Public Safety Complex - Preliminary Drawings_Part7.pdf

PDF 2 MB Posted

Attached to
REQUEST FOR PROPOSAL (RFP) # 49-26-SKL PPEA Project to Construct a Public Safety Facility
Solicitation number
RFP-121372
Issued by
Portsmouth City, Virginia

About this file

This document comprises preliminary architectural and engineering drawings for the Portsmouth Public Safety Complex, a training facility being developed by the City of Portsmouth, Virginia. The drawings are submittal documents dated January 16, 2024, prepared by civil consultants located in Virginia Beach, Virginia, and represent 35 percent design development stage work. The preliminary drawings include detailed plans for the training first floor, encompassing a 10-lane shooting range, rubber bullet trap, weapon cleaning area, storage facilities, decontamination area, mechanical systems, bathrooms, and utility training spaces. The electrical, telecommunications, and security system plans are included as part of the comprehensive preliminary design package.

The electrical design includes a complete power distribution system with a 1000-ampere main distribution panel (MDP) operating at 480Y/277 volts, connected to a utility training transformer and supplemented by a 45-kilovolt-ampere transformer designated as T1 providing 208Y/120-volt service to mechanical rooms. The equipment connection schedule specifies numerous components including a 125-ton condensing unit, dust collector, gas water heater, and multiple air handling units with detailed load ratings, fuse sizes, and disconnect switch specifications. Telecommunications and security infrastructure plans show distributed cabling runs, conduit routing to service handholes, and receptor locations throughout the training facility. All drawings are marked "NOT FOR CONSTRUCTION" and include professional seals and standard architectural notation, indicating these are preliminary design documents subject to further development and refinement before construction documentation is finalized.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E

E

E

E

E

E

E

E

RUBBER

BULLET

TRAP

104T

10 LANE

RANGE

103T

STORAGE

102T

WEAPON

CLEANING

101T

EP101T

D3

MECHANICAL

105T

BATHROOM

109T

PT

STORAGE

110T

DECON

106T

WP

WP

WP

WP WP

WP

UTILITY

TRAINING

CU-1

DC-1

GWH-4

BFP-2

P-9

MECHANICAL

105T

LP1

T1MDP

HL1LCP

REU-1

REU-LIGHTS

RVU-1

RVU-LIGHTS

VIRGINIA BEACH, VIRGINIA 23462

4525 MAIN STREET, SUITE 1400

757·455·5800

1 2 3 4 5 6

A

B

C

D

E

SHEET

B

C

D

E

DESIGN:

DRAWN:

REVIEW:

REVISIONSDESIGNER

A

PROFESSIONAL SEAL

NOT F

OR C

ONSTRUCTIO

N

5032 ROUSE DRIVE, SUITE 200

VIRGINIA BEACH, VA 23462-3764

757.490.9264

CIVIL CONSULTANT

C U s e rs \C a m e ro n .B a n d y \O n e

D ri v e

C la rk

N e x s e n

\D o c u m e n ts \1

P o rt s m o u th C o m p le x R a n g e

E

C a m e ro n .B a n d y .r v t

/1

/2

:4

:2

P

M

TRAINING FIRST FLOOR POWER PLAN

CSA

MSW

SPS

CN 1020535% SUBMITTAL DOCUMENTS

JANUARY 16, 2024

PORTSMOUTH PUBLIC SAFETY COMPLEX

CITY OF PORTSMOUTH

3701 WILLETT DR

PORTSMOUTH, VA 23707

EP101T

GRAPHIC SCALE(S)

# KEY NOTES

GENERAL NOTES

1/8" = 1' - 0" 0 5' 10' 15' 30'

1/4" = 1' - 0" 0 5' 10' 15'1'

SCALE: 1/8" = 1'-0"

TRAINING FIRST FLOOR POWER PLAN

SCALE: 1/4" = 1'-0" EP101T

D3

ENLARGED POWER PLAN

1 CEILING MOUNTED RECEPTACLE FOR CORD REEL. ATTACH TO MOUNTING

PLATE ABOVE BAFFLES.

