Renovate MRI Suite - Full Set Drawings.pdf
PDF 29 MB Posted
- Solicitation number
- 36C24421B0006
About this file
This solicitation is for renovating MRI suites at the Philadelphia VA Medical Center. The project includes demolishing existing structures and systems in the MRI rooms and related spaces, installing new electrical, HVAC, fire suppression, and structural systems, and upgrading MRI equipment. Bidders must be service-disabled veteran-owned small businesses verified through the Center for Veterans Enterprise. The work is to be completed within 270 calendar days of receiving notice to proceed. Interested contractors must be able to provide performance and payment bonds and a 20% bid guarantee. The solicitation and drawings will be available on SAM.gov on or after February 2, 2020. The award will be a firm fixed-price contract contingent on FY21 funding availability.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Abstract of Offers 3-24-2021.pdf | ||
| 36C24421B0006 0004.docx | DOCX document | |
| S102 revised for Addendum 1 dated 3-16-2021.pdf | ||
| 36C24421B0006 0003.docx | DOCX document | |
| Bid Sheet.pdf | ||
| 36C24421B0006 0002.docx | DOCX document | |
| 36C24421B0006 0001.docx | DOCX document | |
| Photo 1.pdf | ||
| Avanto Final Upgrade Drawings 25JUL2006.pdf | ||
| EXHIBIT B Ground Floor Conduit Pathway.pdf | ||
| 180801D AD101 Demolition Plan and Sections AD103.pdf | ||
| AD103 new for Addendum 1.pdf | ||
| Site Visit Sign-In Sheet 02.10.2021.pdf | ||
| Bid Sheet.docx | DOCX document | |
| GI101 revised for Addendum 1.pdf | ||
| EXHIBIT C Bldg 2 Floor 3 locating EC 3A180.pdf | ||
| Espree Final Drawings 06JUN19.pdf | ||
| EXHIBIT A 4th Floor Interstitial Conduit Pathway.pdf | ||
| Photo 2.pdf | ||
| FS2 120 PARTIAL 3RD FLR Layout 1.pdf | ||
| 180801D G101 COVER SHEET.pdf | ||
| 36C24421B0006_2.docx | DOCX document | |
| Renovate MRI Suites - Full Set Specifications.pdf | ||
| MRI Suites - S02 Brand Name or Equal.pdf | ||
| Calculation of Self Performed Work.pdf |
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VHAPHISCHULF
Text Box M
Line
VHAPHISCHULF
Line
Polygon
VHAPHISCHULF
Text Box R3"
VHAPHISCHULF
Text Box
TAPESTRY
EXISTING
VIKING
TOTALPAC 2
RELEASING
PANEL
FIRE ALARM SYSTEM ABBREVIATIONS
A ALHPA-NUMERIC
ACT ACOUSTICAL CEILING TILE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ASC AGENT STORAGE
CONTAINER
ASFP AIR SAMPLING DETECTOR
PANEL
CA CLEAN AGENT
CO2 CARBON DIOXIDE
CONC CONCRETE
CRAC COMPUTER ROOM AIR
CONDITIONER
CRAH COMPUTER ROOM AIR
HANDLER
DCH DRY CHEMICAL
DL DELUGE
DMC DISCONNECTING MEANS
CONTROL
EOL END OF LINE DEVICE
EPO EMERGENCY POWER OFF
ETR EXISTING TO REMAIN
EWFD EARLY WARNING FIRE
DETECTION
FA FIRE ALARM
FAA FIRE ALARM ANNUNCIATOR
PANEL
FAC FIRE ALARM
COMMUNICATOR
FACP FIRE ALARM CONTROL
PANEL
FO FOAM
FP FIRE PUMP
FSA FIRE SYSTEM ANNUNCIATOR
FSCP FIRE SYSTEM CONTROL
PANEL
FTR FIRE ALARM TRANSMITTER
G GRAPHIC
HL HALON
HVAC HEATING, VENTILATION AND
AIR CONDITIONING
MAX MAXIMUM
MIN MINIMUM
MT METAL TILE
N.C. NORMALLY CLOSED
(CONTACT)
N.O. NORMALLY OPEN (CONTACT)
NAC NOTIFICATION APPLIANCE
CIRCUIT
NIC NOT IN CONTRACT
NTS NOT TO SCALE
PA PRE-ACTION SYSTEM
PF FIRE PUMP POWER FAIL
PH FIRE PUMP PHASE
REVERSAL
PL PLASTER
PMO FIRE PUMP CONTROLLER -
MANUAL OFF
POC POINT OF CONNECTION
PR FIRE PUMP RUN
PRV PRESSURE
REGULATING/RELIEF VALVE
RA RETURN AIR (HVAC)
RF RADIO FREQUENCY
RTU ROOF TOP UNIT
RX REMOVE EXISTING DEVICE
SA SUPPLY AIR (HVAC)
SLC SIGNALING LINE CIRCUIT
SPL HIDDEN SPLINE (CEILING)
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
VEWFD VERY EARLY WARNING FIRE
DETECTION
WCH WET CHEMICAL
WM WATER MIST
WP WEATHER PROOF
1. MODIFY EXISTING GAMEWELL-FCI E3 SERIES EMERGENCY EVACUATION
FIRE ALARM SYSTEM TO ACCOMMODATE EQUIPMENT UPGRADES
THROUGHOUT THE MRI SUITES LOCATED ON FLOOR 3 (NORTHEAST
WING) OF BUILDING 2.
2. PROVIDE ALL NECESSARY MATERIALS AND LABOR TO MODIFY THE
EXISTING SYSTEM, AS DESCRIBED IN THE PROJECT SPECIFICATIONS
AND CONTRACT DRAWINGS.
3. EXISTING FIRE ALARM DEVICES SHALL REMAIN IN SERVICE UNTIL NEW
DEVICES HAVE BEEN TESTED AND ACCEPTED BY THE AHJ. EXISTING
SMOKE DETECTORS SHALL BE PROTECTED DURING CONSTRUCTION TO
AVOID FALSE ALARMS.
4. ALL REFERENCE TO THE AUTHORITY HAVING JURISDICTION (AHJ) SHALL
MEAN THE PHILADELPHIA VETERAN AFFAIRS MEDICAL CENTER (VAMC)
SAFETY OFFICER.
5. ALL REFERENCE TO THE ENGINEER SHALL MEAN KOFFEL ASSOCIATES,
INC.
6. ALL REFERENCE TO THE OWNER SHALL MEAN THE VA.
7. OCCUPANT NOTIFICATION THROUGHOUT THE RENOVATED AREAS
SHALL BE PROVIDED BY VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS
CONSISTENT WITH THE EXISTING SYSTEM.
8. COORDINATE BETWEEN MECHANICAL, ELECTRICAL, AND OTHER
TRADES. FINAL CONNECTION AND TESTING OF THE FIRE ALARM
SYSTEM SHALL BE COORDINATED WITH THE APPROPRIATE
SUBCONTRACTOR(S).
9. FIRE ALARM AND DETECTION SYSTEM AND ASSOCIATED COMPONENTS
SHALL COMPLY WITH THE FOLLOWING:
· NFPA 70
, NATIONAL ELECTRICAL CODE
(NEC), 2017 EDITION
· NFPA 72
, NATIONAL FIRE ALARM AND SIGNALING CODE
, 2016 EDITION
· NFPA 101
, LIFE SAFETY CODE
, 2018 EDITION
· VA FIRE PROTECTION DESIGN MANUAL (VAFPDM) SEVENTH EDITION,
DECEMBER 2015
· APPLICABLE LOCAL AND STATE CODES AND REGULATIONS
· THE MANUFACTURER'S REQUIREMENTS
10. UNO, ALL AREAS SHALL BE ASSUMED TO BE PROVIDED WITH A MINIMUM
AMBIENT TEMPERATURE OF 40 DEGREES FAHRENHEIT AND BE FREE OF
EXCESSIVE DUST PARTICLES OR HUMIDITY LEVELS.
11. REFER TO THE FIRE ALARM OPERATIONAL MATRIX ON THIS SHEET FOR
SYSTEM FUNCTION REQUIREMENTS.
12. FIRE ALARM SYSTEM CIRCUITS AND EVACUATION MESSAGING SCHEME
SHALL MATCH EXISTING AND CONFORM TO THE FOLLOWING:
· SIGNALING LINE CIRCUITS (SLC): CLASS B
· NOTIFICATION APPLIANCE CIRCUITS (NAC): CLASS B
13. ALL NEW FIRE ALARM SYSTEM WIRING SHALL BE U.L. LISTED METALLIC
CONDUIT MINIMUM OR SURFACE METAL RACEWAY. SIZE OF CONDUIT
AND PERCENT FILL SHALL BE DETERMINED BY THE CONTRACTOR AND
SHALL BE IN ACCORDANCE WITH NFPA 70. ALL NEW FIRE ALARM
WIRING SHALL BE INSTALLED IN CONDUIT OR RACEWAY THAT IS
SEPARATE FROM ALL OTHER SYSTEMS.
14. ALL NEW FIRE ALARM CONDUIT AND JUNCTION BOXES SHALL BE
INSTALLED AS HIGH AS POSSIBLE. IN NO CASE SHALL ANY PORTION OF
THE FIRE ALARM WIRING BE INSTALLED BELOW THE BOTTOM
HORIZONTAL PLANE OF LIGHTING FIXTURES, WITH THE EXCEPTION OF
DROPS TO INDIVIDUAL FIRE ALARM DEVICES. IN AREAS WITH
SUSPENDED CEILINGS ALL FIRE ALARM CONDUIT OR SURFACE METAL
RACEWAY SHALL BE CONCEALED. ALL CONCEALED CONDUIT SHALL BE
RED. PROVIDE ACCESS PANELS FOR ALL CONCEALED FIRE ALARM
DEVICES AND JUNCTION BOXES, WHERE REQUIRED.
