Portsmouth Public Safety Complex - 35% Outline Specifications
This document is a 35% submittal of outline specifications for the Portsmouth Public Safety Complex construction project in Portsmouth, Virginia, prepared for CN #10205. The project encompasses a comprehensive public safety facility requiring extensive construction work across multiple building systems and components. The specifications are organized into 33 divisions covering general requirements, facility construction, facility services, and site infrastructure, detailing requirements for structural elements (concrete, masonry, and steel framing), building envelope systems (roofing, waterproofing, and thermal protection), interior finishes (gypsum board, ceramic tiling, acoustical ceilings, and flooring), mechanical and electrical systems (HVAC, plumbing, fire suppression, and electrical distribution), and site work (earthwork, paving, and utilities). The document establishes performance standards, material specifications, installation requirements, and quality control procedures for all construction elements, with emphasis on commissioning requirements, testing, and special inspections to be performed by Owner-engaged agencies throughout the construction process.
The specifications incorporate multiple industry standards and codes including ACI standards for concrete, AISC standards for structural steel, NFPA standards for fire protection, and ASTM standards for materials testing. Notable requirements include fire-rated glazing and assemblies, security-related features such as detention doors and hardware, specialized equipment such as shooting range target and bullet trap systems, and high-performance finishes for aluminum and metal components with 20-year warranties. Quality assurance provisions mandate certification and qualification of key contractors (AISC-Certified fabricators and erectors, PCI-certified precast producers), with delegated design responsibility assigned to the Contractor for aluminum-framed systems, cold-formed steel framing, skylights, and security glazing. The project incorporates sustainability requirements for certified wood products, low-emitting adhesives and sealants, and recycled-content materials throughout. As a 35% submittal document, this represents an intermediate stage in design development, with additional details and specifications anticipated in subsequent submittals prior to final construction documentation.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Portsmouth Public Safety Complex 35% Submittal Documents
