Purchase 6DW - Specs.pdf
PDF 3 MB Posted
- Attached to
- Six (6) Double Wide Trailer Purchase
- Solicitation number
- N42158-26-NNSY-900F-0057
About this file
This is a comprehensive specification document for the design, fabrication, quality assurance, delivery, and on-site installation of 24-foot by 40-foot double-wide Temporary Production Facilities (TPFs) to support Norfolk Naval Shipyard project teams.
The TPFs must feature non-combustible construction and be stackable to two units high in one of two configurations: Type A with both egress doors on the same side, or Type B with egress doors on opposing short ends. Geometric requirements include an overall exterior length of 40-41 feet with minimum 39-foot interior clear working length, 24-25-foot exterior width with minimum 23-foot interior width, and minimum 8-foot interior clear height. All units must be hurricane-proof to 110-mph winds during 3-second gusts and weather-proof with HVAC systems capable of maintaining 70 degrees Fahrenheit year-round. Interior specifications include non-combustible wall finishes and framing (steel studs required), drop ceilings with non-combustible materials, vinyl or laminate flooring, and resilient rubber or vinyl wall base. Each TPF requires dual emergency exit signs with battery backup, fire alarm and detection systems with smoke detectors, manual pull stations, and combination audible/visual alarm devices in each module. Electrical requirements include one 100-Amp, 120/240V load center per module with appropriate circuit breakers, 20-Amp 120V quad-type general purpose receptacles, and exterior GFCI receptacles. Information technology infrastructure must include external communications pull boxes ("Hoffman Boxes"), interior LAN/NMCI cabinets with CAT5e and CAT6 cabling terminations, and separate conduit isolation for electrical and data cabling. Additional features include energy-efficient HVAC units with programmable thermostats, fire suppression systems with exterior connections and flow-switch alarms, fire extinguishers at each door, and exterior aluminum siding with full skirting extending to ground. The contractor must provide all labor, materials, equipment, and tools; demonstrate compliance through government inspection at the shipyard; respond to modification requests within 24 hours; and provide lifting sketches, rigging diagrams, and isometric diagrams meeting NAVFAC P-307 standards for potential emergency relocation. All facilities must comply with Unified Facilities Criteria, International Building Code, NFPA standards, OSHA requirements, and Norfolk Naval Shipyard security protocols, including specific locking mechanisms for security islands and nuclear work areas.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TEMPORARY PRODUCTION FACILITIES SPECIFICATIONS (24-ft x 40-ft Double Wide)
Purchase of Temporary Production Facilities to support Norfolk Naval Shipyard Project Teams
In accordance with the Statement of Work, the contractor shall provide 24-ft x 40-ft double wide Temporary Production Facilities (TPF’s). The TPF’s shall be delivered according to the quantities, locations, dates and delivery scheme as outlined in the Statement of Work. This specification package covers the design, fabrication, quality assurance, delivery and on-site assistance of TPF’s in use by Norfolk Naval Shipyard.
The TPF’s shall have non-combustible construction as outlined in the specification package and shall be constructed so that they are stackable two (2) units high. There are two possible configurations of the 24-ft x 40-ft double wide TPF’s that will be designed in this specification package. Type A is described in SECTION 10 and shown in ENCLOSURE (1) and is identified by having both egress doors on the same side of the TPF. Type B is described in SECTION 10 and shown in ENCLOSURE (2) and is identified by having the egress doors on the opposing short ends of the TPF’s.
See Enclosure (1) of the Statement of Work for an aerial view of the location of all TPF’s associated with this project. This drawing shows the contractor the exact location on Norfolk Naval Shipyard to set the TPF’s and provides accurate dimensions to allow the contractor to properly plan for the build. Additionally, this drawing accurately reflects both the configuration and orientation of all TPF’s in the project, the contractor shall build all facilities to this drawing. NOTE: drawings for any TPF’s to be located shipboard are not included as part of this package, for security reasons.
The contractor shall provide all labor, materials, equipment, tools, transportation and supervision necessary to deliver these modular temporary facilities in accordance with the specifications outlined in this document and attached drawings. NOTE: for certain facilities installed shipboard, Norfolk Naval Shipyard will install them, this agreement, if applicable, will be made in the Statement of Work.
This specification defines minimum performance criteria; the contractor may submit standard equipment items that meet or exceed these criteria. Additionally, the contractor is encouraged to suggest alternatives that the contractor believes will meet or exceed the functional criteria included herein, while providing faster delivery, more durability and/or lower life cycle costs.
1. GOVERNMENT RESPONSIBILITY
1.1. Customer agrees to provide the contractor ready access to the job location during contractors working hours (i.e., weekdays between the hours of 0730 and 1600). Ready access to the job site shall be defined as a work space free of shipyard material/obstructions and DOES NOT include shipyard personnel providing escorts for base/classified location access.
1.2. All services such as routine or urgent maintenance or modification requests shall be scheduled during contractors normal working hours, unless an agreement is made to support this work. Emergency services required on the TPF’s may be completed after hours but must be coordinated through the customer for approval.
1.3. The customer is responsible for the cost of all additional or requested maintenance, repairs and/or modifications not specifically covered under this agreement or any applicable warranties. Only the Contracting Officer (KO) may direct the contractor to provide any maintenance, repairs and/or modifications not explicitly covered by this agreement.
1.4. The customer agrees to, upon satisfactory delivery and installation, connect the TPF’s to temporary services such as electrical power, water and fire alarm system.
2. CONTRACTOR RESPONSIBILITY
2.1. Contractor shall comply with the Statement of Work and manufacture the proper number of TPF’s in the correct orientation/configuration and in proper quantities. Additionally, the contractor shall comply with all delivery and/or installation requirements and dates.
