ADDED DATA.pdf

PDF 41 KB Posted

Attached to
CABLE, POWER Federal contract opportunity
Solicitation number
Q5259
Issued by
Defense Logistics Agency Land and Maritime

About this file

This document is an Added Data specification for a power electrical cable with detailed technical requirements. The cable is a 4-conductor, AWG-4 size copper cable of Type W, rated for 90 degrees Celsius, with a black jacket and 2000-volt rating. It is UL-listed and requires a continuous length of 500 feet per roll. The cable must be durably marked at 24-inch intervals with specific information including manufacturer, size, number of conductors, type, temperature rating, voltage, and UL/CSA certification. A technical note highlights that the cable markings are indent-stamped rather than embossed, which ensures the markings will remain legible and not scrape or rub off over time.

View the file

Other files for this federal contract opportunity

Other files attached to CABLE, POWER, newest first.
File Type Posted
Solicitation - SPMYM226Q5259.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ADDED DATA

NIIN LLS054213 DOCUMENT 53497906

CABLE, POWER ELECTRICAL

AWG-4

4 CONDUCTOR, EACH ROLL ROUND 500 FT CONTINUOUS LENGTH REQUIRED

COPPER, TYPE W, 90 DEG C

UL-LISTED

BLACK JACKET, RATED 90 DEGREE CENTIGRADE, 2000 VOLT

EMBOSSED/INDENTED WITH FOLLOWING: MFR

SIZE

NO OF CONDUCTORS

TYPE

TEMP RATING, VOLTAGE OR UL/CSA

CABLES SHALL BE DURABLY MARKED ON THE SURFACE AT INTERVALS NOT EXCEEDING

24 INCHES WITH DATA ABOVE.

TF CABLE PN - W4-4 ADDED DATA -"1-The number of conductors and the size of the conductors is marked on the cable.

2-They are not embossed but Indent Stamped which to me means that they will always be on the cable and they will not scrape or rub off as will the

Embossed type.