Portsmouth, Virginia
Outline Specifications Not for Construction or Regulatory Approval
January 16, 2024
CN #10205
4525 Main Street, Suite 1400 Virginia Beach, Virginia 23462
THIS PAGE IS INTENTIONALLY LEFT BLANK
Portsmouth Public Safety Complex CN #10205
Portsmouth, VA
TABLE OF CONTENTS 1
TABLE OF CONTENTS
Division Section Title
SPECIFICATIONS GROUP
General Requirements Subgroup
DIVISION 01 - GENERAL REQUIREMENTS
019113 GENERAL COMMISSIONING REQUIREMENTS
Facility Construction Subgroup
DIVISION 02 - EXISTING CONDITIONS
024116 STRUCTURE DEMOLITION
DIVISION 03 - CONCRETE
033000 CAST-IN-PLACE CONCRETE
033300 ARCHITECTURAL CONCRETE
034100 PRECAST STRUCTURAL CONCRETE
034500 PRECAST ARCHITECTURAL CONCRETE
DIVISION 04 - MASONRY
042000 UNIT MASONRY
042200 CONCRETE UNIT MASONRY
042613 MASONRY VENEER
DIVISION 05 - METALS
051200 STRUCTURAL STEEL FRAMING
051213 ARCHITECTURALLY EXPOSED STRUCTURAL STEEL FRAMINING
052100 STEEL JOIST FRAMINING
053100 STEEL DECKING
054000 COLD-FORMED METAL FRAMING
055000 METAL FABRICATIONS
055113 METAL PAN STAIRS
055213 PIPE AND TUBE RAILINGS
057300 DECORATIVE METAL RAILINGS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
061000 ROUGH CARPENTRY
061600 SHEATHING
062023 INTERIOR FINISH CARPENTRY
064023 INTERIOR ARCHITECTURAL WOODWORK
064113 WOOD-VENEER-FACED ARCHITECTURAL CABINETS
064116 PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS
064400 ORNAMENTAL WOODWORK
TABLE OF CONTENTS 2
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
071113 BITUMINOUS DAMPPROOFING
071326 SELF-ADHERING SHEET WATERPROOFING
071700 BENTONITE WATERPROOFING
072100 THERMAL INSULATION
072119 FOAMED-IN-PLACE INSULATION
072600 VAPOR RETARDERS
072726 FLUID-APPLIED MEMBRANE AIR BARRIERS
074213.13 FORMED METAL WALL PANELS
075216 STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS MEMBRANE ROOFING
075419 POLYVINYL-CHLORIDE (PVC) ROOFING
076200 SHEET METAL FLASHING AND TRIM
077100 ROOF SPECIALTIES
077129 MANUFACTURED ROOF EXPANSION JOINTS
077200 ROOF ACCESSORIES
078100 APPLIED FIRE PROTECTION
078413 PENETRATION FIRESTOPPING
078443 JOINT FIRESTOPPING
079200 JOINT SEALANTS
079219 ACOUSTICAL JOINT SEALANTS
079513.13 INTERIOR EXPANSION JOINT COVER ASSEMBLIES
079513.16 EXTERIOR EXPANSION JOINT COVER ASSEMBLIES
DIVISION 08 - OPENINGS
081113 HOLLOW METAL DOORS AND FRAMES
083113 ACCESS DOORS AND FRAMES
083113.53 SECURITY ACCESS DOORS AND FRAMES
083313 COILING COUNTER DOORS
083323 OVERHEAD COILING DOORS
084113 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
084413 GLAZED ALUMINUM CURTAIN WALLS
085113 ALUMINUM WINDOWS
086300 METAL-FRAMED SKYLIGHTS
088000 GLAZING
088300 MIRRORS
088813 FIRE-RATED GLAZING
088853 SECURITY GLAZING
089119 FIXED LOUVERS
DIVISION 09 - FINISHES
092216 NON-STRUCTURAL METAL FRAMING
092900 GYPSUM BOARD
093013 CERAMIC TILING
095113 ACOUSTICAL PANEL CEILINGS
095133 ACOUSTICAL METAL PAN CEILINGS
095426 SUSPENDED WOOD CEILINGS
TABLE OF CONTENTS 3
096466 WOOD ATHLETIC FLOORING
096513 RESILIENT BASE AND ACCESSORIES
096516 RESILIENT SHEET FLOORING
096519 RESILIENT TILE FLOORING
096536 STATIC-CONTROL RESILIENT FLOORING
096566 RESILIENT ATHLETIC FLOORING
096623 RESINOUS MATRIX TERRAZZO FLOORING
096723 RESINOUS FLOORING
096813 TILE CARPETING
096900 ACCESS FLOORING
097200 WALL COVERINGS
097723 FABRIC-WRAPPED PANELS
098433 SOUND-ABSORBING WALL UNITS
098436 SOUND-ABSORBING CEILING UNITS
098438 SOUND ABSORPTION PANELS
099113 EXTERIOR PAINTING
099124 INTERIOR PAINTING (MPI STANDARDS)
DIVISION 10 - SPECIALTIES
101100 VISUAL DISPLAY UNITS
102100 EQUIPMENT SCREENS
102213 WIRE MESH PARTITIONS
102600 WALL AND DOOR PROTECTION
102800 TOILET, BATH, AND LAUNDRY ACCESSORIES
102813.63 DETENTION TOILET ACCESSORIES
104300 EMERGENCY AID SPECIALTIES
104413 FIRE PROTECTION CABINETS
104416 FIRE EXTINGUISHERS
105113 METAL LOCKERS
105129 PHENOLIC LOCKERS
107516 GROUND-SET FLAGPOLES
DIVISION 11 - EQUIPMENT
111313 LOADING DOCK BUMPERS
111916 DETENTION GUN LOCKERS
114000 FOODSERVICE EQUIPMENT
116623 GYMNASIUM EQUIPMENT
116723.05 SHOOTING RANGE TARGET EQUIPMENT
116723.15 SHOOTING RANGE BULLET TRAP EQUIPMENT
116723.25 SHOOTING RANGE BULLET PROTECTION EQUIPMENT
119812 DETENTION DOORS AND FRAMES
119814 DETENTION DOOR HARDWARE
DIVISION 12 - FURNISHINGS
122113 HORIZONTAL LOUVER BLINDS
122413 ROLLER WINDOW SHADES
123216 MANUFACTURED PLASTIC-LAMINATE-CLAD CASEWORK
TABLE OF CONTENTS 4
123616 METAL COUNTERTOPS
123623.13 PLASTIC-LAMINATE-CLAD COUNTERTOPS
123661.16 SOLID SURFACING COUNTERTOPS
123661.19 QUARTZ AGGLOMERATE COUNTERTOPS
124816 ENTRANCE FLOOR GRILLES
DIVISION 13 – SPECIAL CONSTRUCTION
133419 METAL BUILDING SYSTEMS
DIVISION 14 - CONVEYING EQUIPMENT
142123.16 MACHINE ROOM-LESS ELECTRIC TRACTION PASSENGER ELEVATORS
Facility Services Subgroup
DIVISION 21 - FIRE SUPPRESSION
210523 GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING
210529 HANGERS AND SUPPORTS FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT
211000 WATER-BASED FIRE-SUPPRESSION SYSTEMS
212200 CLEAN-AGENT FIRE-EXTINGUISHING SYSTEMS
213116 DIESEL-DRIVE, CENTRIFUGAL FIRE PUMPS
DIVISION 22 - PLUMBING
220500 COMMON WORK RESULTS FOR PLUMBING
220523 GENERAL-DUTY VALVES FOR PLUMBING PIPING
220529 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT
220553 IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT
220719 PLUMBING PIPING INSULATION
221113 FACILITY WATER DISTRIBUTION PIPING
221116 DOMESTIC WATER PIPING
221119 DOMESTIC WATER PIPING SPECIALTIES
221123.13 DOMESTIC-WATER PACKAGED BOOSTER PUMPS
221123.21 INLINE, DOMESTIC-WATER PUMPS
221313 FACILITY SANITARY SEWERS
221316 SANITARY WASTE AND VENT PIPING
221319 SANITARY WASTE PIPING SPECIALTIES
221319.13 SANITARY DRAINS
221323 SANITARY WASTE INTERCEPTORS
221414 STORM DRAINAGE PIPING
221423 STORM DRAINAGE PIPING SPECIALTIES
221429 SUMP PUMPS
223300 ELECTRIC, DOMESTIC-WATER HEATERS
223400 FUEL-FIRED, DOMESTIC-WATER HEATERS
224100 RESIDENTIAL PLUMBING FIXTURES
224200 COMMERCIAL PLUMBING FIXTURES
224500 EMERGENCY PLUMBING FIXTURES
224600 SECURITY PLUMBING FIXTURES
224716 PRESSURE WATER COOLERS
TABLE OF CONTENTS 5
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
230500 COMMON WORK RESULTS FOR HVAC
230523 GENERAL-DUTY VALVES FOR HVAC PIPING
230529 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
230548.13 VIBRATION CONTROLS FOR HVAC
230553 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT
230593 TESTING, ADJUSTING, AND BALANCING FOR HVAC
230713 DUCT INSULATION
230719 HVAC PIPING INSULATION
230800 COMMISSIONING OF HVAC
230923 DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC
230923.11 CONTROL VALVES
230923.12 CONTROL DAMPERS
230923.14 FLOW INSTRUMENTS
230923.16 GAS INSTRUMENTS
230923.17 LEVEL INSTRUMENTS
230923.19 MOISTURE INSTRUMENTS
230923.21 MOTION INSTRUMENTS
230923.23 PRESSURE INSTRUMENTS
230923.27 TEMPERATURE INSTRUMENTS
231113 FACILITY FUEL-OIL PIPING
231123 FACILITY NATURAL-GAS PIPING
231213 FACILITY FUEL-OIL PUMPS
231323 FACILITY ABOVEGROUND FUEL-OIL STORAGE TANKS
232113 HYDRONIC PIPING
232116 HYDRONIC PIPING SPECIALTIES
232123 HYDRONIC PUMPS
232300 REFRIGERANT PIPING
232513 WATER TREATMENT FOR CLOSED-LOOP HYDRONIC SYSTEMS
233113 METAL DUCTS
233300 AIR DUCT ACCESSORIES
233346 FLEXIBLE DUCTS
233416 CENTRIFUGAL HVAC FANS
233423 HVAC POWER VENTILATORS
233433.13 COMMERCIAL AIR CURTAINS
233439 HIGH-VOLUME, LOW-SPEED FANS
233533 LISTED KITCHEN VENTILATION SYSTEM EXHAUST DUCTS
233600 AIR TERMINAL UNITS
233713.13 AIR DIFFUSERS
233713.23 REGISTERS AND GRILLES
233713.43 SECURITY REGISTERS AND GRILLES
233813 COMMERCIAL-KITCHEN HOODS
235216 CONDENSING BOILERS
235523.13 LOW-INTENSITY, GAS-FIRED, RADIANT HEATERS
237223.23 PACKAGED, OUTDOOR, HEAT WHEEL ENERGY RECOVERY UNITS
237313.16 INDOOR, SEMI-CUSTOM AIR-HANDLING UNITS
TABLE OF CONTENTS 6
237333.16 INDOOR, INDIRECT, GAS-FIRED HEATING AND VENTILATING UNITS
237416.13 PACKAGED, LARGE-CAPACITY, ROOFTOP AIR-CONDITIONING UNITS
238123.12 LARGE CAPACITY (7 TONS (25 KW) AND LARGER), COMPUTER-ROOM AIR-CONDITIONERS, FLOOR-MOUNTED UNITS
238126 SPLIT-SYSTEM AIR-CONDITIONERS
238129 VARIABLE-REFRIGERANT-FLOW HVAC SYSTEMS
238239.13 CABINET UNIT HEATERS
238239.16 PROPELLER UNIT HEATERS
238239.19 WALL AND CEILING UNIT HEATERS
238413.29 SELF-CONTAINED STEAM HUMIDIFIERS
DIVISION 26 - ELECTRICAL
260010 SUPPLEMENTAL REQUIREMENTS FOR ELECTRICAL
260011 FACILITY PERFORMANCE REQUIREMENTS FOR ELECTRICAL
260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
260523 CONTROL-VOLTAGE ELECTRICAL POWER CABLES
260526 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