2.2. The contractor understands that the customer will need to make modifications to the TPF’s in order to support the shipyards requirements. At time of receipt of the specification package the contractor understands the following modifications will be required in order to support shipyard requirements:
1. Installation/mounting of Dry-Erase Boards on walls
2. Mounting paper file/organization systems on walls
3. Running additional information technology networks both interior and exterior to the walls
For additional modifications required by the customer, the contractor will respond to written requests within 24 hours of receipt of the request.
2.3. Before any leased/purchased TPF will be accepted by the government, an inspection will be performed to ensure that the contractor has provided a product that adheres to the agreed upon specifications outlined in the document. The inspection will be performed at the shipyard after delivery, Norfolk Naval Shipyard will not travel to the contractor’s facility to conduct the inspection. If the inspection is not satisfactory, the contractor has ten (10) business days to correct the discrepancies (at contractor cost), or the TPF will not be accepted by the government.
The inspection will consist of the government comparing the TPF to the agreed upon specs package and generating a punch list for the contractor.
2.4. For purchased units, contractors must provide TPF and material to install TPF. TPF Material list is shown in Enclosure 17.
2.5. Norfolk Naval Shipyard is an industrial environment so the contractor should expect damage beyond normal wear and tear.
3. Guiding Documents
3.1. The resulting project shall comply with all governing codes and Naval standards including the most recent Unified Facilities Criteria, International Building Code, Americans with Disabilities Act Standards for Accessible Design and Requirements for Lifting Equipment. Guiding Documents:
Unified Facilities Criteria (UFC) 1-200-01, 3-301-01 and 3-600-01 National Fire Protection Association (NFPA) 1, Fire Code National Fire Protection Association (NFPA) 70, National Electric Code (NEC) National Fire Protection Association (NFPA) 101, Life Safety Code
4. Safety Documents
4.1. Per Federal Acquisition Regulation (FAR) 22.102-1 (a) entitled “Safety”, contractors are hereby informed that their employees or representatives present on property under Naval Facilities Engineering Command cognizance performing service and/or construction contracts administered by Naval Facilities Engineering Command (NAVFAC) shall comply with EM 385-1-1, US Army Corps of Engineers Safety and Health Requirements Manual.
4.2. During the performance of this service and/or construction contract, the contractor is aware that their employees or representatives may be required to board U.S. Navy ships to build, set and construct TPF’s. Per FAR 22.102-1 (a) “Safety’, contractors are hereby informed that their employees or representatives present on property under Norfolk Naval Shipyard cognizance must follow Federal and State OSHA requirements and Norfolk Naval Shipyard OSHE program manual, NAVSHIPYDNORINST P5090.2. Requirements or safety requirements for site specific location of the contract.
Contractors and Non-NNSY Government Agencies (NNGAs) are hereby informed that their employees or representatives present on property under Norfolk Naval Shipyard (NNSY) cognizance must adhere to Federal OSHA requirements for Hazardous Energy Control (HEC) IAW 29 CFR 1915.89 and must follow HEC procedures as identified in Naval Sea Systems Command’s (NAVSEA) Occupational Safety, Health and Environment Corporate Manual (OSHECM) Chapter 250 (latest revision), when performing work under an NNSY contract. All HEC work to be performed by contractors and NNGAs requires that NNSY Technical Point of Contact (TPOC) and/or Contracting Officers Representative (COR) be notified of the HEC scope of work prior to starting work. Any changes or deviations in the initial scope of HEC work require NNSY TPOCs and/or CORs be informed of the change/deviation. Appendix 250.B-1 through B-3 of OSHECM Chapter 250 for multiple employer work identifies when contractors and NNGAs are required to assign their Lockout/Tags-Plus Coordinator (LOTC) to coordinate HEC work with the cognizant NNSY LOTC. HEC locks shall be provided by the contractor or NNGA for their employees use. The HEC locks shall have red bodies with name labels or tags affixed, identifying who installed the HEC lock(s) and a point of contact telephone number. HEC lock name labels and tags must be made of materials that will hold up to the environment to which they are exposed. HEC tags used for Tags-Plus work shall be provided by the cognizant NNSY LOTC to the contractor of NNGA for their use if machinery, equipment or systems (MES) cannot be locked out. OSHECM Chapter 250 Tags-Plus procedures will be strictly followed.
Contractors and NNGAs may obtain electronic copies of OSHECM Chapter 250 (latest revision) and access the OSHA 1915.896 website by using the following link to NNSY’s public access website:
http://www.navsea.navy.mil/shipyards/norfolk/default.aspx
Names and contact information for NNSY LOTCs and/or the Facility Custodian will be provided by NNSY TPOC and/or CORs set forth elsewhere in this award document.
4.3. Section 4.2 only applies to contractors in the performance of service and/or construction contracts onboard Naval warships at Norfolk Naval Shipyard.
5. Facility Configuration
5.1. The geometric requirements of the 24-ft x 40-ft modular units shall be as follows (all dimensions are given to wall finish and not to the studs):
Overall exterior length shall be at least 40-ft but no greater than 41-ft.
Minimum interior clear working length shall be at least 39-ft.
Overall exterior width shall be at least 24-ft but no greater than 25-ft.
Minimum interior clear working width shall be at least 23-ft.
Minimum interior clear working height (floor to ceiling) must be at least 8-ft.
5.2. The contractor shall utilize Enclosures (3-8) of this TPF specification package for the detailed interior layout drawings of each TPF, including the layout of all services and utilities. Enclosure (1) of the Statement of Work will provide the contractor with the exterior configuration and orientation of each TPF. The contractor shall manufacture all TPF’s in strict adherence to the drawings.
