- J012--Hydraulic Survey of Suppression System and Name Plate Installation Northampton VA Medical Center
- Solicitation number
- 36C24125Q0682
About this file
The document is a Performance Work Statement (PWS) for a hydraulic fire suppression system survey at the Edward P. Boland Campus VA Medical Center in Leeds, Massachusetts. The primary objectives include reviewing existing design documentation, conducting a comprehensive field survey of dry and wet sprinkler systems, performing NFPA 13 code review and calculations for both 1978 and 2025 code years, and creating new riser name plates.
The contractor must provide professional engineering services with a registered fire protection professional having at least 5 years of Massachusetts-specific experience. Deliverables include hydraulic calculations, code compliance analysis, stamped drawings in CAD and PDF formats, and a narrative summarizing all work completed. The survey must cover various building occupancies, with specific scheduling requirements for clinical and non-clinical areas. The solicitation is a small business set-aside with a submission deadline of August 5, 2025, at 4:00 PM EST, with a site visit scheduled for July 30, 2025, at 10 AM. The contract will be awarded on a best-value basis, considering price, past performance, and technical capabilities.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24125Q0682.docx | DOCX document | |
| Northampton VA Medical Center Site Map.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachments: Building 1 Fire Suppression System Survey and Design Basis Reconstitution
1979_Record
2000_sprinkler_survey_drawings
2011_Westend_renovation
Department of Veterans Affairs
LEEDS, MASSACHUSETTS 01053
BUILDING 1 WEST WING
GERI PSYCH UNIT
PROJECT NO. 126.107
AS BUILT DRAWING PACKAGE
FEBRUARY 14, 2019
VFOTNE
MTR
A
P E
D S
RI
A
FF
A
SNARETE
ES OF
AM
ERIC
AU
N
ITED
STAT
DRAWING LIST
1-M301 MECHANICAL THIRD FLOOR ATTIC SECTIONS
1-M501 MECHANICAL DETAILS SHEET 1
1-M502 MECHANICAL DETAILS SHEET 2
1-M503 MECHANICAL DETAILS SHEET 3
1-M601 MECHANICAL CONTROLS SHEET 1
1-M602 MECHANICAL CONTROLS SHEET 2
1-M701 MECHANICAL RISER DIAGRAMS SHEET 1
1-M702 MECHANICAL RISER DIAGRAMS SHEET 2
1-M801 MECHANICAL SCHEDULES SHEET 1
1-M802 MECHANICAL SCHEDULES SHEET 2
1-E001 ELECTRICAL LEGEND & NOTES
1-EL103 ELECTRICAL SECOND FLOOR LIGHTING RENOVATION PLAN
1-EL104 ELECTRICAL THIRD FLOOR ATTIC LIGHTING RENOVATION PLAN
1-EP103 ELECTRICAL SECOND FLOOR POWER RENOVATION PLAN
1-EP104 ELECTRICAL THIRD FLOOR ATTIC POWER RENOVATION PLAN
1-ES103 ELECTRICAL SECOND FLOOR SIGNAL RENOVATION PLAN
1-ES104 ELECTRICAL THIRD FLOOR ATTIC SIGNAL RENOVATION PLAN
1-E501 ELECTRICAL DETAILS
1-E601 ELECTRICAL POWER DISTRIBUTION DIAGRAM
1-E602 ELECTRICAL LOW VOLTAGE DIAGRAMS
1-F001 FIRE PROTECTION LEGEND
1-FX103 FIRE PROTECTION SECOND FLOOR RENOVATION PLAN
1-FX104 FIRE PROTECTION THIRD FLOOR ATTIC RENOVATION PLAN
1-F501 FIRE PROTECTION DETAILS
1-A103 SECOND FLOOR PLAN
1-A104 THIRD FLOOR ATTIC PLAN
1-AI103 SECOND FLOOR REFLECTED CEILING PLAN
1-A201 RENOVATION EXTERIOR ELEVATIONS SHEET 1
1-A202 RENOVATION EXTERIOR ELEVATIONS SHEET 2
1-A301 SECOND FLOOR ROOM FINISH SCHEDULE
1-A302 SECOND FLOOR DOOR SCHEDULE
1-A401 ENLARGED PLANS & INTERIOR ELEVATIONS SHEET 1
1-A402 ENLARGED PLANS & INTERIOR ELEVATIONS SHEET 2
1-A403 ENLARGED PLANS & INTERIOR ELEVATIONS SHEET 3
1-A404 ENLARGED PLANS & INTERIOR ELEVATIONS SHEET 4
1-P001 PLUMBING LEGEND & SCHEDULES
1-PL101 PLUMBING BASEMENT RENOVATION PLAN
1-PL102 PLUMBING FIRST FLOOR RENOVATION PLAN
1-PL103 PLUMBING SECOND FLOOR RENOVATION PLAN
1-PL104 PLUMBING THIRD FLOOR ATTIC RENOVATION PLAN
1-P501 PLUMBING DETAILS SHEET 1
1-P502 PLUMBING DETAILS SHEET 2
1-P503 PLUMBING DETAILS SHEET 3
1-M001 MECHANICAL LEGEND & NOTES
1-MH101 MECHANICAL BASEMENT RENOVATION PLAN
1-MH102 MECHANICAL FIRST FLOOR RENOVATION PLAN
1-MH103 MECHANICAL SECOND FLOOR RENOVATION PLAN
1-MH104 MECHANICAL THIRD FLOOR ATTIC DUCTWORK RENOVATION PLAN
1-MP104 MECHANICAL THIRD FLOOR ATTIC PIPING RENOVATION PLAN
1-EP101 ELECTRICAL BASEMENT POWER RENOVATION PLAN
1-M504 MECHANICAL DETAILS SHEET 4
1-GI001 COVER SHEET
SITE PLANVICINITY MAP
1-LS103 SECOND FLOOR LIFE SAFETY PLAN
Drawing Title
Approved: Safety Manager
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Scale
Revisions Date
WEST WING
BUILDING 1
126.107
NORTHAMPTON
February 11, 2011
KEY PLAN:
421 NORTH MAIN STREET, LEEDS, MA 01053
Drawn
GERI-PSYCH UNIT
OF
Professional Seal
Department of Veterans Affairs
CT I
ENGINEERS
GOLDSTEIN - MILANOLLC
Structural Engineers
125 Main Street Reading, MA 01867
(781) 670-9990 tel
(781) 670-9939 fax
GOLDSTEIN - MILANOLLC
FOUNDED 1890
978 667-2900
ARCHITECTS ENVIRONMENTAL CONSULTANTS
381 BOSTON ROAD BILLERICA MASSACHUSETTS 01821-1803
tel: (508) 748-2620 fax: (508) 748-0059
525 Mill Street Marion, MA 02738
THOMPSON
CONSULTANTS, INC.