260529 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
260533.13 CONDUITS FOR ELECTRICAL SYSTEMS
260533.16 BOXES AND COVERS FOR ELECTRICAL SYSTEMS
260533.23 SURFACE RACEWAYS FOR ELECTRICAL SYSTEMS
260536 CABLE TRAYS FOR ELECTRICAL SYSTEMS
260543 UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS
260544 SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLING
260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS
260573.16 COORDINATION STUDIES
260800 COMMISSIONING OF ELECTRICAL SYSTEMS
260913 ELECTRICAL POWER MONITORING
260923 LIGHTING CONTROL DEVICES
260936 MODULAR DIMMING CONTROLS
260943.23 RELAY-BASED LIGHTING CONTROLS
262213 LOW-VOLTAGE DISTRIBUTION TRANSFORMERS
262313 PARALLELING LOW-VOLTAGE SWITCHGEAR
262413 SWITCHBOARDS
262416 PANELBOARDS
262719 MULTI-OUTLET ASSEMBLIES
262726 WIRING DEVICES
262733 POWER DISTRIBUTION UNITS
262813 FUSES
262816 ENCLOSED SWITCHES AND CIRCUIT BREAKERS
262913.03 MANUAL AND MAGNETIC MOTOR CONTROLLERS
262923 VARIABLE-FREQUENCY MOTOR CONTROLLERS
262933 CONTROLLERS FOR FIRE PUMP DRIVERS
263213.13 DIESEL-ENGINE-DRIVEN GENERATOR SETS
263343 BATTERY CHARGERS
263600 TRANSFER SWITCHES
264113 LIGHTNING PROTECTION FOR STRUCTURES
TABLE OF CONTENTS 7
264313 SURGE PROTECTIVE DEVICES FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS
265000 LIGHTING
265613 LIGHTING POLES AND STANDARDS
DIVISION 27 – ELECTRONIC SAFETY AND SECURITY
271513 COMMUNICATIONS COPPER HORIZONTAL CABLING
DIVISION 28 – ELECTRONIC SAFETY AND SECURITY
284621.11 ADDRESSABLE FIRE-ALARM SYSTEMS
Site and Infrastructure Subgroup
DIVISION 31 - EARTHWORK
311000 SITE CLEARING
312000 EARTH MOVING FOR SITEWORK
312319 DEWATERING
315000 EXCAVATION SUPPORT AND PROTECTION
DIVISION 32 - EXTERIOR IMPROVEMENTS
321216 ASPHALT PAVING
321313 CONCRETE PAVING
321373 CONCRETE PAVING JOINT SEALANTS
321400 UNIT PAVING
321713 PARKING BUMPERS
323113 CHAIN LINK FENCES AND GATES
323300 SITE FURNISHINGS
329113 SOIL PREPARATION
329200 TURF AND GRASSES
329300 PLANTS
DIVISION 33 - UTILITIES
334100 STORM UTILITY DRAINAGE PIPING
END OF TABLE OF CONTENTS
GENERAL COMMISSIONING REQUIREMENTS 019113 - 1
SECTION 019113 - GENERAL COMMISSIONING REQUIREMENTS
1.1 COMMISSIONING TEAM
A. Members Appointed by Contractor(s):
1. Commissioning Coordinator.
2. Project superintendent.
3. Subcontractors, installers, suppliers, and specialists.
B. Members Appointed by Owner:
1. Commissioning Authority.
2. Owner representative(s).
3. Architect.
1.2 REPORT FORMAT AND ORGANIZATION
A. Commissioning Report:
1. Include a table of contents and an index for each test.
2. Include major tabs for each Specification Section.
3. Include minor tabs for each test.
4. Within each minor tab, include the following:
a. Test specification.
b. Pre-startup reports.
c. Approved test procedures.
d. Test data forms, completed and signed.
e. Commissioning issue reports, showing resolution of issues, and documentation related to resolution of issues pertaining to a single test. Arrange data forms, commissioning issue reports (showing resolution of issues), and documentation related to resolution of issues for each test repetition together within the minor tab, in reverse chronological order (most recent on top).
1.3 CONSTRUCTION CHECKLISTS
A. Material Checks:
1. Service connection requirements.
2. Optional features.
3. Delivery receipt check.
4. Installation Checks:
a. Location.
b. Configuration.
c. Compliance with manufacturers' written installation instructions.
GENERAL COMMISSIONING REQUIREMENTS 019113 - 2
d. Attachment to structure.
e. Access clearance to allow for maintenance, service, repair, removal, and replacement.
f. Utility connections.
g. Labeling and identification.
h. Startup checks.
B. Initial operation of equipment.
C. Performance Tests:
1. Static tests.
2. Component performance tests.
3. Equipment and assembly performance tests.
4. System performance tests.
5. Intersystem performance tests.
D. Deferred Construction Checklists:
1. List of deferred construction checklists by number and title.
2. Target schedule for completion of deferred construction checklists.
E. Delayed Construction Checklists:
1. List of delayed construction checklists, by construction checklist number and title.
2. Target schedule for completion of delayed construction checklists.
1.4 GENERAL EXECUTION REQUIREMENTS
A. Coordination of commissioning activities with the construction schedule.
B. Performance of commissioning activities, including tests and documentation of results of actions as construction proceeds.
C. Performance of test demonstrations for Owner's witness.
D. Reporting test data and commissioning issue resolutions.
E. Scheduling personnel to participate in and perform commissioning activities.
F. Operation of the equipment and systems.
G. Preparation of commissioning activity reports.
END OF SECTION 019113
Portsmouth, Virginia
STRUCTURE DEMOLITION 024116 - 1
SECTION 024116 - STRUCTURE DEMOLITION
PART 1 - GENERAL (To be included in next submittal.)
PART 2 - PRODUCTS
2.1 SOIL MATERIALS
A. Satisfactory Soils: Comply with requirements in Section 312000 "Earth Moving for Sitework."
PART 3 - EXECUTION (To be included in next submittal.)
END OF SECTION 024116
CAST-IN-PLACE CONCRETE 033000 - 1
SECTION 033000 - CAST-IN-PLACE CONCRETE
1.1 SUMMARY
A. Concrete standards.
B. Concrete materials.
C. Concrete mixture materials.
1.2 WARRANTY
A. Materials and Workmanship: Manufacturer agrees to furnish replacement sheet vapor retarder/termite barrier material and accessories for sheet vapor retarder/ termite barrier and accessories that do not comply with requirements or that fail to resist penetration by termites within specified warranty period.
1. Warranty Period: 10 years from date of Substantial Completion.
1.3 PRODUCTS
A. Concrete General: ACI 301and ACI 117.
B. Concrete Materials:
1. Portland Cement: ASTM C150, Type I, Type II, Type I/II.
2. Fly Ash: ASTM C618, Class C or F.
3. Slag Cement: ASTM C989/C989M, Grade 100 or 120.
4. Aggregate: Normal weight.
5. Water.
C. Admixtures:
1. Air-Entraining Admixture: ASTM C260/C260M.
2. Water-Reducing Admixture: ASTM C494/C494M, Type A.
3. Retarding Admixture: ASTM C494/C494M, Type B.
4. Water-Reducing and -Retarding Admixture: ASTM C494/C494M, Type D.
5. High-Range, Water-Reducing Admixture: ASTM C494/C494M, Type F.
6. High-Range, Water-Reducing and -Retarding Admixture: ASTM C494/C494M, Type G.
7. Admixtures with special properties, with documentation of claimed performance enhancement, ASTM C494/C494M, Type S.
D. Mixing: Ready mixed.
1.4 CONCRETE MIXTURES
A. Compressive Strength (28 Days):
CAST-IN-PLACE CONCRETE 033000 - 2
1. Footings and Grade Beams: As indicated on drawings.
2. Foundation Walls: As indicated on drawings.
3. Slabs-on-Ground: As indicated on drawings.
4. Concrete Toppings: As indicated on drawings.
5. Building Frame Members: As indicated on drawings.
6. Building Walls: As indicated on drawings.
1.5 INSTALLATION
A. Floor and Slab Finishes:
1. Scratch Finish: Surfaces to receive concrete floor toppings.
2. Float Finish: Surfaces to receive trowel finish and surfaces to be covered with fluid-applied or sheet waterproofing.
3. Trowel Finish: Surfaces exposed to view or to be covered with resilient flooring.
4. Trowel and Fine-Broom Finish: Surfaces to be covered with ceramic or quarry tile to be installed by either thickset or thinset method.
5. Broom Finish: Exterior concrete.
B. Formed Finishes: Surface Finish 2.0.
C. Accessories:
1. Expansion- and Isolation-Joint-Filler Strips: ASTM D1751, asphalt-saturated cellulosic fiber or ASTM D1752, cork or self-expanding cork.
2. Semirigid Joint Filler: Two-component, semirigid, 100 percent solids, in accordance with
ASTM D2240.
3. Bonding Agent: ASTM C1059/C1059M, Type II, nonredispersible, acrylic emulsion or styrene butadiene.
4. Floor Slab Protective Covering: 8 ft. wide cellulose fabric.
1.6 FIELD QUALITY CONTROL
A. Testing: By Owner-engaged agency.
B. Special Inspections: By Owner-engaged special inspector.
END OF SECTION 033000
ARCHITECTURAL CONCRETE 033300 - 1
SECTION 033300 - ARCHITECTURAL CONCRETE
1.1 QUALITY ASSURANCE
A. Field sample panels for each finish, color, and texture variation.
B. Mockups to demonstrate typical joints, surface finish, color, texture, tolerances, and standard of workmanship.
1.2 CONCRETE, GENERAL
A. ACI 301.
B. Design Standards: ACI 318.
1.3 MATERIALS
A. Form-Facing Materials: Nonabsorptive form-facing panels complying with Section 033000
"Cast-in-Place Concrete," and form ties.
