Power Cart Salient Characteristics Sheet - FamCamp.pdf
PDF 230 KB Posted
- Attached to
- Solicitation - Electric Transformer
- Solicitation number
- FA487725QA270
About this file
This document is a Salient Characteristics sheet for a Fam Camp Transformer, specifying detailed technical requirements for a 167 KVA Pad Mount Transformer to be delivered to the 355th CES Squadron. The transformer must have a 13.8 kV Delta Primary, 120/240V Secondary, and be filled with mineral oil, with key features including a primary side Dead Front, 4-Position Load Break Switch, and a 5-Position Tap Changer that is Hot Stick Operable.
Electrical specifications include 3-Phase to Single Phase conversion, 167 KVA capacity at 60 Hz, 120/240 VAC, and a Primary Voltage Class of 15 kV. The transformer is a Loop Feed Type with a secondary voltage of 1.2 kV, designed as a Pad Mounted, Compartmental - Type H unit with dimensions of approximately 55.12" wide x 45.67" deep x 33.07" high. The product comes with a 1-year warranty and is intended for use in a military facility electrical infrastructure.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| CLSExport_355 CES Transformer.pdf | ||
| COMBOSOL-355CES Transformer.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SALIENT CHARACTERISTICS
FOR
Fam CampTransformer
1.0. SCOPE OF WORK:
All proposed products shall meet or exceed the following minimum specifications outlined in this Salient Characteristics. All items shall be delivered to the 355th CES Squadron.
1.1. PRODUCT PERFORMANCE SPECIFICATION:
Item must meet the following minimum specifications:
SPECIFICATIONS
Headers 167 KVA Pad Mount Transformer - 13.8 kV Delta Primary, 120/240V Secondary - Mineral Oil /ONAN
Features: • Primary side Dead Front
• Load Break Switch: 4 - Position Load Break Switch
• Liquid Filled Pad Mounted
• Top Charged: 5-Position Tap Changer, Hot Stick Operable
Warranty: • 1 Year
Electrical requierments:
• 3-Phase to Single Phase
• 167 KVA Capacity
• 60 Hz
• 120/240 VAC
• 13.8 kVA Primary
• Primary Voltage Class 15 kV
• Loop Feed Type Transformer
• Secondary 1.2 kV
Type:
Dimensions:
• Pad Mounted, Compartmental - Type H
• ~ 55.12" - W x 45.67" - D x 33.07" - H
File details come from the government source that posted it. Updated .