15. ALL NEW WALL-MOUNTED AUDIBLE AND/OR VISUAL NOTIFICATION
APPLIANCES SHALL BE MOUNTED A MINIMUM OF 80 INCHES AND A
MAXIMUM OF 96 INCHES ABOVE THE FINISHED FLOOR, PER NFPA 72.
16. NEW PENETRATIONS OF FIRE-RATED ASSEMBLIES SHALL BE SEALED
WITH A U.L. CERTIFIED THROUGH-PENETRATION SYSTEM APPROPRIATE
FOR THE RATING OF THE WALL PENETRATED. REFER TO SHEET GI102
FOR WALL RATINGS.
17. CONDUCT A FULL ACCEPTANCE TEST OF ALL NEW INITIATING DEVICES
REQUIRED AS PART OF THIS PROJECT. EVERY NEW INITIATING DEVICE
SHALL BE TESTED FOR ACTIVATION OF THE NOTIFICATION APPLIANCES
AS WELL AS TRANSMISSION OF SIGNAL IDENTIFICATION TO THE
OUTSIDE MONITORING STATION. IN ADDITION, ANY EXISTING CIRCUIT
THAT IS MODIFIED SHALL HAVE AT LEAST 10 PERCENT OF ITS
RESPECTIVE DEVICES RE-TESTED.
18. PROVIDE ALL MATERIALS AND TECHNICAL SUPPORT TO PERFORM
ACCEPTANCE TEST IN ACCORDANCE WITH NFPA 72. SYSTEM
ACCEPTANCE TESTING SHALL BE WITNESSED BY THE AHJ. ALL
SUPERVISORY AND TROUBLE ALARMS SHALL BE CLEARED BEFORE THE
SYSTEM IS ACCEPTED.
19. ALL NEW FIRE ALARM DEVICES SHALL BE LABELED WITH THEIR
SPECIFIC DEVICE ADDRESS SUCH THAT THEY ARE VISIBLE FROM THE
FLOOR. COORDINATE ALL NEW DEVICE ADDRESSES WITH THE AHJ
PRIOR TO PROGRAMMING INTO THE SYSTEM.
20. ALL NEW FIRE ALARM DEVICES SHALL BE COMPATIBLE WITH THE
EXISTING GAMEWELL-FCI E3 SERIES SYSTEM. NEW NOTIFICATION
APPLIANCES SHALL BE MANUFACTURED BY SYSTEM SENSOR TO MATCH
EXISTING AND ENSURE SYNCHRONIZATION.
FIRE ALARM PROJECT NOTES:
FIRE ALARM NOTES,
ABBREVIATIONS, AND SYMBOLS
FA1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
BID DOCUMENTS
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
Phase
STAMP
CONSULTANTS
321 4 5 6 7 8 9 10
Project Director
08/07/20
Revisions: Date:
RENOVATE MRI SUITE FOR
EQUIPMENT UPGRADES
ARCHITECTURE
PLANNING
ENGINEERING
BURDETTE KOEHLER MURPHY &
ASSOCIATES, INC.
MECHANICAL / ELECTRICAL ENGINEERS
BLAIR HILL LANE, SUITE 400
BALTIMORE, MARYLAND 21209
410.323.0600 - FAX 410.377.2543
BUILDING COST CONSULTANTS
COST ESTIMATING
12917 - 30TH AVENUE
PLATTSMOUTH, NEBRASKA 68048
402.298.8260 - FAX 402.298.8290
RICKERT ENGINEERING, INC.
STRUCTURAL ENGINEERING
8813 WALTHAM WOODS ROAD, SUITE 301
BALTIMORE, MARYLAND 21234
410.663.5110 - FAX 410.663.5114
35OfDwg.
DELLC Project Number : 180801D
ARCHITECT/ENGINEER OF RECORD
642-CSI-117
321 4 5 6 7 8 9 10
A
B
C
D
E
F
CORPORAL MICHAEL J. CRESCENZ
VA MEDICAL CENTER
PHILADELPHIA, PA
08/07/2020
8815 Centre Park Drive, Suite 200 Columbia, Maryland 21045
410-750-2246 / www.koffel.com
FIRE PROTECTION ENGINEERING
8815 CENTRE PARK DR., SUITE 200
COLUMBIA, MARYLAND 21045
410.750.2246 - FAX 410.750.2588
KOFFEL ASSOCIATES, INC.
BID DOCUMENTS
BUILDING FULLY SPRINKLERED
MLD KLC
FIRE ALARM CONTROL PANEL
VOICE EVACUATION PANEL
GRAPHIC ANNUNCIATOR PANEL
REMOTE COMMAND UNIT
ADDRESSABLE INPUT MODULE
(MONITOR MODULE)
ADDRESSABLE OUTPUT MODULE
(CONTROL/RELAY MODULE)
NAC POWER EXTENDER PANEL
ADDRESSABLE NOTIFICATION MODULE
DUCT DETECTOR REMOTE TEST STATION
FIRE ALARM TERMINAL CABINET
FIRE ALARM AMPLIFIER
ROOM TEMPERATURE SENSOR
REMOTE FIRE ALARM CONTROL PANEL
FIRE ALARM SPEAKER
(SUBSCRIPT "C" DENOTES CEILING-MOUNTED)
FIRE ALARM HORN/STROBE
(SUPERSCRIPT DENOTES CANDELA RATING;
(SUBSCRIPT "WP" DENOTES WEATHER PROOF)
VISIBLE NOTIFICATION APPLIANCE
(SUPERSCRIPT DENOTES CANDELA RATING)
COMBINATION FIRE ALARM SPEAKER/STROBE
(SUPERSCRIPT DENOTES CANDELA RATING;
SUBSCRIPT "C" DENOTES CEILING-MOUNTED)
ALARM BELL
WATER MOTOR GONG
ELECTRO-MAGNETIC DOOR HOLDER
FIRE DAMPER
COMBINATION FIRE/SMOKE DAMPER
AREA NOT IN CONTRACT
RATE COMPENSATION HEAT DETECTOR
COMBINATION FIXED TEMPERATURE
AND RATE OF RISE HEAT DETECTOR
PHOTOELECTRIC SMOKE DETECTOR
PHOTOELECTRIC SMOKE DETECTOR WITH
INTEGRATED RELAY BASE
ADDRESSABLE DUCT SMOKE DETECTOR WITH
INTEGRAL RELAY - SUPPLY
(SUBSCRIPT DENOTES AIR HANDLING UNIT ID
AND NUMBER)
ADDRESSABLE DUCT SMOKE DETECTOR WITH
INTEGRAL RELAY - RETURN
(SUBSCRIPT DENOTES AIR HANDLING UNIT ID
AND NUMBER)
ADDRESSABLE DUCT SMOKE DETECTOR WITH
INTEGRAL RELAY
(SUPERSCRIPT DENOTES SMOKE DAMPER)
NEW POINT OF CONNECTION TO EXISTING
CIRCUIT
CARBON MONOXIDE DETECTOR
FLOW SWITCH
PRESSURE SWITCH
WATER PRESSURE SWITCH
LOW AIR PRESSURE SWITCH
HIGH AIR PRESSURE SWITCH
COMBINATION HIGH/LOW
AIR PRESSURE SWITCH
TAMPER SWITCH
VALVE WITH TAMPER SWITCH
MANUAL PULL STATION
HEAT DETECTOR
FIXED TEMPERATURE HEAT DETECTOR
RATE OF RISE HEAT DETECTOR
R
F
F
LH
HA
LA
W
FACP
GAP
RCU
AIM
AOM
NAC
EOL
XX
P,RB
P
R/F
R/C
XX
RTS
S
C
FIRE ALARM LINETYPES:
TYPICAL NEW DEVICE
TYPICAL EXISTING DEVICE TO REMAIN
TYPICAL EXISTING DEVICE TO BE REMOVED
FATC
XX
C
AMP
XX
WP
AHU-X
R
AHU-X
SD
EVAC
RT
PRIOR TO START OF WORK, CONTRACTOR SHALL PERFORM A FULL FUNCTIONAL TEST OF
THE EXISTING GAMEWELL-FCI E3 SERIES FIRE ALARM SYSTEM PER CHAPTER 14 OF NFPA 72.
ANY DEFECTS IN THE EXISTING SYSTEM/CIRCUITS SHALL BE DOCUMENTED AND REPORTED
TO THE VA CONTRACTING OFFICER IMMEDIATELY. ALL TESTING SHALL BE COORDINATED
WITH THE PHILADELPHIA VAMC SAFETY OFFICER. OTHERWISE, ANY DEFECTIVE CIRCUITS
FOUND WILL BE PRESUMED TO BE THE RESPONSIBILITY OF THE CONTRACTOR.
FIRE ALARM SYSTEM SYMBOLS:
PRE-CONSTRUCTION NOTE:
EXISTING
REMOTE
POWER
SUPPLY
FACP
120 V
EXISTING
AMP
PANEL
(3A180 -
ELEC CLOSET)
EXISTING
NAC
PANEL
C CC
EXISTING
FATC
#6
120 V
EXISTING
RFACP
#7
(NODE 32)
120 V (3A180 - ELEC
CLOSET)
(3A180 - ELEC
CLOSET)
TO MAIN FACP
F
P
AIM AOM EOL
120 V (4A100 - MECH
CLOSET)
EOL
EOL
P P
EOL
BUILDING 2 -
4TH FLOOR
BUILDING 2 -
3RD FLOOR
FIRE ALARM RISER GENERAL NOTES:
1. RISER IS INTENDED TO SHOW GENERAL SYSTEM ARCHITECTURE
AS IT RELATES TO THIS PROJECT. DIAGRAM REPRESENTS
MULTIPLE TYPICAL DEVICES, APPLIANCES, AND CIRCUITS.
2. CONTRACTOR IS RESPONSIBLE FOR VERIFYING QUANTITY AND
LOCATION OF ALL EXISTING FIRE ALARM PANELS AND DEVICES.