B. Bar supports.
C. Concrete Materials:
1. Portland Cement: ASTM C150, Type I, Type II, Type I/II, Type III, white, supplemented with fly ash.
2. Normal Weight Aggregate: Uniformly graded.
3. Water.
4. Admixtures: Air entraining.
5. Color pigment.
D. Curing Materials: Absorptive cover.
1.4 CONCRETE MIXTURES
A. Portland Cement Replacement: Use fly ash, slag cement, and silica fume to reduce portland cement.
B. Compressive Strength (28 Days): 4000 psi, ready mixed.
1.5 INSTALLATION
A. Final Concrete Finish: Smooth formed.
END OF SECTION 033300
PRECAST STRUCTURAL CONCRETE 034100 - 1
SECTION 034100 - PRECAST STRUCTURAL CONCRETE
1.1 QUALITY ASSURANCE
A. Fabricator: PCI-certified plant.
B. Installer Qualifications: PCI Certificate of Compliance.
C. Quality-Control Standard: PCI MNL 116.
D. Sample panels.
E. Mockups.
1.2 PERFORMANCE REQUIREMENTS
A. Design Standards: ACI 318 and PCI MNL 120.
B. Structural Performance: Fabricator to design precast structural concrete units.
1. Dead Loads: As indicated on drawings .
2. Concrete Topping Load: As indicated on drawings.
3. Live Loads: As indicated on drawings.
4. Roof Loads: As indicated on drawings.
5. Snow Loads: As indicated on drawings.
6. Seismic Loads: As indicated on drawings.
7. Wind Loads: As indicated on drawings.
8. Project-Specific Loads: As indicated on drawings.
1.3 CONCRETE, GENERAL
A. ACI 301.
1.4 MATERIALS
A. Form liners.
B. Reinforcing Materials:
1. Reinforcing Bars: Steel.
2. Steel Bar Mats: Steel.
3. Welded Wire Reinforcement: Plain steel.
C. Prestressing tendons.
D. Concrete Materials:
PRECAST STRUCTURAL CONCRETE 034100 - 2
1. Portland Cement: ASTM C150/C150M, Type I or Type III.
2. Supplementary Cementitious Materials: Fly ash Ground granulated blast-furnace slag.
3. Face-Mixture Coarse Aggregates: Uniformly graded.
4. Coloring admixture.
5. Air-entraining admixture.
6. Chemical Admixtures: Water reducing and retarding Water reducing and accelerating
Plasticizing.
E. Steel Connections: Galvanized.
F. Bearing Pads: Frictionless.
G. Grout: Nonmetallic, nonshrink.
H. Insulated Panel Accessories:
1. Insulation: Molded polystyrene.
2. Wythe connectors.
1.5 CONCRETE MIXTURES
A. Portland Cement Replacement:
1. Use fly ash, slag cement, and silica fume to reduce portland cement. Use if required for replacing part of the portland cement, which would otherwise be used in concrete, with other cementitious materials.
2. Use fly ash, pozzolan, ground granulated blast-furnace slag, and silica fume to reduce portland cement by 40 percent.
B. Compressive Strength (28 Days):
1. Normal-Weight Concrete: 5000 psi.
2. Lightweight Concrete: 5000 psi.
1.6 FABRICATION
A. Formed Surfaces: Commercial finishes.
B. Architectural Formed Finishes: Textured surface.
1.7 SOURCE QUALITY CONTROL
A. Testing Agency: Owner engaged to evaluate fabricator's quality-control and testing methods.
1.8 FIELD QUALITY CONTROL
A. Special Inspections: Owner engaged.
PRECAST STRUCTURAL CONCRETE 034100 - 3
B. Testing Agency: Owner engaged.
END OF SECTION 034100
PRECAST ARCHITECTURAL CONCRETE 034500 - 1
SECTION 034500 - PRECAST ARCHITECTURAL CONCRETE
1.1 QUALITY ASSURANCE
A. Installer: PCI-certified erector.
B. Fabricator: PCI-certified plant.
C. Quality Standard: PCI MNL 117.
D. Sample panels for each finish, color, and texture variation.
E. Mockups.
1.2 PERFORMANCE REQUIREMENTS
A. Design Standards: ACI 318 and PCI MNL 120.
B. Structural Performance: Fabricator to design architectural precast concrete units.
1. Wind Loads: As indicated on the drawings.
2. Seismic Loads: As indicated on the drawings .
3. Project-Specific Loads: As indicated on the drawings.
1.3 PRECAST ARCHITECTURAL CONCRETE
A. Provide unit types as indicated on Drawings, including wall panels.
B. Materials:
1. Reinforcing Materials:
a. Reinforcing Bars: Galvanized steel.
b. Steel Bar Mats: Steel.
2. Prestressing tendons.
3. Concrete Materials:
a. Portland Cement: ASTM C150/C150M, Type I or Type III.
b. Supplementary Cementitious Materials: Fly ash.
c. Aggregates: Normal weight.
1) Face-Mixture Coarse Aggregates: Uniformly graded.
d. Coloring admixture.
e. Admixtures: Air entraining.
4. Steel Connections: Stainless.
PRECAST ARCHITECTURAL CONCRETE 034500 - 2
5. Bearing Pads: Elastomeric or High-density plastic.
6. Grout: Nonmetallic, nonshrink.
C. Concrete Mixtures:
1. Compressive Strength (28 Days):
a. Normal-Weight Concrete Face and Backup Mixtures: 5000 psi.
D. Finishes: Abrasive blast.
1.4 SOURCE QUALITY CONTROL
A. Testing Agency: Contractor engaged.
1.5 FIELD QUALITY CONTROL
A. Special Inspections: Contractor engaged.
B. Testing Agency: Contractor engaged.
END OF SECTION 034500
UNIT MASONRY 042000 - 1
SECTION 042000 - UNIT MASONRY
1.1 QUALITY ASSURANCE
A. Sample panels for exposed unit masonry construction.
1.2 PERFORMANCE REQUIREMENTS
A. Net-Area Compressive Strengths of Structural Unit Masonry: As indicated.
B. Determine net-area compressive strength of masonry by unit-strength method.
1.3 MATERIALS
A. Concrete Masonry Units (CMUs):
1. CMUs: Normal weight.
2. Insulated CMUs.
B. Masonry Lintels: Prefabricated or built-in-place CMU lintels.
C. Reinforcement: Uncoated-steel reinforcing bars.
D. Masonry-Joint Reinforcement:
1. Interior Walls: Hot-dip galvanized, carbon steel.
2. Exterior Walls: Hot-dip galvanized, carbon steel.
E. Ties and Anchors: Galvanized steel.
1. Corrugated-metal ties.
2. Individual wire ties.
3. Adjustable anchors for connecting to structural steel framing.
4. Adjustable anchors for connecting to concrete.
5. Partition top anchors.
6. Rigid anchors.
F. Weep/Vent Holes: Vinyl weep hole/vents.
G. Reinforcing bar positioners.
H. Mortar:
1. Portland cement-lime mortar unless otherwise indicated.
2. Portland cement-lime for exterior masonry.
3. Portland cement-lime for reinforced masonry.
UNIT MASONRY 042000 - 2
1.4 INSTALLATION
A. Match existing masonry coursing, bonding, color, and texture.
B. Bond Pattern: Running bond.
C. Parge cavity face of backup wythe.
D. Clean masonry waste recycled as fill material.
1.5 FIELD QUALITY CONTROL
A. Testing Agency: Owner engaged.
B. Inspections: Special inspections in accordance with Level 2 in TMS 402.
C. Testing: One set of tests for each 5000 sq. ft. of wall area.
END OF SECTION 042000
CONCRETE UNIT MASONRY 042200 - 1
SECTION 042200 - CONCRETE UNIT MASONRY
1.1 QUALITY ASSURANCE
A. Sample panels for exposed masonry assemblies.
1.2 PERFORMANCE REQUIREMENTS
A. Net-Area Compressive Strengths of Structural Unit Masonry: As indicated.
B. Determine net-area compressive strength of masonry by unit-strength method.
1.3 MATERIALS
A. Concrete Masonry Units (CMUs):
1. CMUs: Normal weight.
2. Insulated CMUs.
B. Masonry Lintels: Built-in-place CMU lintels.
C. Reinforcing Steel: Uncoated-steel reinforcing bars.
D. Masonry-Joint Reinforcement:
1. Interior Walls: Hot-dip galvanized, carbon steel.
2. Exterior Walls: Hot-dip galvanized, steel.
E. Ties and Anchors: Galvanized steel.
1. Adjustable anchors for connecting to structural steel framing.
2. Adjustable anchors for connecting to concrete.
3. Partition top anchors.
4. Rigid anchors.
F. Reinforcing bar positioners.
G. Mortar:
1. Portland cement-lime mortar unless otherwise indicated.
2. Portland cement-lime for exterior masonry.
3. Portland cement-lime for reinforced masonry.
1.4 FIELD QUALITY CONTROL
A. Testing Agency: Owner engaged.
CONCRETE UNIT MASONRY 042200 - 2
B. Inspections: Special inspections according to Level B in TMS 402/ACI 530/ASCE 5.
C. Testing: One set of tests for each 5000 sq. ft. of wall area.
END OF SECTION 042200
MASONRY VENEER 042613 - 1
SECTION 042613 - MASONRY VENEER
1.1 QUALITY ASSURANCE
A. Mockups of typical wall areas.
1.2 MATERIALS
A. Clay Face Brick:
1. Color and Texture: Match Architect's samples.
B. Ties and Anchors: Stainless steel.
1. Adjustable Masonry-Veneer Anchors: Screw attached.
C. Embedded Flashing:
1. All Flashing: Stainless steel.
2. Partially Exposed Flashing: Stainless steel.
3. Concealed (Flexible) Flashing: Rubberized asphalt.
a. Used with stainless steel drip edge.
