PW#2025-045_Leschi_South_Moorage_Facility_Upland_Utility_Installation_Plan_Set_-_signed.pdf

PDF 19 MB Posted

Attached to
Leschi South Moorage Facility Upland Utility Installation
Solicitation number
PW#2025-045
Issued by
King County, Washington

About this file

This is a plan set for the Leschi South Moorage Facility Upland Utility Installation project in Seattle, Washington, prepared for the City of Seattle. The document contains detailed electrical, utility, and site infrastructure plans signed on December 3, 2025. The project involves installation of electrical, water, and sewer utility infrastructure at 100 Lakeside Ave S, Seattle, WA 98144 in preparation for marine construction. Work scope includes trenching, surfacing restoration, replacement or installation of curb ramps, shore power pedestals, lighting systems, wiring, and complete electrical systems for service areas, floating docks, and gangways. The plans include specifications for utility details, ADA-accessible ramp replacements, fire department connections, and reduced pressure backflow assemblies. Electrical work encompasses service entrance coordination with Seattle City Light (Service Request #2306154), temporary power provisions, and demolition of existing electrical systems on current docks and piers. The document emphasizes coordination with float manufacturers, utility locating services, and adherence to Seattle City codes and the National Electrical Code.

The Engineer's Estimate for the project is $500,000.00, with partial funding provided by the Washington State Parks Clean Vessel Act Program and the U.S. Fish and Wildlife Services Clean Vessel Act Grant Program. The plans specify that all work shall comply with codes adopted by the City of Seattle, King County, and the State of Washington. Stainless steel hardware (316 grade) is required for mounting and support of electrical equipment installed outside above grade or over water. Power outages are limited to one eight-hour period during normal business hours (8 AM–5 PM), and temporary power shall be provided by utility company sources rather than portable generators. All conductors must be labeled in junction boxes and at terminations, and the contractor is responsible for obtaining all necessary permits and certificates of inspection before final payment requests.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

12/03/2025 https://seattlegov.na1.adobesign.com/verifier?tx=CBJCHBCAABAADoDdpE1QMS-C7d6bgihmAvrDSg5aFqJE

PLAN

ELEVATION

FIRE DEPARTMENT CONNECTION (FDC)

SCALE: 1"=1'-0"

C3.3

SECTION

FRONT ELEVATION

TYPICAL SHEET PILE PENETRATIONS

SCALE: 1-1/2"=1'-0"

C3.3

REDUCED PRESSURE BACKFLOW ASSEMBLY (RPBA) - SCHEMATIC

SCALE: 1"=1'-0"

C3.1

ALSO, VERIFY ALL UNDERGROUND UTILITIES NOT

LOCATED BY THE 811 SERVICE BY USING A

COMMERCIAL LOCATION SERVICE AND CALL SPR

INSPECTION REQUEST LINE (206) 684-7034.

<<<CAUTION>>>

CALL 811 BEFORE YOU DIG!

WWW.CALL811.COM

42028

S

F

E T

T A

IN

O

GT

N

O

WASH

R

ETGIE

S

DE IG

E

E E

N

O

R

LNA

P

F O

R

SSE

I N

LESCHI SOUTH MOORAGE FACILITY

UTILITY UPLAND INSTALLATION

UTILITY DETAILS

C3.3

ALSO, VERIFY ALL UNDERGROUND UTILITIES NOT

LOCATED BY THE 811 SERVICE BY USING A

COMMERCIAL LOCATION SERVICE AND CALL SPR

INSPECTION REQUEST LINE (206) 684-7034.

<<<CAUTION>>>

CALL 811 BEFORE YOU DIG!

WWW.CALL811.COM

42028

S

F

E T

T A

IN

O

GT

N

O

WASH

ETGIE

S

DE IG

E

E E

N

O

R

LNA

P

F O

R

SSE

I N

LESCHI SOUTH MOORAGE FACILITY

UTILITY UPLAND INSTALLATION

ADA ACCESSIBLE RAMP, TYPE 422a

SCALE: 3/8"=1'-0"

C4.1

ADA ACCESSIBLE RAMP, TYPE 422a

SCALE: 3/8"=1'-0"

C4.1

ADA ACCESSIBLE RAMP, TYPE 422d

SCALE: 3/8"=1'-0"

C4.1

ADA ACCESSIBLE RAMP, TYPE 422a

SCALE: 3/8"=1'-0"

C4.1

ADA ACCESSIBLE RAMP, TYPE 422a

SCALE: 3/8"=1'-0"

C4.1

ADA ACCESSIBLE RAMP, TYPE 422a

SCALE: 3/8"=1'-0"

C4.1

ACCESSIBLE RAMP REPLACEMENT

PLAN AND DETAILS

C4.2

CONNECTOR, FEMALE AND MALE RESPECTIVELY

X SHEET NOTE REFERENCE (FLAG NOTES)

PHOTOCELL

XXX = AMPACITY Y = POLES

METER: KILOWATT HOUR

UTILITY CO. APPROVED SOCKET WITH METER INSTALLED

METER: COMBINATION KILOWATT HOUR/KVAR METER

TRANSIENT VOLTAGE SURGE SUPPRESSER

NORMALLY CLOSED PUSH BUTTON

NORMALLY OPEN PUSH BUTTON

POTENTIAL TRANSFORMER

METER: POWER FACTOR

GROUND WYE CONNECTOR

CONNECTION TO GROUND

FUSED SWITCH, WITH FUSE AND SWITCH AMPERE RATING

DRAWOUT CIRCUIT BREAKER

GROUND FAULT TRIP UNIT

CAPACITOR, POWER FACTOR CORRECTION, SIZE IN KVAR

CIRCUIT BREAKER, MEDIUM VOLTAGE, DRAWOUT

ABBREVIATIONS

CURRENT TRANSFORMER

SHUNT TRIP

MOTOR - GENERATOR

CIRCUIT BREAKER

DELTA CONNECTION

CONTACTOR COIL

DISTRIBUTION PANEL

EXISTING

DRAWING

CABINET

CEILING

CIRCUIT

DIVISION

DISCONNECT

DIAMETER

COPPER

DIRECT CURRENT

CONDUIT ONLY

CIRCUIT BREAKER

AMPERES

BATTERY

AUXILIARY

AUTOMATIC

ALUMINUM (ALLOY)