3. CONTRACTOR IS RESPONSIBLE FOR VERIFYING LOCATION OF ALL
NEW CONNECTIONS OF NEW DEVICES.
4. CONTRACTOR MAY RE-USE EXISTING NAC OR AUDIO CIRCUITS OR
CREATE NEW CIRCUITS FROM SPARE EXISTING REMOTE POWER
SUPPLIES.
FIRE ALARM RISER
FA1 NTS
FIRE ALARM MATRIX
FA1 NTS
RFACP
AutoCAD SHX Text 2215 Conowingo Rd, Suite 100 Bel Air, Maryland 21015-1457 410.836.6611
AutoCAD SHX Text
35% SUBMISSION
AutoCAD SHX Text
70% SUBMISSION
AutoCAD SHX Text
100% SUBMISSION
AutoCAD SHX Text
100% RESUBMISSION
AutoCAD SHX Text 01/14/19
AutoCAD SHX Text 06/29/20
AutoCAD SHX Text 04/27/20
AutoCAD SHX Text 05/24/19
AutoCAD SHX Text
75% SUBMISSION
AutoCAD SHX Text 07/15/19
AutoCAD SHX Text
BID SUBMISSION
AutoCAD SHX Text 08/07/20
AutoCAD SHX Text
100% RESUBMISSION
AutoCAD SHX Text 07/27/20
E F G
EXISTING MRI PRE-ACTION
FIRE ALARM ZONE
EXISTING MRI PRE-ACTION
FIRE ALARM ZONE
C
P
P
P
PP
P
P
P
P
P
P
P
C
C
C
C
C
FIRE ALARM PLAN - THIRD FLOOR -
DEMO/EXISTING
1/4" = 1'-0"
FIRE ALARM PLAN - THIRD FLOOR - DEMO/EXISTING1
FA2
1. UNO, EXISTING FIRE ALARM SYSTEM INFRASTRUCTURE SHALL REMAIN.
2. COORDINATE REMOVAL AND REPLACEMENT OF EXISTING FIRE ALARM DEVICES IN
MRI SCANNING ROOMS WITH OTHER TRADES AND CONSTRUCTION PHASING.
REFER TO ARCHITECTURAL PLANS FOR PHASING INFORMATION. PROTECT
EXISTING FIRE ALARM DEVICES WHERE CEILINGS AND/OR FINISHES ARE
TEMPORARILY REMOVED. ALL PROPOSED SYSTEM OUTAGES SHALL BE SUBMITTED
IN WRITING TO THE COR FOR APPROVAL AT LEAST ON WEEK IN ADVANCE.
3. UNO, ALL EXISTING FIRE ALARM INITIATING DEVICES ARE PART OF ZONE 2P03-02
[NODE 32]. EXISTING FIRE ALARM AND NAC POWER EXTENDER PANELS ARE
LOCATED IN ELECTRICAL CLOSET 3A180.
4. EXISTING SMOKE DETECTORS LOCATED WITHIN MRI SCANNING ROOMS AND
ADJACENT EQUIPMENT ROOMS ARE PART OF PRE-ACTION SPRINKLER SYSTEM. THE
INTEGRATED VIKING TOTALPAC 2 RELEASING PANEL IS LOCATED IN MECHANICAL
ROOM 4A100.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
BID DOCUMENTS
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
Phase
STAMP
CONSULTANTS
321 4 5 6 7 8 9 10
Project Director
08/07/20
Revisions: Date:
RENOVATE MRI SUITE FOR
EQUIPMENT UPGRADES
ARCHITECTURE
PLANNING
ENGINEERING
BURDETTE KOEHLER MURPHY &
ASSOCIATES, INC.
MECHANICAL / ELECTRICAL ENGINEERS
BLAIR HILL LANE, SUITE 400
BALTIMORE, MARYLAND 21209
410.323.0600 - FAX 410.377.2543
BUILDING COST CONSULTANTS
COST ESTIMATING
12917 - 30TH AVENUE
PLATTSMOUTH, NEBRASKA 68048
402.298.8260 - FAX 402.298.8290
RICKERT ENGINEERING, INC.
STRUCTURAL ENGINEERING
8813 WALTHAM WOODS ROAD, SUITE 301
BALTIMORE, MARYLAND 21234
410.663.5110 - FAX 410.663.5114
35OfDwg.
DELLC Project Number : 180801D
ARCHITECT/ENGINEER OF RECORD
642-CSI-117
321 4 5 6 7 8 9 10
A
B
C
D
E
F
CORPORAL MICHAEL J. CRESCENZ
VA MEDICAL CENTER
PHILADELPHIA, PA
08/07/2020
8815 Centre Park Drive, Suite 200 Columbia, Maryland 21045
410-750-2246 / www.koffel.com
FIRE PROTECTION ENGINEERING
8815 CENTRE PARK DR., SUITE 200
COLUMBIA, MARYLAND 21045
410.750.2246 - FAX 410.750.2588
KOFFEL ASSOCIATES, INC.
BID DOCUMENTS
BUILDING FULLY SPRINKLERED
FA2
KLCMHB
SHEET KEY NOTES:
REMOVE AND REPLACE EXISTING SMOKE DETECTOR TO SUPPORT NEW MRI
EQUIPMENT.
GENERAL NOTES:
AutoCAD SHX Text 3A151
AutoCAD SHX Text
MRI ROOM
AutoCAD SHX Text 3A152
AutoCAD SHX Text
MRI ROOM
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text 3A152C
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text 3A152C
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
SOILD
AutoCAD SHX Text 3A151o
AutoCAD SHX Text
LINEN
AutoCAD SHX Text 3A151Q
AutoCAD SHX Text
LINEN
AutoCAD SHX Text 3A151P
AutoCAD SHX Text
TECH AREA
AutoCAD SHX Text 3A151L
AutoCAD SHX Text
CLOSET
AutoCAD SHX Text
CONTROL
AutoCAD SHX Text 3A151K
AutoCAD SHX Text
ROOM
AutoCAD SHX Text 3A151B
AutoCAD SHX Text
RECEPTION
AutoCAD SHX Text 3A151J
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 3A151i
AutoCAD SHX Text
INPATIENT
AutoCAD SHX Text 3A151C
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 3A151F
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 3A151H
AutoCAD SHX Text
TOILET
AutoCAD SHX Text 3A151D
AutoCAD SHX Text
CHANGING
AutoCAD SHX Text 3A151E
AutoCAD SHX Text
CHANGING
AutoCAD SHX Text 3A151G
AutoCAD SHX Text
TECH AREA
AutoCAD SHX Text 3A152A
AutoCAD SHX Text
CLOSET
AutoCAD SHX Text 3A151A
AutoCAD SHX Text
WAITING
AutoCAD SHX Text 3A152
AutoCAD SHX Text
CONTROL ROOM
AutoCAD SHX Text C3-8
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 2215 Conowingo Rd, Suite 100 Bel Air, Maryland 21015-1457 410.836.6611
AutoCAD SHX Text
TRUE NORTH
AutoCAD SHX Text
%%UKEY PLAN
AutoCAD SHX Text
%%UBUILDING 1
AutoCAD SHX Text
%%UBUILDING 2
AutoCAD SHX Text
PROJECT LOCATION
AutoCAD SHX Text
35% SUBMISSION
AutoCAD SHX Text
70% SUBMISSION
AutoCAD SHX Text
100% SUBMISSION
AutoCAD SHX Text
100% RESUBMISSION
AutoCAD SHX Text 01/14/19
AutoCAD SHX Text 06/29/20
AutoCAD SHX Text 04/27/20
AutoCAD SHX Text 05/24/19
AutoCAD SHX Text
75% SUBMISSION
AutoCAD SHX Text 07/15/19
AutoCAD SHX Text
BID SUBMISSION
AutoCAD SHX Text 08/07/20
AutoCAD SHX Text
100% RESUBMISSION
AutoCAD SHX Text 07/27/20
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 8'
AutoCAD SHX Text 4'
AutoCAD SHX Text 2'
AutoCAD SHX Text 1/4" = 1'-0"
EXISTING MRI PRE-ACTION
FIRE ALARM ZONE
EXISTING MRI PRE-ACTION
FIRE ALARM ZONE
E F G
P
P
P
PP
P P
P
P
P
P
P
C
C
C
C
C
C
C
C
FIRE ALARM PLAN - THIRD FLOOR -
NEW WORK
1/4" = 1'-0"
FIRE ALARM PLAN - THIRD FLOOR - NEW WORK1
FA3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
BID DOCUMENTS
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
Phase
STAMP
CONSULTANTS
321 4 5 6 7 8 9 10
Project Director
08/07/20
Revisions: Date:
RENOVATE MRI SUITE FOR
EQUIPMENT UPGRADES
ARCHITECTURE
PLANNING
ENGINEERING
BURDETTE KOEHLER MURPHY &
ASSOCIATES, INC.
MECHANICAL / ELECTRICAL ENGINEERS
BLAIR HILL LANE, SUITE 400
BALTIMORE, MARYLAND 21209
410.323.0600 - FAX 410.377.2543
BUILDING COST CONSULTANTS
COST ESTIMATING
12917 - 30TH AVENUE
PLATTSMOUTH, NEBRASKA 68048
402.298.8260 - FAX 402.298.8290
RICKERT ENGINEERING, INC.
STRUCTURAL ENGINEERING
8813 WALTHAM WOODS ROAD, SUITE 301
BALTIMORE, MARYLAND 21234
410.663.5110 - FAX 410.663.5114
35OfDwg.