4. Drainage Plane Flashing: Hybrid flashing material with drainage mesh applied to stainless steel.
D. Weep/Vent Holes: Vinyl weep hole/vents or open-head joints.
E. Cavity drainage material: Mortar deflector.
F. Mortar:
1. Pigmented mortar for exposed mortar joints.
1.3 INSTALLATION
A. Match existing masonry coursing, bonding, color, and texture.
B. Bond Pattern: One-third running bond.
C. Clean masonry waste recycled as fill material.
1.4 FIELD QUALITY CONTROL
MASONRY VENEER 042613 - 2
B. Inspections: Special inspections in accordance with Level 2 in TMS 402.
END OF SECTION 042613
STRUCTURAL STEEL FRAMING 051200 - 1
SECTION 051200 - STRUCTURAL STEEL FRAMING
1.1 SUMMARY
A. Structural steel as classified by ANSI/AISC 303.
1.2 QUALITY ASSURANCE
A. Fabricator Qualifications: AISC-Certified Plant, Category BU or IAS Fabricator Inspection
Program for Structural Steel.
B. Installer Qualifications: AISC-Certified Erector, Category ACSE.
C. Quality Standards: ANSI/AISC 303, ANSI/AISC 341, and ANSI/AISC 360.
1.3 PERFORMANCE REQUIREMENTS
A. Connection Design: ANSI/AISC 303, Sections 3.1.1 and 3.1.2, Option 3 and 3B.
1.4 MATERIALS
A. Structural-Steel Shapes: W-shapes channels angles Plate and bar Cold-formed hollow structural sections and steel pipe.
B. Steel castings.
C. Steel forgings.
D. Bolts, Nuts, and Washers: High strength.
E. Anchor Rods: Headed rods, nuts, plate washers, and washers.
F. Connectors: Shear stud connectors Threaded rods.
G. Structural slide bearings.
H. Primer: Fabricator's standard, nonasphaltic.
I. Shrinkage-Resistant Grout: Nonmetallic, shrinkage resistant.
J. Prefabricated Building Columns:
1. Fire-Resistance Rating: As indicated.
STRUCTURAL STEEL FRAMING 051200 - 2
1.5 FABRICATION
A. Shop Connections:
1. High-Strength Bolts: Snug tightened.
2. Welded connections.
3. Shear stud connectors.
B. Surface Preparation of Steel: SSPC-SP 2.
C. Surface Preparation of Galvanized Steel: SSPC-SP 16.
1. Galvanize: Exterior structural steel and lintels, shelf angles, located in exterior walls.
1.6 SOURCE QUALITY CONTROL
A. Testing Agency: Owner engaged.
1.7 INSTALLATION
A. Field Connections:
1. High-Strength Bolts: Snug tightened.
2. Welded connections.
3. Shear stud connectors.
1.8 FIELD QUALITY CONTROL
A. Special Inspector: Owner engaged.
B. Testing Agency: Owner engaged.
END OF SECTION 051200
ARCHITECTURALLY EXPOSED STRUCTURAL STEEL FRAMING 051213 - 1
SECTION 051213 - ARCHITECTURALLY EXPOSED STRUCTURAL STEEL FRAMING
1.1 SUMMARY
A. Architecturally exposed structural-steel (AESS) framing.
1. Requirements in Section 051200 "Structural Steel Framing" also apply to AESS.
1.2 DEFINITIONS
A. AESS: ANSI/AISC 303, Section 10.
1.3 QUALITY ASSURANCE
A. Fabricator Qualifications: AISC-Certified Plant, Category STD or IAS accredited, AC 172.
B. Installer Qualifications: AISC-Certified Erector, Category ACSE.
C. Shop-Painting Applicator Qualifications: AISC-Sophisticated Paint Endorsement or SSPC-QP3.
D. Mockups for AESS.
1.4 MATERIALS
A. Steel Primer: Fabricator's standard, nonasphaltic.
B. Etching cleaner for galvanized steel.
1.5 FABRICATION
A. Special care used in handling and fabricating AESS according to ANSI/AISC 303.
1. Category AESS 1.
2. Category AESS 2.
3. Category AESS 3.
4. Category AESS 4.
B. Cleaning Corrosion-Resisting (Weathering) AESS: SSPC-SP 6 (WAB)/NACE WAB-3.
C. Surface Preparation: SSPC-SP 2.
D. Galvanize: Lintels located in exterior walls.
ARCHITECTURALLY EXPOSED STRUCTURAL STEEL FRAMING 051213 - 2
1.6 ERECTION
A. AESS erected according to AISC 303 and AISC 360.
END OF SECTION 051213
STEEL JOIST FRAMING 052100 - 1
SECTION 052100 - STEEL JOIST FRAMING
1.1 PERFORMANCE REQUIREMENTS
A. Engineering design of special joists and connections by Contractor.
1.2 MATERIALS
A. K-series.
B. LH-series steel joists.
1. End Arrangement: Underslung.
2. Top-Chord Arrangement: Parallel.
C. Primer: SSPC-Paint 15.
D. Primer: Comply with Section 099113 "Exterior Painting" and Section 099123 "Interior
Painting."
1.3 INSTALLATION
A. Connections: Field welded.
1.4 FIELD QUALITY CONTROL
END OF SECTION 052100
STEEL DECKING 053100 - 1
SECTION 053100 - STEEL DECKING
1.1 QUALITY ASSURANCE
A. Electrical Raceway Units: UL labeled.
B. FM Approvals' RoofNav Listing: Steel roof deck.
1.2 STEEL DECK
A. Roof Deck: Galvanized- steel sheet.
1. Profile Depth: As indicated on drawings.
B. Composite Floor Deck: Galvanized- steel sheet.
1. Profile Depth: As indicated on drawings.
C. Accessories: Flexible closure strips pour stops column closures, end closures, shear stud connectors.
1.3 INSTALLATION
A. Install deck panels and accessories in accordance with SDI standards.
1. Roof Deck: Mechanically fastened.
2. Floor Deck: Mechanically fastened.
1.4 FIELD QUALITY CONTROL
A. Testing Agency: Owner engaged.
B. Tests and Inspections:
1. Special inspections and qualification of welding special inspectors in accordance with
SDI QA/QC.
2. Shear Stud Connectors: In accordance with AWS D1.1/D1.1M for stud welding.
END OF SECTION 053100
COLD-FORMED METAL FRAMING 054000 - 1
SECTION 054000 - COLD-FORMED METAL FRAMING
1.1 QUALITY ASSURANCE
A. Code-compliance certification of studs and tracks.
1.2 PERFORMANCE REQUIREMENTS
A. Delegated Design: For cold-formed steel framing.
1.3 MATERIALS
A. Steel Sheet: ASTM A1003/A1003M, Structural Grade, with G60, metallic coating.
B. Exterior Non-Load-Bearing Wall Framing: Standard C-shaped, punched steel studs and U-shaped, unpunched track.
1. Minimum Steel Thickness: 0.0428 inch.
2. Vertical deflection clips and Drift clips.
C. Interior Non-Load-Bearing Wall Framing: Standard C-shaped, punched steel studs and U-shaped, unpunched track.
1. Minimum Steel Thickness: 0.0428 inch.
2. Vertical deflection clips and Drift clips.
D. Roof Rafter Framing: Standard C-shaped steel sections.
1. Minimum Steel Thickness: 0.0428 inch.
E. Ceiling Joist Framing: Standard C-shaped, unpunched steel sections.
1. Minimum Steel Thickness: 0.0428 inch.
F. Soffit Framing: Standard C-shaped, unpunched steel sections.
1. Minimum Steel Thickness: 0.0428 inch.
G. Framing Accessories: Supplementary framing Bracing, bridging, and solid blocking Web stiffeners Anchor clips End clips Foundation clips Gusset plates Stud kickers and knee braces
Joist hangers and end closures Hole reinforcing plates and backer plates.
