Plans.pdf
PDF 15 MB Posted
- Solicitation number
- 0000039624
- Issued by
- Sacramento County, Sacramento City, West Sacramento City, California
About this file
This is an approved architectural and engineering plans document prepared by the California Department of General Services Division of the State Architect (DSA) for the Department of Motor Vehicles (DMV) HQ East Elevator Modernization project located at 2415 1st Avenue, Sacramento, California. The project comprises the modernization of eight elevators—six passenger elevators (Cars #1-6) and two freight elevators (Cars #7-8)—with Car #8 designated as an add alternate not included in the base project scope. The passenger elevators are rated at 4,000 pounds capacity, while the freight elevators are rated at 6,000 pounds capacity. Work includes replacement of existing elevator motors, controllers, and related electrical systems; installation of new LED lighting in elevator cars; modernization of call stations and car operating panels to meet current accessibility standards; and installation of new emergency communication systems. The plans were submitted for DSA plan check on October 28, 2025, with backcheck submittal on November 14, 2025, and received fire and panic approval on February 26, 2026. The project encompasses basement through penthouse levels with machine rooms located on the second floor for Cars #1-6 and on the penthouse level for Car #7, with service and construction scheduled to occur while the facility remains operational.
The plans specify compliance with the 2022 California Building Code, California Electrical Code, and California Fire Code, with detailed accessibility requirements for elevator car dimensions, control locations, signage, and communication systems. Work includes demolition of existing DC machines and replacement with new AC gearless machines, relocation of elevator controllers #3 and #4 to the main machine room, and replacement of existing elevator feeders and conduit where necessary. The project requires coordination with existing building systems, temporary wiring to maintain power during construction phases, and fire stopping of all conduit penetrations in fire-rated walls. Contract 25-318776 for Project 15501 requires a B License and Certificate of Reported Compliance (CRC) for any fleet vehicles subject to California Air Resources Board regulations. Sealed bids were to be received by July 22, 2026, at the DGS Office of Business and Acquisition Services, with project oversight provided by Clint Sierer (916-375-4352) and coordination with Architectural Elevator Consulting LLC.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Project_Manual.pdf | ||
| Bid_Package_Documents.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
12-31-202512-31-2027
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
2/26/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-4219
V3
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
FLS ACS
02-123762
03/12/2026
01-29-2026
ISSUE DATE: JUNE 2, 2026
48" MIN. (FIELD VERIFY)
2022 CBC TABLE 11B-407.4.1
(E) EXCEPTION EXISTING ELEVATOR CAR
" M
IN
. (F
IE
LD
V
ER
IFY
C
BC
TA
BL
E
B-
7.4 .1
(E ) E
XC
EP
TIO
N
EX
IS
TIN
G
EL
EV
AT
OR
C
AR
DIM. (PER ELEVATOR TYPE)
2022 CBC TABLE
11B-407.4.1
" M
IN
C
BC
B-
8.2
.1
" M
IN
C
BC
B-
7.4
.6.
4.1 48
" M
AX
(A T T
.O . B
UT
TO
N)
C
BC
B-
8.2 .1
HOISTWAY SIGNAGE
(2022 CBC 11B-407.2.3)
M
IN
C
BC
B-
7.2
.2.
EMERGENCY
CONTROL
" M
AX
(A T T
.O . B
OT
TO
N)
C
BC
B-
8.2 .1
HALL SIGNALS
(2022 CBC 11B-407.2.1)
CALL BUTTONS
(2022 CBC 11B-407.2.1)
" M
IN
(A T B
.O . B
OT
TO
N)
C
BC
B-
8.2 .1
EMERGENCY
COMMUNICATION
SYSTEM
CAR POSITION INDICATOR
(2022 CBC 11B-407.4.8.1)
CAR CONTROLS
(2022 CBC 11B-407.2.1)
2 1 2 M
IN
2 1 2 M
IN
2 12 MIN
HOISTWAY SIGNAGE
(2022 CBC 11B-407.2.3.1)
" M
AX
(A T B
AS
EL
IN
E
OF
H
IG
HE
ST
RA
IS
ED
C
HA
RA
CT
ER
S)
C
BC
B-
3.4
.1
" M
IN
(A T B
AS
EL
IN
E
OF
LO
W
ES
T B
RA
IL
CE
LL
S)
C
BC
B-
3.4
.1
2"
WHITE ON BLACK
BACKGROUND
1 2" MI
N
LOCATES ABOVE
CAR CONTROL
PANEL OR DOOR
18 SQ FT MIN
NOTES:
1. ELEVATORS SHALL COMPLY WITH 11B-407 AND WITH ASME A17.1: THEY SHALL BE PASSENGER ELEVATORS AS CLASSIFIED BY ASME A17.1. ELEVATOR OPERATION SHALL BE AUTOMATIC.
2. COMBINED PASSENGER AND FREIGHT ELEVATORS: WHEN THE ONLY ELEVATORS PROVIDED FOR USE BY THE PUBLIC AND EMPLOYEES ARE COMBINATION PASSENGER AND FREIGHT ELEVATORS, THEY SHALL COMPLY WITH SECTION 11B-407 AND WITH ASME A17.1.
3. CALL BUTTONS & KEYPADS: SHALL BE LOCATED WITHIN ONE OF THE REACH RANGES SPECIFIED IN 11B-308 MEASURED TO THE CENTERLINE OF THE HIGHEST OPERABLE PART.
4. CALL BUTTONS: SHALL HAVE SQUARE SHOULDERS, BE 3/4 INCH MINIMUM IN THE SMALLEST DIMENSION AND SHALL BE RAISED 1/8" PLUS OR MINUS 1/32 INCH ABOVE THE SURROUNDING SURFACE. THE BUTTONS SHALL BE ACTIVATED BY A MECHANICAL MOTION THAT IS DETECTABLE.
5. CLEAR FLOOR SPACE: COMPLYING WITH 11B-305 SHALL BE PROVIDED AT CALL CONTROLS.
6. THE CALL BUTTON THAT DESIGNATES THE UP DIRECTION SHALL BE LOCATED ABOVE THE CALL BUTTON THAT DESIGNATES THE DOWN DIRECTION.
7. CALL BUTTONS: SHALL HAVE VISIBLE SIGNALS THAT WILL ACTIVATE WHEN EACH CALL IS REGISTERED AND WILL EXTINGUISH WHEN EACH CALL IS ANSWERED. CALL BUTTONS SHALL BE INTERNALLY ILLUMINATED WITH A WHITE LIGHT OVER THE ENTIRE SURFACE OF THE BUTTON.
8. A VISIBLE AND AUDIBLE SIGNAL: SHALL BE PROVIDED AT EACH HOISTWAY ENTRANCE TO INDICATE WHICH CAR IS ANSWERING A CALL AND THE CAR'S DIRECTION OF TRAVEL. WHERE IN-CAR SIGNALS ARE PROVIDED THEY SHALL VISIBLE FROM THE FLOOR AREA ADJACENT TO THE HALL CALL
BUTTONS.
9. VISIBLE SIGNALS: SHALL BE CENTERED AT 72 INCHES MINIMUM ABOVE THE FINISH FLOOR OR GROUND. THE VISIBLE SIGNAL ELEMENTS SHALL BE A MINIMUM 2 1/2 INCHES HIGH BY 2 1/2 INCHES WIDE. SIGNALS SHALL BE VISIBLE FROM THE FLOOR AREA ADJACENT TO THE HALL CALL BUTTON.
10. AUDIBLE SIGNALS: SHALL SOUND ONCE FOR THE UP DIRECTION AND TWICE FOR THE DOWN DIRECTION, OR SHALL HAVE VERBAL ANNUNCIATORS THAT INDICATE THE DIRECTION OF ELEVATOR CALL TRAVEL. AUDIBLE SIGNALS SHALL HAVE A FREQUENCY OF 1500 Hz MAXIMUM. VERBAL
ANNUNCIATORS SHALL HAVE A FREQUENCY OF 300 Hz MINIMUM AND 3,000 Hz MAXIMUM. THE AUDIBLE SIGNAL AND VERBAL ANNUNCIATORS SHALL BE 10 dB MINIMUM ABOVE AMBIENT, BUT SHALL NOT EXCEED 80 dB, MEASURED AT THE HALL CALL BUTTON.