EQUIPMENT CONNECTION SCHEDULE - SHEET

EQUIPMENT

DESIGNATION DESCRIPTION

ROOM

NUMBER

LOAD

RATING (HP,

KW, ETC) FLA MCA MOCP VOLTS PHASE

DISCONNECT SWITCH

REMARKSRATING (A) FUSE SIZE (A) NEMA TYPE MIN KAIC

BFP-2 BACKFLOW PREVENTER 105T 0 A 0 A 20 A 120 V 1 30A 1 10

CU-1 CONDENSING UNIT 125 TONS 155 A 160 A 175 A 480 V 3 200A 3R 14

DC-1 DUST COLLECTOR UNIT 15 HP(EST) 21 A 27 A 40 A 480 V 3 60A 3R 14

GWH-4 GAS WATER HEATER 0 A 0 A 20 A 120 V 1 30A 1 10

REU-1 AIR HANDLING UNIT 105T - 124 A 132 A 150 A 480 V 3 200A 1 14

RVU-1 AIR HANDLING UNIT 105T - 87 A 132 A 110 A 480 V 3 200A 1 14

LEVEL 1

1003YSE

100Y

XFMR

"UTILITY

TRAINING"

480Y/277V

MDP

1000 A

LCP

480Y/277V

HL1

100 A

XFMR

"T1"

45 KVA

208Y/120V

LP1

150 A

MECHANICAL

105T

BY DE

SPD

1 1

VIRGINIA BEACH, VIRGINIA 23462

4525 MAIN STREET, SUITE 1400

757·455·5800

1 2 3 4 5 6

A

B

C

D

E

SHEET

B

C

D

E

DESIGN:

DRAWN:

REVIEW:

REVISIONSDESIGNER

A

PROFESSIONAL SEAL

NOT F

OR C

ONSTRUCTIO

N

5032 ROUSE DRIVE, SUITE 200

VIRGINIA BEACH, VA 23462-3764

757.490.9264

CIVIL CONSULTANT

C U s e rs \C a m e ro n .B a n d y \O n e

D ri v e

C la rk

N e x s e n

\D o c u m e n ts \1

P o rt s m o u th C o m p le x R a n g e

E

C a m e ro n .B a n d y .r v t

/1

/2

:4

:2

P

M

TRAINING POWER RISER DIAGRAM

CSA

MSW

SPS

CN 1020535% SUBMITTAL DOCUMENTS

JANUARY 16, 2024

PORTSMOUTH PUBLIC SAFETY COMPLEX

CITY OF PORTSMOUTH

3701 WILLETT DR

PORTSMOUTH, VA 23707

EP701T

# KEY NOTES

GENERAL NOTES

DRY-TYPE TRANSFORMER SCHEDULE

XFMR

DESIGNATION

ROOM

NUMBER

TRANSFORMER DATA PRIMARY WIRE SIZE SECONDARY WIRE SIZE TRANSFORMER GEC SIZE

MOUNTING COMMENTS

KVA

RATING K-RATING

TEMPERATURE

RISE (C)

BUSSING

MATERIAL

PRIMARY

VOLTAGE

SECONDARY

VOLTAGE

ENCLOSURE

TYPE PRI CONDUCTORS

PRI

CONDUIT SEC CONDUCTORS

SEC

CONDUIT

GEC

SIZE

GEC CONDUIT

PVC 40

GEC CONDUIT

PVC 80

T1 105T 45 1 150 480 V 208Y/120V 3#4, 1#8G 1 1/4" 3#1/0, 1#1/0N, 1#6G 2" #6 1/2" 1/2"

POWER FEEDER SCHEDULE

FEEDER

MARK FEEDER DESCRIPTION

MIN

CONDUIT

SIZE

MIN

CONDUIT

SIZE OF

EMT, IMC,

RMC

MIN

CONDUIT

SIZE OF

PVC 40,

HDPE, PVC

[3/4"MIN]

MIN

CONDUIT

SIZE OF

EMT, IMC,

RMC

[3/4"MIN]

MIN

CONDUIT

SIZE OF

PVC 40,

HDPE, PVC

80 REMARKS

100Y 3#1, 1#1N, 1#8G 2" 2" 2" 2" 2"

1003YSE 3 SETS, EACH WITH 3-400, 1-400N 0" 3" 3 1/2" 3" 3 1/2"