Unless any exceptions are directly created in the Statement of Work, all TPF’s will be manufactured according to the standard designs created as part of this specification package.
5.3. All TPF’s are to be manufactured of non-combustible construction. Strict adherence to this requirement is mandatory and deviations will not be authorized in any circumstances.
5.4. The TPF’s shall be designed to be stacked two (2) units high, Enclosure (1) of the Statement of Work displays which TPF units will actually be stacked. It shall be acceptable for the contractor to designate certain units as top units only. In the case the contractor manufactures TPF units that are only capable of serving as top units, they shall be clearly marked as top units only.
5.5. All units shall be hurricane proof up to 110-mph winds during a 3 second gust (nominal wind speed (Vasd)).
The TPF’s shall also be weather proof, proper insulation shall be provided so that the HVAC units are able to maintain 68 degrees Fahrenheit year-round. The contractor shall sufficiently stiffen the TPF units so that no swaying is felt in the upper units.
5.6. All TPF’s must be designed with axle’s/ chassis that disconnect without having personnel underneath the TPF.
NNSY personnel are not able to work under a suspended load due to safety requirements.
If contractor provides TPF’s with axles that require disconnection from beneath the TPF, contractor is to remove the axles at no additional cost to the government, after the TPF has reached its final destination.
6. Interior Space
6.1. The interior layout of each unit shall strictly adhere to the drawings included as Enclosures (3-8) in this specification package.
6.2. Interior support columns are authorized to be included in the interior of each TPF. If the columns are required in the TPF’s, there shall be a minimum of 22-ft and a maximum of 26-ft between the columns. The maximum dimensions of the columns shall be 4” x 4”, and the column should be set no more than 8-inches off the centerline of the TPF. Two (2) columns per module authorized.
6.3. At each egress point, the contractor shall provide one (1) LED emergency exit sign that is mounted above the doors. The LED emergency exit signs shall be the combination type combining the emergency exit sign with an emergency light. Each combination sign shall be outfitted with two lamp heads. The signs shall have a white finish with red letters.
The combination emergency exit signs shall have battery backup providing the UL recognized 90 minute emergency lighting and illumination of the word “EXIT”.
Combination exit signs shall have a test switch for the customer to provide periodic inspections.
There shall be a combination exit sign at every exterior door.
6.4. Floor coverings are to be vinyl or similar laminate (easy to clean) flooring. Flooring materials such ceramic, stone, porcelain, glass or hardwood (engineered or natural) will not be accepted by the government. Carpet is not authorized as an acceptable flooring material.
6.5. Interior walls are to have a resilient wall base that is made from rubber, vinyl or similar materials. Wood is not authorized in order to maintain non-combustible properties. The wall base shall be a minimum height of 2.5-inches and thickness of 0.080”.
6.6. Interior walls are to comply with non-combustible construction requirements in that the wall finish should be not flammable or combustible. Gypsum board or similar materials will be acceptable. A material safety data sheet shall be provided by the contractor that displays the hazards of the wall finish as the material is exposed to high temperatures and special precautions needed by emergency responders.
6.7 Interior wall structures are also to comply with non-combustible construction requirements, no wood will be authorized in this purpose. Acceptable materials will be a non-combustible framing system consisting of steel studs and the associated tracks. Contractor may propose an alternative non-combustible framing system if it meets or exceeds the functional requirements and presents an economic benefit to the government.
6.8. Ceilings of the TPF shall be a drop ceiling rather than a traditional drywall ceiling supported by the studs/joists overhead. The drop ceiling grid and support structure shall comply with non-combustible construction requirements and consist of metal or similar non-combustible/not flammable material. Ceiling panels shall also comply with non-combustible construction requirements and the contractor will provide a material safety data sheet to identify the hazards as the material is exposed to high temperatures and begins decomposition.
6.9. Contractor shall install a fully functioning fire alarm and detection system. The following list provides the minimum design requirements of the fire alarm and detection system:
One (1) control panel is required for each set of interconnected TPF’s. The control panel must be compatible with, at minimum, the following input devices: smoke detectors, pull stations, waterflow devices, tamper switches and other normally open contact devices. The customer is not defining any specific models or devices, contractor is responsible for ensuring control panel is compatible with all input devices.
There shall be at minimum one (1) smoke detector in each module of the TPF. The smoke detector shall be located at the center of each module.
There shall be a manual fire alarm pull station located within 36-inches of each door. The pull station shall meet all applicable Americans with Disabilities Act and Uniform Federal Accessibility standards.
The interior fire alarm system shall consist of both audible and visual alarm devices. The alarm shall consist of a combination device utilizing both a strobe and audible horn. Each module shall have one combination alarm device.
6.10. Contractor will be responsible for demonstrating proper operation of the fire alarm and fire detection system in accordance with this specification package in the presence of the shipyard representative. Note: Contractor is responsible for interconnecting all units and modules to the control panel. The contractor will not be connecting the TPF’s into any shipyard systems.
6.11. Provide one (1) 3-inch diameter hole in each module at the location designated “Internal Cabling Hole”.
Every internal cabling hole will have a PVC pipe fit the interior diameter of the hole. This hole will provide the connection point between the “External Communications Pull-Box” and the “LAN/NMCI Cabinet”. The internal cabling hole that is not serving this purpose shall have a suitable cover to prevent leaks.
6.12. All HVAC ducting shall be located within the ceiling. All supply and return diffusers shall be located in the ceiling none are authorized to be located in any walls. Contractor to provide an adequate number of diffusers based on the design of the HVAC unit/system and the requirement for the system to maintain 70 degrees year round in all conditions. Diffusers must fit neatly within the drop ceiling grid.