11. FLOOR DESIGNATIONS: SHALL BE PROVIDED ON BOTH JAMBS OF ELEVATOR HOISTWAY ENTRANCES. FLOOR DESIGNATIONS SHALL BE PROVIDED IN BOTH RAISED CHARACTERS AND BRAILLE. RAISED CHARACTERS SHALL BE 2 INCHES HIGH. A RAISED STAR, PLACED TO THE LEFT OF THE
FLOOR DESIGNATION, SHALL BE PROVIDED ON BOTH JAMBS AT THE MAIN ENTRY LEVEL. THE OUTSIDE DIAMETER OF THE STAR SHALL BE 2 INCHES AND ALL POINTS SHALL BE OF EQUAL LENGTH. RAISED CHARACTERS, INCLUDING THE STAR, SHALL BE WHITE ON A BLACK BACKGROUND, BRAILLE COMPLYING WITH SECTION 11B-703.3 SHALL BE PLACED BELOW THE CORRESPONDING RAISED CHARACTERS AND THE STAR. THE BRAILLE TRANSLATION FOR THE STAR SHALL BE "MAIN". APPLIED PLATES ARE ACCEPTABLE IF THEY ARE PERMANENTLY FIXED TO THE JAMB.
12. ELEVATOR DOOR REQUIREMENTS: ELEVATOR DOORS SHALL BE THE HORIZONTAL SLIDING TYPE. CAR GATES SHALL BE PROHIBITED. ELEVATOR AND HOISTWAY DOORS SHALL OPEN AND CLOSE AUTOMATICALLY. EXCEPTION: EXISTING MANUALLY OPERATED HOISTWAY SWING DOORS SHALL BE PERMITTED PROVIDED THEY COMPLY WITH CLEAR DOOR WIDTH AND OPENING FORCE REQUIREMENTS AND THE CAR DOOR CLOSING IS NOT INITIATED UNTIL THE HOISTWAY DOOR IS CLOSED.
13. REOPENING DEVICE: ELEVATOR DOORS SHALL BE PROVIDED WITH A REOPENING DEVICE THAT SHALL STOP AND REOPEN A CAR DOOR AND HOISTWAY DOOR AUTOMATICALLY IF THE DOOR BECOMES OBSTRUCTED BY AN OBJECT OR PERSON. EXCEPTION: IN EXISTING ELEVATORS MANUALLY
OPERATED DOORS SHALL NOT BE REQUIRED TO COMPLY.
14. THE REOPENING DEVICE: SHALL BE ACTIVATED BY SENSING AN OBSTRUCTION PASSING THROUGH THE OPENING AT 5 INCHES NOMINAL AND 29 INCHES NOMINAL ABOVE THE FINISH FLOOR. THE REOPENING DEVICE SHALL NOT REQUIRE PHYSICAL CONTACT TO BE ACTIVATED, ALTHOUGH CONTACT SHALL BE PERMITTED BEFORE THE DOOR REVERSES. THE REOPENING DEVICE SHALL REMAIN EFFECTIVE TO 20 SECONDS MINIMUM.
15. DOOR AND SIGNAL TIMING: THE MINIMUM ACCEPTABLE TIME FROM NOTIFICATION THAT A CAR IS ANSWERING A CALL UNTIL THE DOORS OF THAT CAR START TO CLOSE SHALL BE CALCULATED FROM THE FOLLOWING EQUATION: T=D/(1.5 FT/S) OR T=D/(457 MM/S) = 5 SECONDS MINIMUM WHERE "T" EQUALS THE TOTAL TIME IN SECONDS AND "D" EQUALS THE DISTANCE FROM THE POINT IN THE LOBBY OR CORRIDOR 60 INCHES DIRECTLY IN FRONT OF THE FARTHEST CALL BUTTON CONTROLLING THAT CAR TO THE CENTERLINE OF ITS HOISTWAY DOOR. EXCEPTION: FOR CARS WITH IN-CAR LANTERNS, T SHALL BE PERMITTED TO BEGIN WHEN THE SIGNAL IS VISIBLE FROM THE POINT 60 IN INCHES DIRECTLY IN FRONT OF THE FARTHEST HALL CALL BUTTON AND THE AUDIBLE SIGNAL IS SOUNDED.
16. DOOR DELAY: ELEVATOR DOORS SHALL REMAIN FULLY OPEN IN RESPONSE TO A CAR CALL FOR 5 SECONDS MINIMUM.
17. DOOR WIDTH: SHALL COMPLY WITH TABLE 11B-407.4.1 DIAGRAMS. EXCEPTION: IN EXISTING ELEVATORS, A POWER-OPERATED CAR DOOR WITH A CLEAR WIDTH OF 32 INCHES MINIMUM SHALL BE PERMITTED.
18. CAR DIMENSIONS: INSIDE DIMENSIONS OF ELEVATOR CARS SHALL COMPLY WITH TABLE 11B-407.4.1. EXCEPTION: IN EXISTING BUILDINGS, WHERE EXISTING SHAFT CONFIGURATION PROHIBITS STRICT COMPLIANCE, EXISTING ELEVATOR CAR CONFIGURATIONS THAT PROVIDE A CLEAR FLOOR
AREA OF 18 SQUARE FEET MINIMUM AND ALSO PROVIDE AN INSIDE CLEAR DEPTH OF 54 INCHES MINIMUM AND A CLEAR WIDTH OF 48 INCHES MINIMUM SHALL BE PERMITTED.
19. FLOOR SURFACES: IN ELEVATOR CARS SHALL BE STABLE, FIRM AND SLIP RESISTANT, AND SHALL COMPLY WITH SECTIONS 11B-302 AND 11B-303.
20. PLATFORM TO HOISTWAY CLEARANCE: THE CLEARANCE BETWEEN THE CAR PLATFORM SILL AND THE EDGE OF ANY HOISTWAY LANDING SHALL BE 1 14 INCH MAXIMUM.
21. LEVELING: EACH CAR SHALL BE EQUIPPED WITH A SELF-LEVELING FEATURE THAT WILL AUTOMATICALLY BRING AND MAINTAIN THE CAR AT FLOOR LANDINGS WITHIN A TOLERANCE OF 1/2 INCH UNDER RATED LOADING TO ZERO LOADING CONDITIONS.
22. ILLUMINATION: THE LEVEL OF ILLUMINATION AT THE CAR CONTROLS, PLATFORM, CAR THRESHOLD AND CAR LANDING SILL SHALL BE 5 FOOT-CANDELS (54 LUX) MINIMUM.
23. ELEVATOR CAR CONTROLS: WHERE PROVIDED ELEVATOR CAR CONTROLS SHALL CONFORM WITH OPERABLE PARTS REQUIREMENTS. EXCEPTION: IN EXISTING ELEVATORS, WHERE A NEW CAR OPERATING PANEL IS PROVIDED, EXISTING CAR OPERATING PANELS MAY REMAIN OPERATIONAL
AND SHALL NOT BE REQUIRED TO COMPLY.
24. CONTROL LOCATION: CONTROLS SHALL BE LOCATED WITHIN ONE OF THE REQUIRED REACH RANGES. EXCEPTION: WHERE THE ELEVATOR PANEL SERVES MORE THAN 16 OPENINGS AND A PARALLEL APPROACH TO THE CONTROLS IS PROVIDED, BUTTONS WITH FLOOR DESIGNATIONS SHALL
BE PERMITTED TO BE 54 INCHES MAXIMUM ABOVE THE FINISH FLOOR; OR IN EXISTING ELEVATORS, CAR CONTROL BUTTONS WITH FLOOR DESIGNATIONS SHALL BE PERMITTED TO BE LOCATED 54 INCHES MAXIMUM ABOVE THE FINISH FLOOR WHERE A PARALLEL APPROACH IS PROVIDED
25. BUTTONS: BUTTONS SHALL HAVE SQUARE SHOULDERS, BE 3/4 INCH MINIMUM IN THEIR SMALLEST DIMENSION AND BE RAISED 1/8 INCH PLUS OR MINUS 1/32 INCH ABOVE THE SURROUNDING SURFACE. BUTTONS SHALL BE ARRANGED WITH NUMBERS IN ASCENDING ORDER. WHEN TWO OR
MORE COLUMNS OF BUTTONS ARE PROVIDED THEY SHALL READ FROM LEFT TO RIGHT. CAR CONTROL BUTTONS SHALL BE ILLUMINATED. CAR CONTROL BUTTONS SHALL BE ACTIVATED BY A MECHANICAL MOTION THAT IS DETECTABLE.
26. KEYPADS: CAR CONTROL KEYPADS SHALL BE IN A STANDARD TELEPHONE KEYPAD ARRANGEMENT.
27. EMERGENCY CONTROLS: BUTTONS SHALL HAVE THEIR CENTERLINES 35 INCHES MINIMUM ABOVE THE FINISH FLOOR. EMERGENCY CONTROLS, INCLUDING THE EMERGENCY ALARM, SHALL BE GROUPED AT THE BOTTOM OF THE PANEL.
