Red_Mountain_Generator_Specs___002_.pdf

PDF 154 KB Posted

Attached to
1PA5A008833.02 HUU Diesel Generator Set
Solicitation number
0000040898
Issued by
Sonoma County, San Francisco City, California

About this file

This is a specification document issued by the California Department of Forestry and Fire Protection for the procurement of two diesel prime power duty rated generator sets to support emergency communications equipment at CAL FIRE's Red Mountain repeater site (HUU Unit). The generators will replace aging and failing units currently housed indoors in a generator vault. The specified equipment consists of 25-35KW diesel standby generators rated for 120V/240V single phase, 3-wire operation, with prime power duty rating and 100% power factor capability. Each generator unit shall be stationary and skid-mounted at approximately 32 x 66 inches, NFPA 110 approved, and equipped with a digital control panel, electronic governor, integrated voltage regulator, low coolant shutdown, 1000W block heater, and standard duty air cleaner with radiator. The system must be capable of switching duties at programmable intervals of approximately 100 hours with N+1 architecture redundancy, supporting up to 8,760 hours per year of operation. Deliverables include freight to 135 Ridgway Avenue, Santa Rosa, California 95401, with offloading by CAL FIRE personnel, along with operations and maintenance manuals (two copies) and a six-month warranty from startup or 1,500 hours, whichever occurs first.

The specification also includes requirements for a 200-ampere open transition transfer switch with contactor type controller, rated for 120/240 single phase, 60Hz operation, three-pole configuration, and housed in a NEMA 3R enclosure. Each generator set includes single circuit breakers rated at 200A, battery and cables, and an external emergency shut-off push button. The document does not specify pricing terms, set-asides, response deadlines, or contract award dates within the provided specification details.

View the file

Other files

File Type Posted
Bidders_Instructions_1.2025.pdf PDF
Request_for_Quote_1PA5A008833.02.pdf PDF
Bidder_Declaration_Form.pdf PDF
calfire720__2_.pdf PDF
Cal_Recycle_Form.pdf PDF
Std204.pdf PDF
std205.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATE OF CALIFORNIA NATURAL RESOURCES AGENCY Gavin Newsom, Governor

“The Department of Forestry and Fire Protection serves and safeguards the people and protects the property and resources of California.”

DEPARTMENT OF FORESTRY AND FIRE PROTECTION

P.O. Box 944246

SACRAMENTO, CA 94244-2460

(916) 653-7772 Website: www.fire.ca.gov

Diesel Prime Power Duty Rated Generator Set Specifications

SCOPE

This specification sets forth the requirements for the 2 (two) Diesel Prime Power Duty Rated Generator Sets, required to support emergency communications equipment at CAL FIRE’s Red Mountain repeater site (HUU) Unit. These will replace two aging and failing units, housed indoors in a generator vault. System should be capable of switching duties at programmable intervals of approximately 100 hours and N+1 Architecture redundancy, capable of up to 8760 hours per year.

GENERATOR SPECIFICATIONS

• 25-35KW Diesel Standby Generator

• 120V/240V

• Single Phase, 3-Wire.

• Prime Power Duty Rated

• 100% Power Factor

• Stationary Skid Mounted approximately 32 x 66 inches

• NFPA 110 Approved

• Diesel

• Alternator – 125C Temp Rise Over 40C Amb

• Digital Control Panel

• Low Coolant Shutdown

• Electronic Governor

• Integrated Voltage Regulator

• Single Circuit Breakers – 200A; Battery and Cables

• 1000W Block Heater

• Standard Duty Air Cleaner

• Standard Radiator

• Operations & Maintenance Manuals (2 Copy)

• Includes: Freight to 135 Ridgway Ave, Santa Rosa, CA 95401 (Offload by CALFIRE

Personnel); 6 month from startup/1500 hour warranty

• External emergency shut-off push button

TRANSFER SWITCH SPECIFICATIONS

http://www.fire.ca.gov/

• 200A Open Transition Transfer Switch

• Contactor Type

• Controller

• 120/240 Single Phase

• 60HZ

• Three Pole

• NEMA 3R Encloser