ENGINEER:
ARCHITECT &
SPACE PLANNER:
STRUCTURAL:
CODE CONSULTANT:
Phone: (617) 523-8227 Fax: (617) 523-8016
Code Consulting www.rwsullivan.com
The Schrafft Center, 529 Main St., Suite 203 Boston, Massachusetts 02129-1107
R. W. Sullivan Engineering
1167.01RWS Job #:
VFOTNE
MTR
A
P E
D S
RI
A
FF
A
SNARETE
ES OF
AM
ERIC
AU
N
ITED
STAT
FEBRUARY 14, 2019
ASBESTOS DESIGNER:
Approved: Project Engineer
AS-BUILT DOCUMENTS
COVER SHEET
SFG JJH NO SCALE
1-GIOO1
1 53
Drawing Title
Approved: Safety Manager
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Scale
Revisions Date
WEST WING
BUILDING 1
126.107
NORTHAMPTON
February 11, 2011
KEY PLAN:
421 NORTH MAIN STREET, LEEDS, MA 01053
Drawn
GERI-PSYCH UNIT
OF
Professional Seal
Department of Veterans Affairs
CT I
ENGINEERS
GOLDSTEIN - MILANOLLC
Structural Engineers
125 Main Street Reading, MA 01867
(781) 670-9990 tel
(781) 670-9939 fax
GOLDSTEIN - MILANOLLC
FOUNDED 1890
978 667-2900
ARCHITECTS ENVIRONMENTAL CONSULTANTS
381 BOSTON ROAD BILLERICA MASSACHUSETTS 01821-1803
tel: (508) 748-2620 fax: (508) 748-0059
525 Mill Street Marion, MA 02738
THOMPSON
CONSULTANTS, INC.
ENGINEER:
ARCHITECT &
SPACE PLANNER:
STRUCTURAL:
CODE CONSULTANT:
Phone: (617) 523-8227 Fax: (617) 523-8016
Code Consulting www.rwsullivan.com
The Schrafft Center, 529 Main St., Suite 203 Boston, Massachusetts 02129-1107
R. W. Sullivan Engineering
1167.01RWS Job #:
VFOTNE
MTR
A
P E
D S
RI
A
FF
A
SNARETE
ES OF
AM
ERIC
AU
N
ITED
STAT
FEBRUARY 14, 2019
ASBESTOS DESIGNER:
Approved: Project Engineer
AS-BUILT DOCUMENTS
FIRE PROTECTION
LEGEND
SFG JJH NTS
1-F001 50 53
Drawing Title
Approved: Safety Manager
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Scale
Revisions Date
WEST WING
BUILDING 1
126.107
NORTHAMPTON
February 11, 2011
KEY PLAN:
421 NORTH MAIN STREET, LEEDS, MA 01053
Drawn
GERI-PSYCH UNIT
OF
Professional Seal
Department of Veterans Affairs
CT I
ENGINEERS
GOLDSTEIN - MILANOLLC
Structural Engineers
125 Main Street Reading, MA 01867
(781) 670-9990 tel
(781) 670-9939 fax
GOLDSTEIN - MILANOLLC
FOUNDED 1890
978 667-2900
ARCHITECTS ENVIRONMENTAL CONSULTANTS
381 BOSTON ROAD BILLERICA MASSACHUSETTS 01821-1803
tel: (508) 748-2620 fax: (508) 748-0059
525 Mill Street Marion, MA 02738
THOMPSON
CONSULTANTS, INC.
ENGINEER:
ARCHITECT &
SPACE PLANNER:
STRUCTURAL:
CODE CONSULTANT:
Phone: (617) 523-8227 Fax: (617) 523-8016
Code Consulting www.rwsullivan.com
The Schrafft Center, 529 Main St., Suite 203 Boston, Massachusetts 02129-1107
R. W. Sullivan Engineering
1167.01RWS Job #:
VFOTNE
MTR
A
P E
D S
RI
A
FF
A
SNARETE
ES OF
AM
ERIC
AU
N
ITED
STAT
FEBRUARY 14, 2019
ASBESTOS DESIGNER:
Approved: Project Engineer
AS-BUILT DOCUMENTS
FIRE PROTECTION
DETAILS
SFG JJH NTS
1-F501 53 53
ELEVATOR
BATHTUB
CENTER WALL
ON COLUMN
CENTER WALL ON COLUMN
A L
IG
N
A L
IG
N
ALIGN
A L
IG
N
T O
E X
IS
T
IN
G
CENTER DOOR
IN EXISTING
CORRIDOR
MIN.
SEE ENLARGED
PLAN FOR DETAILS
ALIGN WITH
COLUMN
ALIGN FACE WITH
EXTERIOR WALL
ALIGN WITH
COLUMN
CENTER WALL
ON COLUMN
NOTE JOG IN
STRUCTURE
NOTE JOG IN
STRUCTURE
CENTER DOOR
IN CORRIDOR
SEE ENLARGED
PLAN FOR DETAILS
2WA-6, 2WA-5
EXISTING EXPANSION
JOINT
2WB-75
2WB-73
2WB-782WB-80
2WB-66
2WB-65
2WB-64
2WB-672WB-68
2WB-62
2WB-69
2WB-61
2WB-76
2WB-77
2WB-79
2WB-74
2WCS-1
2WB-48
VITREOUS CHINAC_SINKSK-6676
2WB-542WB-53
2WCo-5
2WCo-4
2WCo-3
2WCo-22WCo-1
2WB-702WB-60
2WB-57
2WB-72
2WB-71
2WB-592WB-58
2WB-56
2WB-55
2WB-52
2WB-51
2WB-81
2WB-432WB-44
2WB-45
2WB-46
2WB-47
2WB-49
2WB-50
2WC-422WC-41
2WC-40
2WC-39
2WC-38
2WC-37
2WA-27
2WA-262WA-25
2WA-24
2WA-23
2WA-22
2WA-212WA-202WA-19
2WA-18
2WA-172WA-13
2WA-12
2WA-10
2WA-282WA-29
2WA-30
2WA-312WA-322WA-332WA-342WA-35
2WA-36
2WA-12WA-2
2WA-3
2WA-4
2WA-52WA-6
2WA-72WA-8
2WA-9
SECOND FLOOR PLAN PROPOSED RENOVATIONS
SCALE: 18" = 1'-0"
HOUSE B
HOUSE A
B
C
I
J
A
D
E
F
G
H
K
L
M
N
O
P
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28
TELE/DATA
CLOSET
2WA-16
2WA-14
2WA-15
KEY NOTES
PIPE SIZE # OF SPRINKLER
HEADS
SPRINKLER PIPE SIZE SCHEDULE
Drawing Title
Approved: Safety Manager
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Scale
Revisions Date
WEST WING
BUILDING 1
126.107
NORTHAMPTON
February 11, 2011
KEY PLAN:
421 NORTH MAIN STREET, LEEDS, MA 01053
Drawn
GERI-PSYCH UNIT
OF
Professional Seal
Department of Veterans Affairs
CT I
ENGINEERS
GOLDSTEIN - MILANOLLC
Structural Engineers
125 Main Street Reading, MA 01867
(781) 670-9990 tel
(781) 670-9939 fax
GOLDSTEIN - MILANOLLC
FOUNDED 1890
978 667-2900
ARCHITECTS ENVIRONMENTAL CONSULTANTS
381 BOSTON ROAD BILLERICA MASSACHUSETTS 01821-1803
tel: (508) 748-2620 fax: (508) 748-0059
525 Mill Street Marion, MA 02738
THOMPSON
CONSULTANTS, INC.