28. DESIGNATIONS AND INDICATORS OF CAR CONTROLS: CONTROL BUTTONS SHALL BE IDENTIFIED BY RAISED CHARACTERS OR SYMBOLS, WHITE ON A BLACK BACKGROUND, COMPLYING WITH SECTION 11B-703.2 AND BRAILLE COMPLYING WITH SECTION 11B-703.3. RAISED CHARACTERS OR
SYMBOLS AND BRAILLE DESIGNATIONS SHALL BE PLACED IMMEDIATELY TO THE LEFT OF THE CONTROL BUTTON TO WHICH THE DESIGNATIONS APPLY. A MINIMUM CLEAR SPACE OF 38 INCH OR OTHER SUITABLE MEANS OF SEPARATION SHALL BE PROVIDED BETWEEN ROWS OF CONTROL
BUTTONS.
29. SYMBOLS: THE CONTROL BUTTON FOR THE EMERGENCY STOP, ALARM, DOOR OPEN, DOOR CLOSE, MAIN ENTRY FLOOR, AND PHONE, SHALL BE IDENTIFIED WITH RAISED SYMBOLS AND BRAILLE AS SHOWN IN TABLE 11B-407.4.7.1.3.
30. VISIBLE INDICATORS: BUTTONS WITH FLOOR DESIGNATIONS SHALL BE PROVIDED WITH VISIBLE INDICATORS TO SHOW THAT A CALL HAS BEEN REGISTERED. THE VISIBLE INDICATION SHALL EXTINGUISH WHEN THE CAR ARRIVES AT THE DESIGNATED FLOOR.
31. KEYPADS: KEYPADS SHALL BE IDENTIFIED BY VISUAL CHARACTERS COMPLYING WITH SECTION 11B-703.5 AND SHALL BE CENTERED ON THE CORRESPONDING KEYPAD BUTTON. THE NUMBER FIVE KEY SHALL HAVE A SINGLE RAISED DOT. THE DOT SHALL HAVE A BASE DIAMETER OF 0.118 INCH
MINIMUM TO 0.120 INCH MAXIMUM AND A HEIGHT OF 0.025 INCH MINIMUM TO 0.037 INCH MAXIMUM.
32. CAR POSITION INDICATORS: AUDIBLE AND VISIBLE CAR POSITION INDICATORS SHALL BE PROVIDED IN ELEVATOR CARS. CHARACTERS SHALL BE 1/2 INCH HIGH MINIMUM. INDICATORS SHALL BE LOCATED ABOVE THE CAR CONTROL PANEL OR ABOVE THE DOOR. AS THE CAR PASSES A FLOOR
AND WHEN A CAR STOPS AT A FLOOR SERVED BY THE ELEVATOR, THE CORRESPONDING CHARACTER SHALL ILLUMINATE.
33. AUDIBLE INDICATORS: THE SIGNAL SHALL BE AN AUTOMATIC VERBAL ANNUNCIATOR WHICH THE ANNOUNCES THE FLOOR AT WHICH THE CAR IS ABOUT TO STOP. THE VERBAL ANNUNCIATOR SHALL BE 10 dB MINIMUM ABOVE AMBIENT, BUT SHALL NOT EXCEED 80 dB, MEASURED AT THE
ANNUNCIATOR. THE VERBAL ANNUNCIATOR SHALL HAVE A FREQUENCY OF 300 Hz MINIMUM TO 3,000 Hz MAXIMUM. EXCEPTION: FOR ELEVATORS THAT HAVE A RATED SPEED OF 200 FEET PER MINUTE OR LESS, A NON-VERBAL AUDIBLE SIGNAL WITH A FREQUENCY OF 1500 Hz MAXIMUM WHICH SOUNDS AS THE CAR PASSES OR IS ABOUT TO STOP AT A FLOOR SERVED BY THE ELEVATOR SHALL BE PERMITTED.
34. EMERGENCY COMMUNICATIONS: RAISED SYMBOLS OR CHARACTERS, WHITE ON A BLACK BACKGROUND, AND BRAILLE SHALL BE PROVIDED ADJACENT TO THE DEVICE AND SHALL COMPLY WITH SECTIONS 11B-703.2 AND 11B-703.3. EMERGENCY TWO-WAY COMMUNICATION SYSTEMS BETWEEN
THE ELEVATOR CAR AND A POINT OUTSIDE THE HOISTWAY SHALL COMPLY WITH ASME A17.1.
35. SUPPORT RAIL: SUPPORT RAILS SHALL BE PROVIDED ON AT LEAST ONE WALL OF THE CAR. CLEARANCE BETWEEN SUPPORT RAILS AND ADJACENT SURFACES SHALL BE 1-1/2 INCHES MINIMUM. TOP OF SUPPORT RAILS SHALL BE 31 INCHES MINIMUM TO 33 INCHES MAXIMUM ABOVE THE FLOOR OF THE CAR. THE ENDS OF THE SUPPORT RAIL SHALL BE 6 INCHES MAXIMUM FROM ADJACENT WALLS. SUPPORT RAILS SHALL BE SMOOTH AND ANY SURFACE ADJACENT TO THEM SHALL BE FREE OF SHARP OR ABRASIVE ELEMENTS. ALLOWABLE STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS USED WHEN A VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS IS APPLIED AT ANY POINT ON THE SUPPORT RAIL, FASTENER, MOUNTING DEVICE, OR SUPPORTING STRUCTURE.
FLOOR DESIGNATIONS ON JAMBS OF
ELEVATOR HOISTWAY ENTRANCES
(2022 CBC FIGURE 11B-407.2.3.1)
2415 1ST AVE.
SACRAMENTO, CA 95818
State of California
Department of General Services Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105 West Sacramento, California 95605
Clint Sierer 916 375-4352 Phone Clinton.Sierer@dgs.ca.gov
DMV HQ EAST ELEVATOR
MODERNIZATION
02/19/25 95% PLAN CHECK SUBMITTAL-
05/06/25 95% REFINED SCOPE CHECK SET-
05/29/25 95% REFINED SCOPE REVIEW-
DEPARTMENT OF MOTOR VEHICLES
DMV
Project Number: 000000000015501
08/22/25 FINAL 100% REVIEW-
10/28/25 DSA PLAN CHECK SUBMITTAL-
11/14/25 DSA BACKCHECK SUBMITTAL-
G2-0
NONE
ACCESSIBILITY DETAILS
SCALE:
N/A
12-31-2025
11/12/2025
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
2/26/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-4219
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
FLS ACS
02-123762
03/12/2026
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
A
B
C
D
E
F
G
H
J
A
B
C
D
E
F
G
H
J
CAR #1 CAR #2 CAR #3 CAR #4
CAR #6 CAR #5
CAR #8
CAR #7
FREIGHT
ONLY
CAR #1 CAR #2 CAR #3 CAR #4
TYP
TYP
CAR #6 CAR #5
TYP
TYP TYP TYP
CAR #8
CAR #7
FREIGHT ONLY
CAR #8
CAR #7
FREIGHT ONLY
CAR #1 CAR #2 CAR #3 CAR #4
TYP
TYP
CAR #6 CAR #5
TYP
TYP TYP TYP
2415 1ST AVE.
SACRAMENTO, CA 95818
State of California
Department of General Services Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105 West Sacramento, California 95605
Clint Sierer 916 375-4352 Phone Clinton.Sierer@dgs.ca.gov
DMV HQ EAST ELEVATOR
MODERNIZATION
ELEVATION KEY PLAN
DMV HQ EAST
BASEMENT
1ST FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
6TH FLOOR
PENTHOUSE
02/19/25 95% PLAN CHECK SUBMITTAL-
05/06/25 95% REFINED SCOPE CHECK SET-
05/29/25 95% REFINED SCOPE REVIEW-
DEPARTMENT OF MOTOR VEHICLES
DMV
Project Number: 000000000015501
08/22/25 FINAL 100% REVIEW-
10/28/25 DSA PLAN CHECK SUBMITTAL-
11/14/25 DSA BACKCHECK SUBMITTAL-
A1-0
NONE
FLOOR PLAN - BASEMENT
LEVEL
SCALE:
N
SCALE:
A1-0 1/8"='-0"
C
B
C
G
GENERAL NOTESKEYNOTES
SCALE: 1/8"=1'-0"A1-0
G
SCALE: 1/8"=1'-0"A1-0
SCALE: 1/8"=1'-0"A1-0
SCALE: 1/8"=1'-0"A1-0
SCALE:
A1-0 1/8"='-0"
C
B
C
ELEVATOR # 8 IS NOT IN THE BASE PROJECT SCOPE.
ELEVATOR # 8 IS AN ADD ALTERNATE.
ELEVATOR # 8 IS NOT IN THE BASE PROJECT SCOPE.
ELEVATOR # 8 IS AN ADD ALTERNATE.
