QQ#_165038JB_Battery_Banks_for_Lucy_Switching_Station,_McMinn_&_Renaissance_Substations.pdf

PDF 177 KB Posted

Attached to
QQ# 165038JB Battery Banks for Lucy Switching Station, McMinn & Renaissance Substations
Solicitation number
QQ-2026-302
Issued by
Miami-Dade County, Florida

About this file

This is a Quick Quote solicitation issued by the City of Homestead, Florida, Energy Services Department, seeking quotations for the supply and delivery of three complete 125VDC Battery Bank Systems designated for critical infrastructure at the Lucy Switching Station, McMinn Substation, and Renaissance Substation. The battery banks provide DC power to trip circuit breakers during faults, power emergency lighting, and maintain communications during total AC power loss. Each system comprises 60 flooded lead-acid cells with lead-selenium positive plate alloy, a minimum capacity of 205 Ah at the 8-hour rate, and includes seismic-rated steel racks with acid-resistant coating, insulated connectors, stainless steel terminal lugs, maintenance kits, and flame arrestor vents. Additional line items include Gas Recombination Valves (three sets of 60 valves) and microprocessor-controlled SCR battery chargers with single-phase input options and 130 VDC at 20 amps output. The quotation was released on February 19, 2026, with responses due no later than February 27, 2026, at 3:00 PM EST, submitted electronically through the City's procurement portal. No site visits, bidders' conferences, or award dates are specified in the solicitation.

Pricing must detail fixed and firm costs for goods and services, exclude Federal Excise and State of Florida sales tax, and identify realistic lead times with preference given to vendors able to meet a 14–16 week delivery window. Freight terms are FOB Destination to Homestead, Florida, with the vendor responsible for all hazardous material handling and specialized offloading; collect shipments will not be accepted. Vendors may claim local vendor preference by providing a Local Business Tax Receipt. If pricing derives from government agency contracts, state term contracts, or cooperative contracts, supporting documentation must be provided. All cells must be manufactured in accordance with IEEE 450 and IEEE 485 standards and delivered filled and charged, with factory test reports included. Quoted prices remain fixed and firm throughout the contract term and delivery period. No incumbent information, set-asides, or specific funding amounts are identified in the solicitation.

View the file

Other files

File Type Posted
MM260130-01.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

QQ-2026-302 Page 1

QUICK QUOTE

City of Homestead

Discover The Opportunities

Gateway to Everglades & Biscayne National Parks

QQ-2026-302

DATE: THURSDAY, FEBRUARY 19, 2026

Procurement & Contract Services Department

450 SE 6th Avenue Homestead, FL 33030

QUOTE DUE DATE: FRIDAY, FEBRUARY 27, 2026 AT

3:00 PM, EST

RESPONSES MUST BE SUBMITTED

ELECTRONICALLY TO:

https://secure.procurenow.com/portal/cityofhomestead

1. INTRODUCTION

1.1. Summary

Project Overview

The City of Homestead Energy Services Dept (HPS) is seeking quotes for the supply and delivery of three (3) complete 125VDC Battery Bank Systems. These systems are critical infrastructure components for the Lucy Switching Station, McMinn Substation, and Renaissance Substation. The battery banks serve as the "heart" of the substation’s protection and control system, providing the necessary DC power to trip circuit breakers during faults, power emergency lighting, and maintain communications with the System Control Center during a total AC power loss.

1.2. Procurement Contact

Jhara Baker Buyer 1 450 SE 6th Ave Homestead, FL 33030

Department: HPS Energy | Electric Services

1.3. Timeline

Quote Request Date: February 19, 2026

Quote Due Date: February 27, 2026, 3:00pm

2. SCOPE OF WORK

2.1. Technical Specifications: 125VDC Station Battery Systems

1. Scope of Work

The vendor shall furnish and deliver three (3) complete 125VDC stationary battery systems, including racks and accessories, to the City of Homestead. These systems are intended for heavy-duty utility substation service, providing critical protection and control power.

https://secure.procurenow.com/portal/%7bproject.government.code%7d

QQ-2026-302 Page 2

2. Technical Requirements

• System Voltage: 125 VDC (Nominal).

• Number of Cells: 60 cells per system.

• Cell Type: Flooded Lead-Acid with Lead-Selenium (Low Antimony) positive plate alloy.

• Plate Design: Flat plate, optimized for medium-to-high rate discharge.

• Capacity: Minimum 205 Ah at the 8-hour rate (C8) to 1.75 Volts per cell (VPC) at 77°F (25°C).

• Container Material: High-impact, transparent plastic (SAN or equivalent) for easy visual inspection of electrolyte levels and plate condition.

• Basis of Design: Hoppecke Grid Power VM 2-210 or approved technical equivalent.

3. Required Accessories (Per System)

• Racks: Two-step or two-tier seismic-rated steel racks with acid-resistant coating.

• Connectors: Insulated inter-cell and inter-tier flexible cable connectors.

• Terminal Lugs: Two (2) hole NEMA stainless steel lugs for final connection to the DC charger/panel.

• Maintenance Kit: One (1) set per system, including a digital hydrometer, thermometer, and cell numbering stickers.

• Flame Arrestors: Standard ceramic flip-top flame arrestor vents.

4. Additional Component 1: (Gas Recombination valves)

• Requirement: Bidders shall provide a separate line-item cost for Gas Recombination Valves

(Hoppecke AquaGen Pro or equivalent).