ENGINEER:
ARCHITECT &
SPACE PLANNER:
STRUCTURAL:
CODE CONSULTANT:
Phone: (617) 523-8227 Fax: (617) 523-8016
Code Consulting www.rwsullivan.com
The Schrafft Center, 529 Main St., Suite 203 Boston, Massachusetts 02129-1107
R. W. Sullivan Engineering
1167.01RWS Job #:
VFOTNE
MTR
A
P E
D S
RI
A
FF
A
SNARETE
ES OF
AM
ERIC
AU
N
ITED
STAT
FEBRUARY 14, 2019
ASBESTOS DESIGNER:
Approved: Project Engineer
AS-BUILT DOCUMENTS
FIRE PROTECTION
SECOND FLOOR
RENOVATION PLAN
SFG JJH 1/8"=1'-0"
1-FX103
51 53 x .2
THIRD FLOOR ATTIC PLAN PROPOSED RENOVATIONS
SCALE: 18" = 1'-0"
HOUSE B
HOUSE A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23
B
C
I
J
A
D
E
F
G
H
K
L
M
N
O
P
24 25 26 27 2817.2 17.4 17.6 17.8
15.313.512.511.510.53.5 4.5 5.5 6.5
8.1 9.1
1.8
D.4
D.8
E.4
E.8
F.4
F.8
H.5
G
G
KEY NOTES
Drawing Title
Approved: Safety Manager
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Scale
Revisions Date
WEST WING
BUILDING 1
126.107
NORTHAMPTON
February 11, 2011
KEY PLAN:
421 NORTH MAIN STREET, LEEDS, MA 01053
Drawn
GERI-PSYCH UNIT
OF
Professional Seal
Department of Veterans Affairs
CT I
ENGINEERS
GOLDSTEIN - MILANOLLC
Structural Engineers
125 Main Street Reading, MA 01867
(781) 670-9990 tel
(781) 670-9939 fax
GOLDSTEIN - MILANOLLC
FOUNDED 1890
978 667-2900
ARCHITECTS ENVIRONMENTAL CONSULTANTS
381 BOSTON ROAD BILLERICA MASSACHUSETTS 01821-1803
tel: (508) 748-2620 fax: (508) 748-0059
525 Mill Street Marion, MA 02738
THOMPSON
CONSULTANTS, INC.
ENGINEER:
ARCHITECT &
SPACE PLANNER:
STRUCTURAL:
CODE CONSULTANT:
Phone: (617) 523-8227 Fax: (617) 523-8016
Code Consulting www.rwsullivan.com
The Schrafft Center, 529 Main St., Suite 203 Boston, Massachusetts 02129-1107
R. W. Sullivan Engineering
1167.01RWS Job #:
VFOTNE
MTR
A
P E
D S
RI
A
FF
A
SNARETE
ES OF
AM
ERIC
AU
N
ITED
STAT
FEBRUARY 14, 2019
ASBESTOS DESIGNER:
Approved: Project Engineer
AS-BUILT DOCUMENTS
FIRE PROTECTION
THIRD FLOOR ATTIC
RENOVATION PLAN
SFG JJH 1/8"=1'-0"
1-FX104
52 53
2018_eastend_flr2 renovation
MATERIAL APPROVAL SUBMITTAL
(See Instructions on Reverse)
TO: (Contracting Officer) FROM: (Contractor) DATE
CONTRACT NUMBER SUBMISSION NUMBER SUBMITTAL
NEW RESUBMITTAL
PREVIOUS SUBMISSION NUMBER PROJECT NUMBER
TO BE COMPLETED BY CONTRACTOR FOR GOVERNMENT USE ONLY
ITEM
NO.
SPECIFICATION SECTION/
PARA NO./DRAWING NO.
DESCRIPTION OF MATERIAL
(Include Type, Model Number, Mfg., etc. & file name of attachments)
AP-
PROVED
DISAP-
PROVED
SEE
REVERSE INITIAL
BY COMPLETING THIS FORM, THE UNDERSIGNED CONTRACTOR CERTIFIES THAT
THE MATERIAL COMPLIES WITH ALL SPECIFICATIONS OF SUBJECT CONTRACT.
DATE TYPE OR PRINT NAME AND TITLE SIGNATURE
FOR GOVERNMENT USE ONLY
TO: (A/E)
For Evaluation and Action
DATE TYPE OR PRINT NAME AND GRADE SIGNATURE
TO: (VA Engineer / COR)
RECOMMEND APPROVAL DISAPPROVAL AS INDICATED ABOVE AND SUBJECT TO ANY APPLICABLE COMMENTS ON THE REVERSE
DATE TYPE OR PRINT NAME AND GRADE SIGNATURE
TO: (Contracting)
APPROVED DISAPROVED AS INDICATED ABOVE AND SUBJECT TO ANY APPLICABLE COMMENTS ON THE REVERSE SIDE. REQUEST
RESUBMITTAL ON DISAPPROVED ITEMS WITHIN DAYS OF DATE SHOWN BELOW.