AS NOTED
LEGENDDEMOLITION KEYNOTES
12-31-2025
11/12/2025
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
2/26/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-4219
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
FLS ACS
02-123762
12 6
J
H
G
F
E
D
C
B
A
151413121110 9 8 7 6 5 4 3 2 1
1514131110 9 8 7 5 4 3 2 1
J
H
G
F
E
D
C
B
A
CAR #1 CAR #2 CAR #3 CAR #4
CAR #6 CAR #5
CAR #8
CAR #7
FREIGHT
ONLY
FIRE
CONTROL
TYP
CAR #1 CAR #2 CAR #3 CAR #4
FIRE
CONTROL
TYP
TYP
TYP
CAR #6 CAR #5
TYP
TYP TYP TYP
CAR #8
CAR #7
FREIGHT ONLY
CAR #1 CAR #2 CAR #3 CAR #4
FIRE
CONTROL
TYP
TYP
TYP
CAR #8
CAR #7
FREIGHT ONLY
CAR #6 CAR #5
TYP
TYP TYP TYP
2415 1ST AVE.
SACRAMENTO, CA 95818
State of California
Department of General Services Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105 West Sacramento, California 95605
Clint Sierer 916 375-4352 Phone Clinton.Sierer@dgs.ca.gov
DMV HQ EAST ELEVATOR
MODERNIZATION
ELEVATION KEY PLAN
DMV HQ EAST
BASEMENT
1ST FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
6TH FLOOR
PENTHOUSE
02/19/25 95% PLAN CHECK SUBMITTAL-
05/06/25 95% REFINED SCOPE CHECK SET-
05/29/25 95% REFINED SCOPE REVIEW-
DEPARTMENT OF MOTOR VEHICLES
DMV
Project Number: 000000000015501
08/22/25 FINAL 100% REVIEW-
10/28/25 DSA PLAN CHECK SUBMITTAL-
11/14/25 DSA BACKCHECK SUBMITTAL-
A2-0
NONE
FLOOR PLANS - LEVEL 1
GENERAL NOTES
SCALE:
N
A
B
C
G
H
KEYNOTES
SCALE:
A2-0 1/8"='-0"
SCALE: 1/8"=1'-0"A2-0
SCALE: 1/8"=1'-0"A2-0
SCALE: 1/8"=1'-0"A2-0
SCALE: 1/8"=1'-0"A2-0
SCALE:
A2-0 1/8"='-0"
A
B
87 10
C
G
H
ELEVATOR # 8 IS NOT IN THE BASE PROJECT SCOPE.
ELEVATOR # 8 IS AN ADD ALTERNATE.
ELEVATOR # 8 IS NOT IN THE BASE PROJECT SCOPE.
ELEVATOR # 8 IS AN ADD ALTERNATE.
AS NOTED
LEGENDDEMOLITION KEYNOTES
12-31-2025
11/12/2025
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
2/26/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-4219
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
FLS ACS
02-123762
CAR #7
FREIGHT
ONLY
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
A
B
C
D
E
F
G
H
J
A
B
C
D
E
F
G
H
J
CAR #1 CAR #2 CAR #3 CAR #4
CAR #6 CAR #5
CAR #8
TYP
CAR #1 CAR #2 CAR #3 CAR #4
TYP
TYP
TYP
CAR #6 CAR #5
TYP
TYP TYP TYP
CAR #7
FREIGHT ONLY
CAR #8
CAR #1 CAR #2 CAR #3 CAR #4
TYP
TYP
TYP
CAR #7
FREIGHT ONLY
CAR #8
CAR #6 CAR #5
TYP
TYP TYP TYP
2415 1ST AVE.
SACRAMENTO, CA 95818
State of California
Department of General Services Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105 West Sacramento, California 95605
Clint Sierer 916 375-4352 Phone Clinton.Sierer@dgs.ca.gov
DMV HQ EAST ELEVATOR
MODERNIZATION
ELEVATION KEY PLAN
DMV HQ EAST
BASEMENT
1ST FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
6TH FLOOR
PENTHOUSE
02/19/25 95% PLAN CHECK SUBMITTAL-
05/06/25 95% REFINED SCOPE CHECK SET-
05/29/25 95% REFINED SCOPE REVIEW-
DEPARTMENT OF MOTOR VEHICLES
DMV
Project Number: 000000000015501
08/22/25 FINAL 100% REVIEW-
10/28/25 DSA PLAN CHECK SUBMITTAL-
11/14/25 DSA BACKCHECK SUBMITTAL-
A3-0
NONE
FLOOR PLANS - LEVEL 2
GENERAL NOTES
SCALE:
N
A
B
C
G
H
KEYNOTES
SCALE:
A3-0 1/8"='-0"
SCALE: 1/8"=1'-0"A3-0
SCALE: 1/8"=1'-0"A3-0
SCALE: 1/8"=1'-0"A3-0
SCALE: 1/8"=1'-0"A3-0
SCALE:
A3-0 1/8"='-0"
A
B
87 10
C
G
H
ELEVATOR # 8 IS NOT IN THE BASE PROJECT SCOPE.
ELEVATOR # 8 IS AN ADD ALTERNATE.
ELEVATOR # 8 IS NOT IN THE BASE PROJECT SCOPE.
ELEVATOR # 8 IS AN ADD ALTERNATE.
AS NOTED
LEGENDDEMOLITION KEYNOTES
12-31-2025
11/12/2025
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
2/26/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-4219
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
FLS ACS
02-123762
A
B
C
D
E
F
G
H
J
A
B
C
D
E
F
G
H
J
CAR #7
FREIGHT
ONLY
CAR #1 CAR #2 CAR #3 CAR #4
CAR #6 CAR #5
TYP
CAR #1 CAR #2 CAR #3 CAR #4
TYP
TYP
TYP
CAR #6 CAR #5
TYP
TYP TYP TYP
CAR #7
FREIGHT ONLY
CAR #1 CAR #2 CAR #3 CAR #4
TYP
TYP
TYP
CAR #7
FREIGHT ONLY
CAR #6 CAR #5
TYP
TYP TYP TYP
2415 1ST AVE.
SACRAMENTO, CA 95818
State of California
Department of General Services Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105 West Sacramento, California 95605
Clint Sierer 916 375-4352 Phone Clinton.Sierer@dgs.ca.gov
DMV HQ EAST ELEVATOR
MODERNIZATION
ELEVATION KEY PLAN
DMV HQ EAST
BASEMENT
1ST FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
6TH FLOOR
PENTHOUSE
02/19/25 95% PLAN CHECK SUBMITTAL-
05/06/25 95% REFINED SCOPE CHECK SET-
05/29/25 95% REFINED SCOPE REVIEW-
DEPARTMENT OF MOTOR VEHICLES
DMV
Project Number: 000000000015501
08/22/25 FINAL 100% REVIEW-
10/28/25 DSA PLAN CHECK SUBMITTAL-
11/14/25 DSA BACKCHECK SUBMITTAL-
A4-0
NONE
FLOOR PLANS - TYPICAL
LEVELS 3-6
GENERAL NOTESLEGEND
SCALE:
N
A
B
C
G
H
KEYNOTES DEMOLITION KEYNOTES
SCALE:
A4-0 1/8"='-0"
SCALE: 1/8"=1'-0"A4-0
SCALE: 1/8"=1'-0"A4-0
SCALE: 1/8"=1'-0"A4-0
SCALE: 1/8"=1'-0"A4-0
SCALE:
A4-0 1/8"='-0"
A
B
87 10
C
G
H
AS NOTED
12-31-2025
11/12/2025
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
2/26/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-4219
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
FLS ACS
02-123762
FREIGHT
ONLY
A
B
C
D
E
F
G
H
J
2 3 4 5 6 7 8 9 10 11 12 13 14
2 3 4 5 6 7 8 9 10 11 12 13 14
A
B
C
D
E
F
G
H
J
CAR #1 CAR #2 CAR #3 CAR #4
CAR #6 CAR #5
CAR #1 CAR #2 CAR #3 CAR #4
TYP
TYP
CAR #6 CAR #5
TYP TYP TYP
CAR #7
FREIGHT ONLY
CAR #1 CAR #2 CAR #3 CAR #4
TYP
TYP
CAR #6 CAR #5
TYP TYP TYP
CAR #7
FREIGHT ONLY
2415 1ST AVE.