6.13. For every module within the TPF’s, the contractor is to provide two (2) rows of surface mount fluorescent twin tube strip type interior light fixtures. The light fixtures shall have an energy efficient ballast and utilize 32-watt fluorescent bulbs.
One row of light fixtures shall be mounted 3-ft from the interior face of the exterior wall and the other row of light fixtures shall be mounted 3-ft from the open end of the module.
Contractor to design lighting system in accordance with applicable codes and ensure proper lighting is available in the TPF.
TPF’s with interior rooms should have their own light fixtures that do not obstruct the wall layout.
6.14. Provide one (1) light switch located within 1-ft of every egress door in all units. To provide for greater energy efficiency the light switch should have the dimming function.
For TPF’s with no rooms, there shall be no zones in the TPF’s, each light switch should activate all lights.
6.15. The contractor will provide one (1) fire extinguisher at the interior of each external egress door. The fire extinguisher shall be Dry Chemical suitable for fires of Class A, B and C. The fire extinguisher shall have minimum capacity of 10 lbs. Contractor is to provide a bracket inside of each door for mounting the fire extinguisher.
6.16 There shall be a fully functional fire suppression system with exterior connections on the mechanical ends of the units. Each unit shall have one row of sprinklers, containing a minimum of three sprinklers, in the center of the unit. Each row of sprinklers shall be fitted with a flow switch that is connected to the main fire alarm control box, so that it sounds an alarm when water starts to flow.
Test and certify fire suppression systems. Hang tags visibly on fire suppression system and provide paperwork to technical POC indicating that testing is complete and tested satisfactorily prior to delivery.
7. Electrical Requirements
Note: in larger TPF’s such as a double wide or triple wide each module shall have its own electrical system.
7.1. Provide one (1) internally mounted LOAD Center electrical panel in each module, see Enclosures (3-6) for the required location of each Load Center. The Load Center shall be the main breaker type with a voltage rating of 120/240 V AC and a rated current of 100 A. The main breaker shall be mounted flush into the wall and include a flush cover as well. The main breaker shall be outfitted and provided with all applicable circuit breakers.
7.2. The circuit breakers are to be 20 A, 1 Pole with an operational voltage of 120 V AC. The breakers shall be the standard switch type breakers. The following circuit breakers shall be provided and in adequate numbers in order to eliminate the risk of tripping any breakers:
In each module, provide an adequate number of breakers to support an expected load of 10 general purpose receptacles; see section 8.4 for detailed information on the receptacles.
Provide an adequate number of circuit breakers to support the lighting and exit sign requirements as identified in Section 7. Breakers on the lighting and exit sign circuits must be Switching Duty Rated.
7.3. Provide an adequate number of 40 A, 2 Pole, 240 V AC circuit breakers in order to support each HVAC unit.
The breakers shall be the standard switch type and these breakers must be HACR rated.
7.4. Provide general purpose receptacles in accordance with the drawings included as Enclosure (3-6). Minor deviations in location are authorized as needed to support the structural requirements of construction are authorized, however; changes to quantity will not be authorized. See below provided specifications for details on the receptacles.
Interior Wall Receptacles: All interior receptacles shall be the quad type rated at 20 A and 120 V. Unless otherwise specified, wall mounted receptacles shall not be mounted more than 15-inches above the floor.
Interior wall receptacles may be installed in conjunction with the data/voice receptacles.
Interior Floor Receptacles: All interior receptacles shall be the quad type rated at 20 A and 120 V.
Receptacles shall not extend more than ½-inch above the floor level. Floor receptacles must include a durable cover that allows for the covering of individual outlets. The interior floor receptacles may be installed in conjunction with the data/voice receptacles.
Exterior Mounted Receptacle: On each module, provide one (1) 120-Volt, 15-Amp duplex GFCI test type receptacle. This outlet is to be wired on its own dedicated circuit and will be mounted on the exterior adjacent to the HVAC unit. This receptacle must be contained within a weatherproof enclosure with a locking cover.
Receptacle Wiring: The quad type receptacles are to be wired on #12 AWG.
7.5. All wire must be THHN or THWN, 75 degrees Celsisus (minimum), size as indicated. Do not substitute wiring type/temperature rating unless the ampacity of wire and conduit fulfill the requirements and are evaluated to ensure NEC compliance.
7.6. Conduit: Electrical Metallic Tubing (EMT) is specified on drawings. The NEC requires EMT to be supported within 3-feet of each box or conduit body and supported every 10-feet at minimum. Liquid-tight Flexible Metal Conduit (LFMC) may be used on the exterior instead of EMT. The NEC requires LFMC to be supported within 1-foot of each box or conduit body and supported every 4.5-feet at minimum. \
In order to comply with Norfolk Naval Shipyard, contractor shall ensure that the cabling for electrical power is enclosed in separate conduit, isolated from the CAT 5 and CAT 6 cabling required for the data and voice receptacles.
7.7. The NEC requires the following color code:
Neutral (Grounded Conductor) – White o Note: May be phased. Taped white if larger than #6 AWG
Ground (Equipment Grounding Conductor) – Green
7.8. On the exterior of each module, provide one (1) circuit breaker enclosed in a NEMA-3R circuit breaker enclosure rated for outdoor installation. The circuit breaker shall be 2 Pole with a line rated current of 40 A and a rated operational voltage of 600 V AC.
7.9. The exterior wiring to include a cam-lock connection box feeding the 600 V, 40 A circuit breaker. The Cam- Lok connection shall have one (1) each panel mount black male receptacle and panel mount red male receptacle.