DATE TYPE OR PRINT NAME AND GRADE SIGNATURE
18-023
M. Chapman COR: J. Goldin IRONCLAD SERVICES, INC 02-20-19
VA241-13-D-0039 TO 36C24118N9726 211313-01-R1
631-17-100 / 631-C87025
1 21 13 13 PARA 1.4 SHOP DRAWINGS - WET SPRINKLER SYSTEM X
02-20-19 Paul Irizarry (PM) / Tammy Chaves (APM)
DuBois & King, Inc. / Chase Engineering Approved
03-11-2019 Matthew Chase, P.E. / R. Kischko, P.E.
RENOVATE BLDG 1, SPECIALTY CARE CLINICS - NORTHAMPTON VAMC
Tammy Chaves Digitally signed by Tammy Chaves Date: 2019.02.19 11:50:46 -05'00'
JG
X
3/12/2019 Josee Goldin
COMMENTS
(Number to correspond with applicable Item Number on reverse)
INSTRUCTIONS TO CONTRACTORS
1. The term "material" is defined as articles, supplies, raw materials, equipment, parts, components, and completed end items that are to be incorporated into the work required by the contract.
2. This form is to be used by Contractors for submitting Shop Drawings (*.DWG or *.PDF format), Manufacturer's Literature and Certificates (scanned as * .PDF) to the Government for approval in accordance with the provisions of this contract. Unless otherwise specified, it is to be prepared, signed, and E-mailed to the Contracting Officer with appropriate attachments. One paper format copy shall be submitted as well.
3. Item(s) to be approved will be clearly tabbed or identified. Data pertaining to item(s) to be approved will be clearly identified or tabbed, particularly where documents are voluminous, in order to properly evaluate the materials or articles to be incorporated in the work. Each attachment will be numbered to correspond with the item number shown on the face of this form.
4. Requests submitted shall be numbered consecutively, by contract, in the space entitled "Submission No.". This number, in addition to the Contract No., will be used to identify each Material Approval Submittal. Resubmissions will be indicated in the appropriate block and the insertion of previous submission number and data in addition to a new submission number. A single submission should be used for all work of a section of the specifications, but in NO instance should the submission include work for more than one (1) contract. Allow reasonable time in accordance with the project specifications for review of the submittal(s) by the A/E and Government. Submittals requiring priority handling will be submitted by separate submittal using the form and so marked across the face of the form.
5. This Material Approval Submittal is not valid unless it is signed by the Contracting Officer. This approval is required as called for by the Contracting Officer under the terms of this contract. One paper copy of the submittal is to be hand signed for Contracting Officers records.
6. The A/E and Government review is limited to checking for conformance with the information given and the design concept expressed in the contract documents. The Contractor and/or Construction Manager remains totally responsible for confirming all dimensions, quantities, fabrication, construction means and methods, techniques, sequences in the work, procedures, and coordination of the work for all trades.
7. This review does not relieve the Contractor of full responsibility for strict compliance with all requirements of contract plans and specifications. Provide and install all supplementary or miscellaneous items, appurtenances, devices and their available options incidental to or necessary for a functionally, sound, secure, complete, compatible and code compliant system.
Randolph, Vermont South Burlington, Vermont Brandon, Vermont Bedford, New Hampshire Laconia, New Hampshire
Keene, New Hampshire Buffalo, New York
SUBMITTAL REVIEW
Project Name: Renovate Building 1, Specialty Care Clinics
Project Number: 524066 / VAMC Project 631-17-100
Project Location: VAMC Leeds, MA
Submittal Items: SHOP DWG - WET-PIPE SPRINKLER SYSTEM (RESUBMIT)
Submittal Number: 21 13 13-01.R1
Submitted by: Ironclad Services, Inc.
ITEM
NO.
SPEC SECTION,
PARA NO.,
DRAWING NO.
DESCRIPTION
A C
C E
P T
E D
A C
C E
P T
A S
N O
T
R
V
IS
S U
B M
IT
J E
C T
21 13 13 PARA 1.4 SHOP DRAWINGS - WET SPRINKLER
SYSTEM
This review is only for general conformance with the design concept and the information given in the
Construction Documents. Corrections or comments made on the shop drawings during this review do not relieve the Contractor from compliance with the requirements of the plans and specifications. Acceptance of a specific item shall not include acceptance of an assembly of which the item is a component. The
Contractor is responsible for: dimensions to be confirmed and correlated at the jobsite; information that pertains solely to the fabrication processes or to the means, methods, techniques, sequences and procedures of construction; coordination of the Work with that of all other trades and performing all
Work in a safe and satisfactory manner. The Engineer assumes no liability for errors or omissions that may be contained herein. The Contractor, by approving and submitting these documents, verifies their accuracy as stipulated on the Contractor’s Shop Drawing Stamp.
Date: 03-11-2019 Reviewed By: Matthew Chase, P.E.
Robert F. Kischko, P.E.
Notes:
1. None.
WATER SUPPLY INFORMATION
NOTES:
1. ADJUST SPRINKLER DROPS AS NECESSARY TO CLEAR OBSTRUCTIONS SUCH AS THE CEILING
GRID SYSTEM, LIGHT FIXTURES, HVAC DUCTWORK, DIFFUSERS, GRILLS, ETC.
2. REFER TO THE FLOOR PLANS FOR SPRINKLER HEAD TYPES.
ALL BLACK STEEL SCHEDULE 40
PIPING, TYPICAL
PROVIDE LENGTH TO
SUIT
PROVIDE LENGTH TO
SUIT
1"REDUCING COUPLING TO
SPRINKLER HEAD
CEILING
PROVIDE LENGTH TO
SUIT
SPRINKLER BRANCH
LINE OR MAIN
SPRINKLER HEAD ARM OVER DETAIL1 NTS
DESIGN AND GENERAL NOTES
1. OCCUPANCY: EXISTING VA MEDICAL BUILDING WITH HOSPITAL/MEDICAL ROOMS. LIGHT HAZARD OCCUPANCY PER
NFPA 13, 2013 EDITION. EXISTING BUILDING IS TYPE-II B UNPROTECTED CONSTRUCTION WITH CONCRETE DECK AND
CONCRETE BEAMS (PER SITE VISIT)
2. THIS IS AN EXISTING BUILDING WITH EXISTING SPRINKLERS, STANDPIPES AND FIRE PUMP. RED HAWK IS TO RELOCATE (162) PENDENT SPRINKLERS FROM EXISTING 1" OUTLETS AND ADD (1) CHECK VALVE TO THE EXISTING
ZONE CONTROL SERVING THE AREA OF WORK.