DOUBLE POLE SINGLE THROW

DOUBLE POLE DOUBLE THROW

AUTOMATED LIGHTING CONTROL

BELOW FINISHED GRADE

CONDUIT (CIRCULAR RACEWAY)

AMERICAN WIRE GAUGE

AUTOMATIC TRANSFER SWITCH

AMPERE (RATED) SWITCH

ABOVE FINISHED GRADE

ABOVE FINISHED FLOOR

AMPERE (RATED) FUSES

CUBIC FEET PER MINUTE

CURRENT TRANSFORMER

DPDT

DWG

E (E)

DP

DPST

BFG

CO

DC

DISC

DIV

DIA

CT

CU

CLG

CKT

CFM

CAB

CB

C

AS

AUX

BAT

AWG

AUTO

ATS

A, AMP

ALC

AFG

AL

AFF

AF

K KEY OPERATED

KW

KVA

KCM

KO

THOUSAND CIRCULAR MILS

KILO VOLT-AMPERES

KILOWATTS

KNOCK OUT

IMC

IES

GRD

GRC

GND

GEN

GFI

FLA

FLEX

FAA

EWH

ENCL

EOL

EWC

EPA

EMT

FU

HP

ID

IN

IG

HZ

FC

FA

EF

FUSE

INTERMEDIATE METAL CONDUIT

HERTZ (CYCLES PER SECOND)

GROUND FAULT CIRCUIT

GALVANIZED RIGID STEEL CONDUIT

ILLUMINATING ENGINEERING SOCIETY

ISOLATED GROUND

INSIDE DIAMETER

HORSEPOWER

INCANDESCENT

IN-GROUND

INTERRUPTER

GENERATOR

GROUND

FIRE ALARM ANNUNIATOR

ELECTRIC WATER HEATER

ELECTRIC WATER COOLER

EFFECTIVE PROJECTED AREA

ELECTRICAL METALLIC TUBING

FULL LOAD AMPERES

FLEXIBLE

FOOT CANDLES

FIRE ALARM

ENCLOSURE

END OF LINE

EXHAUST FAN

TRANSFORMER

VFD EQUIPMENT

MOUNTED

TIME CLOCK

SENSOR

BRANCH CIRCUIT PANELBOARDS, SURFACE AND RECESS

FUSED DISCONNECT SWITCH, SIZE AS NOTED OR IF NOT SHOWN

DRIVE WITH INTEGRAL DISCONNECT DIV. 16 TO INSTALL

CONNECTION TO DIV. 15 FURNISHED VARIABLE FREQUENCY

MOTOR CONNECTION. X = HORSEPOWER (WHERE SHOWN)

MAGNETIC MOTOR STARTER (CONTROLLER) OR CONTACTOR

DISTRIBUTION & EQUIPMENT

WALL MOUNTED DUAL LEVEL SWITCHING OCCUPANCY

EMERGENCY POWER OFF, HEAVY-DUTY OIL TIGHT RED

SERVICE AND/OR DISTRIBUTION EQUIPMENT

CONTACTOR. SIZE AS NOTED OR IF NOT SHOWN SIZE PER

DISCONNECT W/ MAGNETIC MOTOR STARTER (CONTROLLER) OR

MUSHROOM HEAD PUSH-BUTTON - BREAK GLASS TYPE

LIGHTING CONTROL PANEL

LIGHTING CONTROL STATION

SIZE PER CONNECTED MOTOR SIZE ('MECH'=BY DIVISION 15, TYP).

CONNECTED MOTOR SIZE. ('MECH'=BY DIVISION 15, TYP).

SIZE AS NOTED OR IF NOT SHOWN SIZE PER CONNECTED

MOTOR SIZE. ('MECH'=BY DIVISION 15, TYP).

SIZE PER CONNECTED MOTOR SIZE ('MECH'=BY DIVISION 15, TYP).

DISCONNECT SWITCH, SIZE AS NOTED OR IF NOT SHOWN

SYMBOL

SOLENOID

HATCHED= 277/480V

SOLID= 120/208V

DESCRIPTION

RELAY COIL

RIGID NONMETALLIC CONDUIT (PVC)

PHASE

FEET

INCHES

REQUIRED

UNDERWRITERS LAB

TELEPHONE

SECONDARY

TIMECLOCK

TERMINAL BOARD

SWITCHGEAR

SWITCHBOARD

WEATHERPROOF

VOLT-AMPERES

TRANSFORMER

UNLESS OTHERWISE NOTED

VARIABLE FREQUENCY DRIVE

SINGLE POLE SINGLE THROW

SINGLE POLE DOUBLE THROW

WATT

WITH

WITHOUT

TYPICAL

VOLTS

SURFACE

PRIMARY

PB PUSH-BUTTON

XFMR

PNL

+,POS

PEND

PH

PANEL

POSITIVE

PENDANT

PHASE

', FT

", IN

LIGHT CONTROL PANEL

MINIMUM CIRCUIT AMPERES

NATIONAL ELECTRICAL

NATIONAL ELECTRICAL CODE

OWNER FURNISHED, OWNER

NIGHT LIGHT (UNSWITCHED)

MANUFACTURE'S ASSOC.

OWNER FURNISHED CONTRACTOR

NEUTRAL (GROUNDED CONDUCTOR)

-,NEG NEGATIVE

OD

OFOI

P

OS

OFCI

NO

NTS

OC

NEMA

NL

OUTSIDE DIAMETER

OCCUPANCY SENSOR

INSTALLED

INSTALLED

POLE

NORMALLY OPEN

NOT TO SCALE

ON CENTER

MLO

-N-

NEC

NC

MTR

MTD

MCA

MFR

MISC

MIN

MAX

LCP

MAIN LUGS ONLY

NORMALLY CLOSED

MOTOR

MOUNTED

MANUFACTURER

MISCELLANEOUS

MINIMUM

MAXIMUM

VA

W/

WP

W/O

VFD

W

UL

UON

V

TYP

TEL

SPDT

SURF

SWGR

SWBD

SPST

TC

TB

REQD

SEC

RNC

PRI

KITCHEN EQUIPMENT REFERENCE

FEEDER NOMINAL AMPACITY & TYPE: SEE FEEDER

DETAIL REFERENCES ARE SHOWN. ALL DETAILS APPLY

TO ALL APPLICABLE SITUATIONS, UON.