SACRAMENTO, CA 95818
State of California
Department of General Services Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105 West Sacramento, California 95605
Clint Sierer 916 375-4352 Phone Clinton.Sierer@dgs.ca.gov
DMV HQ EAST ELEVATOR
MODERNIZATION
ELEVATION KEY PLAN
DMV HQ EAST
BASEMENT
1ST FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
6TH FLOOR
PENTHOUSE
02/19/25 95% PLAN CHECK SUBMITTAL-
05/06/25 95% REFINED SCOPE CHECK SET-
05/29/25 95% REFINED SCOPE REVIEW-
DEPARTMENT OF MOTOR VEHICLES
DMV
Project Number: 000000000015501
08/22/25 FINAL 100% REVIEW-
10/28/25 DSA PLAN CHECK SUBMITTAL-
11/14/25 DSA BACKCHECK SUBMITTAL-
A5-0
NONE
FLOOR PLAN - PENTHOUSE
LEVEL
N
C
B
C
G
SCALE:
GENERAL NOTESKEYNOTES
SCALE: 1/8"=1'-0"A5-0
SCALE: 1/8"=1'-0"A5-0
SCALE: 1/8"=1'-0"A5-0
SCALE: 1/8"=1'-0"A5-0
C
B
87 10
SCALE:
A5-0 1/8"='-0"SCALE:
A5-0 1/8"='-0"
C
G
AS NOTED
LEGENDDEMOLITION KEYNOTES
12-31-2025
11/12/2025
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
2/26/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-4219
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
FLS ACS
02-123762
LEGEND
O
THE CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE CODES AND REGULATIONS
INCLUDING BUT NOT LIMITED TO THE LATEST ADOPTED EDITIONS OF:
2022 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE
PART 1, TITLE 24, CALIFORNIA CODE OF REGULATIONS (CCR)
2022 CALIFORNIA BUILDING CODE (CBC)
PART 2, TITLE 24, CCR
BASED ON THE 2021 INTERNATIONAL BUILDING CODE (IBC)
2022 CALIFORNIA ELECTRICAL CODE (CEC)
PART 3, TITLE 24 CCR
BASED ON THE 2020 NATIONAL ELECTRICAL CODE (NEC)
2022 CALIFORNIA FIRE CODE (CFC)
PART 9, TITLE 24,
BASED ON THE 2021 INTERNATIONAL FIRE CODE (IFC)
APPLICABLE CODES
1. COPPER CONDUCTORS WITH THHN/THWN INSULATION, UON
POWER WIRE SPECIFICATIONS
EXISTING TO BE REMOVED AND SALVAGED
EXISTING TO BE DEMOLISHED
RELOCATED EQUIPMENT.
NEW PLANS-FINAL LOCATION OF
DEMO PLANS-EXISTING TO BE RELOCATED.
EXISTING TO REMAIN
(RS)
(D)
(RL)
(E)
GREEN
GREEN
WHITE
WHITE
BLUE
RED
RED
BLACK
BLACK
240V
240Y/120V
POWER WIRE COLOR CODE
SYSTEM
208Y/120V
480Y/277V
PHASE A
BLACK
YELLOW
PHASE B
RED
BROWN
PHASE C
BLUE
ORANGE
NEUTRAL
WHITE
GRAY
GROUND
GREEN
GREEN
(AIP)
ABANDON IN PLACE. (D) ABOVE GROUND CONDUITS
1"C-2#12, 1#12G
MULTIPLE RUNS OF RACEWAY AND CIRCUIT CONDUCTORS
U = # OF PARALLEL RUNS
V = CONDUIT SIZE
W = # OF PHASE/NEUTRAL CONDUCTORS IN EACH CONDUIT
(U)V"C-W#X, Y#Z X = PHASE/NEUTRAL CONDUCTOR SIZE
Y = #OF GROUND CONDUCTORS IN EACH CONDUIT
Z = GROUND CONDUCTOR SIZE
EXAMPLE: (2)3/4"C-2#12-1#12G INDICATES TWO 3/4"
CONDUITS EACH WITH 2#12 AND 1#12G CONDUCTORS
ELECTRICAL SYMBOLS COMMON
& CONNECTORS DOWN TO 3" BELOW GROUND LEVEL.
REMOVE AND (D) CONDUCTORS IN UG CONDUITS.
PLUG UG CONDUITS AND ABANDON IN PLACE.
SINGLE RUN OF RACEWAY AND CIRCUIT CONDUCTORS.
FIRST NUMBER IS RACEWAY SIZE.
THE FOLLOWING NUMBERS ARE THE CONDUCTOR
QUANTITIES AND SIZES.
EXISTING TO BE REMOVED AND REPLACED WITH NEW(RP)
A AMPERES
AC ALTERNATING CURRENT
AMPERES INTERRUPTING CAPACITY, SYMMETRICAL
AUTOMATIC TRANSFER SWITCH
AMERICAN WIRE GAUGE
CONDUIT, CONDUCTOR
AICS
ATS
AWG
C
CB CIRCUIT BREAKER
CL CONTINUOUS LOAD
CKT CIRCUIT
CNTL CONTROL
CO CONDUIT ONLY
DTL DETAIL
DWG DRAWING
E EXISTING
G, GND GROUND
GFCI GROUND-FAULT CIRCUIT INTERRUPTER
HP HORSEPOWER
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
HZ HERTZ
JB JUNCTION BOX
KCMIL THOUSAND CIRCULAR MILS
KVA KILOVOLT-AMPERES
KW KILOWATT
LTG LIGHTING
MAX MAXIMUM
MCC MOTOR CONTROL CENTER
MIN MINIMUM
MLO MAIN LUGS ONLY
MTD MOUNTED
N NEUTRAL
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NO. NUMBER
P POLE
PG&E PACIFIC GAS & ELECTRIC
PH, Ø PHASE
PVC POLYVINYL CHLORIDE
RECPT RECEPTACLE
REQ'D REQUIRED
SMUD SACRAMENTO MUNICIPAL UTILITY DISTRICT
SW SWITCH
TYP TYPICAL
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
V VOLT
VFD VARIABLE FREQUENCY DRIVE
W WATTS, WIRE
W/ WITH
WP WEATHERPROOF
XFMR TRANSFORMER
NTS NOT TO SCALE
ABOVE FINISHED FLOORAFF
ABOVE FINISHED GRADEAFG
FTL FEED THROUGH LUGS
IFS INTEGRATED FACILITIES SWITCHGEAR
ELECTRICAL ABBREVIATIONS
HCAI DEPARTMENT OF HEALTHCARE ACCESS AND INFORMATION
VA VOLT AMPERS
1. DEMOLITION DRAWINGS ARE BASED ON CASUAL FIELD OBSERVATION AND
EXISTING RECORD DOCUMENTS. REPORT DISCREPANCIES TO ARCHITECT
BEFORE DISTURBING EXISTING INSTALLATION.
2. DISCONNECT ELECTRICAL SYSTEMS IN WALLS, FLOORS, AND CEILINGS
SCHEDULED FOR REMOVAL.
3. PROVIDE TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN EXISTING
SYSTEMS IN SERVICE DURING CONSTRUCTION.
4. REMOVE, RELOCATE, AND EXTEND EXISTING INSTALLATIONS TO
ACCOMMODATE NEW CONSTRUCTION. REPAIR ADJACENT CONSTRUCTION
AND FINISHES DAMAGED DURING DEMOLITION AND EXTENSION WORK. REMOVE
EXPOSED ABANDONED WIRE AND CABLE. PATCH SURFACES WHERE REMOVED
CABLES PASS THROUGH BUILDING FINISHES.
5. DISCONNECT ABANDONED CIRCUITS, OUTLETS AND REMOVE CIRCUIT,
DEVICES, WIRE AND CABLE. REMOVE ABANDONED BOXES, OUTLETS IF
RACEWAY, WIRE AND CABLE SERVICING THEM IS ABANDONED AND REMOVED.
PROVIDE BLANK COVER FOR ABANDONED BOXES WHICH ARE NOT REMOVED.
6. ENSURE ACCESS TO EXISTING BOXES, WIRING CONNECTIONS AND OTHER
INSTALLATIONS WHICH ARE TO REMAIN ACTIVE AND WHICH REQUIRE ACCESS.
MODIFY INSTALLATION OR PROVIDE ACCESS PANEL AS APPROPRIATE.
ELECTRICAL DEMOLITION NOTES
1. THE CONTRACTOR SHALL VISIT JOB SITE AND VERIFY CONDITIONS BEFORE
BIDDING.
2. THE FACILITY SHALL REMAIN IN OPERATION DURING ALL PHASES OF WORK.
WHERE SYSTEM SHUTDOWNS AND POWER OUTAGES ARE UNAVOIDABLE, SUCH
WORK SHALL BE SCHEDULED WITH THE FACILITY MANAGER AND SHALL OCCUR
AT SUCH TIMES AS TO CAUSE THE LEAST DISRUPTION OF NORMAL FACILITY
FUNCTIONS. INCLUDE ALL PREMIUM LABOR IN BID PROPOSAL TO COVER WORK
REQUIRED TO BE PERFORMED BEFORE OR AFTER "NORMAL" WORKING HOURS.
3. COORDINATE SEQUENCE OF WORK WITH OWNER. MAKE ALL NECESSARY
CONNECTIONS AS REQUIRED TO MAINTAIN POWER DURING THE STAGES OF
WORK.