The receptacles shall be rated for 600 V AC up to 400 Amps continuous and capable of receiving cable size #6 – 250 MCM. Provide receptacle covers for the Cam-Lok connection box that provides a NEMA 3R rated environmental seal. The colors of the receptacle covers shall be red and black corresponding to the colors of the Cam-Lok connection box.
7.10. The 600 V, 40 A circuit breaker is to feed the transformer. It is to be a single-phase, 15-kVA, 480/240-volt primary and 240/120-volt secondary transformer. The transformer should be on the exterior of the TPF located adjacent to the HVAC unit and enclosed in a NEMA 3R rated outdoor suitable enclosure. The transformer is to feed the interior load center electrical panel. A typical transformer wiring diagram is shown in Enclosures (9-10), use the manufacturers wiring schematic to connect transformer. Transformer size may be adjusted depending on the load demand of the units.
7.11. There shall be one (1) Cam-Lok connection box, exterior circuit breaker, transformer and internal load center electrical panel per module NOT per building. Contractor is responsible for providing all electrical equipment.
Norfolk Naval Shipyard will provide the power and connection to the Cam-Lok connections.
7.12. Input connections of the temporary production facilities electrical system shall be per NEC requirements and using Cam-Lok receptacles. See Enclosure (11).
7.13. Transformer frame shall be bonded to the unit frame using appropriate size bonding jumper from NEC Table 250.122, per NEC. Contractor is responsible for bonding.
7.14. Electrical system wiring shall comply with NFPA 70 (National Electric Code) where applicable.
7.15. All units shall be electrically bonded together. All cabling shall run internal to the walls, floor or ceiling;
there shall be NO exposed wiring. Contractor is responsible for bonding. \
8. INFORMATION TECHNOLOGY INFRASTRUCTURE REQUIREMENTS
8.1. The contractor shall provide an external communications pull box on each unit in every location labeled “External Communications Pull Box” as shown in Enclosures (3-6). The External Communications Pull Box shall be mounted on the exterior of the TPF’s in conjunction with the “Internal Cabling Hole”. These boxes are commonly referred to as “Hoffman Boxes” and shall have the approximate dimensions of 18-inches wide x 18 inches high x 6 inches deep.
Provide two (2) 3-inch (diameter) holes located on each of three (3) sides (left, right and bottom) of the External Communications Pull Box in order to provide NNSY personnel the ability to run conduit through the openings. Utilize Enclosure (12) to determine the design of the External Communications Pull Box and the location of the holes.
On the inner face of the External Communications Pull Box, provide one (1) 3-inch diameter hole that aligns with the Internal Cabling Hole when mounted on the TPF. The hole shall be located as shown in Enclosure (1-6).
NOTE: there shall be one (1) External Communications Pull Box per TPF, not module. This means one double wide TPF shall have one (1) not two.
8.2. On the interior side of the Internal Cabling hole in the interior of the TPF, contractor shall provide one (1) Wall Cabinet designated on drawing in Enclosure (3-6) as LAN/NMCI Cabinet. The contractor shall provide 1.75” Uni-Strut for mounting the LAN/NMCI Cabinet. The LAN/NMCI cabinets are to be grounded and if any additional mounting materials are required (i.e., backboard, etc.) they shall comply with non-combustible requirements. Each LAN/NMCI Cabinet is to have its own dedicated 20-Amp, 120-Volt power. Interior power requirements for the LAN/NMCI Cabinet are to comply with Section 8 of this specification package.
The size requirements of the LAN/NMCI Cabinet are (minimum) 24-inches high, 21.25-inches wide and a usable depth of 22-Inches.
NOTE: there shall be one (1) LAN/NMCI Cabinet per TPF not module. This means one (1) double wide TPF will have one (1).
8.3. If the shipyard has identified the requirement for monitors in any of the TPF’s, the contractor shall provide 1.75-inch Uni-Strut in the locations identified. The Uni-Strut will be mounted horizontally across the wall and must be able to support a minimum of 100 lbs.
At each monitor location, contractor is to provide a dedicated power source (20-Amp, 120-Volt). This receptacle is to be quad type.
At each monitor location the contractor is to provide a dedicated Double Gang Data/Voice Receptacle.
The power source and data/voice receptacle may be installed in conjunction; however, conduit may not be shared. The power source and data/voice must be installed underneath the UNi-Strut at a height not less than 48-inches.
NOTE: contractor is not responsible for providing any monitors.
8.4. In each location designated “Double-Gang Data/Voice Receptacle”, contractor shall provide the cabling for four (4) each CAT5e Local Area Network (LAN) drops and four (4) each CAT6 voice drops. The POC for technical questions on Information Technology Infrastructure is Code 109 at Norfolk Naval Shipyard. The COR and/or Technical POC will ensure the most current C109 POC is identified. Utilize paragraphs 9.5 and 9.6 for definitions of a LAN ad Voice drop.
The double gang data and voice receptacles are not required to be installed in conjunction utilizing an 8-hole face plate. Two (2) four-port outlet frames are authorized.
8.5. A LAN drop consists of two (2) each Green and two (2) each Blue CAT5e cables. These drops shall meet EIA/TIA 568B standards for installation, labelling and testing/verification. On the walls, the LAN drops will be terminated on 110-style wall jacks; which shall be color-coded to represent the color of the CAT5e cable supplying the jack. At the LAN/NMCI Cabinet, the LAN drops will be terminated on a 568B/110-style/48 port patch panel (example part number TC-P48C5E). Labeling of the drops shall follow the following style: UNIT # - FLOOR – DROP #. NOTE: Contractor is to make the termination on the 48-port patch panel.
The double gang data receptacles shall be configured as shown in the attached drawing, Enclosure (13).
