PS_11_Rehabilitation_Project.pdf

PDF 1 MB Posted

Attached to
Pump Station 11 Rehabilitation Project
Solicitation number
2026-50
Issued by
Dillon County, South Carolina

About this file

This is a technical specification document and project drawing set for the Pump Station 11 Rehabilitation Project issued by Dorchester County Water & Sewer in South Carolina, located at 6739 Bent Creek Drive, North Charleston, SC 29420. The project encompasses comprehensive rehabilitation of an existing pump station, including removal and replacement of the access hatch, vent cap with a Wager Model 1800 Vertical Odor Control unit, and three submersible pumps specified as Sulzer units. Additional work includes investigation and potential repair of the wetwell structural integrity using chemical grout if needed, replacement of existing coating with Raven 405 epoxy, installation of a Rosemount 8750W magnetic flow meter, verification of pump bases, and replacement of all discharge piping both inside and outside the wetwell in accordance with Dorchester County pump station standards. All ductile iron pipe (DIP) materials shall be lined with Permashield 431 by Tnemec and painted with Tnemec 110GN Clover or DCWS-approved equivalent. The electrical scope involves removal and relocation of an inadequate HVAC panel within the site due to hydrogen sulfide odor concerns, construction of a concrete slab for a diesel generator installation, and replacement of the electrical panel with a non-air-conditioned panel equipped with soft starters, with all wiring and conduits complying with current electrical codes.

All materials must be manufactured in the United States and conform to Dorchester County specifications and details. The lift station shall remain in bypass throughout the construction period, and the contractor is responsible for proper disposal of all removed materials with coordination of any usable materials to Dorchester County. The project drawings indicate detailed technical specifications including specific valve types (AVK swing check valves, plug valves), control systems (Pulsar Ultra 5 Level Controller with Pulsar DBR Transducer), alarm systems (Federal Signal 350-120-30 panel-mounted alarm horn or DCWS-approved equivalent), and SCADA integration with a remote terminal unit. The document includes comprehensive plan and section views with specifications for concrete work, rebar sizing, geotechnical and structural engineer recommendations, and detailed electrical elevation drawings showing panel mounting, floodlighting, and conduit routing requirements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PS011 REHABILITATION

PROJECT

LOCATION MAP

N

PS011

PS011 Work List

• All materials shall be made in the US and shall conform to Dorchester County specifications and details.

• The lift station shall be in bypass all throughout construction.

• Remove and replace the access hatch.

• Remove and replace the vent cap with “size on size” DIP vent pipe (Wager Model

1800 Vertical Odor Control with Rain Shield)

• Add lighting.

• Investigate the structural integrity of the wetwell. If found deficient, remove and replace.

o For active infiltration, use necessary chemical grout.

o Replace existing coating with Raven 405 epoxy (125 mil).

o Verify pump bases.

• Remove and replace three (3) new submersible pumps with Sulzer (see attached pump curves and drawdown).

• Remove and replace all discharge piping (inside and outside the wetwell), and shall follow current Dorchester County pump station standards.

o All DIP pipe and fittings shall be lined with Permashield 431 by Tnemec.

o All DIP above-ground piping shall be painted with Tnemec 110GN Clover or

DCWS-approved equivalent.

o Add a magnetic flow meter Rosemount 8750W.

• Electrical o Panel has inadequate HVAC. Remove, replace, and relocate within the site due to strong H2S odor. Construct a concrete slab.

o Install a diesel generator on a concrete slab.

o Replace the electrical panel with a non-air-conditioned panel with soft stats.

All wiring and necessary electrical conduits shall comply with all current codes.

• All materials shall be disposed of by the Contractor. Coordinate with Dorchester County regarding any usable materials.