1.4 INSTALLATION
A. Fasten framing by welding or screw fastening.
1. Exterior Non-Load-Bearing Wall Stud Spacing: As required.
COLD-FORMED METAL FRAMING 054000 - 2
2. Interior Non-Load-Bearing Wall Stud Spacing: As required.
3. Joist Spacing: As required.
1.5 FIELD QUALITY CONTROL
A. Testing: By Owner-engaged agency.
END OF SECTION 054000
METAL FABRICATIONS 055000 - 1
SECTION 055000 - METAL FABRICATIONS
1.1 PRODUCTS
A. Materials: Steel plates, shapes, and bars Steel tubing Steel pipe Slotted channel framing.
B. Miscellaneous Framing and Supports: Galvanized where indicated.
1. Steel framing and supports for overhead doors low partitions mechanical and electrical equipment applications where framing and supports are not specified in other Sections.
2. Elevator machine beams, hoist beams, divider beams.
3. Steel shapes for supporting elevator door sills.
C. Prefabricated Building Columns: Fire-resistance rating as indicated.
D. Shelf angles, galvanized at exterior walls.
E. Metal Ladders Including Elevator Pit Ladders: Steel.
1. Galvanized exterior ladders.
F. Alternating Tread Devices: Steel.
1. Galvanized exterior alternating tread devices.
G. Metal Floor Plate: Steel.
H. Elevator pit sump covers.
I. Structural-Steel Door Frames:
1. Galvanized exterior frames.
J. Metal Bollards: Steel shapes, as indicated.
1. Primed using zinc-rich primer.
K. Vehicular barrier cable systems, including design.
L. Downspout guards.
1. Galvanized.
2. Primed using zinc-rich primer.
M. Metal Downspout Boots: Cast aluminum.
N. Loose bearing and leveling plates, galvanized.
O. Loose steel lintels, galvanized at exterior walls.
METAL FABRICATIONS 055000 - 2
P. Anchor bolts, steel pipe sleeves, slotted-channel inserts, and wedge-type inserts cast into concrete or built into unit masonry.
Q. Steel weld plates and angles not specified in other Sections, for casting into concrete.
END OF SECTION 055000
METAL PAN STAIRS 055113 - 1
SECTION 055113 - METAL PAN STAIRS
1.1 SUMMARY
A. Preassembled steel stairs with concrete-filled treads.
B. Steel railings and guards attached to metal stairs.
C. Steel handrails attached to walls adjacent to metal stairs.
1.2 PERFORMANCE REQUIREMENTS
A. Engineering design of steel stairs , railings, and guards by Contractor.
1.3 MATERIALS
A. Abrasive Nosings: Extruded aluminum.
1.4 STEEL-FRAMED STAIRS
A. Stair Standard: NAAMM AMP 510, "Metal Stairs Manual," Monumental stair, Architectural and fire access stairs are Commercial Class.
B. Stringers: Monumental stair steel plates and channels. Fire access stairs are rectangular tubes.
C. Metal Pan Stairs: Uncoated, cold-rolled steel sheet.
D. Steel Tube Railings and Guards:
1. Rails and Posts: 1-5/8-inch-diameter top and bottom rails and 1-1/2-inch-square posts.
2. Picket Infill: 1/2-inch-square pickets spaced to prohibit the passage of a 4-inch diameter sphere.
END OF SECTION 055113
PIPE AND TUBE RAILINGS 055213 - 1
SECTION 055213 - PIPE AND TUBE RAILINGS
1.1 SUMMARY
A. Steel railings.
1.2 PERFORMANCE REQUIREMENTS
A. Engineering design of railings by Contractor.
1.3 FABRICATION
A. Changes in Direction of Members: By bending.
B. Connections: Welded.
C. Toe boards.
1.4 FINISHES
A. Steel and Iron: Primed with universal shop primer.
END OF SECTION 055213
DECORATIVE METAL RAILINGS 057300 - 1
SECTION 057300 - DECORATIVE METAL RAILINGS
1.1 SUMMARY
A. Steel decorative railings.
1.2 QUALITY ASSURANCE
A. Contractor to engineer railings to withstand structural loads.
B. Mockups for each form and finish of railing.
1.3 MATERIALS
A. Steel bar stock.
1.4 FABRICATION
A. Connections: Welded.
B. Changes in Direction of Members: By bending.
C. Infill Panels:
1. Expanded Metal: Steel.
1.5 FINISHES
A. Steel: Ungalvanized, primed with universal shop primer.
END OF SECTION 057300
ROUGH CARPENTRY 061000 - 1
SECTION 061000 - ROUGH CARPENTRY
1.1 SUMMARY
A. Section Includes:
1. Rooftop equipment bases and support curbs.
2. Wood blocking, cants, and nailers.
3. Wood furring.
4. Wood sleepers.
5. Plywood backing panels.
1.2 MATERIALS
A. Maximum Moisture Content:
1. Dimension Lumber: 15 percent for 2-inch nominal thickness or less, 19 percent for more than 2-inch nominal thickness.
B. Preservative Treatment:
1. Preservative Treatment: AWPA U1; Use Category UC2, but Use Category UC3b for exterior construction and Use Category UC4a for items in contact with ground.
a. Preservative Chemicals: Containing no arsenic or chromium. Do not use inorganic boron (SBX) for sill plates.
C. Fire-Retardant-Treatment:
1. Exterior type for exterior locations and where indicated.
2. Interior Type A, High Temperature (HT) for enclosed roof framing, framing in attic spaces, and where indicated.
3. Interior Type A unless otherwise indicated.
4. Application: All rough carpentry. Items indicated and as follows:
a. Concealed blocking.
b. Plywood backing panels.
D. Shear Wall Panels:
E. Miscellaneous Lumber:
1. Dimension Lumber: Construction or No. 2 grade southern pine.
2. Concealed Boards: 15 percent maximum moisture content.
a. Mixed southern pine, No. 2.
F. Plywood Backing Panels: Fire-retardant treated.
ROUGH CARPENTRY 061000 - 2
G. Fasteners: Hot-dip galvanized steel where exposed to weather, in ground contact, in contact with treated wood, or in area of high relative humidity.
H. Miscellaneous Materials:
1. Sill-Sealer Gaskets: Neoprene foam.
2. Flexible flashing.
3. Water-repellent preservative.
1.3 INSTALLATION
A. Furring to Receive Plywood or Hardboard Paneling: 1-by-3-inch nominal-size furring at 24 inches o.c.
B. Furring to Receive Gypsum Board: 1-by-2-inch nominal-size furring at 16 inches o.c.
END OF SECTION 061000
SHEATHING 061600 - 1
SECTION 061600 - SHEATHING
1.1 MATERIALS
A. Wall Sheathing:
1. Glass-Mat Gypsum: Type X, 1/2 inch thick.
B. Parapet Sheathing:
1. Glass-Mat Gypsum: Type X, 1/2 inch thick.
2. Cementitious backer units.
C. Fasteners: Hot-dip galvanized steel where exposed to weather, in ground contact, in contact with treated wood, or in area of high relative humidity.
