Q&A Document 1.pdf

PDF 2 KB Posted

Attached to
Lake Fire Alarm
Solicitation number
C10384
Issued by
Kit Carson County, Denver City, Colorado

About this file

This document is a Questions and Answers (Q&A) document for the Lake Fire Alarm project issued by Denver Public Schools, specifically for Project C10384. The Q&A addresses three key technical questions from potential bidders regarding fire alarm system installation requirements, including conduit specifications, device protection, and wire gauge requirements. Specifically, the document clarifies that fire alarm system wire must be installed in Electrical Metallic Tubing (EMT), with the ability to reuse existing conduit and pull new wire, and that free-hanging fire alarm wire will not be accepted.

The technical specifications outline precise installation guidelines, such as wire guard requirements being limited to gymnasiums and locker rooms, and wire conductor specifications mandating 16-AWG for Initiating Device Circuits and Signaling Line Circuits, and 14-AWG for Notification Appliance Circuits. The Q&A was issued on 12/11/2024 and provides critical technical guidance for bidders to ensure compliance with Denver Public Schools' fire alarm system replacement standards at Lake Middle School, helping potential contractors understand the exact requirements for the project.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions & Answers - 1

Project C10384 - Lake Fire Alarm

Buying Organization Denver Public Schools

No Question/Answer Question Date

Q1 Question: Conduit Requirements

Is full conduit required?

Answer: Fire alarm system wire and cable shall be installed in Electrical Metallic Tubing (EMT). We can reuse the current EMT and just pull new wire in it. If there is no conduit in place we must add new. Free hanging FA wire will not be accepted.

12/11/2024

Q2 Question: Devices Cages

Are wire guards required for all devices, or just in gym area?

Answer: Only in gymnasiums and locker rooms.

12/11/2024

Q3 Question: Wire Requirements

Are there any specific specifications for Fire Alarm wire?

Answer: D. Wire: 1. Number and size of conductors shall be as recommended by the fire alarm system manufacturer, but not less than 16-AWG for Initiating Device Circuits and Signaling Line Circuits, and

14-AWG for Notification Appliance Circuits.

12/11/2024

Questions & Answers - 1

File details come from the government source that posted it. Updated .