3. SYSTEM HAS BEEN HYDRAULICALLY CALCULATED TO .10 GPM PER SQ. FT. OVER THE MOST REMOTE 900 SQ. FT.
AREA HAS BEEN REDUCED BY 40% FOR CEILINGS UNDER 10'-0" PER NFPA 13 11.2.3.2.3.
4. ALL PIPING TO BE SCHEDULE 40 BLACK STEEL PIPE WITH THREADED ENDS AND CAST IRON FITTINGS.
5. ALL HANGERS TO BE SIZED AND LOCATED IN ACCORDANCE WITH NFPA 13, 2013 EDITION.
6. PENDENTS IN ACOUSTIC CEILING TILES TO BE LOCATED AT QUARTER POINTS OR CENTER OF THE TILE.
7. STRUCTURAL AND LOAD BEARING ANALYSIS OF THE FIRE SPRINKLER SYSTEM AND ITS RELATED COMPONENTS
HAS NOT BEEN INCLUDED AS ART OF THIS CONTRACT.
8. EARTHQUAKE BRACING IS NOT INCLUDED AS PART OF THIS CONTRACT. THIS BUILDING IS SEISMIC DESIGN
CATEGORY B AND SEISMIC BRACING IS NOT REQUIRED PER ASCE 7 13.1.4 (2).
9. ALL AREAS TO BE HEATED (ABOVE 40ºF) BY OWNER; PIPE IS FILLED WITH WATER AND MUST BE KEPT FROM
FREEZING.
NOTE: PER RFI RESPONSE, ALL CURTAINS TO HAVE 18" MESH FROM THE CEILING DOWN AS TO NOT OBSTRUCT SPRINKLER
SPRAY PATTERNS.
STYLE COLOR HEAD K = NPT ORIF. ESCUT. WRENCHCNTSYM
SPRINKLER SYMBOLS
MFG. TEMP
C-PLATE
TEMPMODEL# (SIN) #
163 RLEIABLE F1FR-56 PENDENT CHROME 155° 135° 5.6 1/2" 1/2" CONCEALED GFR2RA1414
CPIPE ABOVE FINISH FLOOR (AFF)
HYDRAULIC REFERENCE NODE
CEILING HEIGHT
L
SYMBOL LEGEND THIS DRAWING IS PREPARED BY RED HAWK FIRE &
SECURITY FOR USE IN CONJUNCTION WITH THIS
PROJECT AND IS FOR USE SOLELY WITH RESPECT TO
RED HAWK WORK ON SUCH PROJECT. RED HAWK
FIRE & SECURITY RETAINS ALL COMMON LAW,
STATUTORY AND OTHER RESERVED RIGHTS
INCLUDING COPYRIGHT. THIS DRAWING AND
ASSOCIATED CALCULATIONS SHALL NOT BE USED BY
OTHERS ON OTHER PROJECTS OR FOR PERFORMANCE,
COMPLETION, OR ADDITION TO THIS PROJECT BY
OTHERS EXCEPT BY AGREEMENT OF RED HAWK
IN WRITING AND WITH APPROPRIATE COMPENSATION
TO SUCH.
BRANCHLINE FABRICATION TAG
4-WAY SEISMIC BRACE (IF REQUIRED)
LATERAL SEISMIC BRACE (IF REQUIRED)
LONGITUDINAL SEISMIC BRACE (IF REQUIRED)
MAIN FABRICATION TAG
REV.# DATE REVISION DR. BY
DRAWN BY: CHECKED BY: UNDERWRITER: JOB #
SCALE: SHEET
NO.
DATE:
RED HAWK
FIRE & SECURITY
9 SULLIVAN ROAD
HOLYOKE, MA. 01040
TEL 413-568-4709 FAX 413-562-7298
www.RedHawkUS.com
MA SC#5864, EXPIRES 11/ 8/ 2018
RI FPM#374, MA FA#607C
RI FA#9065, CT ELC#105916-L5
163014
VAMC BLDG. 1 SPECIALITY CARE
421 NORTH MAIN STREET
LEEDS, MA. 01053
FIRE SPRINKLER PLAN
M.T. S.H.
AS NOTED 9/17/2018 FP 1 OF 3
CT FRP#0040818-F1
1/11/19 SUBMITTAL SET KFM
2/14/19 REVISED PER SUBMITTAL COMMENTS KFM
GENERAL NOTES:
2. DENOTES HYDRAULIC REFERENCE POINTS.
NOTE: ALL SPRINKLERS THAT ARE 2'-6" OR LESS WITHIN HEAT DIFUSSERS ARE
TO BE INTERMEDIATE TEMPERATURE PER NFPA 13, 2013 EDITION.
GENERAL NOTES:
1. SEE FP 1 OF 3 FOR DESIGN AND GENERAL INFORMATION.
2. DENOTES HYDRAULIC REFERENCE POINTS.
TO BE INTERMEDIATE TEMPERATURE PER NFPA 13, 2013 EDITION.
CPIPE ABOVE FINISH FLOOR (AFF)
HYDRAULIC REFERENCE NODE
CEILING HEIGHT
L
SYMBOL LEGEND THIS DRAWING IS PREPARED BY RED HAWK FIRE &
SECURITY FOR USE IN CONJUNCTION WITH THIS
PROJECT AND IS FOR USE SOLELY WITH RESPECT TO
RED HAWK WORK ON SUCH PROJECT. RED HAWK
FIRE & SECURITY RETAINS ALL COMMON LAW,
STATUTORY AND OTHER RESERVED RIGHTS
INCLUDING COPYRIGHT. THIS DRAWING AND
ASSOCIATED CALCULATIONS SHALL NOT BE USED BY
OTHERS ON OTHER PROJECTS OR FOR PERFORMANCE,
COMPLETION, OR ADDITION TO THIS PROJECT BY
OTHERS EXCEPT BY AGREEMENT OF RED HAWK
IN WRITING AND WITH APPROPRIATE COMPENSATION
TO SUCH.
BRANCHLINE FABRICATION TAG
4-WAY SEISMIC BRACE (IF REQUIRED)
LATERAL SEISMIC BRACE (IF REQUIRED)
LONGITUDINAL SEISMIC BRACE (IF REQUIRED)
MAIN FABRICATION TAG
REV.# DATE REVISION DR. BY
DRAWN BY: CHECKED BY: UNDERWRITER: JOB #
SCALE: SHEET
NO.