• Performance: Valves must be capable of reducing hydrogen gas emissions and watering intervals by at least 95% under float-charge conditions.

5. Additional Component 2: (Battery Charger)

• Microprocessor-controlled SCR battery charger with single phase and 120/208/240 VAC in, 130

VDC at 20 amps out, HMI User interface LCD screen, standard filtration, standard AC/DC breakers (14KAIC/5KAIC), and NEMA 1 cabinet

6. Quality Assurance & Testing

• Standards: Cells must be manufactured in accordance with IEEE 450 (Maintenance/Testing) and

IEEE 485 (Sizing) guidelines.

• Factory Test: Each system must be factory-charged and tested for capacity and voltage consistency before shipment. Test reports must be included with the delivery.

7. Delivery & Shipping Terms

• Condition: Cells shall be delivered filled and charged (Wet-cell) unless otherwise specified.

QQ-2026-302 Page 3

• Freight: FOB Destination: Homestead, FL. The vendor is responsible for all hazardous material handling and specialized offloading requirements.

• Lead Time: Bidders must state the firm's delivery lead time. Preference may be given to vendors able to meet the 14–16 week window.

3. PRICING PROPOSAL

In submitting a Quotation, the Supplier acknowledges and agrees that the Quotation shall:

A. detail the fixed and firm price of the Goods and/or Services;

B. specify a realistic lead time;

C. include a full description, part number and brand name where these differ to what is shown on the City's request;

D. does not include Federal Excise and State of Florida sales tax;

E. If pricing is in accordance with another government agency's contract, State term contract, or

Cooperative contract, that information shall be provided with its submission to include tabulations, agreements and any other applicable documentation.

F. be prepared to fulfill according to the delivery terms specified in the Quick Quote.

G. Freight terms are F.O.B. destination, freight prepared by Seller unless otherwise agreed upon in advance and will be stated on the Purchase Order. Collect shipments will not be accepted.

The City will accept a Quotation by issuing a Purchase Order to the Supplier. No Quotation shall be deemed accepted by the City unless a Purchase Order has been issued to the Supplier.

Under no circumstances should a vendor fill an order for any City department without a Purchase Order issued by the City of Homestead.

If the vendor is awarded a Purchase Order (Contract) under this request, the price(s) quoted shall remain fixed and firm during the term of this Contract and/or delivery and acceptance of goods.

Line Item Description Unit of

Measure

Unit Cost

1 125VDC Battery Bank (60 Cells), Flooded Lead-

Selenium, 205Ah @ C8. Includes seismic rack and standard accessories (Quantity 3 systems).

3 Sets

2 Gas Recombination Valves (Set of 60) for (Quantity

3 sets)

3 Sets

3 Microprocessor controlled SCR battery charger with single phase and 120/208/240 VAC in, 130 VDC at

20 amps out

QQ-2026-302 Page 4

Line Item Description Unit of

Measure

Unit Cost

4 Freight/Shipping (FOB Destination: Homestead, FL) for all equipment.

Lot

4. SUBMITTALS

The City request Suppliers to provide a Quotation for the supply of the Goods and/or Services detailed in this Quick Quote by the submission due date.

All correspondence from the Supplier to the City (including submission of the Quotation) shall be submitted electronically.

In the event that the Supplier chooses not to submit a Quotation, the City requests that the Supplier duly inform the City’s contact person of that fact.

All Quotations must be received no later than Friday, February 27, 2026, 3:00 pm, EST. The responsibility for submitting quotes before the stated time and date is solely the responsibility of the vendor. The City will not be responsible for delays caused for any occurrence.

RESPONSE TO THIS REQUEST REQUIRES THAT ALL TERMS ARE ADHERED TO. SUPPLIER SUBMITTING

ADDITIONAL TERMS & CONDITIONS MAY BE CAUSE FOR NON-CONSIDERATION AND REJECTION OF

QUOTE.

4.1. CERTIFICATION*

I certify that this quote submission is made without prior understanding, agreement, or connection with any corporation, firm or person submitting a quote for the same materials, supplies, or equipment, and is in all respects fair and without collusion or fraud. I agree to abide by all terms and conditions of this request and certify that I am authorized to act on behalf of the bidder/contractor/supplier.

☐ Please confirm

*Response required

4.2. LOCAL VENDOR PREFERENCE*

Are you seeking LOCAL VENDOR PREFERENCE?

☐ Yes

☐ No

*Response required

When equals "Yes"

4.2.1. LOCAL BUSINESS TAX RECEIPT*

Upload a copy of your Local Business Tax Receipt.

For more information see:

https://www.homesteadfl.gov/168/Business-Tax-Receipt https://www.homesteadfl.gov/faq.aspx?qid=60 https://library.municode.com/fl/homestead/codes/code_of_ordinances?nodeId=PTIICOCI_CH2AD_ARTVIIICOPU_DIV2COBI_S2-411PULI https://www.homesteadfl.gov/168/Business-Tax-Receipt https://www.homesteadfl.gov/faq.aspx?qid=60

QQ-2026-302 Page 5

*Response required

4.3. QUOTE DOCUMENTATION

If this quotation is being submitted under a cooperative or piggyback contract, please upload a document listing the contract name and number, or any other required information listed in the SCOPE

OF WORK or PRICING PROPOSAL section(s).

All pricing, terms, and conditions must comply with the referenced agreement.

4.4. Lead Time*

*Response required

4.5. Warranty*

*Response required https://procurement.opengov.com/portal/cityofhomestead/projects/239066/document?section=undefined