DELLC Project Number : 180801D
ARCHITECT/ENGINEER OF RECORD
642-CSI-117
321 4 5 6 7 8 9 10
A
B
C
D
E
F
CORPORAL MICHAEL J. CRESCENZ
VA MEDICAL CENTER
PHILADELPHIA, PA
08/07/2020
8815 Centre Park Drive, Suite 200 Columbia, Maryland 21045
410-750-2246 / www.koffel.com
FIRE PROTECTION ENGINEERING
8815 CENTRE PARK DR., SUITE 200
COLUMBIA, MARYLAND 21045
410.750.2246 - FAX 410.750.2588
KOFFEL ASSOCIATES, INC.
BID DOCUMENTS
BUILDING FULLY SPRINKLERED
FA3
KLCMHB
1. UNO, EXISTING FIRE ALARM SYSTEM INFRASTRUCTURE SHALL REMAIN.
2. COORDINATE REMOVAL AND REPLACEMENT OF EXISTING FIRE ALARM DEVICES IN
MRI SCANNING ROOMS WITH OTHER TRADES AND CONSTRUCTION PHASING.
REFER TO ARCHITECTURAL PLANS FOR PHASING INFORMATION. PROTECT
EXISTING FIRE ALARM DEVICES WHERE CEILINGS AND/OR FINISHES ARE
TEMPORARILY REMOVED. ALL PROPOSED SYSTEM OUTAGES REQUIRE THAT A
WRITTEN SHUTDOWN REQUEST IS SUBMITTED TO THE VA COR A MINIMUM OF 14
CALENDAR DAYS PRIOR TO THE SHUTDOWN.
3. UNO, ALL EXISTING FIRE ALARM INITIATING DEVICES ARE PART OF ZONE 2P03-02
[NODE 32]. EXISTING FIRE ALARM AND NAC POWER EXTENDER PANELS ARE
LOCATED IN ELECTRICAL CLOSET 3A180.
4. SMOKE DETECTORS LOCATED WITHIN MRI SCANNING ROOMS AND ADJACENT
EQUIPMENT ROOMS ARE PART OF PRE-ACTION SPRINKLER SYSTEM. THE
INTEGRATED VIKING TOTALPAC 2 RELEASING PANEL IS LOCATED IN MECHANICAL
ROOM 4A100.
5. NEW FIRE ALARM DEVICES SHALL BE COMPATIBLE WITH THE EXISTING GAMEWELL-
FCI SERIES E3 FIRE ALARM SYSTEM. INSTALLATION OF ALL NEW FIRE ALARM
DEVICES SHALL COINCIDE WITH CONSTRUCTION PHASING. REFER TO
ARCHITECTURAL PLAN FOR PHASING INFORMATION.
6. LOCATE ALL NEW SMOKE DETECTORS A MINIMUM OF 3 FEET AWAY FROM HVAC
DIFFUSERS.
7. ALL NEW FIRE ALARM SPEAKERS SHALL BE TAPPED AT
WATT.
SHEET KEY NOTES:
PROVIDE NEW SMOKE DETECTOR AND CONNECT TO PRE-ACTION SYSTEM
RELEASING PANEL.
GENERAL NOTES:
AutoCAD SHX Text 3A151
AutoCAD SHX Text
MRI ROOM
AutoCAD SHX Text 3A152
AutoCAD SHX Text
MRI ROOM
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text 3A152C
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text 3A152C
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
SOILD
AutoCAD SHX Text 3A151o
AutoCAD SHX Text
LINEN
AutoCAD SHX Text 3A151Q
AutoCAD SHX Text
LINEN
AutoCAD SHX Text 3A151P
AutoCAD SHX Text
TECH AREA
AutoCAD SHX Text 3A151L
AutoCAD SHX Text
CLOSET
AutoCAD SHX Text
CONTROL
AutoCAD SHX Text 3A151K
AutoCAD SHX Text
ROOM
AutoCAD SHX Text 3A151B
AutoCAD SHX Text
RECEPTION
AutoCAD SHX Text 3A151J
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 3A151i
AutoCAD SHX Text
INPATIENT
AutoCAD SHX Text 3A151C
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 3A151F
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 3A151H
AutoCAD SHX Text
TOILET
AutoCAD SHX Text 3A151D
AutoCAD SHX Text
CHANGING
AutoCAD SHX Text 3A151E
AutoCAD SHX Text
CHANGING
AutoCAD SHX Text 3A151G
AutoCAD SHX Text
TECH AREA
AutoCAD SHX Text 3A152A
AutoCAD SHX Text
CLOSET
AutoCAD SHX Text 3A151A
AutoCAD SHX Text
WAITING
AutoCAD SHX Text 3A152
AutoCAD SHX Text
CONTROL ROOM
AutoCAD SHX Text C3-8
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
LIMIT OF DISTURBANCE
AutoCAD SHX Text
LIMIT OF DISTURBANCE
AutoCAD SHX Text
LIMIT OF DISTURBANCE
AutoCAD SHX Text
LIMIT OF DISTURBANCE
AutoCAD SHX Text 2215 Conowingo Rd, Suite 100 Bel Air, Maryland 21015-1457 410.836.6611
AutoCAD SHX Text
TRUE NORTH
AutoCAD SHX Text
%%UKEY PLAN
AutoCAD SHX Text
%%UBUILDING 1
AutoCAD SHX Text
%%UBUILDING 2
AutoCAD SHX Text
PROJECT LOCATION
AutoCAD SHX Text
35% SUBMISSION
AutoCAD SHX Text
70% SUBMISSION
AutoCAD SHX Text
100% SUBMISSION
AutoCAD SHX Text
100% RESUBMISSION
AutoCAD SHX Text 01/14/19
AutoCAD SHX Text 06/29/20
AutoCAD SHX Text 04/27/20
AutoCAD SHX Text 05/24/19
AutoCAD SHX Text
75% SUBMISSION
AutoCAD SHX Text 07/15/19
AutoCAD SHX Text
BID SUBMISSION
AutoCAD SHX Text 08/07/20
AutoCAD SHX Text
100% RESUBMISSION
AutoCAD SHX Text 07/27/20
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 8'
AutoCAD SHX Text 4'
AutoCAD SHX Text 2'
AutoCAD SHX Text 1/4" = 1'-0"
FIRE SUPPRESSION NOTES,
ABBREVIATIONS, AND SYMBOLS
1. MODIFY EXISTING FIRE SPRINKLER SYSTEM TO ACCOMMODATE EQUIPMENT
UPGRADES THROUGHOUT THE MRI SUITES LOCATED ON FLOOR 3
(NORTHEAST WING) OF BUILDING 2. UNO, EXISTING SPRINKLERS, PIPING,
AND FIRE PUMP ARE EXISTING TO REMAIN.
2. PROVIDE ALL NECESSARY MATERIALS AND LABOR TO FURNISH AND INSTALL
THE SYSTEM AS DESCRIBED IN THE PROJECT SPECIFICATIONS AND
CONTRACT DRAWINGS.
3. EXISTING PATTERSON MODEL 6X5MAA ELECTRIC-DRIVE HORIZONTAL
SPLIT-CASE FIRE PUMP IS LOCATED IN THE SUB-BASEMENT OF BUILDING 2.
PUMP IS RATED FOR 1,000 GPM AT 125 PSI.
4. ALL REFERENCE TO THE AUTHORITY HAVING JURISDICTION (AHJ) SHALL
MEAN THE DEPARTMENT OF VETERANS AFFAIRS (VA) MEDICAL CENTER
PHILADELPHIA SAFETY OFFICER.
5. ALL REFERENCE TO THE ENGINEER SHALL MEAN KOFFEL ASSOCIATES, INC.
6. ALL REFERENCE TO THE OWNER SHALL MEAN THE VA.
7. INSTALLATION OF FIRE SPRINKLER SYSTEM AND ASSOCIATED COMPONENTS
SHALL BE IN ACCORDANCE WITH THE FOLLOWING:
· NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2016
EDITION
· NFPA 25, STANDARD FOR THE INSPECTION, TESTING, AND MAINTENANCE OF
WATER-BASED FIRE PROTECTION SYSTEMS, 2017 EDITION
· NFPA 101
, LIFE SAFETY CODE
®, 2018 EDITION
· VA FIRE PROTECTION DESIGN MANUAL (VAFPDM), SEVENTH EDITION,
DECEMBER 2015
· THE MANUFACTURER'S REQUIREMENTS
· APPLICABLE STATE AND LOCAL CODES AND REGULATIONS
8. THE FOLLOWING DESIGN CRITERIA APPLIES:
· LIGHT HAZARD: 0.10 GPM/SQ FT OVER 1,500 SQ FT
· ORDINARY HAZARD GROUP II: 0.20 GPM/SQ FT OVER 1,500 SQ FT
PER SECTION 11.2.3.2.3.1 OF NFPA 13, A REDUCTION IN THE DESIGN AREA UP TO
40% IS PERMITTED WHERE LISTED QUICK-RESPONSE SPRINKLERS ARE UTILIZED.
REFER TO SHEET FS3 FOR SPRINKLER HAZARD CLASSIFICATIONS.
9. THE FOLLOWING WATER SUPPLY DATA IS PROVIDED:
STATIC (CHURN) PRESSURE: 175 PSI
RESIDUAL PRESSURE: 170 PSI
FLOW: 1,024 GPM
LOCATION: FIRE PUMP DISCHARGE FLANGE IN SUB-BASEMENT OF BLDG 2
DATE OF TEST: JUNE 12, 2018
10. WHERE REQUIRED, ALL HYDRAULIC CALCULATIONS SHALL YIELD AT LEAST A
10 PERCENT SAFETY FACTOR FOR EACH SPRINKLER DESIGN AREA,
INCLUDING REQUIRED HOSE STREAMS, PER SECTION 6.1.D OF THE VAFPDM.
11. ALL NEW MATERIALS SHALL BE LISTED BY UNDERWRITERS LABORATORIES,
INC. (U.L.) FOR USE ON COMMERCIAL FIRE PROTECTION SYSTEMS. UNO,
SPRINKLERS SHALL ALSO BE FACTORY MUTUAL (FM) APPROVED, PER
SECTION 6.1.K OF THE VAFPDM.