DATE:
RED HAWK
FIRE & SECURITY
9 SULLIVAN ROAD
HOLYOKE, MA. 01040
TEL 413-568-4709 FAX 413-562-7298
www.RedHawkUS.com
MA SC#5864, EXPIRES 11/8/2018
RI FPM#374, MA FA#607C
RI FA#9065, CT ELC#105916-L5
163014
VAMC BLDG. 1 SPECIALITY CARE
421 NORTH MAIN STREET
LEEDS, MA. 01053
FIRE SPRINKLER PLAN
M.T. S.H.
AS NOTED 9/17/2018 FP 2 OF 3
CT FRP#0040818-F1
EXAM
OPTOMETRY EXAM
CHIEF OFFICE
CLEAN INST.
EXAM
WAITING DILATION
OPTOMETRY EXAM
ELECTRICAL
PRE-TEST
OFFICE SUPPORT
OPTOMETRY EXAM
WASHROOM
LOW VISION EXAM
TRAINING: LOW VISION/
POLYTRAUMA
VIST
WASHROOM
BROS
2212A
BROS STOR.
MED./PREP.
OPTOMETRY EXAM
WASHROOM
OPTOMETRY EXAM
EYEGLASS FITTING
DIRTY INST.
PHOTOGRAPHY
ULTRASOUND/
TOMOGRAPHY
OPTOMETRY EXAM
OFFICE
OPTOMETRY EXAM
2234A
FAMILY/BARIATRIC
WASHROOM
WAITING
RECEPTION
WAITING
2233A
WASHROOM
MAS. OFFICE
H.K.
2236B
I.T.
OFFICE
CLEAN LINEN
OXYGEN STOR.
WASHROOM
EXAM
NURSE STATION:
INTAKE/EXIT
INTERVIEW
OFFICE
2264B
ANTEROOM
OFFICE
MED. PREP.
GENERAL
PROCEDURE
2264A
WASHROOM
CORR.
STAFF LOUNGE/ LOCKERS
DIRTY
LINEN
CONFERENCE
2242B
ELEC.
CONSULT/ EXAM
EKG/STRESS
TESTING
CORRIDOR
STOR.
2201A
WASHROOM
WASHROOM
CORR.
VISUAL FIELDS
KIOSK
CORR.
OFFICE
DIRTY INST.
OFFICE (FUTURE
EXAM/CONSULT)
SHOE STOR.
SHOE SHOP
EXAM
EXAM
EXAM
CHIEF OFFICE
CONSULT/ EXAM
EXAM
EXAM
EXAM
EXAM
EXAM
CLEAN SUPPLY
CARDIO EQUIP.
ADMIN. OFFICE
ADMIN. OFFICE
EXAM
WASHROOM
CORRIDOR
CORR.
POD. STERILE
INSTRUMENTS
2242A
ELEC.
EYVF1
SRCS1
EYOT2
WRC01
TLTU1
TLTU1
OFA09
XDUS1
USCL1
TLTU1
UCCL1
OFA09
MEDP1
SRE01
EYOT2
OFA09
OFA09
ITAC1
TLTU1
JANC1
EYOT2
EYOT2
EYVS1
TLTU1
TLTU1
TLTU1
TLTU1
EXRG3 EXRG3 EXRG3 EXRG3
EXRG3
EXRG3
EXRG3
OFA09
OFA09
UCCL1
OPEC1
OPTM1
SRE01
EYOT4
UCCL1
RECP1
WRC01
SRGC2
ITAC1CRA01
RECP4
TLTF3EXRG3 EXRG3 EXRG3
ITAC1
OFA09SL001USCL1
OFA09
WRC01UCCL1
PRTM1
EXRG3
EXRG3
EXRG3
EXRG3
OFA09
MEDP1
OFA09
EXRG4
EYOT2
EYOT2
EYOT2
EYOT2
OFA09
USCL1
TRGM1
TLTB1
OFA09
OFA09
EYVF1
SRCS1
EYFD1
ITAC1
2236A
ELEC.
ITAC1
PRTM1
2-PC-10
2-PC-8
2-PC-9
CORR.
UCCL1
STYLE COLOR HEAD K = NPT ORIF. ESCUT. WRENCHCNTSYM
SPRINKLER SYMBOLS
MFG. TEMP
C-PLATE
TEMPMODEL# (SIN) #
163 RLEIABLE F1FR-56 PENDENT CHROME 155° 135° 5.6 1/2" 1/2" CONCEALED GFR2RA1414
CPIPE ABOVE FINISH FLOOR (AFF)
HYDRAULIC REFERENCE NODE
CEILING HEIGHT
L
SYMBOL LEGEND THIS DRAWING IS PREPARED BY RED HAWK FIRE &
SECURITY FOR USE IN CONJUNCTION WITH THIS
PROJECT AND IS FOR USE SOLELY WITH RESPECT TO
RED HAWK WORK ON SUCH PROJECT. RED HAWK
FIRE & SECURITY RETAINS ALL COMMON LAW,
STATUTORY AND OTHER RESERVED RIGHTS
INCLUDING COPYRIGHT. THIS DRAWING AND
ASSOCIATED CALCULATIONS SHALL NOT BE USED BY
OTHERS ON OTHER PROJECTS OR FOR PERFORMANCE,
COMPLETION, OR ADDITION TO THIS PROJECT BY
OTHERS EXCEPT BY AGREEMENT OF RED HAWK
IN WRITING AND WITH APPROPRIATE COMPENSATION
TO SUCH.
BRANCHLINE FABRICATION TAG
4-WAY SEISMIC BRACE (IF REQUIRED)
LATERAL SEISMIC BRACE (IF REQUIRED)
LONGITUDINAL SEISMIC BRACE (IF REQUIRED)
MAIN FABRICATION TAG
REV.# DATE REVISION DR. BY
DRAWN BY: CHECKED BY: UNDERWRITER: JOB #
SCALE: SHEET
NO.
DATE:
RED HAWK
FIRE & SECURITY
9 SULLIVAN ROAD
HOLYOKE, MA. 01040
TEL 413-568-4709 FAX 413-562-7298
www.RedHawkUS.com
MA SC#5864, EXPIRES 11/8/2018
RI FPM#374, MA FA#607C
RI FA#9065, CT ELC#105916-L5
163014
VAMC BLDG. 1 SPECIALITY CARE
421 NORTH MAIN STREET
LEEDS, MA. 01053
FIRE SPRINKLER PLAN
M.T. S.H.