AutoCAD SHX Text

MJ TEE

AutoCAD SHX Text %%uLEGEND

AutoCAD SHX Text

VALVE

AutoCAD SHX Text

RESTRAINED JOINT

AutoCAD SHX Text

MJ FLANGE

AutoCAD SHX Text

CHECK VALVE

AutoCAD SHX Text

COVER W/ SAFETY

AutoCAD SHX Text

VALVE VAULT

AutoCAD SHX Text

WETWELL &

AutoCAD SHX Text

CONCRETE

AutoCAD SHX Text

3/4" CHAMFER

AutoCAD SHX Text

(TYP. ALL EXPOSED

AutoCAD SHX Text

6" DIP VENT PIPE

AutoCAD SHX Text

WETWELL ACCESS

AutoCAD SHX Text

WAGER MODEL 1800

AutoCAD SHX Text

USE SULZER PUMPS ONLY

AutoCAD SHX Text

SUBMERSIBLE PUMP

AutoCAD SHX Text

316 S.S. LIFTING CHAIN

AutoCAD SHX Text

316 S.S. GUIDE RAILS

AutoCAD SHX Text

NSAN

AutoCAD SHX Text

NFM

AutoCAD SHX Text

GROUT

AutoCAD SHX Text

PUMP UNITS OFF

AutoCAD SHX Text

HIGH WATER ALARM

AutoCAD SHX Text

HATCH DRAIN

AutoCAD SHX Text

PRECAST WETWELL

AutoCAD SHX Text

S.S. ANCHOR BOLTS

AutoCAD SHX Text

W/ 2" PROJECTION

AutoCAD SHX Text

(8 REQ'D)

AutoCAD SHX Text

WETWELL

AutoCAD SHX Text

3' MIN.

AutoCAD SHX Text

3' COVER MIN.

AutoCAD SHX Text

12" MIN.

AutoCAD SHX Text

COMPACTED

AutoCAD SHX Text

BACKFILL

AutoCAD SHX Text

#57 STONE

AutoCAD SHX Text

TYPICAL PUMP STATION

AutoCAD SHX Text

DORCHESTER COUNTY WATER & SEWER

AutoCAD SHX Text SCALE: %%u NTS

AutoCAD SHX Text

DRAWN BY: %%U STL

AutoCAD SHX Text

APPROVED BY: %%U ACR

AutoCAD SHX Text

DRAWING:

AutoCAD SHX Text S-23

AutoCAD SHX Text

DATE: %%U NOVEMBER 2025

AutoCAD SHX Text

SECTION W/ FLOW METER

AutoCAD SHX Text NOTES: USE PULSAR ULTRA 5 LEVEL CONTROLLER WITH PULSAR DBR TRANSDUCER. ALL ABOVE GROUND DIP PIPING SHALL BE COATED PER DCWS SPECIFICATIONS. COLOR SHOULD BE TNEMEC 110GN CLOVER OR DCWS APPROVED.

AutoCAD SHX Text

AVK SWING CHECK VALVE

AutoCAD SHX Text

PLUG VALVE

AutoCAD SHX Text

BYPASS CONNECTION

AutoCAD SHX Text

VERTICAL ODOR CONTROL

AutoCAD SHX Text

#4 REBAR 12" O.C.E.W. (TYP)

AutoCAD SHX Text

#4 REBAR 12" O.C.E.W. (TYP)

AutoCAD SHX Text

GRATE (HALLIDAY

AutoCAD SHX Text

MAGNETIC FLOW METER

AutoCAD SHX Text

5 X PIPE DIAMETER

AutoCAD SHX Text

3 X PIPE DIAMETER

AutoCAD SHX Text

(X' DIAMETER)

AutoCAD SHX Text

MIN. 8'

AutoCAD SHX Text

TOP OF

AutoCAD SHX Text

BOTTOM OF

AutoCAD SHX Text

SURFACES)

