OF THE BUILDING

AND PIPED WITH EQUAL LENGTHS OF 1/4" TUBING TO A PIPE MANIFOLD. PIPING BY TCC.

LOCATIONS TO BE DETERMINED PER MANUFACTURER'S RECOMMENDATIONS AND

ENGINEER'S APPROVAL. TCC SHALL PRIME AND PAINT THE DEVICE ENCLOSURE.

GLOBAL SENSORS SHALL CONTINUOUSLY UPDATE FMCS FOR USE IN CONTROLLING

MECHANICAL EQUIPMENT AS REQUIRED IN SEQUENCES OF OPERATION.

MOUNT ON NORTH FACE OF BUILDING.

VERIFY FINAL INSTALLATION LOCATION

WITH ENGINEER UNLESS SHOWN ON

DRAWINGS FOR EXACT LOCATION.

GLOBAL O.A.

TEMP SENSOR

W/ SUNSHIELD

GLOBAL O.A.

RELATIVE

HUMIDITY

SENSOR

GLOBAL AIR

PRESSURE

SENSOR

H P

T

SUPPLY

AIR TEMP

ACTVELOCITY AND

STATIC SENSOR

DAMPER ACTUATORDAMPER

MOD.

TAB

AIRFLOW

PRIMARY AIR FROM ZONE

CONDITIONING AHU

SUPPLY

AIR

PLENUM AIR

START/

STOP

PRESSURE INDEPENDENT

TERMINAL AIR BOX (TAB)

WALL MTD

TEMP SENSOR

SEQUENCE OF OPERATION:

• FMCS TAB CONTROLLER SHALL MODULATE THE TAB DAMPER, TAB ELECTRIC REHEAT COIL, AND FAN, TO MAINTAIN SPACE TEMPERATURE OF 72°F (ADJ.) WITH 5°F (ADJ.) DEAD BAND BASED ON A SIGNAL FROM A WALL MOUNTED TEMPERATURE SENSOR. SEE DRAWINGS FOR TEMPERATURE SENSOR REQUIREMENTS.

SPACES WITH ADJUSTABLE THERMOSTATS WILL ALLOW A +/- 3°F (ADJ.) OFFSET FROM THE DDC

SETPOINT.

• AT FULL COOLING, THE TAB SHALL BE OPEN TO MAXIMUM CFM POSITION. THE REHEAT COIL SHALL BE

DE-ENERGIZED AND THE SUPPLY FAN SHALL BE OFF.

• UPON A FALL IN SPACE TEMPERATURE, THE TAB SHALL MODULATE CLOSED UNTIL SPACE SETPOINT IS MAINTAINED, OR UNTIL IT REACHES ITS MINIMUM SCHEDULED CFM POSITION PER THE TAB SCHEDULE.

THE REHEAT COIL SHALL BE DE-ENERGIZED AND THE SUPPLY FAN SHALL BE OFF.

• UPON A FURTHER FALL IN SPACE TEMPERATURE THE SUPPLY FAN SHALL BE ENERGIZED. THE REHEAT COIL SHALL REMAIN DE-ENERGIZED AND THE TAB DAMPER SHALL REMAIN AT MINIMUM SCHEDULED CFM

POSITION PER THE TAB SCHEDULE.

• ON A FURTHER REDUCTION THE REHEAT COIL SHALL BE ENERGIZED AND MODULATE TO MAINTAIN

SPACE SETPOINT.

• THE FMCS SHALL UTILIZE OUTPUT FROM ALL TERMINAL AIR BOX POSITIONS TO RESET THE…