NOT TO SCALE

A1

POWER RISER DIAGRAMS

1 SEE DRY-TYPE TRANSFORMER SCHEDULE FOR FEEDER SIZE.

2 LIGHTING CONTROL PANEL.

E

E

E

RUBBER

BULLET

TRAP

104T

10 LANE

RANGE

103T

STORAGE

102T

WEAPON

CLEANING

101T

MECHANICAL

105T

BATHROOM

109T

PT

STORAGE

110T

DECON

106T

RT1

VIRGINIA BEACH, VIRGINIA 23462

4525 MAIN STREET, SUITE 1400

757·455·5800

1 2 3 4 5 6

A

B

C

D

E

SHEET

B

C

D

E

DESIGN:

DRAWN:

REVIEW:

REVISIONSDESIGNER

A

PROFESSIONAL SEAL

NOT F

OR C

ONSTRUCTIO

N

5032 ROUSE DRIVE, SUITE 200

VIRGINIA BEACH, VA 23462-3764

757.490.9264

CIVIL CONSULTANT

C U s e rs \C a m e ro n .B a n d y \O n e

D ri v e

C la rk

N e x s e n

\D o c u m e n ts \1

P o rt s m o u th C o m p le x R a n g e

E

C a m e ro n .B a n d y .r v t

/1

/2

:4

:2

P

M

TRAINING FIRST FLOOR TELECOM PLAN

CSA

MSW

SPS

CN 1020535% SUBMITTAL DOCUMENTS

JANUARY 16, 2024

PORTSMOUTH PUBLIC SAFETY COMPLEX

CITY OF PORTSMOUTH

3701 WILLETT DR

PORTSMOUTH, VA 23707

ET101T

GRAPHIC SCALE(S)

# KEY NOTES

GENERAL NOTES

1/8" = 1' - 0" 0 5' 10' 15' 30'

SCALE: 1/8" = 1'-0"

TRAINING FIRST FLOOR TELECOM PLAN

1 4"C TO SERVICE HANDHOLE. SEE ES101 FOR SIZE AND LOCATION.

C R

C R

CR

C R

C R

C R

CR

E

E

E

E

E

RUBBER

BULLET

TRAP

104T

10 LANE

RANGE

103T

STORAGE

102T

WEAPON

CLEANING

101T

MECHANICAL

105T

WP

WP

WP

WP

WP

WP

VIRGINIA BEACH, VIRGINIA 23462

4525 MAIN STREET, SUITE 1400

757·455·5800

1 2 3 4 5 6

A

B

C

D

E

SHEET

B

C

D

E

DESIGN:

DRAWN:

REVIEW:

REVISIONSDESIGNER

A

PROFESSIONAL SEAL

NOT F

OR C

ONSTRUCTIO

N

5032 ROUSE DRIVE, SUITE 200

VIRGINIA BEACH, VA 23462-3764

757.490.9264

CIVIL CONSULTANT

C U s e rs \C a m e ro n .B a n d y \O n e

D ri v e

C la rk

N e x s e n

\D o c u m e n ts \1

P o rt s m o u th C o m p le x R a n g e

E

C a m e ro n .B a n d y .r v t

/1

/2

:4

:2

P

M

TRAINING FIRST FLOOR SECURITY PLAN

CSA

MSW

SPS

CN 1020535% SUBMITTAL DOCUMENTS

JANUARY 16, 2024

PORTSMOUTH PUBLIC SAFETY COMPLEX

CITY OF PORTSMOUTH

3701 WILLETT DR

PORTSMOUTH, VA 23707

EY101T

GRAPHIC SCALE(S)

# KEY NOTES

GENERAL NOTES

1/8" = 1' - 0" 0 5' 10' 15' 30'

SCALE: 1/8" = 1'-0"

TRAINING FIRST FLOOR SECURITY PLAN

10_Electrical_Telecom_35% Design Development
RANGE
EP101T - TRAINING FIRST FLOOR POWER PLAN
EP701T - TRAINING POWER RISER DIAGRAM
ET101T - TRAINING FIRST FLOOR TELECOM PLAN
EY101T - TRAINING FIRST FLOOR SECURITY PLAN

File details come from the government source that posted it. Updated .