Additionally, the receptacle shall utilize the green and blue color scheme.
Enclosure (3-6) identifies locations where the double gang data receptacles are installed in the floor. In these locations, the receptacles shall not extend more than 1/2-inch above the floor level and each jack must have individual durable covers that provide for the covering of individual jacks not in use.
8.6. A Voice drop consists of two (2) each CAT6 cables and will be referred to as “Voice Drops”. These drops shall meet EIA/TIA 568B standards for installation, labelling and testing/verification. Contractor is responsible to terminate the voice drops on 110-style wall jacks and the cabinet end will be terminated on a 568B/110-style wall mount panel. Labeling of the drops shall follow the following style: UNIT # - FLOOR – DROP #.
Enclosure (3-6) identifies locations where the voice drops are installed in the floor. In these locations, the receptacles shall not extend more than 1/2 – inch above the floor level and each jack must have individual durable covers that provide for the covering of individual jacks not in use.
8.7. Contractor is authorized to install the double gang data and voice receptacles in conjunction with power receptacles; however, the CAT5e, CAT6 and electrical cabling must be installed in individual conduit, sharing conduit is not authorized with these TPF’s.
8.8. The contractor shall run all cabling internal to the walls, floor or ceiling; the government will not accept any facilities with exposed wiring.
8.9. In all cases the contractor is responsible for completing the termination of all CAT5 and CAT 6 cables on the wall panels and providing both the cross connect hardware and labor to cross connect individual TPF modules. The contractor will not physically tie in any TPF to Norfolk Naval Shipyard IT infrastructure.
9. EXTERIOR SPACE
9.1. There are two possible configurations for the 24-ft x 40-ft double wide TPF’s. The first configuration is Type A. Type A is identified as the TPF having both external on the same side of the unit; both doors will be located on one long edge of the TPF. All mechanical equipment (HVAC, Transformer, IT, etc.) will be located on the short edge. Type B is identified as having the external ends on opposite sides of the short sides. The mechanical equipment will also be located on the short side. References enclosures (14 & 15) for detailed configuration drawings of Type A and Type B 24-ft x 40-ft TPF’s.
In cases of stacked TPF’s, the upper and lower level units will be identical configurations.
9.2. Each TPF will have two (2) exterior egress doors. All doors shall have a 36-inch width and 7-foot height and be non-combustible fire rated doors constructed from 18-gauge commercial steel. The doorframe and saddle threshold shall be of the same construction and material requirements. Contractor is to provide a heavy-duty hydraulic door closer capable of closing the door from any open position in order to comply with Norfolk Naval Shipyard security requirements. Additionally the doors are to contain a door sweep and weather stripping. No windows or other vision attachments are to be included on the doors.
In all cases, exterior egress doors are to swing outward.
9.3. There are two type of locks authorized for use on exterior egress doors, the government will specify which locking mechanism is required for each door.
In order to comply with the Norfolk Naval Shipyard security memo, Enclosure (16), for spaces identified as a security island the exterior doors shall be equipped with the Schlage ND44S Locking mechanism or similar as authorized by the security memo. The exterior egress doors shall be equipped with a slap handle rather than a traditional door knob; the slap handle must be on both sides of the door.
o Contractor to provide 10 sets of keys for each lock.
In order to comply with the Norfolk Naval Shipyard security memo, ENCLOSURE (16), for spaces identified as a Nuclear Work Area the exterior doors shall be equipped with a CDX10 locking mechanism.
The CDX10 locking mechanism shall be installed with a key override and a slap handle on the exterior side and a panic bar on the interior side.
o Contractor to provide 10 sets of keys for each lock. Contractor also to provide the factory set combination along with instructions for setting a new combination.
9.4. Windows will not be authorized in any of the TPF units.
9.5. Provide a decal on each temporary production facility with the following information:
Contractor Company Name Contract Number Unique Unit Number (different number for each TPF)
The decal shall be a minimum of 8.5-inch x 11-inch in black writing on a white background. The decal shall be located on the exterior door of each unit and be weather proof to prevent fading or rubbing off in inclement weather.
9.6. In order to support stacking of the units, the contractor is responsible to provide all gaskets, universal bridge lock fittings, double cone two-position twistloc w/ preloc, bolts, brackets, seam closures and any necessary seals, stacking and locking devices necessary for installation.
9.7. In cases of stacked temporary facilities, contractor shall seal the gap between the upper level and lower level units from the weather in order to prevent leaking and other maintenance issues.
9.8. Contractor is to install siding on the exterior of each TPF in the form of aluminum panels or a similar material that will withstand being in an industrial environment and exposed to the weather for the life of the contract.
Contractor is to continue the siding into skirting all the way around the trailer and the skirting shall extend all the way to the ground.
9.9. Provide an energy efficient HVAC unit in each TPF module. The HVAC unit shall be located as shown in the attached drawings, Enclosures (3-6). In all cases, the unit must be able to maintain 70 degrees Fahrenheit for 365 days per year. The units shall be energy star rated.
9.10. Provide one (1) each Interior Wall Mount Programmable Thermostat for each HVAC unit. The contractor shall provide instructions for each thermostat.
9.11. All units shall be hurricane proof up to 110-mph winds and shall also be weather proof.
9.12. A fire alarm device shall be installed on the exterior of each TPF that is tied into the interior fire alarm system.
The exterior fire alarm device shall contain both an audible horn and visual strobe. In accordance with the interior fire alarm and detection system, the contractor will be responsible for displaying proper operation of the fire alarm device.
9.13. Provide one (1) 60-watt exterior surface mounted fluorescent light fixture (shielded) adjacent to every exterior door in all units. Contractor may utilize an LED light fixture on the exterior of each trailer if it meets the requirements described.
