Text version
One each: Cooper Power Systems Voltage Regulator Catalog # VRF383KCL7100006JR
Cooper Power Systems Catalog No. VRF383KCL7100006JR Voltage Regulator:
Regulator Identifier WF383K008N00R002VR Voltage (V) 7260 Amperage (A) 1093 kVA 833/933 1111/1244 Frequency (Hz) 60 BIL (kV) 110 Temperature Rise (°C) 55/65 Style Substation Cooling Class ONAN/ONAF Fluid Type Mineral Oil Phase Quantity Single Phase Set Voltage (V) 7200 IDPT Included Design Type Type A Short Circuit Requirement Designed for lesser of 25x rated of 16kA max short circuit withstand Tap Changer QD8 (T875) Aux Windings Fan Winding Bushing Terminals & Connectors 4-hole spade connectors, qty 3 Series Arrester 3kV MOV-type arrester Shunt Arrester(s) Arrester(s) included Shunt Arrester Rating {kV) 10 Shunt Arrester Class Intermediate Shunt Arrester Bracket Material Mild steel Shunt Arrester Location L bushing only, qty 1 Loss Guarantee Type For reference only Loss Type Low (2018) Tank Material All mild steel Substation Base Base included Hanger Brackets No hanger brackets Tank Hardware Drain valve w/ sampler, Upper fill plug Ground Provisions 2-hole ground pads (qty 2 on opposite corners of tank) Liquid Sight Glass Included, qty 1 Liquid Sight Glass Placement Critical level Liquid Temperature Gauge Dial-type Liquid Temperature Gauge Contacts 2 sets Pressure Relief Valve Included, w/ pull ring Coating Color ANSI 70 Gray - Munsell 5BG7.0/0.4 Nameplate Material Aluminum Nameplate Units Standard Language Package English Pallet Standard 2-way lift Control Mounting Location Standard
Control Identifier CL7E00000A1000T5
Control Type CL-7 Control Usage Single-phase Control Language English Tap Changer Capacitor Location External Tap Changer Capacitor (µF) 50 Cable Conductors 14-pin VR1 Cable 1Oft. (3m) Port 1 Communications Card None Port 1 Protocol DNP, IEC 60870-5, 2179, MODBUS Serial & MODBUS TCP/IP Port 2 Communications Card None Port 2 Protocol DNP, IEC 60870-5, 2179, MODBUS Serial & MODBUS TCP/IP Reverse Power Flow Capabilities Included Control Box Material Mild steel Control Box Size Standard Control Box Rating NEMA 3R VR Cable Entry Bottom Control Box Grounding #6-250MCM Notes/Comments/Clarifications:
All regulators will be provided with a bypass (series) arrester connected across the series winding and an oil sight gauge.