12. SPRINKLER TYPES SHALL BE AS DESCRIBED IN THE PROJECT
SPECIFICATIONS. NEW SPRINKLERS IN MRI SCANNING ROOMS SHALL BE U.L.
LISTED NON-FERROUS CONCEALED TYPE.
13. NEW SPRINKLERS SHALL BE LOCATED IN SUSPENDED CEILING TILES AS
INDICATED ON SHEET FS4. ARMOVERS AND DROPS TO INDIVIDUAL
SPRINKLERS SHALL BE FIELD CUT TO ENSURE PROPER SPRINKLER
PLACEMENT.
14. NEW SPRINKLER PIPE SHALL MEET THE FOLLOWING CRITERIA:
· PIPE SIZES 2" AND SMALLER: SCHEDULE 40, BLACK STEEL, MEETING ASTM
A53 (TYPE E GRADE B) OR A795 (TYPE E GRADE A) SPECIFICATIONS,
CONNECTED WITH THREADED FITTINGS.
· PIPE SIZES 2½" AND LARGER: SCHEDULE 10, BLACK STEEL, MEETING ASTM
A135 OR A795 TYPE E GRADE A SPECIFICATIONS, CONNECTED WITH LISTED
GROOVED COUPLINGS.
· WITHIN MRI SCANNING ROOMS: NON-FERROUS PIPE. NOTE THAT PLASTIC
PIPE IS NOT PERMITTED.
15. NEW PIPE FITTINGS SHALL INCLUDE:
· THREADED FITTINGS FOR SCHEDULE 40 PIPE SHALL CONFORM TO SECTION
6.4 OF NFPA 13.
· ROLL GROOVED FITTINGS FOR SCHEDULE 10 PIPE SHALL BE UL LISTED.
COUPLINGS SHALL COMPLY WITH ASTM A536, AND A183 SPECFICIATIONS
WITH GRADE E, TYPE A GASKETS. ALL COMPONENTS SHALL BE FROM A
SINGLE MANUFACTURER.
· WITHIN MRI SCANNING ROOMS: NON-FERROUS PIPE FITTINGS.
16. ALL NECESSARY CONNECTIONS TO THE FIRE ALARM SYSTEM SHALL BE
MADE BY AND COORDINATED WITH THE FIRE ALARM CONTRACTOR. SYSTEM
ACCEPTANCE TESTS SHALL BE CONDUCTED BY THE FIRE ALARM
CONTRACTOR AND WITNESSED BY THE OWNER. COORDINATE ALL TESTING
WITH THE VAMC PHILADELPHIA SAFETY OFFICER.
17. ALL HANGERS SHALL BE U.L. LISTED FOR USE WITH SPRINKLER SYSTEMS.
HANGER INSTALLATION AND SPACING SHALL BE IN ACCORDANCE WITH NFPA
13.
18. SEISMIC PROTECTION SHALL BE PROVIDED FOR ALL NEW SPRINKLER
SYSTEM PIPING IN ACCORDANCE WITH SECTION 6.1.I OF THE VAFPDM AND
NFPA 13.
19. ALL SPRINKLER SYSTEM PIPING AND HANGERS SHALL BE CONCEALED
WHEREVER POSSIBLE. PROVIDE ACCESS PANELS FOR ALL VALVES, WHERE
REQUIRED.
20. NEW FIRE SPRINKLER PIPE PENETRATIONS OF FIRE-RATED ASSEMBLIES
SHALL BE SEALED WITH A U.L. CERTIFIED THROUGH-PENETRATION SYSTEM
APPROPRIATE FOR THE RATING OF THE WALL PENETRATED. REFER TO
SHEET GI102 FOR WALL RATINGS.
21. CONTRACTOR SHALL BE RESPONSIBLE FOR DEVELOPMENT OF SHOP
DRAWINGS, HYDRAULIC CALCULATIONS (WHERE REQUIRED), PERMIT FEES,
APPROVAL OF SHOP DRAWINGS, AND ACCEPTANCE OF THE SYSTEM BY THE
AHJ.
22. PRIOR TO SUBMITTING AN APPLICATION FOR SPRINKLER PERMIT TO THE
AHJ, PROVIDE TWO COPIES OF ALL SHOP DRAWINGS, HYDRAULIC
CALCULATIONS (WHERE REQUIRED), AND PRODUCT DATA SHEETS TO THE
OWNER FOR REVIEW AND COMMENT. PERMIT APPLICATION SHALL NOT BE
MADE UNTIL SUCH TIME THAT THE ENGINEER COMPLETED A REVIEW OF THE
SHOP DRAWING PACKAGE.
23. UPON COMPLETION OF WORK, A HYDROSTATIC TEST SHALL BE PERFORMED
IN ACCORDANCE WITH NFPA 13. IF MODIFICATIONS TO THE EXISTING FIRE
SPRINKLER SYSTEM AFFECT LESS THAN 20 SPRINKLERS, SYSTEM MAY BE
TESTED AT SYSTEM WORKING PRESSURE FOR TWO HOURS. IF MORE THAN
20 SPRINKLERS ARE AFFECTED, THE NEW PORTION OF THE SYSTEM SHALL
BE ISOLATED AND TESTED AT NOT LESS THAN 200 PSI, OR 50 PSI IN EXCESS
OF SYSTEM WORKING PRESSURE (WHICHEVER IS GREATER), FOR TWO
HOURS. ALL HYDROSTATIC TESTING SHALL BE WITNESSED BY THE AHJ.
FIRE SUPPRESSION PROJECT NOTES:
FIRE SUPPRESSION ABBREVIATIONS
PENDENT SPRINKLER;
ON DROP NIPPLE
SPRINKLER GUARD;
SHOWN ON UPRIGHT SPRINKLER
OPEN SPRINKLER/DISCHARGE NOZZLE
WATER SPRAY NOZZLE
WINDOW SPRINKLER
HYDRAULIC REFERENCE NODE
HEIGHT INDICATOR
NON-SPRINKLERED AREA
FULLY SPRINKLERED AREA
PARTIALLY SPRINKLERED AREA
AREA NOT IN CONTRACT
CALCULATED REMOTE AREA
SPRINKLER ZONE BOUNDARY
PRESSURE GAUGE
ALARM CHECK VALVE
DRY PIPE VALVE
DRY PIPE VALVE WITH
QUICK OPENING DEVICE
DELUGE VALVE
PRE-ACTION VALVE
FIRE HYDRANT
FIRE DEPARTMENT CONNECTION
FIRE DEPARTMENT CONNECTION;
FREE STANDING
DRY SIDEWALL SPRINKLER
SIDEWALL SPRINKLER
UPRIGHT SPRINKLER
PENDENT SPRINKLER
UPRIGHT SPRINKLER;
ON SPRIG
CONCENTRIC REDUCER
ECCENTRIC REDUCER
FLUSHING CONNECTION OR CAP
CONTROL VALVE
ANGLE VALVE
CHECK VALVE
OS&Y GATE VALVE
BUTTERFLY VALVE
NON-INDICATING CONTROL VALVE
BACKFLOW PREVENTER;
DOUBLE CHECK TYPE
BACKFLOW PREVENTER;
REDUCED PRESSURE ZONE TYPE
POST-INDICATING VALVE
ZONE CONTROL ASSEMBLY
PRESSURE REGULATING VALVE
PRESSURE RELIEF VALVE
NEW SYSTEM PIPING
EXISTING PIPING TO REMAIN
DEMO EXISTING PIPING
POINT OF CONNECTION
MECHANICAL COUPLING
PIPE HANGER
LATERAL BRACE; TWO WAY
LATERAL BRACE; FOUR WAY
SYSTEM RISER
DRAIN RISER
HOSE VALVE
HOSE REEL STATION
AGENT STORAGE CONTAINER
(XX DENOTES SYSTEM TYPE)
PIPE ELBOW DOWN
PIPE TEE DOWN
8'-0"
AS
AS
NS
XX
XX
ZCA
OWNER'S INFORMATION CERTIFICATE
NOYES
WILL THERE BE ANY STORAGE OR PRODUCTS
OVER 12 FT (3.5 M) IN HEIGHT?
WILL THERE BE ANY STORAGE OF PLASTIC,
RUBBER, OR SIMILAR PRODUCTS OVER 5 FT (1.3 M)
HIGH EXCEPT AS DESCRIBED ABOVE?
THIS FORM HAS BEEN COMPLETED BY KOFFEL
ASSOCIATES ON BEHALF OF THE OWNER BASED ON
INFORMATION PROVIDED BY THE OWNER AND HIS AGENTS.
I CERTIFY THAT I HAVE KNOWLEDGE OF THE INTENDED USE
OF THE PROPERTY AND THAT THE ABOVE INFORMATION IS
CORRECT.
SIGNATURE OF OWNER'S REPRESENTATIVE OR AGENT
DATE: AUGUST 08, 2020
KOFFEL ASSOCIATES, INC.