ELEVATION/PHOTO TAG: REFER TO NUMBER

SECTION TAG: REFER TO DETAIL NO. ON DRAWING.

NOT ALL DETAIL REFERENCES ARE SHOWN. ALL

REFER TO DETAIL NO. ON DRAWING INDICATED NOT ALL

AND SHEET INDICATED

Y-Y DETAILS APPLY.

Y-Y

X

X

Y-Y X

X

XXX.X SCHEDULE.

SPECIAL PURPOSE RECEPTACLE- WALL , CEILING

AT 6" O.C. (LENGTH AS INDICATED).

TWO-PIECE SURFACE METAL RACEWAY WITH RECEPTACLE

NEMA CONFIGURATION AS NOTED

ELECTRICAL EQUIPMENT CONNECTION.

TELE/POWER POLE, POWER POLE

TWO-PIECE SURFACE METAL RACEWAY WITH RECEPTACLE

FLUSH FLOOR BOX DEVICE - DEVICE TYPES PER

PEDESTAL FLOOR DEVICE - DEVICE TYPES PER

AS NOTED, LENGTH AS INDICATED ON THE DRAWINGS

AND WITH ALL FITTINGS AS REQUIRED

NORMALLY CLOSED CONTACTOR OR RELAY CONTACTS

NORMALLY OPEN CONTACTOR OR RELAY CONTACTS

PROVIDE #10 AWG NEUTRALS. USE LIQUID-TIGHT FLEX.

BATTERY (GENERAL)

HAND/OFF/AUTO SWITCH

DESCRIPTION

SYMBOLS SHOWN.

SYMBOLS SHOWN.

DUPLEX RECEPTACLE - WALL - DEDICATED

FAULT CIRCUIT INTERRUPTER

POWER DEVICES

SIMPLEX RECEPTACLE - WALL, CEILING, FLOOR

DUPLEX RECEPTACLE - WALL, CEILING, FLOOR

DOUBLE DUPLEX RECEPTACLE - WALL, CLG, FLOOR

DUPLEX RECEPTACLE - WALL - HALF SWITCHED

DUPLEX RECEPTACLE AT SPECIAL HEIGHT

DUPLEX RECEPTACLE - WALL - WITH INTEGRAL GROUND

DUPLEX RECEPTACLE W/ WEATHERPROOF COVER

DOUBLE DUPLEX RECEPTACLE AT SPECIAL HEIGHT

DUPLEX RECEPTACLE - WALL - ABOVE COUNTER/

BACKSPLASH. SEE ARCHITECTURAL DRAWINGS.

DESCRIPTION

OVERLOAD PROTECTION

KEY OPERATED SWITCH

WEATHERPROOF SWITCH

TIMER SWITCH

TWO POLE SWITCH

THREE WAY SWITCH

FOUR WAY SWITCH

SINGLE POLE SWITCH (SUPERSCRIPT DENOTES SIMILARLY

MARKED LUMINARIES CONTROLLED TOGETHER)

DIMMER SWITCH. NUMBER INDICATES WATTAGE RATING. IF

SWITCH WITH PILOT (PILOT IS "ON" WHEN SWITCH IS "ON")

SWITCH WITH PILOT (PILOT IS "ON" WHEN SWITCH IS "OFF")

SWITCHING CONTROLS

NOT SHOWN 800W MINIMUM.

MOTOR RATED TOGGLE W/THERMAL

FLUORESCENT WALL BRACKET - RESTROOM

ADA APPROVED WALL SCONCE

DIRECTIONAL HID FIXTURE

POLE MOUNTED LUMINAIRE

INDICATES FACES, ARROW AS SHOWN

FIXTURE TYPE IDENTIFICATION DESIGNATION

ILLUMINATED EXIT SIGN, SHADED QUADRANT

"FOOT" INDICATES WALL MOUNTED LUMINAIRE

SYMBOL

XXX

DESCRIPTION

SWITCH

BUS BAR

BUS DUCT

OVERLOADS

SYMBOL

BATTERY POWER EMERGENCY UNIT EQUIPMENT (SEE

SCHEDULE FOR QUANTITY OF HEADS) - WALL,

OPTICAL SENSOR AND REFLECTOR

REMOTE HEAD

CEILING MOUNTED.

HID FIXTURE

SHADING OF ANY LUMINAIRE INDICATES CONNECTION

DOWNLIGHT - SURFACE, RECESSED CEILING MOUNT

WALL WASH - SURFACE, RECESSED CEILING MOUNT

FLUORESCENT STRIPLIGHT - POWER FEED SECTION,

FLUORESCENT RECESSED LUMINAIRE

(REFER TO LUMINAIRE SCHEDULE FOR TYPE)

FLUORESCENT SURFACE-MOUNTED LUMINAIRE

TO EMERGENCY CIRCUIT.

(REFER TO LUMINAIRE SCHEDULE)

FLOOR OR GRADE MOUNTED FIXTURE

FEED THOUGH SECTION, LENGTH AS SHOWN.

SYMBOL

TRACK LIGHTING WITH HEADS AS INDICATED.

LIGHTING

DESCRIPTION SYMBOL

REFERENCE SYMBOLS

STROKES INDICATE QUANTITY OF #12 AWG. CONDUCTORS,

INSULATED BUSHING & PULLROPE.

CONTRACTOR SHALL SCHEDULE OR STANDARD WIRING

CONDUIT RUN TURNED UP THROUGH FLOOR OR CEILING.

CONDUIT STUBBED OUT AT LOCATION SHOWN. PROVIDED

CEILING, EXTEND TO ACCESSIBLE LOCATION BOTH SIDES.