10. FACILITY RELOCATION
10.1. In emergent situations, Norfolk Naval Shipyard may be required to relocate the TPF’s. In order to best maintain contractor equipment, the following must be provided:
Units shall be fitted with suitable attachments for overhead lifting as defined:
Single Point Lifts: the lifting attachment shall be capable of supporting the gross weight of the facility with a design factor of five-to-one based on ultimate strength. The lifting attachment shall accept a standard shackle (Federal Specification RR-C-271D, type IVA) which is capable of supporting the gross weight of the facility.
Multiple Point Lifts: each lifting attachment shall be capable of supporting one-half the gross weight of the facility with a design factor of five-to-one. Each lifting attachment shall be designed to accept a standard anchor shackle (Federal Specification RR-C-271D, type IVA) which is capable of supporting one-half the gross weight of the facility.
Design of the lifting attachments shall be such that the attachments and shackles are not side loaded more than 10-degrees outside the plane of the attachment, unless specified by the manufacturer. Lifting attachments shall be located such that the lifting slings do not contact the equipment. Whenever practical, the lifting attachments shall be located above the center of gravity, such that the lifting slings do not contact the facility.
If necessary, a spreader beam certified to NAVFAC P-307 shall be provided by the contractor. The contractor is also to provide the gear for the lower rigging from the spreader beam.
10.2. The facilities shall be marked in a prominent location with the gross weight.
10.3. The facilities shall be provided with a lifting sketch/rigging diagram that meets the requirements of section (13).
The lifting sketch shall detail any specific requirements and/or configurations, that must be met prior to lifting (i.e., “engage swing lock”, “tilt mast back fully”, “rotate lifting basket over side”, “utilize 10’ minimum length slings”, “spreader beam required”, etc.).
A copy of the lifting sketch shall be provided with the equipment and copies shall be forwarded to the government points of contacts and NNSY code 714.
10.14. Permanently affixed isometric diagram shall be placed near the gross weight label and shall include:
Show one (1) individual unit.
Show center of gravity location.
List manufacturer and gross weight.
Indicate minimum standard anchor shackle size and minimum sling length.
Provide three (3) paper copies of the isometric rigging diagram to the shipyard POC.
11. LIFTING REQUIREMENTS
11.1. Lifting sketches, as a minimum, shall identify the following:
The weight of the load The location of the center of the gravity The minimum crane capacity The minimum capacity/length of slings The minimum capacity of other standard rigging gear The attachment (lifting) points for the load o The attachment point for multiple leg lifts shall be sized such that each attachment point can support one-half of the loads weight at the anticipated lift angle.
o The attachment point for single leg lifts shall be sized such that the attachment point can support the entire load’s weight.
Limitations on allowable orientations for any parts making up the lifting assembly.
For single leg vertical lifts using twisted rope (wire or synthetic), two parallel ropes each capable of supporting the entire load alone shall be required unless a method is used to prevent unlacing of the rope.
A minimum D/d ratio of one shall be required where wire rope slings pass over any object, or in the eyes of the wire slings. A minimum D/d ratio of two shall be required where synthetic rope slings pass over any object, or in the eyes of the synthetic rope slings.
o “D” represents the diameter of the object the sling passes over o “d” represents the diameter of the sling o Table 14-3 of NAVFAC P-307 lists efficiency factors at various D/d ratios
Components in each handling assembly shall be sized based on the worst case of distribution of loads.
Note: When making a two, three or four-point lift, the handling gear shall be sized so that two legs can support the load without exceeding the safe working load (SWL) at the lift angle expected, unless an equalizing method is used.
When nonstandard gear is required (i.e., round stock lifting bars, spreader bars, etc.) written instructions shall be provided that ensure:
o The proper material is being used o The item is certified IAW NAVFAC P-307 o Any special requirements are followed to ensure that engineering assumptions are met (i.e., eccentricity of the bearing points)
A load indicating device (LID) and a pre-determined stopping point will be in the rigging configuration;
applicable to engineering estimated weights and loads are not covered by a technical work document (TWD), unless otherwise approved by NNSY Code-714.
11.2. A detailed lift plan shall be submitted for approval by Norfolk Naval Shipyards Engineers no later than 30 days prior to any deliveries being made. Contact the shipyard representative for the current Code 714 representative.
The lifting diagram must be clearly displayed on each TPF.