D. Miscellaneous Materials:
1. Sealant for gypsum sheathing.
2. Sheathing tape.
1.2 INSTALLATION
A. Gypsum Sheathing:
1. Screw to cold-formed metal framing.
END OF SECTION 061600
INTERIOR FINISH CARPENTRY 062023 - 1
SECTION 062023 - INTERIOR FINISH CARPENTRY
1.1 SUSTAINABILITY REQUIREMENTS
1. Certified wood.
2. Low-emitting adhesives.
3. Low-emitting composite wood products.
1.2 SUMMARY
A. Section Includes:
1. Interior trim.
2. Paneling.
3. Shelving
1.3 MATERIALS
A. Preservative Treatment by Pressure Process: All interior lumber and plywood.
B. Interior Standing and Running Trim:
1. Lumber Trim for Opaque Finish (Painted): White pine.
2. Moldings for Opaque Finish (Painted): White pine or primed MDF.
C. Hardwood Veneer Paneling:
1. Face Veneer Species: As indicated on drawings.
2. Thickness: 3/4-inch.
3. Factory finished.
D. Shelving: MDF.
1.4 INSTALLATION
A. Veneer Paneling: Installed according to manufacturer’s instructions.
END OF SECTION 062023
INTERIOR ARCHITECTURAL WOODWORK 064023 - 1
SECTION 064023 - INTERIOR ARCHITECTURAL WOODWORK
1.1 SUMMARY
A. Section Includes:
1. Interior standing and running trim.
2. Interior frames and jambs.
3. Finishing of interior architectural woodwork.
1.2 SUSTAINABILITY REQUIREMENTS
1. Recycled content.
2. Certified wood.
3. Low-emitting composite wood products.
1.3 QUALITY ASSURANCE
A. Manufacturer's Qualifications: AWI's Quality Certification Program licensed participant or equivalent.
1.4 INTERIOR STANDING AND RUNNING TRIM FOR TRANSPARENT FINISH
A. Architectural Woodwork Standards Grade: Premium.
B. Species: Red oak.
C. Cut: Plain sliced/plain sawn.
D. Fire-retardant treated.
1.5 INTERIOR STANDING AND RUNNING TRIM FOR OPAQUE FINISH
A. Architectural Woodwork Standards Grade: Premium.
B. Wood Species: Any closed-grain hardwood.
C. Fire-retardant treated.
1.6 INTERIOR FRAMES AND JAMBS FOR TRANSPARENT FINISH
A. Architectural Woodwork Standards Grade: Premium.
B. Species: Red oak.
INTERIOR ARCHITECTURAL WOODWORK 064023 - 2
C. Cut: Plain sliced/plain sawn.
D. Fire Rating: 20 minutes.
1.7 INTERIOR FRAMES AND JAMBS FOR OPAQUE FINISH
A. Architectural Woodwork Standards Grade: Custom.
B. Wood Species: Any closed-grain hardwood.
C. Fire Rating: 20 minutes.
1.8 PRESERVATIVE-TREATED-WOOD MATERIALS
A. Treat interior architectural woodwork in contact with concrete or masonry.
1.9 FINISHING
A. Transparent Finish: Premium Grade.
1. Shop finished.
B. Opaque Finish: Same grade as item to be finished.
1. Shop primed.
2. Field finished.
1.10 INSTALLATION
A. Lumber and trim for painted applications; primed, including both faces and edges.
END OF SECTION 064023
WOOD-VENEER-FACED ARCHITECTURAL CABINETS 064113 - 1
SECTION 064113 - WOOD-VENEER-FACED ARCHITECTURAL CABINETS
1.1 SUSTAINABILITY REQUIREMENTS
1. Recycled content.
2. Certified wood.
3. Low-emitting composite wood products.
1.2 SUMMARY
A. Section Includes: Wood cabinets for transparent finish.
1.3 QUALITY ASSURANCE
A. Manufacturer's Qualifications: AWI's Quality Certification Program licensed participant or equivalent certification..
1.4 WOOD CABINETS FOR TRANSPARENT FINISH
A. Architectural Woodwork Standards Grade: Premium.
B. Type of Construction: Frameless.
C. Door and Drawer-Front Style: Flush overlay.
D. Wood for Exposed Surfaces: As indicated on Drawings.
1. Species: As indicated on drawings.
2. Cut: As indicated on drawings.
3. Veneer Matching:
a. Veneer Leaves: Book match.
b. Within Panel Faces: Center-balance match within panel face.
c. Cabinet veneers in each space from a single flitch.
E. Semiexposed Surfaces: Same species and cut as for exposed surfaces.
1.5 MATERIALS
A. Fire-Retardant-Treated Materials: Where indicated on Drawings.
B. Cabinet Hardware:
1. Hinges: Frameless, concealed.
2. Pulls: Back mounted.
3. Adjustable shelf supports: metal.
WOOD-VENEER-FACED ARCHITECTURAL CABINETS 064113 - 2
4. Door and Drawer Silencers: BHMA A156.16, L03011.
5. Soft-Close Mechanisms
6. Exposed Hardware Finishes: Satin stainless steel.
1.6 FINISHING
A. Transparent Finish: Premium grade.
1. Shop finished.
END OF SECTION 064113
PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS 064116 - 1
Copyright © 2023 by the American Institute of Architects. Warning: This AIA MasterSpec based document is protected by U.S. Copyright Law and International
Treaties. A valid, current MasterSpec license is required for editing or use of this document.
SECTION 064116 - PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS
1.1 SUSTAINABILITY REQUIREMENTS
1. Recycled content.
2. Certified wood.
3. Low-emitting composite wood products.
1.2 SUMMARY
A. Section Includes:
1. Plastic-laminate-clad architectural cabinets.
2. Cabinet hardware and accessories.
1.3 QUALITY ASSURANCE
A. Manufacturer's Qualifications: AWI's Quality Certification Program licensed participant or equivalent certification.
1.4 PLASTIC-LAMINATE-CLAD CABINETS
A. Architectural Woodwork Standards Grade: Custom.
B. Type of Construction: Frameless.
C. Door and Drawer-Front Style: Flush overlay.
D. Laminate Cladding for Exposed Surfaces:
1. Plastic-Laminate Grade:
a. Horizontal Surfaces and Edges: Grade HGS
b. Vertical Surfaces: Grade VGS
c. Post-formed Surfaces: Grade HGP
E. Materials for Semiexposed Surfaces: High-pressure decorative laminate, ISO 4586-3.
1.5 MATERIALS
A. Fire-Retardant-Treated Materials: Where indicated on Drawings.
B. Cabinet Hardware:
1. Hinges: Frameless, concealed.
2. Pulls: Back mounted.
PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS 064116 - 2
Copyright © 2023 by the American Institute of Architects. Warning: This AIA MasterSpec based document is protected by U.S. Copyright Law and International
3. Adjustable shelf supports: Metal.
4. Locks: Door and drawer.
5. Drawer and Door Silencers: ANSI/BHMA A156.16, L03011.
6. Soft-close Mechanisms.
7. Exposed Hardware Finishes: Satin stainless steel.
END OF SECTION 064116
ORNAMENTAL WOODWORK 064400 - 1
Copyright © 2023 by the American Institute of Architects. Warning: This AIA MasterSpec based document is protected by U.S. Copyright Law and International
SECTION 064400 - ORNAMENTAL WOODWORK
1.1 SUMMARY
A. Section Includes:
1. Interior ornamental woodwork.
2. Finishing of ornamental woodwork.
1.2 SUSTAINABILITY REQUIREMENTS
1. Recycled content.
2. Certified wood.
3. Low-emitting composite wood products.
1.3 QUALITY ASSURANCE
A. Manufacturer's Qualifications: AWI's Quality Certification Program licensed participant or equivalent certification..
1.4 INTERIOR ORNAMENTAL WORK FOR TRANSPARENT FINISH
A. Architectural Woodwork Standards Grade: Premium.
B. Wood Species and Cut: Match species and cut indicated for other types of transparent-finished architectural woodwork located in same area of building unless otherwise indicated.
1. Species: As indicated on drawings.
2. Cut: As indicated on drawings.
1.5 INTERIOR ORNAMENTAL WORK FOR OPAQUE FINISH
A. Architectural Woodwork Standards Grade: Premium.
B. Wood Species: Eastern white pine, sugar pine, or western white pine.
1.6 MATERIALS
A. Wood materials are preservative treated and, where indicated on drawings, fire-retardant treated.
1.7 SHOP FINISHING
A. Same grade as woodwork.
ORNAMENTAL WOODWORK 064400 - 2
Copyright © 2023 by the American Institute of Architects. Warning: This AIA MasterSpec based document is protected by U.S. Copyright Law and International
B. Premium for transparent finish. Premium for opaque finish.
C. Extent: Transparent-finished ornamental woodwork shop finished; opaque-finished ornamental woodwork field finished.
END OF SECTION 064400
BITUMINOUS DAMPPROOFING 071113 - 1
SECTION 071113 - BITUMINOUS DAMPPROOFING
1.1 MATERIALS
A. Cold-applied, emulsified asphalt.
1.2 INSTALLATION
A. Cold-Applied, Emulsified-Asphalt Dampproofing:
1. Concrete Foundations: One fibered brush or spray coat or one trowel coat.
END OF SECTION 071113
SELF-ADHERING SHEET WATERPROOFING 071326 - 1
SECTION 071326 - SELF-ADHERING SHEET WATERPROOFING
1.1 QUALITY ASSURANCE
A. Installer Qualifications: An entity that employs installers and supervisors who are trained and approved by waterproofing manufacturer.