TERMINATE WITH BUSHINGS. (1) 1 1/4" CO UON. COORDINATE

LOCATIONS WITH CABLE INSTALLER(S) PRIOR TO

HOME RUN TO INDICATED DESTINATION, 3/4"C. MIN. UON

PRACTICES FOR BRANCH CIRCUITS.

TELEPHONE/DATA SLEEVE THROUGH WALL, ABOVE

LIGHTNING SYSTEM AIR TERMINAL

MOUNTED. 4" SQ. BOX, UON.

FLEXIBLE CONDUIT CONNECTION

GROUND ROD CONNECTION

JUNCTION BOXES WALL, CEILING AND FLUSH FLOOR

GROUND ROD CONNECTION WITH TEST WELL BOX

PULL BOX, MIN. SIZE PER NEC., UON.

UNDERGROUND PULLBOX/VAULT (P=POWER T=TEL/COM U=UTILITY)

UON. NOTE: NOT ALL WIRING IS SHOWN ON DRAWING.

DESCRIPTION

DIAGRAMS

SYMBOL

HANDHOLE OR JUNCTION BOX

CABLE TRAY

ROUGH-IN.

NEUTRAL

CORE AS REQUIRED.

GROUND, ISOLATED

HOT

GROUND

WIRING

LOW VOLTAGE CONDUCTORS

COMMUNICATION CONDUIT / CABLE

MEDIUM VOLTAGE CONDUIT

GROUNDING GRID OR CONDUCTORS

CONDUIT CONCEALED IN CEILING OR WALL. LINE WEIGHT

CONDUIT EXPOSED. LINE WEIGHT TOP TO BOTTOM= NEW,

CONDUIT CONCEALED IN OR BELOW CONCRETE BELOW GRADE.

UNDER PIER. LINE WEIGHT TOP TO BOTTOM= NEW,

EXISTING TO REMAIN.

TOP TO BOTTOM = NEW, EXISTING TO REMAIN.

EXISTING CONDUIT & WIRING TO BE REMOVED

EXISTING TO REMAIN.

DESCRIPTIONSYMBOL

DEPTH

RECESS

REMARKSVOLTS CATALOG NUMBERWATTSLAMP TYPE

TOTAL

TYPE QTY.

LAMP IMFORMATION

LUMINAIRE SCHEDULE

MANUFACTURERSIZE / DESCRIPTIONTYPE MOUNTING

P

ELECTRICAL LEGEND*

COURTEST PHONE WITH ENCLOSURE

POWER PEDESTAL

W = SLIP NUMBER(S) SERVED

X = 30 = 30A,120V OUTLET

X = 50 = 50A,120/240V OUTLET

X = 100 = 100A,120/240V OUTLET

Y = UNIT SUBSTATION

Z = CIRCUIT NUMBER

NOTE: 'X' DESIGNATES OUTLET PER SLIP. MULTIPLE REFERENCES

UNDERGROUND PULLBOX/VAULT

NOTE: ALL FIXTURES TO BE SUPPLIED WITH LOW TEMPERATURE BALLASTS.

CABLE TV WIRE / CONDUIT

PROJECT NOTES

FROM THE FINISHED FLOOR TO THE CENTERLINE OF THE OUTLETS (U.O.N.).

THEN LOCATE OUTLETS AS NOTED BELOW. OUTLET HEIGHTS ARE MEASURED

DRAWINGS. IF SPECIAL OUTLET HEIGHTS ARE NOT SHOWN OR REQUIRED,

SPECIAL OUTLET HEIGHTS ARE SHOWN ON THE ELECTRICAL OR ARCHITECTURAL

DEVICE MOUNTING HEIGHTS

RECEPTACLE

LIGHT SWITCHES

PANEL BOARD

TELEPHONE/OUTLET-WALL

TELEPHONE/DATA OUTLET-DESK

MANUAL PULL STATION

AUDIBLE/VISUAL ANNUNCIATOR

KEYPAD/CARD READER

NO MORE THAN +96" OR LESS THAN +80"

+72 INCHES TO TOP OF PANELBOARD

+54 INCHES VERTICAL

+18 INCHES VERTICAL

+60 INCHES VERTICAL

+48 INCHES TO LEVER/OPERATING DEVICE

+48 INCHES VERTICAL

+18 INCHES VERTICAL

AERIAL CONDUCTOR(S)/OVERHEAD LINE

(i.e. 30/50) INDICATES MULTIPLE OUTLETS PER SLIP.

1. GENERAL: WORK SHALL BE DONE IN ACCORDANCE WITH CODES AS

ADOPTED BY THE CITY OF SEATTLE, KING COUNTY, AND THE STATE OF

WASHINGTON.

2. LOCATIONS OF ELECTRICAL DEVICES, LIGHTING FIXTURES, ETC.,

INDICATED ON CIVIL PLANS - INCLUDING SECTIONS, ELEVATIONS,

NOTES, OR OTHER INDICATORS - TAKE PRECEDENCE OVER

LOCATIONS SHOWN ON ELECTRICAL DRAWINGS.

3. REFER TO CIVIL, ETC., DRAWINGS FOR WORK IN OTHER DIVISIONS.

INFORMATION CONVEYED WITHIN THE ELECTRICAL DRAWINGS

ILLUSTRATING OR REFERENCING WORK OF OTHER DIVISIONS IS

FOR REFERENCE ONLY. SPECIFICATION BY THE APPROPRIATE

DIVISIONS SHALL APPLY.

4. GENERAL NOTES ARE SHOWN ON SHEETS MOST RELEVANT TO SPECIFIC

NOTE; HOWEVER, GENERAL NOTES ON EACH SHEET SHALL APPLY IN

PRACTICE TO ALL ELECTRICAL DRAWINGS.

5. NOT ALL COMPONENTS OF THE ELECTRICAL SYSTEMS ARE SHOWN (FOR

SIMPLICITY). PROVIDE MATERIALS AND LABOR NECESSARY FOR A

COMPLETE AND OPERATIONAL SYSTEM.