4. EXISTING DEVICES SHOWN WERE TAKEN FROM EXISTING DRAWINGS (NOT "AS
BUILT" DRAWINGS) AND LIMITED SITE SURVEYS AND MAY NOT BE EXACTLY AS
SHOWN. CONTRACTOR SHALL VISIT JOB SITE AND VERIFY CONDITIONS PRIOR TO
BIDDING.
5. REFER TO THOSE DRAWINGS SHOWING OTHER WORK, AND COORDINATE
PLACEMENT OF WORK WITH THAT OF OTHER TRADES. REPORT ANY CONFLICT
TO ARCHITECT PRIOR TO INSTALLING WORK, ADJUST WORK AS DIRECTED BY
ARCHITECT.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING NEW FIRE
STOPPING OF ALL NEW OR EXISTING CONDUIT OR CABLE PENETRATIONS IN NEW
OR EXISTING FIRE RATED WALLS WITHIN THE LIMITS OF WORK. EXISTING AND
NEW WIRING UTILIZING AN EXISTING CONDUIT WITH EXISTING FIRE STOPPING
WITH NO VISUAL DAMAGE DOES NOT REQUIRE NEW FIRE STOPPING. IF
CONTRACTOR OBSERVES EXISTING PENETRATIONS IN RATED WALLS WITHOUT
FIRE STOPPING OR ARE OBVIOUSLY OUT OF COMPLIANCE WITHIN THE PROJECT
AREA, THEN THESE PENETRATIONS WILL NEED TO BE PROVIDED WITH FIRE
STOPPING ASSEMBLY PER LATEST CODE REQUIREMENT.
7. PROVIDE UPDATED TYPE WRITTEN PANEL INDEXES FOR ALL MODIFIED PANELS
ON THIS PROJECT.
ELECTRICAL NOTES SHEET DESCRIPTION
SHEET INDEX
E0-1 SYMBOLS, NOTES, SCHEDULES AND ABBREVIATIONS
E0-2
OVERALL & ENLARGED PLANS - 1ST FLOORE2-0
OVERALL & ENLARGED PLANS - BASEMENTE1-0
ONE LINE DIAGRAM & PANEL SCHEDULE
CLG. WALL SYMBOLS DESCRIPTIONFLOOR
ELECTRICAL SYMBOLS - PLANS
WALL MOUNTED LED LIGHT
SMOKE DETECTOR - PHOTOELECTRIC TYPE
HEAT DETECTOR
FIRE ALARM SYMBOLS - PLANS
OVERALL & ENLARGED PLANS - 2ND FLOORE3-0
X X DEFINED AS:
DUPLEX RECEPTACLE 18" AFF UON
G = GFCI
WP = WATERPROOF, PROVIDE WHILE IN USE COVER
S
ELEVATOR PIT DETAIL
SCALE: NONE
REFER TO DETAIL FOR THREADED
ROD CONNECTION TO STRUCTURAL
CEILING, TYPICAL.
TOTAL WEIGHTTRADE
(LBS/LINEAL FOOT)SIZE
TUBING (EMT)
ELECTRICAL METALLIC
NOTES:
1. SPACING BETWEEN HANGERS SHALL BE PER CEC REQUIREMENTS, NOT EXCEEDING 3 FEET OF EACH
RACEWAY TERMINATION, MAXIMUM OF 10 FEET BETWEEN SUPPORTS.
8" OR 14" DIA. ALL THREADED ROD.
2"
4"
1"
4"
2" 2"
UNISTRUT CONDUIT HANGER
#J1207 (3/4"), J1210 (1"), J1212
(1-1/4"), J1215 (1-1/2"), OR J1220 (2")
MAX.
DOUBLE NUTS
1.
ALTERNATE MOUNTING
LOCATION.
CONDUIT SUPPORT
NOTES:
SPACING BETWEEN SUPPORTS SHALL BE 10'-0" MAXIMUM.
2.
CONDUIT CLIP CADDY
K8, K12, K16, OR K20
TOTAL WEIGHTTRADE
(LBS/LINEAL FOOT)SIZE
TUBING (EMT)
ELECTRICAL METALLIC
3/4"
1"
1-1/4"
0.72
1.09
1.73
COMBINED WEIGHT OF CONDUITS BETWEEN SUPPORTS MAY NOT EXCEED 5 LBS/ LINEAR FOOT.
1/4" OR 3/8"
THREADED ROD
FOR 3/8" THREADED ROD REFER TO DETAIL FOR 3/8"
THREADED ROD TO CONC FILLED METAL DECK DETAIL
8" DIAMETER HILTI KBTZ
WITH 2" EMBEDMENT
INTO LOW FLUTE, ROD
COUPLING, AND
HANGER ROD.
1 5/8 x 1 5/8 x 12GA CHANNEL, 18" MINIMUM LENGTH.
CHANNEL NUT.
8" OR 14" DIAMETER THREADED
ROD, W/ LARGE FLAT WASHERS
AND DOUBLE NUTS.
150# MAX
(E) NORMAL WEIGHT CONCRETE ON
METAL DECK
150# MAX
2" MIN
THREADED ROD CONDUIT SUPPORT DETAIL
SCALE: NONE
CONDUIT TRAPEZE SUPPORT SYSTEM
SCALE: NONE
CONDUIT SUPPORT DETAIL
SCALE: NONE
THREADED ROD TO METAL DECK DETAIL
SCALE: NONE
TYPICAL - PROVIDE
DOUBLE NUTS AT END OF
ROD WITH MIN. OF 1 INCH
OF THREADED ROD
EXPOSED.
2" MIN
0.45
0.72
1.09
1.73
2.14
3.09
SINGLE POLE SWITCH- "x" = SEE INDEX BELOW S
SWITCH SUBSCRIPT INDEX:
BLANK = SINGLE POLE SWITCH
3 = THREE WAY SWITCH
PANELBOARDTOP VIEW
FRONT VIEW
ATTACH PANEL TO CHANNEL
WITH 5/8" SPRING NUTS, BOLT
AND FENDER WASHER.
1 5/8" STEEL CHANNEL
CONCRETE WALL
ATTACH CHANNEL TO CONCRETE
WALL WITH 3/8" WEDGE ANCHORS
AND LARGE FLAT WASHERS.
MINIMUM 4" EMBEDMENT.
SURFACE MOUNTED PANEL ON UNISTRUT
SCALE: NONE
OVERALL & ENLARGED PLANS - 3RD-6TH FLOORS -
TYPICALE4-0
OVERALL & ENLARGED PLANS - PENTHOUSE/ROOFE5-0
ENLARGED PLANS - PENTHOUSE/ROOFE5-1
2415 1ST AVE.
SACRAMENTO, CA 95818
State of California
Department of General Services Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105 West Sacramento, California 95605
Clint Sierer 916 375-4352 Phone Clinton.Sierer@dgs.ca.gov
DMV HQ EAST ELEVATOR
MODERNIZATION
02/19/25 95% PLAN CHECK SUBMITTAL-
05/06/25 95% REFINED SCOPE CHECK SET-
05/29/25 95% REFINED SCOPE REVIEW-
DEPARTMENT OF MOTOR VEHICLES
DMV
Project Number: 000000000015501
08/22/25 FINAL 100% REVIEW-
E0-1
NONE
SYMBOLS, NOTES,
SCHEDULES AND
ABBREVIATIONS
10/28/25 DSA PLAN CHECK SUBMITTAL-
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
2/26/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-4219
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
FLS ACS
02-123762
03/12/2026
11-12-2025
1. REFER TO OVERALL FLOOR PLAN FOR PANELBOARD LOCATIONS.
EXISTING PANEL P1 AND ASSOCIATED CONDUIT/FEEDERS TO BE REPLACED. UTILIZE
EXISTING CONDUIT.
INSTALL NEW 125A/3P BREAKER IN THE SPACE INDICATED. REPLACE EXISTING
CONDUIT/FEEDERS ASSOCIATED WITH THE CIRCUIT, (1) 2" CONDUIT WITH (3) #1 AWG &
1 #6 AWG GROUND.
INSTALL NEW 100A/3P SPARE BREAKERS IN THE SPACE INDICATED.