AutoCAD SHX Text

USE ROSEMOUNT 8750W

AutoCAD SHX Text

MAGNETIC FLOW METER SYSTEM

AutoCAD SHX Text

2" DRAIN LINE 316 S.S. W/ UNION & CAM LOCK

AutoCAD SHX Text

AIR RELEASE VALVE

AutoCAD SHX Text

PRESSURE GAUGE

AutoCAD SHX Text

WITH PLUG VALVE

AutoCAD SHX Text

RADAR LEVEL TRANSDUCER

AutoCAD SHX Text

(SEE MOUNTING PLATE DETAIL)

AutoCAD SHX Text

SEWER VALVE WITH RAIN

AutoCAD SHX Text

SHIELD

AutoCAD SHX Text

PER GEOTECHNICAL

AutoCAD SHX Text

ENGINEER RECOMMENDATIONS

AutoCAD SHX Text

PER STRUCTURAL ENGINEER

AutoCAD SHX Text

RECOMMENDATIONS

AutoCAD SHX Text

PER STRUCTURAL ENGINEER

AutoCAD SHX Text

RECOMMENDATIONS

AutoCAD SHX Text

2" ARI MODEL

AutoCAD SHX Text

(TYP. 2 EA.)

AutoCAD SHX Text

ALUMINUM PRODUCTS)

AutoCAD SHX Text

AND BLIND FLANGE

AutoCAD SHX Text

2" SET ADJUSTABLE

AutoCAD SHX Text

NUT AND THREAD

AutoCAD SHX Text

STAND PIPE

AutoCAD SHX Text

#57 STONE PER

AutoCAD SHX Text

GEOTECHNICAL ENGINEER

RECOMMENDATIONS

NSAN

AutoCAD SHX Text

SWING CHECK VALVE

AutoCAD SHX Text

PLUG VALVE

AutoCAD SHX Text

BYPASS

AutoCAD SHX Text

CONNECTION

AutoCAD SHX Text

PRESSURE

AutoCAD SHX Text

GAUGE

AutoCAD SHX Text

TRUE WYE

AutoCAD SHX Text

2" 316 S.S. DRAIN LINE

AutoCAD SHX Text

AIR RELEASE VALVE

AutoCAD SHX Text

CHECK VALVE

AutoCAD SHX Text

MJ FLANGE

AutoCAD SHX Text

RESTRAINED JOINT

AutoCAD SHX Text

PLUG VALVE

AutoCAD SHX Text %%uLEGEND

AutoCAD SHX Text

MJ TEE

AutoCAD SHX Text

CONCRETE PAD

AutoCAD SHX Text

VENT

AutoCAD SHX Text

2' (MIN.) ALL AROUND

AutoCAD SHX Text PLUG VALVE w/BLIND FLANGE

AutoCAD SHX Text

TYPICAL PUMP STATION

AutoCAD SHX Text

DORCHESTER COUNTY WATER & SEWER

AutoCAD SHX Text SCALE: %%u NTS

AutoCAD SHX Text

DRAWN BY: %%U STL

AutoCAD SHX Text

APPROVED BY: %%U ACR

AutoCAD SHX Text

DRAWING:

AutoCAD SHX Text S-22

AutoCAD SHX Text

DATE: %%U NOVEMBER 2025

AutoCAD SHX Text

W/ FLOW METER TOP PLAN

AutoCAD SHX Text

5 X PIPE DIAMETER

AutoCAD SHX Text

3 X PIPE DIAMETER

AutoCAD SHX Text

MAGNETIC FLOW METER

AutoCAD SHX Text

(VERIFY DIRECTION)

AutoCAD SHX Text

USE ROSEMOUNT 8750W

AutoCAD SHX Text

MAGNETIC FLOW METER SYSTEM

AutoCAD SHX Text NOTE: ALL ABOVE GROUND DIP TO BE COATED WITH TNEMEC 110GN CLOVER OR DCWS APPROVED EQUIVALENT.

AutoCAD SHX Text

NFM

W/ UNION & CAM LOCK

FRONT ELEVATION (LEFT TO RIGHT)

EXTEND TUBING UP A

MIN. 4' ABOVE RACK. ------...