6. STAINLESS STEEL HARDWARE: MATERIALS USED FOR THE MOUNTING

AND SUPPORT OF BOXES CABLES, RACEWAYS, LIGHT FIXTURES,

OUTLETS, AND OTHER ELECTRICAL EQUIPMENT, SHALL BE 316

STAINLESS STEEL. THIS REQUIREMENT APPLIES TO THE

AFOREMENTIONED COMPONENTS WHEN INSTALLED OUTSIDE ABOVE

GRADE OR WHEN INSTALLED OVER WATER (APPROACH PIER, PIER, &

FLOATING DOCKS).

7. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. EXACT LOCATIONS OF

ELECTRICAL EQUIPMENT ARE APPROXIMATE. CHANGES MADE BY THE

OWNER IN LOCATING ELECTRCAL COMPONENTS OF UP TO TEN FEET

HORIZONTALLY IS A PART OF THIS CONTRACT FOR FLOATS. THESE

CHANGES MAY BE IMPLEMENTED, AT NO CHARGE TO THE OWNER, UNTIL

FINAL APPROVAL OF SHOP DRAWINGS.

8. COORDINATE LOCATIONS OF ELECTRICAL AND COMMUNICATION

CHASES AND CONDUITS WITH OTHER TRADES. ADJUST LOCATIONS AS

NECESSARY TO AVOID CONFLICTS.

9. CONDUCTORS SHALL BE LABELED IN ALL JUNCTION BOXES AND AT

TERMINATIONS.

10. SCOPE OF WORK: THE SCOPE OF ELECTRICAL WORK FOR THIS PROJECT

INCLUDES BUT IS NOT LIMITED TO THE FOLLOWING:

A. PROVIDE COMPLETE ELECTRICAL SYSTEM FOR SERVICE/UPLAND,

FLOATING DOCKS AND GANGWAYS INCLUDING SHORE POWER

PEDESTALS, LIGHTING, WIRING, ETC.

B. DEMOLITION: REMOVAL OF ELECTRICAL SYSTEMS ON EXISTING

DOCKS AND PIERS. REFER TO OTHER DIVISIONS FOR SPECIFIC

DEMOLITION REQUIREMENTS AND INFORMATION.

C. PERMITS: GIVE ALL NECESSARY NOTICES, OBTAIN ALL PERMITS

AND PAY ALL GOVERNMENT TAXES, FEES AND OTHER COSTS IN

CONNECTION WITH THIS WORK. OBTAIN ALL REQUIRED

CERTIFICATES OF INSPECTION OF THE WORK AND DELIVER SAME

TO THE ENGINEER AT THE TIME OF SUBSTANTIAL COMPLETION

AND BEFORE REQUEST FOR FINAL PAYMENT.

D. SERVICE ENTRANCE WORK: THIS PROJECT INCLUDES THE SCOPE

OF WORK AS DEFINED IN SEATTLE CITY LIGHT (SCL) SERVICE

REQUEST #2306154/ SERVICE CONSTRUCTION LETTER. PROVIDE

SERVICES, SYSTEMS, AND COMPONENTS, AS REQUIRED BY SCL

FOR CUSTOMER. PLAN FOR AND ACCOMMODATE SCL SCHEDULING

AND CONSTRUCTION REQUIREMENTS.

E. COORDINATION WITH FLOAT MANUFACTURER: THE CONTRACTOR

SHALL COORDINATE ELECTRICAL, EQUIPMENT, CHASE, AND

JUNCTION BOX LOCATIONS WITH THE FLOAT MANUFACTURER.

VERIFY PROVISIONS FOR EQUIPMENT ANCHORING, AND THAT

CHASES AND JUNCTION BOX SIZES/LOCATIONS ARE SUITABLE FOR

THE INSTALLATION OF SPECIFIED ELECTRICAL SYSTEM

COMPONENTS USING THE MEANS AND METHODS PLANNED FOR

INSTALLATION. FLOAT SHOP DRAWINGS WILL NOT BE APPROVED

WITHOUT WRITTEN VERIFICATION THAT THE AFOREMENTIONED

COORDINATION HAS TAKEN PLACE AND THAT THE FLOAT SHOP

DRAWINGS HAVE BEEN APPROVED BY THE ELECTRICAL SYSTEM

INSTALLER.

F. POWER OUTAGES: POWER OUTAGES SHALL BE LIMITED TO ONE

8-HOUR PERIOD DURING NORMAL BUSINESS HOURS (8AM-5PM).

G. TEMPORARY POWER: PROVIDE TEMPORARY POWER AS NEEDED

BY ALL TRADES FOR THE EXECUTION OF THIS CONTRACT. INCLUDE

INTERIM POWER REQUIREMENTS MADE NECESSARY DUE TO

PHASED CONSTRUCTION. PROVIDE TEMPORARY POWER

CONNECTIONS TO PERMANENT SERVICES IF OUTAGES ARE

LONGER IN DURATION THAN SPECIFIED IN THE PARAGRAPH ABOVE

OR IF OUTSIDE THE SPECIFIED TIME OF DAY. TEMPORARY POWER

SHALL BE CONNECTED BY UTILITY COMPANY SOURCES. PORTABLE

GENERATORS SHALL NOT BE UTILIZED.

* LEGENDS SHOWN ON INDIVIDUAL SHEETS TAKE

PRECEDENCE OVER THIS LEGEND. NOT ALL SYMBOLS

LISTED ARE USED.

-120LEDLED - KIM LIGHTINGS15 58.3 Light: SOLITAIRE LED

SRSP2/FM/72L-260/4K7/1/

WA/UNV/CC

Pole: AAL PR5-15 WH & BC5

DECORATIVE BASECOVER

SEE CUT SHEET E4.0; PROVIDE

SINGLE GANG FESTOON BOX IN

POLE FOR EPO SWITCH. MOUNT @

+44" ABOVE BASE FLANGE AT

0-DEGREES.