H V
A C
U
N I T
TRANSFORMER
H V
I T
TRANSFORMER
H O
F F
M A
N
B
O X
24-ft x 40-ft Type A Double Wide TPF
Floor Plan
40'
24'
9'-6"31'-6"
3'
Enclosure (1)
I T
TRANSFORMER
H V
I T
TRANSFORMER
H O
F F
M A
N
B
O X
24-ft x 40-ft Type B Double Wide TPF
Floor Plan
40'
24'
9'-6"31'-6"
3'
Enclosure (2)
I T
TRANSFORMER
H V
I T
TRANSFORMER
H O
F F
M A
N
B
O X
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
LAN/NMCI
Cabinet
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang
Data/Voice Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang
Data/Voice Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang
Data/Voice Receptacle
Exterior GFCI Duplex
Receptacle
Exterior GFCI Duplex
Receptacle
Internally Mounted
Electrical Power Panel
Internally Mounted
Electrical Power Panel
Light SwitchLight Switch
Fire
Extinguisher
Fire
Extinguisher
Fire Alarm
Pull-Box
Fire Alarm
Pull-Box
Fire Alarm
Pull-Box
Smoke
Detector
Smoke
Detector
8'-6"7'-6"
8'
7'-6"
7'7'7'
10'-6"10'10'
24-ft x 40-ft Type A Double Wide TPF
Electrical and Information Technology Plan
Enclosure (3)
Internally Mounted
Electrical Power
Ponel
Internally Mounted
Electrical Power
Ponel
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
LAN/NMCI Cabinet
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
Light SwitchFire Alarm
Pull-Box
Light Switch Fire Alarm
Pull-Box
Fire Extinguisher
Fire Extinguisher
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
1'
24-ft x 40-ft Type A Double Wide TPF
Interior Elevation Plan
Enclosure (4)
24-ft x 40-ft Type B Double Wide TPF
Electrical and Information Technology Plan
H V
I T
TRANSFORMER
H V
I T
TRANSFORMER
H O
F F
M A
N
B
O X
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
LAN/NMCI
Cabinet
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang
Data/Voice Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang
Data/Voice Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang
Data/Voice Receptacle
Internally Mounted
Electrical Power Panel
Internally Mounted
Electrical Power Panel
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
General Purpose Receptacle
(Quad-Outlet Type)
Double-Gang Data/Voice
Receptacle
Exterior GFCI Duplex
Receptacle
Exterior GFCI Duplex
Receptacle
Fire
Extinguisher
Fire
Extinguisher
Light Switch
Light Switch
Fire Alarm
Pull-Box
Fire Alarm
Pull-Box
Smoke
Detector
Smoke
Detector
8'-6"7'-6"8'7'-6"
10'-6"10'10'
Enclosure (5)
Light Switch Fire Alarm
Pull-Box
Fire Extinguisher
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
LAN/NMCI Cabinet
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
Internally Mounted
Electrical Power
Ponel
Light SwitchFire Alarm
Pull-Box
Fire Extinguisher
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
Internally Mounted
Electrical Power
Ponel
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
Double-Gang Data/Voice Receptacle
General Purpose Receptacle (Quad-Outlet
Type)
1'
24-ft x 40-ft Type B Double Wide TPF
Interior Elevation Plan
Enclosure (6)
I T
TRANSFORMER
H V
I T
TRANSFORMER
H O
F F
M A
N
B
O X
24-ft x 40-ft Type A Double Wide TPF
Ceiling Plan
Enclosure (7)
24-ft x 40-ft Type B Double Wide TPF
Ceiling Plan
H V
I T
TRANSFORMER
H V
I T
TRANSFORMER
H O
F F
M A
N
B
O X
Enclosure (8)
SUGGESTED EXTERIOR MATERIAL LIST
WIEGMANN ENCLOSURE, 12" X 12" X 6", NEMA
3R JUNCTION BOX, GALVANIZED, 16 GAUGE,
WITH NO KNOCKOUTS. GRAINGER ITEM #6JYT1
CAMLOK, PANEL MOUNT BLACK MALE
RECEPTACLE. CROSS HINDS P/N: E1016-1600
CAMLOK, PANEL MOUNT RED MALE
RECEPTACLE. CROSS HINDS P/N: E1016-1602
SQUARE D CIRCUIT BREAKER ENCLOSURE.
VOLTAGE RATING 480/600 V, CURRENT RATING
15-100 AMPS, FOR FAL TYPE BREAKERS. NEMA
3R RATED. GRAINGER ITEM #1H906
SQUARE D FAL TYPE CIRCUIT BREAKER, 600
VOLT, 40 AMP. 2-POLE MOLDED CASE.
GRAINGER ITEM # 5B825
ACME ELECTRIC TRANSFORMER, 480/240V
PRIMARY, 240/120 V SECONDARY. 15 KVA,
GENERAL PURPOSE, SINGLE PHASE. WALL
MOUNT ENCLOSURE, NEMA 3R RATED. 16.94" X
11.59" X 14.12". GRAINGER ITEM # 4WUC3
PC # ITEM / DESCRIPTION
2A
2C
Enclosure (10)
3'3'
4'
FRONT VIEW
BOTTOM VIEW
RIGHT SIDE VIEW
LEFT SIDE VIEW
3-INCH DIAMETER EXTERNAL
ACCESS PENETRATION HOLE
EXTERNAL COMMUNICATIONS PULL BOX
Enclosure (12)
DOUBLE-GANG DATA/VOICE RECEPTACLE
UNIT
FLOOR
LAN DROP #1
UNIT
FLOOR
LAN DROP #2
UNIT
FLOOR
LAN DROP #3
UNIT
FLOOR
LAN DROP #4
UNIT
FLOOR
VOICE DROP #1
UNIT
FLOOR
VOICE DROP #3
UNIT
FLOOR
VOICE DROP #2
UNIT
FLOOR
VOICE DROP #1
DATA
VOICE
BLUE BLUE
GREEN
GREEN
WHITE
WHITE
WHITE
WHITE
Enclosure (13)
24-ft x 40-ft Type A Double Wide TPF
Elevation Plan
TRANSFORMER
HVAC UNIT
HVAC UNIT
HOFFMAN BOX
TRANSFORMER
CIRCUIT BREAKER
CIRCUIT BREAKER
24'
40'
Front View Left View
Right View
Rear View
Enclosure (14)
40'
24'
24-ft x 40-ft Type B Double Wide TPF
Elevation Plan
Front View Left View
Right View
Rear View
TRANSFORMER
HVAC UNIT
HOFFMAN BOX
CIRCUIT BREAKER
Enclosure (15)
Enclosure (18)
Enclosure (18)
ENCLOSURE
Installation material list
Structural- Contractor must provide all material to structurally co-join two section’s of the
TPF. Material must adhere to meet guiding documents…
This is the start of the file's text. The full file is on GovTribe.