NAME OF OWNER'S REPRESENTATIVE OR AGENT
COMPLETING CERTIFICATE
CONSULTING ENGINEER
RELATIONSHIP AND FIRM OF AGENT
NOYES
INDICATE WHETHER ANY OF THE FOLLOWING SPECIAL
MATERIALS ARE INTENDED TO BE PRESENT:
FLAMMABLE OR COMBUSTIBLE LIQUIDS
AEROSOL PRODUCTS
NITRATE FILM
PYROXYLIN PLASTIC
COMPRESSED OR LIQUEFIED GAS CYLINDERS
LIQUID OR SOLID OXIDIZERS
ORGANIC PEROXIDE FORMULATIONS
IDLE PALLETS
INDICATE WHETHER THE PROTECTION IS INTENDED FOR
ONE OF THE FOLLOWING SPECIALIZED OCCUPANCIES OR
AREAS:
SPRAY AREA OR MIXING ROOM
SOLVENT EXTRACTION
LABORATORY USING CHEMICALS
OXYGEN-FUEL GAS SYSTEM FOR WELDING OR
CUTTING
ACETYLENE CYLINDER CHARGING
PRODUCTION OR USE OF COMPRESSED OR
LIQUEFIED GASES
COMMERCIAL COOKING OPERATION
CLASS A HYPERBARIC CHAMBER
CLEANROOM
INCINERATOR WASTE HANDLING SYSTEM
LINEN HANDLING SYSTEM
WATER-COOLING TOWER
YES NO
NOYES
NAME OF OWNER:
U.S. DEPARTMENT OF VETERAN AFFAIRS (VA)
CORPORAL MICHAEL J. CRESCENZ VA MEDICAL CENTER
BUILDING 2, THIRD FLOOR
3900 WOODLAND AVENUE
PHILADELPHIA, PA 19104
EXISTING OR PLANNED CONSTRUCTION IS:
FIRE RESISTIVE OR NONCOMBUSTIBLE
WOOD FRAME OR ORDINARY
(MASONRY WALLS WITH WOOD BEAMS)
UNKNOWN
IS THE SYSTEM INSTALLATION INTENDED FOR ONE OF THE
FOLLOWING SPECIAL OCCUPANCIES:
AIRCRAFT HANGAR
FIXED GUIDEWAY TRANSIT SYSTEM
RACE TRACK STABLE
MARINE TERMINAL, PIER, OR WHARF
AIRPORT TERMINAL
AIRCRAFT ENGINE TEST FACILITY
POWER PLANT
WATER-COOLING TOWER
NOYES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
BID DOCUMENTS
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
Phase
STAMP
CONSULTANTS
321 4 5 6 7 8 9 10
Project Director
08/07/20
Revisions: Date:
RENOVATE MRI SUITE FOR
EQUIPMENT UPGRADES
ARCHITECTURE
PLANNING
ENGINEERING
BURDETTE KOEHLER MURPHY &
ASSOCIATES, INC.
MECHANICAL / ELECTRICAL ENGINEERS
BLAIR HILL LANE, SUITE 400
BALTIMORE, MARYLAND 21209
410.323.0600 - FAX 410.377.2543
BUILDING COST CONSULTANTS
COST ESTIMATING
12917 - 30TH AVENUE
PLATTSMOUTH, NEBRASKA 68048
402.298.8260 - FAX 402.298.8290
RICKERT ENGINEERING, INC.
STRUCTURAL ENGINEERING
8813 WALTHAM WOODS ROAD, SUITE 301
BALTIMORE, MARYLAND 21234
410.663.5110 - FAX 410.663.5114
35OfDwg.
DELLC Project Number : 180801D
ARCHITECT/ENGINEER OF RECORD
642-CSI-117
321 4 5 6 7 8 9 10
A
B
C
D
E
F
CORPORAL MICHAEL J. CRESCENZ
VA MEDICAL CENTER
PHILADELPHIA, PA
08/07/2020
8815 Centre Park Drive, Suite 200 Columbia, Maryland 21045
410-750-2246 / www.koffel.com
FIRE PROTECTION ENGINEERING
8815 CENTRE PARK DR., SUITE 200
COLUMBIA, MARYLAND 21045
410.750.2246 - FAX 410.750.2588
KOFFEL ASSOCIATES, INC.
BID DOCUMENTS
BUILDING FULLY SPRINKLERED
FS1
KLCMHB
FIRE SUPPRESSION SYSTEM SYMBOLS
NFPA 13 SPRINKLER HAZARD CLASSIFICATIONS:
NONE LIGHT HAZARD
ORDINARY HAZARD GROUP I
ORDINARY HAZARD GROUP II
OH-1
OH-2
PL PLASTER (CEILING)
PMO FIRE PUMP CONTROLLER - MANUAL OFF
POC POINT OF CONNECTION
PR FIRE PUMP RUN
PRV PRESSURE REGULATING VALVE
QR QUICK RESPONSE (SPRINKLER)
RX REMOVE EXISTING DEVICE
SCH SCHEDULE
SPL HIDDEN SPLINE (CEILING)
STL STEEL
T&G TONGUE AND GROOVE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
WC WET CHEMICAL SYSTEM
WM WATER MIST SYSTEM
FPC FIRE PUMP CONTROLLER
GALV GALVANIZED
GYP GYPSUM WALL BOARD (SHEETROCK)
HL HALON SYSTEM
HT HIGH TEMPERATURE (SPRINKLER)
ITC INSPECTORS TEST CONNECTION
JP JOCKEY PUMP
JPC JOCKEY PUMP CONTROLLER
MAX MAXIMUM
MIN MINIMUM
MT METAL TILE
NIC NOT IN CONTRACT
NS NON-SPRINKLERED
NTS NOT TO SCALE
PF FIRE PUMP POWER FAIL
PH FIRE PUMP PHASE REVERSAL
CPVC CHLORINATED POLYVINYL
CHLORIDE
DCH DRY CHEMICAL
DI DUCTILE IRON
DL DELUGE
DN DOWN
DP DRY PENDENT (SPRINKLER)
DS DRY SIDEWALL (SPRINKLER)
EC EXTENDED COVERAGE (SPRINKLER)
ETR EXISTING TO REMAIN
EXP EXPOSED (NO CEILING)
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FHV FIRE HOSE VALVE
FO FOAM
FP FIRE PUMP
ABD AUTOMATIC BALL DRIP
ACT ACOUSTICAL CEILING TILE
AFF ABOVE FINISHED FLOOR
AFFF AQUEOUS FILM FORMING FOAM
AS AUTOMATIC SPRINKLER
ASC AGENT STORAGE CONTAINER
ATR ALL THREAD ROD
BFP BACKFLOW PREVENTER
BOB BOTTOM OF BEAM
CA CLEAN AGENT
CB CONCRETE BEAM
CI CAST IRON
CO2 CARBON DIOXIDE
COL COLUMN
CONC CONCRETE
AutoCAD SHX Text 2215 Conowingo Rd, Suite 100 Bel Air, Maryland 21015-1457 410.836.6611
AutoCAD SHX Text
35% SUBMISSION
AutoCAD SHX Text
70% SUBMISSION
AutoCAD SHX Text
100% SUBMISSION
AutoCAD SHX Text
100% RESUBMISSION
AutoCAD SHX Text 01/14/19
AutoCAD SHX Text 06/29/20
AutoCAD SHX Text 04/27/20
AutoCAD SHX Text 05/24/19
AutoCAD SHX Text
75% SUBMISSION
AutoCAD SHX Text 07/15/19
AutoCAD SHX Text
BID SUBMISSION
AutoCAD SHX Text 08/07/20
AutoCAD SHX Text
100% RESUBMISSION
07/27/20
E F G
2"
2"
1"
2"
1,300 SQ FT
EXISTING MRI PRE-ACTION SPRINKLER ZONE
1,300 SQ FT
EXISTING MRI PRE-ACTION SPRINKLER ZONE
EXISTING WET-PIPE SPRINKLER ZONE 2P03-02
EXISTING WET-PIPE SPRINKLER ZONE 2P03-01
2" 2" 2"
FIRE SUPPRESSION PLAN - THIRD
FLOOR - DEMO/EXISTING
1/4" = 1'-0"
FIRE SUPPRESSION PLAN - THIRD FLOOR - DEMO/EXISTING
FS2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
BID DOCUMENTS
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
Phase
STAMP
CONSULTANTS
321 4 5 6 7 8 9 10
Project Director
08/07/20
Revisions: Date:
RENOVATE MRI SUITE FOR
EQUIPMENT UPGRADES
ARCHITECTURE
PLANNING
ENGINEERING
BURDETTE KOEHLER MURPHY &
ASSOCIATES, INC.
MECHANICAL / ELECTRICAL ENGINEERS
BLAIR HILL LANE, SUITE 400
BALTIMORE, MARYLAND 21209
410.323.0600 - FAX 410.377.2543
BUILDING COST CONSULTANTS
COST ESTIMATING
12917 - 30TH AVENUE
PLATTSMOUTH, NEBRASKA 68048
402.298.8260 - FAX 402.298.8290
RICKERT ENGINEERING, INC.
STRUCTURAL ENGINEERING
8813 WALTHAM WOODS ROAD, SUITE 301
BALTIMORE, MARYLAND 21234
410.663.5110 - FAX 410.663.5114
35OfDwg.
DELLC Project Number : 180801D
ARCHITECT/ENGINEER OF RECORD
642-CSI-117
321 4 5 6 7 8 9 10
A
B
C
D
E
F
CORPORAL MICHAEL J. CRESCENZ
VA MEDICAL CENTER
PHILADELPHIA, PA
08/07/2020
8815 Centre Park Drive, Suite 200 Columbia, Maryland 21045
410-750-2246 / www.koffel.com
FIRE PROTECTION ENGINEERING
8815 CENTRE PARK DR., SUITE 200
COLUMBIA, MARYLAND 21045
410.750.2246 - FAX 410.750.2588
KOFFEL ASSOCIATES, INC.
BID DOCUMENTS
BUILDING FULLY SPRINKLERED
FS2
KLCMHB
GENERAL NOTES:
1. UNO, EXISTING FIRE SPRINKLER SYSTEM INFRASTRUCTURE SHALL REMAIN.
2. EXISTING ZONE VALUE ASSEMBLY FOR ZONE 2P03-02 IS LOCATED ABOVE CEILING IN
STAIR 12.
3. EXISTING VIKING TOTALPAC2 PRE-ACTION VALVE FOR MRI SCANNING ROOMS AND
ADJACENT EQUIPMENT ROOMS IS LOCATED IN MECHANICAL ROOM 4A100. REFER
TO PART PLAN 4/FS4 FOR ADDITIONAL INFORMATION.