-120LEDLED PACES1 LED STEPLIGHT GANGWAY6 TJSL-5000-6WLED-120-STD

-PNT- SURFACE-NLU

FORMED ALUMINUM SURFACE BOX;

DIE CAST AL FACEPLATE; 4K LED'S

FLOATING

DOCKS

-120LEDLED - KIM LIGHTINGS15V POLE MTD LED LUMINAIRE 135 Light: SOLITAIRE LED

SRSP2/FM/72L-600/4K7/

5W/CP/UNV/CC

Pole: AAL PR5-15 WH & BC5

DECORATIVE BASECOVER

SEE CUT SHEET E4.0;SITE

POLE MTD LED LUMINAIRE;

INCLUDE WEATHERPROOF

BREAK GLASS TYPE EPO

SWITCH IN POLE.

SOUTH LESCHI MARINA

WAVE ATTENUATOR AND

PUBLIC ACCESS FACILITY

Also, verify all underground utilities not located by the 811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.

>>>>CAUTION - CALL 811<<<<

UTILITY NOTIFICATION CENTER

BEFORE YOU DIG!

WWW.CALL811.COM

ELECTRICAL LEGEND & SCHEDULES

E0.0

/1 5/2

342719 26

LESCHI SOUTH MOORAGE FACILITY

UPLAND UTILITY INSTALLATION12/03/2025

UPLANDS

PARKING AREA

3 #1/0

3 #4/0

3.00"

4.00"

4.00"

3.00"

3.00"1

275.3

275.4

250.4

250.4K

250.3

3.00"

2.50"

2.50"

3.00"

2.50"

200.3

200.4

180.3

175.3

225.3G 1

#6

#6

#8

#6

#6

4 #1

3 #1

3 #2

4 #2

4 #2

3 #2

3 #2, 1#2/0 -N-

#8

#8

#8

#8

#8

#8

4 #4

4 #4

3 #4

3 #4

4 #4

3 #4

3 #2 #8

2.00"

2.00"

2.00"

2.00"

2.00"1

150.3

125.4

125.3

110.4

100.4

110.3

110.4K

1.25"

1.25"

1.25"

1.50"

1.50"

2.00"

1.50"

1.50"

2.00"

1.50"

1.50"

90.4

80.4

90.3

70.4

80.3

70.3

1.25"

1.00"

1.25"

1.25"

1.00"

1.00"

100.3 1.25" 2.00"1

#10

#10

#10

#10

#10

#10

#10

3 #6, 4 #8

3 #8, 1#4 -N-

4 #8

3 #8

3 #10

3 #8

#10

#12

#12

3 #10

3 #10

2 #10

3 #12

4 #12

1.50"

1.50"

1.50"

1.00"

1.00"

1.50"1

60.3

50.4

50.4K

40.3

35.2

40.4

50.3

0.75"

1.00"

1.00"

0.75"

0.75"

0.75"

1.00"

0.75"1

0.75"1

20.3

30.3

20.2

15.3

15.4

0.75"

0.75"

0.75"

GENERAL NOTES (SCHEDULE):

SCHEDULE REMARKS:

60.4 4 #61.00" 1.50"1 #10

3GROUND

3 #

CONDUCTORS PER SET

PHASE/NEUTRAL

#3/0

#2

#3/0

2 #1/0

#4

#4

5 #3/0

4 #500 KCMIL

3 #500 KCMIL

3 #350 KCMIL

2 #350 KCMIL

4 #350 KCMIL

RNC

SETSTAG

FEEDER

500.3

CONDUITS

MET

4.00"

3.00"

4.00"

3.00"

4.00"

400.4

400.3

400.4K

350.2

300.3

300.4

350.3

3.00"

2.50"

2.50"

COPPER FEEDER SCHEDULE

REMARKS

#4

#4

#4

#4

#4

5 #250 KCMIL

4 #250 KCMIL

4 #300 KCMIL

3 #300 KCMIL

3 #250 KCMIL

4#5

3 #2/0

4 #3/0

3 #1/0

#13 #350 KCM2600.3 -4.00"

1180.2 2 #1/0

1180.1 1 #1/0

TYPE G or W

3 #350 KCMIL 2 #1/0

1200.2 3 #2/0

TYPE SOW

2 #2/0

2 #2

2 #4

2 #4

2 #4

2 #6

2 #6

1225.1 1 #3/0

#12

#12

3.00"

G

DISTRIBUTION PANEL 'BW' 400A - 240/120V, 1P, 3W, 14kAIC, NEMA 4X SS

G G

#2/04 #400 KCMIL31000.4 -4.00"3.00"

SCL XFMR

IN VAULT

BREAKWATER

FLOAT

A. CONDUCTORS AND CONDUITS SHOWN IN THIS SCHEDULE ARE BASED ON

COPPER CONDUCTORS WITH THHN/THWN INSULATION. THIS NOTE INDICATES

THAT CONDUIT (LISTED IN SCHEDULE) IS SIZED BASED ONT TYPE THHN/THWN

WIRE. USE WIRE TYPES AS SPECIFIED IN SECTION 16120 OR AS NOTED

ELSEWHERE IN THE CONTRACT DOCUMENTS.

B. PROVIDE NOTED SIZE GROUND CONDUCTOR IN EACH CONDUIT OF FEEDERS

CONSISTING OF MULTIPLE SETS OF CONDUCTORS.

C. NOT ALL FEEDERS ARE NECESSARILY USED ON THIS PROJECT.

D. NOMINAL AMPACITIES GREATER THAN 100 AMPS ARE FOR 75^C TERMINATIONS.

E. CONDUIT SIZES AND QUANTITIES ON PLANS TAKE PRECEDENCE OVER THOSE

SHOWN IN SCHEDULE. PROVIDE CONDUITS INDICATED IN SCHEDULE FOR

FEEDERS NOT SHOWN ON PLANS.

CABLES NOTED MAY BE USED ONLY WHEN ALLOWED BY CODE AND

PROJECT SPECIFICATIONS.

"MET"=EMT, GRC (RIGID), RAC, OR PVC COATED GRC TYPE CONDUITS.

"RNC"=PVC 40, PVC 80 OR FIBGERGLASS TYPE CONDUITS ROUTED

UNDERGROUND. REFER TO SIZING ON DRAWINGS IF "RNC" CONDUITS

ARE ROUTED ABOVEGROUND. CONDUIT SIZES NOTED ON SINGLE-LINE

DIAGRAM OR ON PLANS SUPERSEDE SIZES NOTED ABOVE IF LARGER.