PANEL MOUNTED ALARM HORN

(FEDERAL SIGNAL 350-120-30 OR

DCWS APPROVED EQUIVALENT).

NEMA 4X MARSHALLING BOX WITH

DIVIDER TERMINALS AND LUGS

PER SPECIFICATIONS.---~

FLOW METER DIPLAY (FM)

DORSETT TECHNOLGIES

REMOTE TERMINAL UNIT (RTU).

CONNECT WITH 32#14, 2"C.

FROM PUMP CONTROL PANEL

FOR ALARMS (VERIFY).

SCADA

RTU

OUTDOOR RATED LED FLOOD LIGHT

MOUNT TO FS BOX

ORIENT TOWARDS WETWIELL.

1/2" FS BOX MOUNTED TO

i----TUBING.

-; I f::

.:u.:

ALARM LIGHT: REMOTE ALARM

LIGHT TO BE SET ABOVE STATION

----FENCING.

SUPPORT CONDUIT ALONG

TUBING.

PUMP CONTROL PANEL (TO BE PROVIDED

WITH LEG STAND KIT IF WIDER THAN 36").

SINGLE POLE WEATHERPROOF SWITCH FOR

CONTROL OF FLOODLIGHT

20AMP GFCI RECEPTACLE WITH

IN-USE WEATHERPROOF COVER

_"x1/2" ALUMINUM FLAT BAR CROSS

MEMBERS WELDED TO SQUARE

ALUMINUM STRUCTURAL TUBING.

_•x_"x_• SQUARE ALUMINUM

STRUCTURAL TUBING.

TYPE "EYS" CONDUIT SEAL SEAL WITH

APPROVED SEALING COMPOUND PER

MANUFACTURER'S RECOMMENDATIONS (TYPICAL)

WI-IERE TUBING IS IN CONTACT WITH

CONCRETE, PAINT WITH 2 COATS OF

BITUMASTIC.

12" DIA. CLASS

"C" CONCRETE

CONDUIT FOR CONDUIT FOR TRANSFER SWITCH,

OAT SWITCH CABLES. SIZE AS REQUIRED (MIN. 2").

" CONDUIT FOR RADAR

TRANSDUCER CABLE.

~----<:,ONDUIT FOR PUMP MOTOR POWER

NOTES:

CABLES, SIZE AS REQUIRED (MIN. 2")

~-----TIIDE "ES" SEALING HUB. SEAL WITH APPROVED SEALING

COMPOUND PER MANUFACTURER'S RECOMMENDATIONS (TYPICAL)

,....______.....,. CONDUIT FOR SCADA WIRING

1. ALL ELECTRICAL CONDUIT UNDERGROUND TO BE NMC SCHEDULE 80.

2. ALL ELECTRICAL CONDUIT ABOVE GROUND TO BE RIGID ALUMINUM CONDUIT (RAC)

3. ALL FASTENERS SHALL BE 316 SS.

4. WATER TIGHT ALUMINUM HUBS AT ALL CABINET PENETRATIONS.

5. ALL TUBING IN CONTACT WITH CONCRETE, PAINT WITH 2 COATS OF BITUMASTC.

REAR ELEVATION (LEFT TO RIGHT)

AUTOMATIC TRANSFER SWITCH

(ATS) PER SPECIFICATIONS OR

DOUBLE THROW SAFETY SWITCH

,-----PER SPECIFICATIONS.

**200 AMP GENERATOR

RECEPTACLE. USE APPLETON

AR20034RS OR CROUSE-HINDS

AR2041 S22 WITH MOUNTING

BOX. ONLY If GEN-SET IS NOT

PERMANENT**

**3R SS TRANSFORMER. OliLY.

FOR 480Y SERVICE,**

MAIN BREAKER (MB) IN NEMA 12

STAINLESS STEEL ENCLOSURE,

GASKETED WITH DRIP SHIELD.