4. REMOVAL AND/OR MODIFICATIONS TO EXISTING FIRE SPRINKLER SYSTEM SHALL
COINCIDE WITH CONSTRUCTION PHASING. REFER TO ARCHITECTURAL PLANS FOR
PHASING INFORMATION. ALL PROPOSED SYSTEM OUTAGES SHALL BE SUBMITTED
IN WRITING TO THE COR FOR APPROVAL AT LEAST ONE WEEK IN ADVANCE.
5. SPRINKLER PROTECTION SHALL REMAIN ACTIVE THROUGHOUT DEMOLITION AND
CONSTRUCTION TO THE EXTENT POSSIBLE.
SHEET KEY NOTES:
REMOVE AND REPLACE EXISTING MRI SPRINKLERS. RE-ALIGN NEW SPRINKLERS
IN NEW CEILING GRID AS NECESSARY.
EXISTING 2" UP TO PRE-ACTION VALVE. REFER TO PART PLAN 4/FS4.
EXISTING 2" STEEL TO 1" COPPER PIPE TRANSITION TO REMAIN.
AutoCAD SHX Text 3A151
AutoCAD SHX Text
MRI ROOM
AutoCAD SHX Text 3A152
AutoCAD SHX Text
MRI ROOM
AutoCAD SHX Text 3A152B
AutoCAD SHX Text
MRI ROOM
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text 3A152C
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text 3A152C
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
SOILD
AutoCAD SHX Text 3A151o
AutoCAD SHX Text
LINEN
AutoCAD SHX Text 3A151Q
AutoCAD SHX Text
LINEN
AutoCAD SHX Text 3A151P
AutoCAD SHX Text
TECH AREA
AutoCAD SHX Text 3A151L
AutoCAD SHX Text
CLOSET
AutoCAD SHX Text
CONTROL
AutoCAD SHX Text 3A151K
AutoCAD SHX Text
ROOM
AutoCAD SHX Text 3A151B
AutoCAD SHX Text
RECEPTION
AutoCAD SHX Text 3A151J
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 3A151i
AutoCAD SHX Text
INPATIENT
AutoCAD SHX Text 3A151C
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 3A151F
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 3A151H
AutoCAD SHX Text
TOILET
AutoCAD SHX Text 3A151D
AutoCAD SHX Text
CHANGING
AutoCAD SHX Text 3A151E
AutoCAD SHX Text
CHANGING
AutoCAD SHX Text 3A151G
AutoCAD SHX Text
TECH AREA
AutoCAD SHX Text 3A152A
AutoCAD SHX Text
MRI ROOM
AutoCAD SHX Text 3A151A
AutoCAD SHX Text
WAITING
AutoCAD SHX Text C3-8
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 2215 Conowingo Rd, Suite 100 Bel Air, Maryland 21015-1457 410.836.6611
AutoCAD SHX Text
TRUE NORTH
AutoCAD SHX Text
%%UKEY PLAN
AutoCAD SHX Text
%%UBUILDING 1
AutoCAD SHX Text
%%UBUILDING 2
AutoCAD SHX Text
PROJECT LOCATION
AutoCAD SHX Text
35% SUBMISSION
AutoCAD SHX Text
70% SUBMISSION
AutoCAD SHX Text
100% SUBMISSION
AutoCAD SHX Text
100% RESUBMISSION
AutoCAD SHX Text 01/14/19
AutoCAD SHX Text 06/29/20
AutoCAD SHX Text 04/27/20
AutoCAD SHX Text 05/24/19
AutoCAD SHX Text
75% SUBMISSION
AutoCAD SHX Text 07/15/19
AutoCAD SHX Text
BID SUBMISSION
AutoCAD SHX Text 08/07/20
AutoCAD SHX Text
100% RESUBMISSION
AutoCAD SHX Text 07/27/20
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 8'
AutoCAD SHX Text 4'
AutoCAD SHX Text 2'
AutoCAD SHX Text 1/4" = 1'-0"
E F G
2" 2" 2"
2"
2"
1"
2"
1,300 SQ FT
EXISTING MRI PRE-ACTION SPRINKLER ZONE
1,300 SQ FT
EXISTING MRI PRE-ACTION SPRINKLER ZONE
OH-2
OH-2
OH-2
EXISTING WET-PIPE SPRINKLER ZONE 2P03-02
EXISTING WET-PIPE SPRINKLER ZONE 2P03-01
OH-2
OH-2
OH-2
FIRE SUPPRESSION PLAN - THIRD
FLOOR - NEW WORK
1/4" = 1'-0"
FIRE SUPPRESSION PLAN - THIRD FLOOR - NEW WORK
FS3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
BID DOCUMENTS
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
Phase
STAMP
CONSULTANTS
321 4 5 6 7 8 9 10
Project Director
08/07/20
Revisions: Date:
RENOVATE MRI SUITE FOR
EQUIPMENT UPGRADES
ARCHITECTURE
PLANNING
ENGINEERING
BURDETTE KOEHLER MURPHY &
ASSOCIATES, INC.
MECHANICAL / ELECTRICAL ENGINEERS
BLAIR HILL LANE, SUITE 400
BALTIMORE, MARYLAND 21209
410.323.0600 - FAX 410.377.2543
BUILDING COST CONSULTANTS
COST ESTIMATING
12917 - 30TH AVENUE
PLATTSMOUTH, NEBRASKA 68048
402.298.8260 - FAX 402.298.8290
RICKERT ENGINEERING, INC.
STRUCTURAL ENGINEERING
8813 WALTHAM WOODS ROAD, SUITE 301
BALTIMORE, MARYLAND 21234
410.663.5110 - FAX 410.663.5114
35OfDwg.
DELLC Project Number : 180801D
ARCHITECT/ENGINEER OF RECORD
642-CSI-117
321 4 5 6 7 8 9 10
A
B
C
D
E
F
CORPORAL MICHAEL J. CRESCENZ
VA MEDICAL CENTER
PHILADELPHIA, PA
08/07/2020
8815 Centre Park Drive, Suite 200 Columbia, Maryland 21045
410-750-2246 / www.koffel.com
FIRE PROTECTION ENGINEERING
8815 CENTRE PARK DR., SUITE 200
COLUMBIA, MARYLAND 21045
410.750.2246 - FAX 410.750.2588
KOFFEL ASSOCIATES, INC.
BID DOCUMENTS
BUILDING FULLY SPRINKLERED
FS3
KLCMHB
GENERAL NOTES:
1. UNO, EXISTING FIRE SPRINKLER SYSTEM INFRASTRUCTURE SHALL REMAIN. ALL
AREAS WHERE CEILINGS ARE NOT BEING REMOVED SHALL REMAIN
OPERATIONAL AT ALL TIMES.
2. EXISTING ZONE VALUE ASSEMBLY FOR ZONE 2P03-02 IS LOCATED ABOVE
CEILING IN STAIR 12.
3. EXISTING VIKING TOTALPAC2 PRE-ACTION VALVE FOR MRI SCANNING ROOMS
AND EQUIPMENT ROOMS IS LOCATED IN MECHANICAL ROOM 4A100. REFER TO
PART PLAN 4/FS4 FOR ADDITIONAL INFORMATION.
4. WHERE REQUIRED, NEW SPRINKLERS WITHIN MRI SCANNING ROOMS SHALL BE
NON-FERROUS CONCEALED TYPE.
5. WHERE REQUIRED, NEW SPRINKLER PIPE WITHIN MRI SCANNING ROOMS SHALL
BE NON-FERROUS AND ROUTED THROUGH THE WAVE FILTER PLATE ABOVE
CEILING BEFORE PENETRATING ROOM.
6. MODIFICATIONS TO EXISTING FIRE SPRINKLER SYSTEM SHALL COINCIDE WITH
CONSTRUCTION PHASING. REFER TO ARCHITECTURAL PLANS FOR PHASING
INFORMATION. ALL PROPOSED SYSTEM OUTAGES SHALL BE SUBMITTED IN
WRITING TO THE COR FOR APPROVAL AT LEAST ONE WEEK IN ADVANCE.
7. SPRINKLER PROTECTION SHALL REMAIN ACTIVE THROUGHOUT DEMOLITION AND
CONSTRUCTION TO THE EXTENT POSSIBLE.
SHEET KEY NOTES:
REMOVE AND REPLACE EXISTING SPRINKLERS. RE-ALIGN NEW SPRINKLERS IN
NEW CEILING GRID AS NECESSARY.
EXISTING 2" UP TO PRE-ACTION VALVE. REFER TO PART PLAN 4/FS4.
EXISTING 2" STEEL TO 1" COPPER PIPE TRANSITION TO REMAIN.