AS NOTED 11/17/2018 FP 3 OF 3
CT FRP#0040818-F1
2/14/19 REVISED PER SUBMITTAL COMMENTS KFM
MATERIAL APPROVAL SUBMITTAL
(See Instructions on Reverse)
TO: (Contracting Officer) FROM: (Contractor) DATE
CONTRACT NUMBER SUBMISSION NUMBER SUBMITTAL
NEW RESUBMITTAL
PREVIOUS SUBMISSION NUMBER PROJECT NUMBER
TO BE COMPLETED BY CONTRACTOR FOR GOVERNMENT USE ONLY
ITEM
NO.
SPECIFICATION SECTION/
PARA NO./DRAWING NO.
DESCRIPTION OF MATERIAL
(Include Type, Model Number, Mfg., etc. & file name of attachments)
AP-
PROVED
DISAP-
PROVED
SEE
REVERSE INITIAL
BY COMPLETING THIS FORM, THE UNDERSIGNED CONTRACTOR CERTIFIES THAT
THE MATERIAL COMPLIES WITH ALL SPECIFICATIONS OF SUBJECT CONTRACT.
DATE TYPE OR PRINT NAME AND TITLE SIGNATURE
FOR GOVERNMENT USE ONLY
TO: (A/E)
For Evaluation and Action
DATE TYPE OR PRINT NAME AND GRADE SIGNATURE
TO: (VA Engineer / COR)
RECOMMEND APPROVAL DISAPPROVAL AS INDICATED ABOVE AND SUBJECT TO ANY APPLICABLE COMMENTS ON THE REVERSE
DATE TYPE OR PRINT NAME AND GRADE SIGNATURE
TO: (Contracting)
APPROVED DISAPROVED AS INDICATED ABOVE AND SUBJECT TO ANY APPLICABLE COMMENTS ON THE REVERSE SIDE. REQUEST
RESUBMITTAL ON DISAPPROVED ITEMS WITHIN DAYS OF DATE SHOWN BELOW.
DATE TYPE OR PRINT NAME AND GRADE SIGNATURE
18-023
M. Chapman COR: J. Goldin IRONCLAD SERVICES, INC 01-31-19
VA241-13-D-0039 TO 36C24118N9726 211313-02
631-17-100 / 631-C87025
1 21 13 13 PARA 1.4 CALCULATIONS - WET-PIPE SPRINKLER SYSTEM
01-31-19 Paul Irizarry (PM) / Tammy Chaves (APM)
RENOVATE BLDG 1, SPECIALTY CARE CLINICS - NORTHAMPTON VAMC
Tammy Chaves Digitally signed by Tammy Chaves Date: 2019.01.31 15:38:13 -05'00'
X
DuBois & King, Inc. / Chase Engineering
Accepted
03-12-2019 Matthew Chase, P.E./Robert F. Kischko, P.E.
JG
3/12/2019 Josee Goldin
COMMENTS
(Number to correspond with applicable Item Number on reverse)
INSTRUCTIONS TO CONTRACTORS
1. The term "material" is defined as articles, supplies, raw materials, equipment, parts, components, and completed end items that are to be incorporated into the work required by the contract.
2. This form is to be used by Contractors for submitting Shop Drawings (*.DWG or *.PDF format), Manufacturer's Literature and Certificates (scanned as * .PDF) to the Government for approval in accordance with the provisions of this contract. Unless otherwise specified, it is to be prepared, signed, and E-mailed to the Contracting Officer with appropriate attachments. One paper format copy shall be submitted as well.
3. Item(s) to be approved will be clearly tabbed or identified. Data pertaining to item(s) to be approved will be clearly identified or tabbed, particularly where documents are voluminous, in order to properly evaluate the materials or articles to be incorporated in the work. Each attachment will be numbered to correspond with the item number shown on the face of this form.
4. Requests submitted shall be numbered consecutively, by contract, in the space entitled "Submission No.". This number, in addition to the Contract No., will be used to identify each Material Approval Submittal. Resubmissions will be indicated in the appropriate block and the insertion of previous submission number and data in addition to a new submission number. A single submission should be used for all work of a section of the specifications, but in NO instance should the submission include work for more than one (1) contract. Allow reasonable time in accordance with the project specifications for review of the submittal(s) by the A/E and Government. Submittals requiring priority handling will be submitted by separate submittal using the form and so marked across the face of the form.
5. This Material Approval Submittal is not valid unless it is signed by the Contracting Officer. This approval is required as called for by the Contracting Officer under the terms of this contract. One paper copy of the submittal is to be hand signed for Contracting Officers records.
6. The A/E and Government review is limited to checking for conformance with the information given and the design concept expressed in the contract documents. The Contractor and/or Construction Manager remains totally responsible for confirming all dimensions, quantities, fabrication, construction means and methods, techniques, sequences in the work, procedures, and coordination of the work for all trades.
7. This review does not relieve the Contractor of full responsibility for strict compliance with all requirements of contract plans and specifications. Provide and install all supplementary or miscellaneous items, appurtenances, devices and their available options incidental to or necessary for a functionally, sound, secure, complete, compatible and code compliant system.
Randolph, Vermont South Burlington, Vermont Brandon, Vermont Bedford, New Hampshire Laconia, New Hampshire
Keene, New Hampshire Buffalo, New York
SUBMITTAL REVIEW
Project Name: Renovate Building 1, Specialty Care Clinics Project Number: 524066 / VAMC Project 631-17-100 Project Location: VAMC Leeds, MA Submittal Items: CALCS - WET-PIPE SPRINKLER SYSTEM Submittal Number: 21 13 13-02.0 Submitted by: Ironclad Services, Inc.
ITEM
NO.
SPEC SECTION,
PARA NO.,
DRAWING NO.
DESCRIPTION
A C
C
EP
T E
D
A C
C
EP
T E
D A
S N
O T
ED
R E
V
IS
E
R E
SU
B
M
IT
R E
JE
C
T E
D
1 21 12 13 PARA 1.4 CALCS - WET-PIPE SPRINKLER
SYSTEM X
This review is only for general conformance with the design concept and the information given in the Construction Documents. Corrections or comments made on the shop drawings during this review do not relieve the Contractor from compliance with the requirements of the plans and specifications. Acceptance of a specific item shall not include acceptance of an assembly of which the item is a component. The Contractor is responsible for: dimensions to be confirmed and correlated at the jobsite; information that pertains solely to the fabrication processes or to the means, methods, techniques, sequences and procedures of construction; coordination of the Work with that of all other trades and performing all Work in a safe and satisfactory manner. The Engineer assumes no liability for errors or omissions that may be contained herein. The Contractor, by approving and submitting these documents, verifies their accuracy as stipulated on the Contractor’s Shop Drawing Stamp.