METERING AS REQUIRED

BY LOCAL UTILITY.

:~:1 ( .J ~-:

-:1 r:

.:u.:

ONDUIT FOR GENERATOR, 5• THICK REINFORCED

SIZE AS REQUIRED (MIN. 2"). CONCRETE PAD. REQUIRED

ONLY WI-IEN PUMP CONTROL

ONDUIT FOR CONTROL PANEL, PANEL IS FURNISHED WITH

SIZE AS REQUIRED (MIN. 2"). LEG STAND KIT.

DORCHESTER COUNTY WATER & SEWER

TYPICAL PUMP STA110N

ELECTRICAL

DRAWING:

S-17

DATE: FEB 2026 DRAWN BY: STL

SCALE: NTS APPROVED BY: GM

AutoCAD SHX Text

TYPICAL PUMP STATION

AutoCAD SHX Text

DORCHESTER COUNTY WATER & SEWER

AutoCAD SHX Text SCALE: %%u NTS

AutoCAD SHX Text

DRAWN BY: %%U STL

AutoCAD SHX Text

APPROVED BY: %%U GAA

AutoCAD SHX Text

DRAWING:

AutoCAD SHX Text S-17

AutoCAD SHX Text

DATE: %%U FEB 2026

AutoCAD SHX Text

ELECTRICAL

AutoCAD SHX Text NOTES: 1. ALL ELECTRICAL CONDUIT UNDERGROUND TO BE NMC SCHEDULE 80. ALL ELECTRICAL CONDUIT UNDERGROUND TO BE NMC SCHEDULE 80. 2. ALL ELECTRICAL CONDUIT ABOVE GROUND TO BE RIGID ALUMINUM CONDUIT (RAC) ALL ELECTRICAL CONDUIT ABOVE GROUND TO BE RIGID ALUMINUM CONDUIT (RAC) 3. ALL FASTENERS SHALL BE 316 SS. ALL FASTENERS SHALL BE 316 SS. 4. WATER TIGHT ALUMINUM HUBS AT ALL CABINET PENETRATIONS. WATER TIGHT ALUMINUM HUBS AT ALL CABINET PENETRATIONS. 5. ALL TUBING IN CONTACT WITH CONCRETE, PAINT WITH 2 COATS OF BITUMASTC.ALL TUBING IN CONTACT WITH CONCRETE, PAINT WITH 2 COATS OF BITUMASTC.

AutoCAD SHX Text

NEMA 4X MARSHALLING BOX WITH DIVIDER TERMINALS AND LUGS PER SPECIFICATIONS.

AutoCAD SHX Text AUTOMATIC TRANSFER SWITCH (ATS) PER SPECIFICATIONS OR DOUBLE THROW SAFETY SWITCH PER SPECIFICATIONS.

AutoCAD SHX Text 6'-0"

AutoCAD SHX Text

20AMP GFCI RECEPTACLE WITH IN-USE WEATHERPROOF COVER

AutoCAD SHX Text

PUMP CONTROL PANEL (TO BE PROVIDED WITH LEG STAND KIT IF WIDER THAN 36").

AutoCAD SHX Text 2'-6"

AutoCAD SHX Text 6" THICK REINFORCED CONCRETE PAD. REQUIRED ONLY WHEN PUMP CONTROL PANEL IS FURNISHED WITH LEG STAND KIT.

AutoCAD SHX Text

OUTDOOR RATED LED FLOOD LIGHT MOUNT TO FS BOX ORIENT TOWARDS WETWELL.

AutoCAD SHX Text

METERING AS REQUIRED BY LOCAL UTILITY.

AutoCAD SHX Text

CONDUIT FOR PUMP MOTOR POWER CABLES, SIZE AS REQUIRED (MIN. 2")

AutoCAD SHX Text __"x1/2" ALUMINUM FLAT BAR CROSS MEMBERS WELDED TO SQUARE ALUMINUM STRUCTURAL TUBING.