AutoCAD SHX Text 3A151
AutoCAD SHX Text
MRI ROOM
AutoCAD SHX Text 3A152
AutoCAD SHX Text
MRI ROOM
AutoCAD SHX Text 3A152B
AutoCAD SHX Text
MRI ROOM
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text 3A152C
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text 3A152C
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
SOILD
AutoCAD SHX Text 3A151o
AutoCAD SHX Text
LINEN
AutoCAD SHX Text 3A151Q
AutoCAD SHX Text
LINEN
AutoCAD SHX Text 3A151P
AutoCAD SHX Text
TECH AREA
AutoCAD SHX Text 3A151L
AutoCAD SHX Text
CLOSET
AutoCAD SHX Text
CONTROL
AutoCAD SHX Text 3A151K
AutoCAD SHX Text
ROOM
AutoCAD SHX Text 3A151B
AutoCAD SHX Text
RECEPTION
AutoCAD SHX Text 3A151J
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 3A151i
AutoCAD SHX Text
INPATIENT
AutoCAD SHX Text 3A151C
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 3A151F
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 3A151H
AutoCAD SHX Text
TOILET
AutoCAD SHX Text 3A151D
AutoCAD SHX Text
CHANGING
AutoCAD SHX Text 3A151E
AutoCAD SHX Text
CHANGING
AutoCAD SHX Text 3A151G
AutoCAD SHX Text
TECH AREA
AutoCAD SHX Text 3A152A
AutoCAD SHX Text
MRI ROOM
AutoCAD SHX Text 3A151A
AutoCAD SHX Text
WAITING
AutoCAD SHX Text C3-8
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 2215 Conowingo Rd, Suite 100 Bel Air, Maryland 21015-1457 410.836.6611
AutoCAD SHX Text
TRUE NORTH
AutoCAD SHX Text
%%UKEY PLAN
AutoCAD SHX Text
%%UBUILDING 1
AutoCAD SHX Text
%%UBUILDING 2
AutoCAD SHX Text
PROJECT LOCATION
AutoCAD SHX Text
35% SUBMISSION
AutoCAD SHX Text
70% SUBMISSION
AutoCAD SHX Text
100% SUBMISSION
AutoCAD SHX Text
100% RESUBMISSION
AutoCAD SHX Text 01/14/19
AutoCAD SHX Text 06/29/20
AutoCAD SHX Text 04/27/20
AutoCAD SHX Text 05/24/19
AutoCAD SHX Text
75% SUBMISSION
AutoCAD SHX Text 07/15/19
AutoCAD SHX Text
BID SUBMISSION
AutoCAD SHX Text 08/07/20
AutoCAD SHX Text
100% RESUBMISSION
AutoCAD SHX Text 07/27/20
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 8'
AutoCAD SHX Text 4'
AutoCAD SHX Text 2'
AutoCAD SHX Text 1/4" = 1'-0"
2"
2"
FIRE SUPPRESSION DETAILS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
BID DOCUMENTS
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
Phase
STAMP
CONSULTANTS
321 4 5 6 7 8 9 10
Project Director
08/07/20
Revisions: Date:
RENOVATE MRI SUITE FOR
EQUIPMENT UPGRADES
ARCHITECTURE
PLANNING
ENGINEERING
BURDETTE KOEHLER MURPHY &
ASSOCIATES, INC.
MECHANICAL / ELECTRICAL ENGINEERS
BLAIR HILL LANE, SUITE 400
BALTIMORE, MARYLAND 21209
410.323.0600 - FAX 410.377.2543
BUILDING COST CONSULTANTS
COST ESTIMATING
12917 - 30TH AVENUE
PLATTSMOUTH, NEBRASKA 68048
402.298.8260 - FAX 402.298.8290
RICKERT ENGINEERING, INC.
STRUCTURAL ENGINEERING
8813 WALTHAM WOODS ROAD, SUITE 301
BALTIMORE, MARYLAND 21234
410.663.5110 - FAX 410.663.5114
35OfDwg.
DELLC Project Number : 180801D
ARCHITECT/ENGINEER OF RECORD
642-CSI-117
321 4 5 6 7 8 9 10
A
B
C
D
E
F
CORPORAL MICHAEL J. CRESCENZ
VA MEDICAL CENTER
PHILADELPHIA, PA
08/07/2020
8815 Centre Park Drive, Suite 200 Columbia, Maryland 21045
410-750-2246 / www.koffel.com
FIRE PROTECTION ENGINEERING
8815 CENTRE PARK DR., SUITE 200
COLUMBIA, MARYLAND 21045
410.750.2246 - FAX 410.750.2588
KOFFEL ASSOCIATES, INC.
BID DOCUMENTS
BUILDING FULLY SPRINKLERED
FS4
KLCMHB
NOTE:
TYPICAL ACOUSTIC CEILING PANEL.
LOCATE SPRINKLER WITHIN AREA
INDICATED.
6"
6"
21"
9"
48"
24"
F
T x
F
T
T
I L E
6"
6"
9"
9"
48"
24"
6"
6"
9"
9"
F
T x
F
T
T
I L E
ALL THREAD ROD
C-CLAMP WITH
LOCKNUT
ADJUSTABLE
SWIVEL RING
D I A
M E
T E
R
HANGER NOTES:
1. MAXIMUM UNSUPPORTED ARMOVER LENGTH SHALL NOT BE GREATER
THAN 36". WHERE SYSTEM PRESSURES EXCEED 100 PSI, MAXIMUM
UNSUPPORTED LENGTH SHALL NOT EXCEED 12".
2. MIN
" ALL THREAD ROD FOR PIPE DIAMETERS 4" AND SMALLER.
3. DO NOT SUPPORT SPRINKLER PIPE FROM BOTTOM CHORDS OF BAR
JOISTS OR FROM ROOF DECKING.
4. WHERE TRAPEZE HANGERS ARE USED, THEY SHALL BE INSTALLED IN
ACCORDANCE WITH NFPA 13: 9.1.1.7.
15'-0"
15'-0"
15'-0"
2"
2`
> 3"
12'-0"
12'-0"
15'-0"
1"
1`
1`
MAX. DISTANCE BETWEEN HANGERS
I-BEAM
F
T x
F
T
T
I L E
9"
9"
24"
24"
6" 6"
THROUGH PENETRANT: ONE PIPE INSTALLED
CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP
SYSTEM. PIPE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF
WALL ASSEMBLY.
FILL MATERIAL: SEALANT - FILL MATERIAL (NOT SHOWN)
APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES
OF WALL. BEAD OF FILL MATERIAL SHALL ALSO BE APPLIED AT
THE PIPE/WALL INTERFACE.
SPRINKLER SYSTEM PIPING
FIRE / SMOKE RATED BARRIER OR
PARTITION
FILL MATERIAL
BLACK STEEL PIPE SLEEVE (IF
PROVIDED, BASED ON SELECTED
UL-LISTED FIRESTOP SYSTEM)
NOTE: PROVIDE UL LISTED THROUGH-PENETRATION
FIRESTOP SYSTEM AT ALL RATED ASSEMBLIES.
REFER TO SHEET GI102 FOR MORE INFORMATION.
ALL THREAD ROD
C-CLAMP WITH
LOCKNUT
ADJUSTABLE
SWIVEL RING
BAR JOIST
NTSSCALE:
SPRINKLER PLACEMENT DETAIL
NTSSCALE:
TYPICAL THROUGH-WALL PENETRATION DETAIL
NTSSCALE:
TYPICAL HANGER DETAILS
I-BEAM OR
JOIST
ONE HANGER PER
TRAPEZE MAXIMUM
SHALLOW CONCRETE ANCHOR FOR
CONCRETE STRUCTURE
ALL THREAD ROD
CONCRETE STRUCTURE
ADJUSTABLE
SWIVEL RING
1/4"=1'-0"SCALE:
FIRE SUPPRESSION PART PLAN - FOURTH FLOOR - EXISTING
SHEET KEY NOTES:
EXISTING 2" DOWN TO THIRD FLOOR. REFER TO SHEET FS3 FOR CONTINUATION.
EXISTING 2" VIKING TOTALPAC 2 PRE-ACTION VALVE TO REMAIN.
EXISTING PRE-ACTION VALVE SUPPLY MAIN.
TO PRE-ACTION SPRINKLERS.
AutoCAD SHX Text F.E.C
AutoCAD SHX Text
STAIR
AutoCAD SHX Text
NO.12
AutoCAD SHX Text 4A100
AutoCAD SHX Text
MECHANICAL EQUIPMENT
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
CART
AutoCAD SHX Text
LIFT-2
AutoCAD SHX Text
SD
AutoCAD SHX Text 2215 Conowingo Rd, Suite 100 Bel Air, Maryland 21015-1457 410.836.6611
AutoCAD SHX Text
35% SUBMISSION
AutoCAD SHX Text
70% SUBMISSION
AutoCAD SHX Text
100% SUBMISSION
AutoCAD SHX Text
100% RESUBMISSION
AutoCAD SHX Text 01/14/19
AutoCAD SHX Text 06/29/20
AutoCAD SHX Text 04/27/20
AutoCAD SHX Text 05/24/19
AutoCAD SHX Text
75% SUBMISSION
AutoCAD SHX Text 07/15/19
AutoCAD SHX Text
BID SUBMISSION
AutoCAD SHX Text 08/07/20
AutoCAD SHX Text
100% RESUBMISSION
AutoCAD SHX Text 07/27/20
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 8'
AutoCAD SHX Text 4'
AutoCAD SHX Text 2'
AutoCAD SHX Text 1/4" = 1'-0"
| 01 G101 COVER SHEET |
| 02 G102 Life Safety Plan |
| 03 GI103 Phasing Plans and Notes |
| 04 G104 ICRA Plan and Details |
| 05 AD101 Demolition Plan and Sections |
| 06 AD102 Demolition Plan, Elevation and Sections |
| 07 AE101 New Work Plan |
| 08 AE201 Enlarged plans, Elevations and Sections |
| 09 AE401 RF Shielding Details and Notes |
| 10 AE601 FINISHES Layout |
| 11 S101 |
| 12 S102 |
| 13 M001 |
| 14 M101 |
| 15 M102 |
| 16 M201 |
| 17 M202 |
| 18 M301 |
| 19 M401 |
| 20 M501 |
| 21 E001 |
| 22 E101 |
| 23 E102 |
| 24 E201 |
| 25 E202 |
| 26 E301 |
| 27 E401 |
| 28 E501 |
| 29 02-FA1-FA1 |
| Sheets and Views |
| 02-FA1-FA1 |
| 30 02-FA2-FA2 |
| Sheets and Views |
| 02-FA2-02-FA2 |
| 31 02-FA3-FA3 |
| Sheets and Views |
| 02-FA3-FA3 |
| 32 02-FS1-FS1 |
| Sheets and Views |
| 02-FS1-FS1 |
| 33 02-FS2-FS2 |
| Sheets and Views |
| 02-FS2-FS2 |
| 34 02-FS3-FS3 |
| Sheets and Views |
| 02-FS3-FS3 |
| 35 02-FS4-FS4 |
| Sheets and Views |
| 02-FS4-FS4 |
File details come from the government source that posted it. Updated .