SHEET NOTES
GENERAL NOTES
DMV BLDG. EAST - SINGLE LINE DIAGRAM
SCALE: NONE
1200A300A/3P
BASEMENT LEVEL
1200A 1200A
.0
V
#2 #4
MS1
#1
V
V
MS2 ( G - 12 - B )
BUSS TIE
CENTROVAC
# 1 + 2
( D - 13 - B )
O
4160 V4160 V
PDS3 ( H - 14 - B )
7/
V
4160 V4160 V
TO PDS4
( H - 14 - B )
TO PDS4
( H - 14 - B )
TO PDS4
( H - 14 - B )
TO PDS4
( H - 14 - B )
TO PDS4
( H - 14 - B )
TO PDS4
( H - 14 - B )
1ST FLOOR LEVEL
2ND FLOOR LEVEL
225A P4 ( C - 11 - 2 )
ESCALATOR
480V
3RD FLOOR LEVEL
4TH FLOOR LEVEL
5TH FLOOR LEVEL
6TH FLOOR LEVEL
PENTHOUSE LEVEL
P1
P3
FREIGHT ELEVATOR
AUTOMATIC TRANSFER
SWITCH
TO FREIGHT
ELEVATOR
TO ELB
EMERGENCY
POWER
MID CITY
SUBSTATION
SMUD RING
FEED # 2308
VOLTAGE DROP CALCULATION
State of California
Department of General Services Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105 West Sacramento, California 95605
Clint Sierer 916 375-4352 Phone Clinton.Sierer@dgs.ca.gov
DMV HQ EAST ELEVATOR
MODERNIZATION
02/19/25 95% PLAN CHECK SUBMITTAL-
05/06/25 95% REFINED SCOPE CHECK SET-
05/29/25 95% REFINED SCOPE REVIEW-
DEPARTMENT OF MOTOR VEHICLES
DMV
Project Number: 000000000015501
08/22/25 FINAL 100% REVIEW-
E0-2
NONE
ONE LINE DIAGRAM & PANEL
SCHEDULE
SCOPE OF WORK
10/28/25 DSA PLAN CHECK SUBMITTAL-
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
2/26/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-4219
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
FLS ACS
02-123762
03/12/2026
A
B
C
D
E
F
G
H
J
A
B
C
D
E
F
G
H
J
E1-0
OVERALL FLOOR PLAN - BASEMENT
SCALE: 1/16" = 1'-0"
NORTH
PLAN
E1-0
E1-0ELEV #4ELEV #3ELEV #2ELEV #1
ELEV #6 ELEV #5
ELEV #7
ELEV #8
B
ENLARGED FLOOR PLAN - CARS #1-4
SCALE: 1/8" = 1'-0"
ENLARGED FLOOR PLAN - CARS #5-6
SCALE: 1/8" = 1'-0"
ENLARGED FLOOR PLAN - CARS #7-8 (CAR 8, ALTERNATE)
SCALE: 1/8" = 1'-0"
A A A A
B
B
G,WP
3S 3S
3S
S
G,WP
G,WP
G,WP
(E)(E)
S
G,WP
(E)
G,WP
(E)
G,WP
(E)
(E)
(E)ELEV #1 ELEV #2 ELEV #3 ELEV #4
ELEV #6 ELEV #5
ELEV #7
ELEV #8
B
B B
B
State of California
Department of General Services Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105 West Sacramento, California 95605
Clint Sierer 916 375-4352 Phone Clinton.Sierer@dgs.ca.gov
DMV HQ EAST ELEVATOR
MODERNIZATION
ELEVATION KEY PLAN
DMV HQ EAST
BASEMENT
1ST FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
6TH FLOOR
PENTHOUSE
02/19/25 95% PLAN CHECK SUBMITTAL-
05/06/25 95% REFINED SCOPE CHECK SET-
05/29/25 95% REFINED SCOPE REVIEW-
DEPARTMENT OF MOTOR VEHICLES
DMV
Project Number: 000000000015501
08/22/25 FINAL 100% REVIEW-
E1-0
NONE
OVERALL & ENLARGED
PLANS - BASEMENT
REPLACE (E) LIGHT FIXTURE. RECONNECT (N) FIXTURE TO (E) CIRCUIT AND LIGHTING
CONTROLS.
SEE DETAIL 1/E0-1 FOR INTERCONNECTION OF SWITCH WITH RECEPTACLE AND
LIGHTING.
EXTEND (E) LIGHTING CIRCUIT TO (N) LIGHT FIXTURE.
CONVENIENCE RECEPTACLES ARE ASSUMED TO BE EXISTING AND IN GOOD,
WORKING CONDITION. IF THERE IS ANY INDICATION OF DAMAGE, OR THEY ARE NOT
FUNCTIONAL, PROVIDE REPLACEMENT.
SHEET NOTES
10/28/25 DSA PLAN CHECK SUBMITTAL-
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
2/26/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-4219
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
FLS ACS
02-123762
03/12/2026
A-1-1
B-1-1
A-2-1
B-2-1
C-1-1
D-1-1
C-2-1
D-2-1
A-3-1 A-4-1
B-3-1 B-4-1
A-5-1
B-5-1
C-3-1 C-4-1
D-3-1 D-4-1
C-5-1
D-5-1
B-7-1
A-7-1A-6-1
B-6-1
A-8-1
B-8-1
D-7-1
C-7-1C-6-1
D-6-1
C-8-1
D-8-1
E-1-1
F-1-1
E-2-1
F-2-1
G-1-1
H-1-1
G-2-1
H-2-1
J-1-1 J-2-1
E-3-1 E-4-1
F-3-1 F-4-1
E-5-1
F-5-1
G-3-1 G-4-1
H-3-1 H-4-1
G-5-1
H-5-1
F-7-1
E-7-1E-6-1 E-8-1
F-8-1
H-7-1
G-7-1 G-6-1
H-6-1
G-8-1
H-8-1
J-3-1 J-4-1 J-5-1 J-7-1J-6-1 J-8-1
B-10-1
A-10-1A-9-1
B-9-1
A-11-1
B-11-1
D-10-1
C-10-1C-9-1
D-9-1
C-11-1
D-11-1
A-12-1
B-12-1
A-13-1 A-14-1
B-13-1 B-14-1
C-12-1
D-12-1
C-13-1 C-14-1
D-13-1 D-14-1
A-15-1
B-15-1
C-15-1
D-15-1
F-10-1
E-10-1E-9-1 E-11-1
F-11-1
H-10-1
G-10-1G-9-1
H-9-1
G-11-1
H-11-1
E-13-1E-12-1
F-12-1
E-14-1
F-13-1 F-14-1
G-12-1
H-12-1
G-13-1 G-14-1
H-13-1 H-14-1
J-10-1J-9-1 J-11-1 J-12-1 J-13-1 J-14-1
E-15-1
F-15-1
G-15-1
H-15-1
J-15-1
STORAGE
12 6
J
H
G
F
E
D
C
B
A
151413121110 9 8 7 6 5 4 3 2 1
1514131110 9 8 7 5 4 3 2 1
J
H
G
F
E
D
C
B
A
Rev: 10/06/23
PH
SG
S
/3 6/
STT
/8
F.E.
STORAGE
STORAGE
529 Sq.Ft.
219 Sq.Ft.
205 Sq.Ft.
OVERALL FLOOR PLAN - 1ST FLOOR
SCALE: 1/16" = 1'-0"
NORTH
PLAN
E2-0
E2-0
E2-0ELEV #4ELEV #3ELEV #2ELEV #1
ELEV #6 ELEV #5
ELEV #7
ELEV #8
ENLARGED PLAN - CARS #1-4
SCALE: 1/8" = 1'-0"
ENLARGED PLAN - CARS #5-6
SCALE: 1/8" = 1'-0"
ENLARGED PLAN - CARS #7-8 (CAR 8, ALTERNATE)
SCALE: 1/8" = 1'-0"
C-4-1
B-8-1 B-9-1
G-10-1
ELEV #1 ELEV #2 ELEV #3 ELEV #4
ELEV #6 ELEV #5 ELEV #7
ELEV #8
State of California
Department of General Services Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105 West Sacramento, California 95605
Clint Sierer 916 375-4352 Phone Clinton.Sierer@dgs.ca.gov
DMV HQ EAST ELEVATOR
MODERNIZATION
ELEVATION KEY PLAN
DMV HQ EAST
BASEMENT
1ST FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
6TH FLOOR
PENTHOUSE
02/19/25 95% PLAN CHECK SUBMITTAL-
05/06/25 95% REFINED SCOPE CHECK SET-
05/29/25 95% REFINED SCOPE REVIEW-
DEPARTMENT OF MOTOR VEHICLES
DMV
Project Number: 000000000015501
08/22/25 FINAL 100% REVIEW-
E2-0
NONE
OVERALL & ENLARGED
FLOOR PLANS - 1ST FLOOR
10/28/25 DSA PLAN CHECK SUBMITTAL-
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
2/26/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-4219
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
FLS ACS
02-123762
03/12/2026
A
B
C
D
E
F
G
H
J
A
B
C
D
E
F
G
H
J Rev: 01/21/2025
OVERALL FLOOR PLAN - 2ND FLOOR
SCALE: 1/16" = 1'-0"
NORTH
PLAN
E3-0
E3-0
E3-0
5,6 E3-0
ELEV #4ELEV #3ELEV #2ELEV #1
ELEV #6 ELEV #5
ELEV #7
ELEV #8
ENLARGED PLAN - CARS #1-4
SCALE: 1/8" = 1'-0"
ENLARGED PLAN - CARS #5-6
SCALE: 1/8" = 1'-0"
ENLARGED PLAN - CARS #7-8 (CAR 8, ALTERNATE)
SCALE: 1/8" = 1'-0"
ELEV #1 ELEV #2 ELEV #3 ELEV #4
ELEV #6 ELEV #5 ELEV #7
ELEV #8
ENLARGED PLAN - MACHINE ROOM - CAR #8 (ALTERNATE)
SCALE: 1/8" = 1'-0"
ENLARGED CEILING PLAN - MACHINE ROOM - CAR #8 (ALTERNATE)
SCALE: 1/8" = 1'-0"
(E) (E)
State of California
Department of General Services Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105 West Sacramento, California 95605
Clint Sierer 916 375-4352 Phone Clinton.Sierer@dgs.ca.gov
DMV HQ EAST ELEVATOR
MODERNIZATION
ELEVATION KEY PLAN
DMV HQ EAST
BASEMENT
1ST FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
6TH FLOOR
PENTHOUSE
02/19/25 95% PLAN CHECK SUBMITTAL-
05/06/25 95% REFINED SCOPE CHECK SET-
05/29/25 95% REFINED SCOPE REVIEW-
DEPARTMENT OF MOTOR VEHICLES
DMV
Project Number: 000000000015501
08/22/25 FINAL 100% REVIEW-
E3-0
NONE
OVERALL & ENLARGED
FLOOR PLANS - 2ND FLOOR
EXISTING ELEVATOR MOTOR TO BE REPLACED WITH MOTOR OF SAME SIZE. REPLACE
MOTOR AND USE EXISTING CONDUIT AND FEEDERS.