AutoCAD SHX Text

EXTEND TUBING UP A MIN. 4' ABOVE RACK.

AutoCAD SHX Text __"x__"x__" SQUARE ALUMINUM STRUCTURAL TUBING.

AutoCAD SHX Text

1/2" FS BOX MOUNTED TO TUBING.

AutoCAD SHX Text

SUPPORT CONDUIT ALONG TUBING.

AutoCAD SHX Text DORSETT TECHNOLGIES REMOTE TERMINAL UNIT (RTU). CONNECT WITH 32#14, 2"C. FROM PUMP CONTROL PANEL FOR ALARMS (VERIFY).

AutoCAD SHX Text

WHERE TUBING IS IN CONTACT WITH CONCRETE, PAINT WITH 2 COATS OF BITUMASTIC.

AutoCAD SHX Text

CONDUIT AND WIRING, SIZE AS REQUIRED (MIN. 2").

AutoCAD SHX Text MAIN BREAKER (MB) IN NEMA 12 STAINLESS STEEL ENCLOSURE, GASKETED WITH DRIP SHIELD.

AutoCAD SHX Text

ALARM LIGHT: REMOTE ALARM LIGHT TO BE SET ABOVE STATION FENCING.

AutoCAD SHX Text **200 AMP GENERATOR RECEPTACLE. USE APPLETON AR20034RS OR CROUSE-HINDS AR2041 S22 WITH MOUNTING BOX. ONLY IF GEN-SET IS NOT ONLY IF GEN-SET IS NOT PERMANENT.**.**

AutoCAD SHX Text

2" CONDUIT FOR RADAR TRANSDUCER CABLE.

AutoCAD SHX Text

2" CONDUIT FOR FLOAT SWITCH CABLES.

AutoCAD SHX Text

FLOW METER DIPLAY (FM)

AutoCAD SHX Text

END CAP

AutoCAD SHX Text PANEL MOUNTED ALARM HORN (FEDERAL SIGNAL 350-120-30 OR DCWS APPROVED EQUIVALENT).

AutoCAD SHX Text

12" DIA. CLASS "C" CONCRETE

AutoCAD SHX Text TYPE "EYS" CONDUIT SEAL. SEAL WITH APPROVED SEALING COMPOUND PER MANUFACTURER'S RECOMMENDATIONS (TYPICAL)

AutoCAD SHX Text

FRONT ELEVATION (LEFT TO RIGHT)

AutoCAD SHX Text

REAR ELEVATION (LEFT TO RIGHT)

AutoCAD SHX Text

SINGLE POLE WEATHERPROOF SWITCH FOR CONTROL OF FLOODLIGHT

AutoCAD SHX Text TYPE "ES" SEALING HUB. SEAL WITH APPROVED SEALING COMPOUND PER MANUFACTURER'S RECOMMENDATIONS (TYPICAL)

AutoCAD SHX Text

CONDUIT FOR GENERATOR, SIZE AS REQUIRED (MIN. 2").

AutoCAD SHX Text

CONDUIT FOR CONTROL PANEL, SIZE AS REQUIRED (MIN. 2").

AutoCAD SHX Text

CONDUIT FOR TRANSFER SWITCH, SIZE AS REQUIRED (MIN. 2").

AutoCAD SHX Text

**3R SS TRANSFORMER. ONLY ONLY FOR 480V SERVICE.**.**

AutoCAD SHX Text

SCADA RTU

AutoCAD SHX Text

CONTROL PANEL

AutoCAD SHX Text

JUNCTION BOX

AutoCAD SHX Text

ATS

AutoCAD SHX Text

FM

AutoCAD SHX Text

MB

AutoCAD SHX Text

2" CONDUIT FOR SCADA WIRING

MIN. 4'

File details come from the government source that posted it. Updated .