PROVIDE GROUND WIRE NOTED ABOVE IN ALL FEEDERS AND BRANCH

CIRCUITS.

TYPE G or W

TYPE G or W

TYPE G or W

TYPE G or W

TYPE G or W

TYPE G or W

TYPE G or W

TYPE G or W

TYPE G or W

TYPE G or W

TYPE G or W

TYPE G or W

TYPE G or W

225.3G

20/120/1175/2175/2

400/2

175/2

225.3G

LIGHT CIRCUIT

35.2

20/1 35/2

TO PUMP-OUT

(SEE SHEET E3.1)

35.2

1. NUMBER NOTED INSIDE BOX CORRESPONDS WITH PEDESTAL

NUMBER AT SLIPS - SEE FLOAT PLANS.

2. EXTEND CIRCUIT TO TYPE S1 AND S15 FIXTURES ON GANGWAYS AND

DOCKS WHERE SHOWN ON PLANS. NOTE : CONNECTIONS TO LIGHT

FIXTURE MUST BE MADE 12" ABOVE SURFACE OF FLOAT - SPLICING

OF CONDUCTORS BELOW ELECTRICAL DATUM PLANE MUST BE MADE

WITH U.L. LISTED EPOXY RESIN SPLICE KIT SUITABLE FOR WET

LOCATIONS.

3. FEEDER TYPE/SIZE APPLIES TO ENTIRE LENGTH OF CIRCUIT FROM

UNIT SUBSTATION TO THE MOST DISTANT PEDESTAL.

4. PROVIDE GROUND FAULT PROTECTED OVER-CURRENT DEVICES AS

REQUIRED TO COMPLY WITH NEC ARTICLE 555. BENDER MODEL

RCMS460 OR APPROVED EQUAL WITH SHUNT TRIP CIRCUIT

BREAKERS.

5. CONNECT EMERGENCY POWER OFF ('EPO') PUSHBUTTONS,

MOUNTED ON TYPE 'S15' LIGHT POLES, TO SHUNT TRIP CIRCUIT

BREAKER USING 3C/#12 SOOW. CONNECT EPO CIRCUIT IN PARALLEL

TO GFCI MONITOR SHUNT TRIP CONTROL OUTPUT.

FLAG NOTES

GENERAL NOTES

1. PROVIDE POWER PEDESTALS DOUBLE LUGGED. LOOP FEED

PEDESTALS USING FEEDERS SHOWN.

225.3G

400.3

TYPE SOW

SCL HANDHOLE

400.3 kW kW

(E) TO MARINA

CT & METER/METER BASE

PER SCL REQMTS; N4X SS

EXISTING MARINA

SERVICE - 400A,

240/120V, 1P, 3W, NEMA 3R

UTILITY CO.

PRIMARY

(2) 4" C.

-0.75" 0.75"

TO SITE LIGHTING

TYPE S15V

20.2

20/1

GFCI/EPO CONTROL

POWER

20.2

SERVICE DISCONNECT; ENCL. CB

400A, 240/120V, 1P, 3W, 22K AIC, NEMA

4X SS; COPPER GRDS PER CODE

400/2

NOTE: PROVIDE DISTRIBUTION PANEL

'BW' IN A FREESTANDING 304 OR 316

POWDER COATED (WHITE) STAINLESS

STEEL (SS) ENCLOSURE WITH INTERNAL

HEATER.

SOUTH LESCHI MARINA

WAVE ATTENUATOR AND

PUBLIC ACCESS FACILITY

Also, verify all underground utilities not located by the 811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.

>>>>CAUTION - CALL 811<<<<

UTILITY NOTIFICATION CENTER

BEFORE YOU DIG!

WWW.CALL811.COM

WIRING DIAGRAMS & CALCULATIONS

E1.0

E1.0

E1.0

/1

5/2

28 2620

LESCHI SOUTH MOORAGE FACILITY

SOUTH LESCHI MARINA

WAVE ATTENUATOR AND

PUBLIC ACCESS FACILITY

Also, verify all underground utilities not located by the 811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.

>>>>CAUTION - CALL 811<<<<

UTILITY NOTIFICATION CENTER

BEFORE YOU DIG!

WWW.CALL811.COM

ELECTRICAL SITE PLAN

E2.1

E3.1

E2.1

E2.1

/1

5/2

To be completed by others prior to start of project.

As-built information to be provided to contractor.

LESCHI SOUTH MOORAGE FACILITY

UPLAND UTILITY INSTALLATION

AFTER CONTRACT EXECUTION.

LANDING FLOAT FIBERGLASS CHASES; FASTEN

MFGR PROVIDED STRUT BELOW

GANGWAY

BELL-END; TYPICAL

STAINLESS STEEL CABLE GRIP

(316 SS)

PORTABLE POWER CABLE;

SEE SLWD FOR QTYS/SIZES

ROUTE CABLE INTO CENTRAL

FLOAT CHASE

ROUTE PORTABLE POWER CABLE OVER

SUPPORT STRUCTURE; CABLE TO REMAIN

ABOVE WATER LEVEL THROUGHOUT

HISTORIC RANGE

PROVIDE CABLE SUPPORT STRUCTURE WITH

(18") RADIUS SADDLE; INCLUDE 14"t HDPE RUB

MATERIAL PERMANENTLY FASTENED TO

SADDLE (CABLE SHALL NOT COME IN

CONTACT WITH ABRASIVE OR METALLIC

SURFACES;TYPICAL).

TYPE 'S1' LUMINAIRE; MOUNTING

PLATE BY GANGWAY FABRICATOR.

LUMINAIRE FLUSH WITH

HORIZONTAL TUBING.

RGS CONDUIT AND FITTINGS

GANGWAY; LUMINAIRE MOUNTING TYPICAL

FOR GANGWAY AND HANDRAILS. ADAPT

MOUNTING DETAILS TO APPROVED GANGWAY

DESIGN.