Date: March 12, 2019 Reviewed By: Matthew Chase, P.E. / Chase Engineering Robert F. Kischko, P.E.
Notes:
1. None.
2024 Firepump Replacement Details
6'-5"
2'- 0"
2'- 6"
LT
LT
LT
LT
EXISTING 4" TIE IN
EXISTING 4" TO TEST HEADER TIE IN
EXISTING 6" FEED
EXISTING FDC CHECK VALVE
36" PANEL CLEARANCE
36"PANEL CLEARANCE
36"PANEL CLEARANCE
5'- 1"
5'- 7"
6'- 3"
7'- 4"
9'- 8 1
/2"
4'-11 1/2"
EXISTING 4" TO TEST HEADER TIE IN
3'-4" 0'-6 1/2"
0'-10 1/2"
0'-11"4'-1"
0'-5 1/2"
1'-8"
0'-4"
0'-11 1/2"0'-11"
0'-6"
0'-7"
0'-6"0'-6"
0'-7"
0'-
0'- 6"
1'- 4"
2'- 1"
0'- 4 1
/2"
4'-0 1/2"
0'-5" 0'-9 1/2"0'-4 1/2"
5'-6"
2'- 2"
0'- 7 1
/2"
0'- 6"
1'- 8 1
/2"
1'-3 1/2" 0'-7" 3'-1"
0'- 4 1
/2" 0'-
9"
0'-4 1/2"
9'-4 1/2"
1'- 4 1
/2"
2'- 7"
2'-7"
JOCKEY SENSING LINE
1'- 3"
JOCKEY PUMP
PUMP SECTION VIEW
SCALE: 1/2" = 1'-0"
REVISIONS:DATE:#
KEY PLAN
4/28/23
M.THOMPSON
1052-0179778
XXXXXXXXXXXXX
FP- 01 OF 01
PUMP ROOM FLOOR PLAN
SCALE: 1/2" = 1'-0"
Report of Inspection, Testing, and Maintenance of Fire Pump
Pump ID: Building Fire Pump
Building Name: Leeds VMAC
Building Owner: Same
Job Site: 135 Goddard Memorial Highway
Norhampton, MA 01603
Date of Test: 2023-12-12
Type of Test: Start Up Test
Testing Firm: Fire System Services, LLC
450 Radmere Road
Cheshire, CT 06410
Testing Firm Contact:
Michael P Roke mike@firesystemsct.com
2034273910
Customer Information
Company Name: Ferguson Fire and Fabrication
Full Name: Craig Smith
Phone Number: 804-263-1889
Email: craig.smith@ferguson.com
Address: 11505 N. Lakeridge Parkway
Ashland, VA 23055
Fire Pump
Pump ID: Building Fire Pump
Pump Type (check one): Horizontal
Vertical In-Line
Vertical Turbine
End-Suction
Manufacturer: SPP
Model: TB08E
Serial Number: USA-01-23-E345
Listed (check all that apply): FM
UL
ULC
Rated Capacity (GPM): 500
Total Dynamic Head (ft):
Head at Churn 0% (PSI): 98
Head at Rated 100% (PSI): 75
Head at Overload 150% (PSI): 61
Rated Speed (RPM): 3550
Pump Rotation: Clockwise
Counterclockwise
Suction From: City Main
Tank Size: NA
Tank Height: NA
Impeller Diameter (In): 0
Fire Pump Driver
Type: Diesel Engine
Electric Motor
Other _________________________
Manufacturer: WEG
Model: 040360P3VFP286TS-W40
Serial Number: 1075679566
Listed (check all that apply): FM
UL
ULC
Rated HP: 40
Rated Speed (RPM): 3540
Frame Size: 284/6TS
Motor Enclosure Type: ODP
Electric Driver
Rated Voltage: 200
Rated Full Load Amps: 109
Phase: 3.0
Cycles (Hz): 60
Service Factor: 1.15
Fire Pump Controller
Type: Electric
Manufacturer: Tornatech
Model: GPS+GPU-208/40/3/60
Serial Number: WZ1310318
Report generated by Fire Pump Tester Software ™ by Hydro Flow Products, Inc.
Listed (check all that apply): FM
UL
ULC
Rated HP: 40
Phase: 3.0
Cycles (Hz): 60
Rated Voltage: 208
On PSI: 145
Off PSI: 155
Type of Start: on
Run Timer Setting (min): 0
Jockey Pump
Manufacturer: Webtrol
Model: NV6B8FE3T
Serial Number: 09232B028300
Rated HP: 1
Rated Speed (RPM): 3435
Rated Flow (GPM): 0
Rated Pressure (PSI): 0
Phase: 3
Cycles (Hz): 60
Rated Voltage: 208
Service Factor: 1.15
Rated Amps: 3.3
Frame Size: W56C
Jockey Pump Controller
Manufacturer: Tornatech
Model: JPLT-208/1/3/60
Serial Number: WZ1310319
Listed (check all that apply): FM
UL
ULC
Rated HP: 1
Phase: 3
Cycles (Hz): 60
Rated Voltage: 208
On PSI: 160
Off PSI: 170
Test Results
Date of Test:2023-12-12
Type:Start Up Test
Fire Department Attendee:NA
Building Representative Attendee:Lee Capistran
Testing Firm Attendee:Michael Roke
Pump Manufacturer Attendee:Same
Flow Device Used:1 3/4" Pitotless Nozzle + Little Hose Monster
Other Information:The pump was tested to capacity and at 150% of capacity. The generator transferred power on loss of normal power at the pump controller. The jockey pump can not reach 170 PSI and shut off because there is a potential leak in the jockey pump discharge line check valve. The system was not put online because of this. Cogswell Sprinkler is looking into this loss of pressure.
PressuresStreamsTotal FlowCorrected
RPMDisch.Suct.NetFlow1Flow GPM% Rated CapacityVoltsAmpsFlow %Press.
1358017070100
Flow Device -
PSI
GPM
098.3
235771657392
Flow DevicePN1.75-
HML
PSI6
GPM256.5
256.551.3
50.990.6
335701436479
Flow DevicePN1.75-
HML
PSI23
GPM502.1
502.1100.4
99.978.1
435611185563
Flow DevicePN1.75-
HML
PSI13
GPM377.5
377.575.5
75.362.6