1.2 WARRANTY
A. Manufacturer's Warranty: Three years for materials only.
1.3 MATERIALS
A. Sheet Waterproofing: Modified bituminous sheet waterproofing, fabric reinforced.
B. Auxiliary Materials:
1. Primer: Waterborne.
2. Metal Termination Bars: Aluminum.
C. Molded-Sheet Drainage Panels: Composite subsurface drainage panel with polymeric film and with nonwoven geotextile facing.
D. Insulation Drainage Panels: Extruded-polystyrene board, unfaced, with grooved drainage channels.
1.4 INSTALLATION
A. Install modified bituminous sheets in accordance with waterproofing manufacturer's written installation instructions.
1.5 FIELD QUALITY CONTROL
A. Testing Agency: Owner engaged.
B. Inspections by manufacturer's full-time site representative.
C. Testing: Flood testing of each deck area.
END OF SECTION 071326
BENTONITE WATERPROOFING 071700 - 1
SECTION 071700 - BENTONITE WATERPROOFING
1.1 QUALITY ASSURANCE
A. Mockups.
1.2 PRECONSTRUCTION TESTING
A. Water testing.
1.3 WARRANTY
A. Materials and Workmanship: Five years.
1.4 MATERIALS
A. Contaminant-resistant geotextile/bentonite sheets.
1.5 FIELD QUALITY CONTROL
A. Manufacturer's representative to inspect application.
B. Testing Agency: Contractor engaged to perform flood testing.
END OF SECTION 071700
THERMAL INSULATION 072100 - 1
SECTION 072100 - THERMAL INSULATION
1.1 MATERIALS
A. Insulation:
1. Polyisocyanurate Board: Foil faced, Type I, Class 1 or Class 2.
2. Glass-Fiber Blanket: Foil faced.
B. Auxiliary Insulating Materials:
1. Insulation fasteners.
2. Adhesive.
END OF SECTION 072100
FOAMED-IN-PLACE INSULATION 072119 - 1
SECTION 072119 - FOAMED-IN-PLACE INSULATION
1.1 MATERIALS
A. Closed-Cell Spray Polyurethane Foam: Type II, minimum density of 1.5 lb/cu. ft..
END OF SECTION 072119
VAPOR RETARDERS 072600 - 1
SECTION 072600 - VAPOR RETARDERS
1.1 MATERIALS
A. Polyethylene Vapor Retarders: 6-mil- thick sheet.
END OF SECTION 072600
FLUID-APPLIED MEMBRANE AIR BARRIERS 072726 - 1
SECTION 072726 - FLUID-APPLIED MEMBRANE AIR BARRIERS
1.1 QUALITY ASSURANCE
A. Installer Qualifications: Trained and approved by manufacturer and ABAA certified.
1.2 MOCKUPS
A. Mockups of wall assembly.
1.3 PERFORMANCE REQUIREMENTS
A. Air-Barrier Assembly Air Leakage: Maximum 0.04 cfm/sq. ft. of surface area at 1.57 lbf/sq. ft..
1.4 AIR-BARRIER MEMBRANES
A. High-Build Air Barrier type.
B. Medium-Build Air Barrier: Vapor-permeable type.
C. Low-Build Air Barrier: Vapor-permeable type.
D. Air Permeance: Maximum 0.004 cfm/sq. ft. of surface area at 1.57-lbf/sq. ft..
E. Vapor Permeance:
1. Vapor-Retarding Type: Maximum 0.1 perm.
F. Fire Propagation Characteristics: Passes NFPA 285.
G. UV Resistance: Can be exposed to sunlight for 180 days.
1.5 FIELD QUALITY CONTROL
A. ABAA Quality Assurance Program.
B. Testing and Inspecting: By Contractor-engaged agency for air-leakage locations air-leakage volume and adhesion.
END OF SECTION 072726
FORMED METAL WALL PANELS 074213.13 - 1
SECTION 074213.13 - FORMED METAL WALL PANELS
1.1 QUALITY ASSURANCE
A. Portable roll-forming equipment allowed.
B. Mockups.
1.2 WARRANTY
A. Special Warranty: Two years.
B. Finishes: 20 years.
1.3 PERFORMANCE REQUIREMENTS
A. Structural Performance: ASTM E1592.
1. Wind Loads: As indicated on Drawings.
2. Other Design Loads: As indicated on Drawings.
3. Deflection Limits: 1/180.
B. Air Infiltration: ASTM E283.
C. Water Penetration: ASTM E331.
D. Fire-Resistance Rating: ASTM E119 and UL listed.
1.4 PRODUCTS
A. Concealed-Fastener, Lap-Seam Metal Wall Panels:
1. Profile: Reveal joint.
2. Material: Aluminum sheet.
3. Exterior Finish: Two-coat fluoropolymer.
B. Accessories: Flashing and trim.
1.5 INSTALLATION
A. Watertight Installation: Sealant or tape at joints.
END OF SECTION 074213.13
STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS
MEMBRANE ROOFING
075216 - 1
SECTION 075216 - STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS
MEMBRANE ROOFING
1.1 PREINSTALLATION MEETINGS
A. Preinstallation roofing conference.
1.2 WARRANTY
A. Special Manufacturer's Materials and Workmanship Warranty: 30 years.
B. Roofing System Installer's Warranty: Two years.
1.3 PERFORMANCE REQUIREMENTS
A. Wind-Uplift Resistance:
1. Zone 1 (Roof Area Field) Uplift Pressure: As indicated on drawings.
2. Zone 2 (Roof Area Perimeter) Uplift Pressure: As indicated on drawings .
3. Zone 3 (Roof Area Corner) Uplift Pressure: As indicated on drawings .
B. FM Approvals' RoofNav Listing: Class 1A-120.
C. SPRI's "Directory of Roof Assemblies" Wind-Uplift Load Capacity Listing: As indicated on drawings .
D. Cool-Roof Performance: Solar Reflective Index: 29.
E. Exterior Fire-Test Exposure: Class A.
1.4 MATERIALS
A. Low-emitting adhesives and sealants.
B. Sheathing paper.
C. Base Sheet: Smooth-surfaced reinforced sheet meeting ASTM D6162/D6162M, Type I, Grade S.
D. Cap Sheet: Granule-surfaced reinforced sheet meeting ASTM D6162/D6162M, Type I, Grade G.
E. Base Flashing Sheet:
1. Granule-Surfaced Base Flashing Sheet: Matching cap sheet.
2. Metal-Surfaced Base Flashing Sheet: ASTM D6298, metal-foil-surfaced.
STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS
MEMBRANE ROOFING
075216 - 2
F. Substrate Board: Glass-mat, gypsum board.
G. Vapor Retarder: Self-adhering, rubberized asphalt sheet.
H. Roof Insulation: Polyisocyanurate board.
1. Tapered Insulation: 1/4 inch per 12 inches.
I. Insulation cant strips.
J. Tapered edge strips.
K. Cover Board: Glass-mat gypsum board.
L. Walkways:
1. Pads: Polymer-modified, reconstituted rubber pads.
2. Cap Sheet Strips: Matching cap sheet.
1.5 INSTALLATION
A. Roof Insulation: Adhered.
B. Roofing System Installation Method: Self-adhered:
END OF SECTION 075216
POLYVINYL-CHLORIDE (PVC) ROOFING 075419 - 1
SECTION 075419 - POLYVINYL-CHLORIDE (PVC) ROOFING
1.1 WARRANTY
A. Manufacturer's Materials and Workmanship Warranty: 30 years.
B. Installer's Warranty: Two years.
1.2 PERFORMANCE REQUIREMENTS
A. Wind Uplift Resistance:
1. Zone 1 (Roof Area Field): As indicated on drawings.
2. Zone 2 (Roof Area Perimeter):…