HORIZONTAL TUBING

MOUNTING PLATE; TYPE 'S1'

SOUTH LESCHI MARINA

WAVE ATTENUATOR AND

PUBLIC ACCESS FACILITY

Also, verify all underground utilities not located by the 811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.

>>>>CAUTION - CALL 811<<<<

UTILITY NOTIFICATION CENTER

BEFORE YOU DIG!

WWW.CALL811.COM

ELECTRICAL FLOAT PLAN

E3.1

ELECTRICAL FLOAT PLAN

SCALE: 1"=20'

SHEET LEGEND

POWER PEDESTAL

V = VOLTAGE (WHEN USED)

W = SLIP NUMBER(S) SERVED

X = 30 = 30A,120V OUTLET

X= 50(1) = 50A, 120V OUTLET

X = 50 = 50A,120/240V OUTLET

X = 60 = 60A,120/240V OUTLET

X = 100 = 100A,120/240V OUTLET

Y = UNIT SUBSTATION

Z = CIRCUIT NUMBER

NOTE: 'X' DESIGNATES OUTLET PER SLIP. MULTIPLE REFERENCES

(i.e. 30/50) INDICATES MULTIPLE OUTLETS PER SLIP.

APPROXIMATE PEDESTAL PLACEMENT LOCATION

JUNCTION BOX - IN FLOAT/ UL LISTED MINIMUM 30" x 17" x 18"d UON

X = P = POWER

X = C = COMMUNICATIONS

Y = DOCK

Z = BOX IDENTIFIER

FIRE PEDESTAL

POLE LIGHT FIXTURE; TYPE AS NOTED SEE LUMINAIRE SCHEDULE,

SHEET E0.0

STEP LIGHT FIXTURE; TYPE AS NOTED, SEE LUMINAIRE SCHEDULE

ELECTRICAL CHASES - INSIDE FLOAT

E3.1

/1

5/2

To be completed by others prior to start of project.

As-built information to be provided to contractor.

30 2622

PLAN

LESCHI SOUTH MOORAGE FACILITY

POWER

PEDESTAL

18"(TYP)

18"(TYP)

TYPE 'S15'

LUMINAIRE

POWER

PEDESTAL

TYPE 'S15'

LUMINAIRE

PILE

(BEYOND)

NON-METALLIC

CHASES (SEE PLAN

FOR SIZES/QTYS)

IN-FLOAT JUNCTION

BOX (BEYONE)

POWER CABLES (SEE SLWD); PROVIDE

PERMANENTLY FASTENED HDPE SHIM

BETWEEN CABLE AND STRUCTURE.

SIDE-WALL @ PILE

POCKET (BEYOND)

LUMINAIRE ANCHORS

PROVIDED BY FLOAT

MANUFACTURER (TYP)

3' -4

2'

-6

FINISHED GRADE.

28" DIA.

TOP OF CONCRETE BASE MUST

BE LEVEL. CONTRACTOR TO

MAKE POLE PLUMB.

1/4" MINIMUM METALLIC

SHRINKAGE RESISTANT GROUT.

36" OF SLACK CONDUCTORS AT

BASE OF POLE - PROTECT WITH

PLASTIC COVERING UNTIL POLE

INSTALLATION. PLUG CONDUITS

TO PREVENT WATER COLLECTING

IN CONDUITS.

CONNECT GROUND CONDUCTOR

TO GROUNDING LUG OF POLE AT

HAND HOLE.

1", 45° TOOLED EDGE.

(3) #3Ø REINFORCING STEEL

HOOPS WITHIN TOP 5" OF

CONCRETE BASE.

ANCHOR BOLTS PER

MANUFACTURER

RECOMMENDATIONS

18" DIAMETER STEEL REINFORCING

BAR CAGE. 6-#7 VERTICAL BARS

WITH #4 HORIZONTAL HOOPS ON 11"

CENTERS TIED TO VERTICAL BARS.

CONCRETE 4000 PSI

CONDUIT.

SOUTH LESCHI MARINA

WAVE ATTENUATOR AND

PUBLIC ACCESS FACILITY

Also, verify all underground utilities not located by the 811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.

>>>>CAUTION - CALL 811<<<<

UTILITY NOTIFICATION CENTER

BEFORE YOU DIG!

WWW.CALL811.COM

DETAILS & PRODUCT INFORMATION

E4.0

E4.0

E4.0

E4.0

E4.0

E4.0

E4.0

NOTE: SPECIFIED LUMINAIRE INCLUDES

CUSTOM SURFACE MOUNTED BACKBOX

AVAILABLE FROM MANUFACTURER.

/1

5/2

To be completed by others prior to start of project.

As-built information to be provided to contractor.

31 2623

LESCHI SOUTH MOORAGE FACILITY

7/1/24

7/1/2024

SCL DESIGN DRAWING - FOR REFERENCE

2412/03/2025

TOPO AND BATHYMETRIC SURVEY

WAVE ATTENUATOR AND

PUBLIC ACCESS FACILITY

26 27

V1.1

Also, verify all underground utilities not located by the 811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.

>>>>CAUTION - CALL 811<<<<

UTILITY NOTIFICATION CENTER

BEFORE YOU DIG!

WWW.CALL811.COM

M A

TC

H

LI

N

E

SH

EE

T

V1 .2

M A

TC

H

LI

N

E

SH

EE

T

V1 .2

10/28 2025

TOPO AND BATHYMETRIC SURVEY

WAVE ATTENUATOR AND

PUBLIC ACCESS FACILITY

27 27

V1.2

Also, verify all underground utilities not located by the 811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.

>>>>CAUTION - CALL 811<<<<

UTILITY NOTIFICATION CENTER

BEFORE YOU DIG!

WWW.CALL811.COM

M A

TC

H

LI

N

E

SH

EE

T

V1 .1

M A

TC

H

LI

N

E

SH

EE

T

V1 .1

10/28 2025

12/03/2025 https://seattlegov.na1.adobesign.com/verifier?tx=CBJCHBCAABAADoDdpE1QMS-C7d6bgihmAvrDSg5aFqJE

2025-12-03T16:37:52+0000
Certified by Adobe Acrobat Sign

File details come from the government source that posted it. Updated .