FIRE ALARM DEVICES IN THIS SPACE ARE EXISTING TO REMAIN.
MACHINE ROOM LIGHTING IS EXISTING TO REMAIN. EXISTING LIGHTS MEET MINIMUM
FOOTCANDLE LEVEL CRITERIA.
SHEET NOTES
10/28/25 DSA PLAN CHECK SUBMITTAL-
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
2/26/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-4219
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
FLS ACS
02-123762
03/12/2026
A
B
C
D
E
F
G
H
J
A
B
C
D
E
F
G
H
J
18/54
36/5436/14
OVERALL FLOOR PLAN - 3RD-6TH FLOOR - TYPICAL
SCALE: 1/16" = 1'-0"
NORTH
PLAN
E4-0
E4-0
E4-0ELEV #4ELEV #3ELEV #2ELEV #1
ELEV #6 ELEV #5
ELEV #7
ELEV #8
ENLARGED PLAN - CARS #1-4
SCALE: 1/8" = 1'-0"
ENLARGED PLAN - CARS #5-6
SCALE: 1/8" = 1'-0"
ENLARGED PLAN - CAR #7
SCALE: 1/8" = 1'-0"
ELEV #1 ELEV #2 ELEV #3 ELEV #4
ELEV #6 ELEV #5 ELEV #7
State of California
Department of General Services Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105 West Sacramento, California 95605
Clint Sierer 916 375-4352 Phone Clinton.Sierer@dgs.ca.gov
DMV HQ EAST ELEVATOR
MODERNIZATION
ELEVATION KEY PLAN
DMV HQ EAST
BASEMENT
1ST FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
6TH FLOOR
PENTHOUSE
02/19/25 95% PLAN CHECK SUBMITTAL-
05/06/25 95% REFINED SCOPE CHECK SET-
05/29/25 95% REFINED SCOPE REVIEW-
DEPARTMENT OF MOTOR VEHICLES
DMV
Project Number: 000000000015501
08/22/25 FINAL 100% REVIEW-
E4-0
NONE
OVERALL & ENLARGED
FLOOR PLANS - 3RD-6TH
FLOOR - TYPICAL
10/28/25 DSA PLAN CHECK SUBMITTAL-
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
2/26/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-4219
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
FLS ACS
02-123762
03/12/2026
A
C
D
E
F
G
H
J
2 3 4 5 6 7 8 9 10 11 12 13 14
2 3 4 5 6 7 8 9 10 11 12 13 14
A
B
C
D
E
F
G
H
J
OVERALL FLOOR PLAN - PENTHOUSE/ROOF
SCALE: 1/16" = 1'-0"
NORTH
PLAN
E5-0
E5-0
E5-0
1,2,3 E5-1
4,5 E5-1
6,7 E5-1
ENLARGED PLAN - CARS #1-4
SCALE: 1/8" = 1'-0"
ENLARGED PLAN - CARS #5-6
SCALE: 1/8" = 1'-0"
ENLARGED PLAN - CAR #7
SCALE: 1/8" = 1'-0"
ELEV #1 ELEV #2 ELEV #3 ELEV #4
ELEV #6 ELEV #5
ELEV #7
State of California
Department of General Services Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105 West Sacramento, California 95605
Clint Sierer 916 375-4352 Phone Clinton.Sierer@dgs.ca.gov
DMV HQ EAST ELEVATOR
MODERNIZATION
ELEVATION KEY PLAN
DMV HQ EAST
BASEMENT
1ST FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
6TH FLOOR
PENTHOUSE
02/19/25 95% PLAN CHECK SUBMITTAL-
05/06/25 95% REFINED SCOPE CHECK SET-
05/29/25 95% REFINED SCOPE REVIEW-
DEPARTMENT OF MOTOR VEHICLES
DMV
Project Number: 000000000015501
08/22/25 FINAL 100% REVIEW-
E5-0
NONE
OVERALL & ENLARGED
PLANS - PENTHOUSE/ROOF
10/28/25 DSA PLAN CHECK SUBMITTAL-
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
2/26/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-4219
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
FLS ACS
02-123762
03/12/2026
#1 #2
#1 #1 #2 #2 #3 #3 #4 #4
#1 #2 #3 #4
ENLARGED PLAN - MACHINE ROOM - CARS #1-4
SCALE: 1/8" = 1'-0"
ENLARGED CEILING PLAN - MACHINE ROOM - CARS #1-4
SCALE: 1/8" = 1'-0"
ENLARGED PLAN - MACHINE ROOM - DEMO - CARS #1-4
SCALE: 1/8" = 1'-0"
#1 #2
#1 #1 #2 #2 #3 #3 #4 #4
#1 #2 #3 #4
#1 #2
#1 #1 #2 #2 #3 #3 #4 #4
#1 #2 #3 #4
(E) (E) (E) (E) (E)
(E)
(E)(E)
(E)
(E)
(E)(E)(E)
(E) (E)
(E) (E)
ENLARGED PLAN - MACHINE ROOM - CARS #5-6
SCALE: 1/8" = 1'-0"
ENLARGED CEILING PLAN - MACHINE ROOM - CARS #5-6
SCALE: 1/8" = 1'-0"
ENLARGED PLAN - MACHINE ROOM - CARS #7
SCALE: 1/8" = 1'-0"
ENLARGED CEILING PLAN - MACHINE ROOM - CARS #7
SCALE: 1/8" = 1'-0"
(E)
(E)
(E)
(E)
(E)
(E)
(E) (E)
(E) (E)
#3 #4
#3 #4
State of California
Department of General Services Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105 West Sacramento, California 95605
Clint Sierer 916 375-4352 Phone Clinton.Sierer@dgs.ca.gov
DMV HQ EAST ELEVATOR
MODERNIZATION
ELEVATION KEY PLAN
DMV HQ EAST
BASEMENT
1ST FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
6TH FLOOR
PENTHOUSE
02/19/25 95% PLAN CHECK SUBMITTAL-
05/06/25 95% REFINED SCOPE CHECK SET-
05/29/25 95% REFINED SCOPE REVIEW-
DEPARTMENT OF MOTOR VEHICLES
DMV
Project Number: 000000000015501
08/22/25 FINAL 100% REVIEW-
E5-1
NONE
ENLARGED PLANS -
PENTHOUSE/ROOF
EXISTING PANEL P1 AND ASSOCIATED FEEDERS TO BE REPLACED.
EXISTING AC-DC CONVERTER TO BE DEMOLISHED. NEW MOTORS WILL BE FED
DIRECTLY FROM AC PANELS.
EXISTING ELEVATOR MOTOR TO BE REPLACED WITH MOTOR OF SAME SIZE. REPLACE
MOTOR AND USE EXISTING CONDUIT AND FEEDERS. VERIFY EXISTING
OVERCURRENT PROTECTION DEVICE IS MINIMUM 90 AMP, 3 POLE.
EXISTING WIREWAY TO BE DEMOLISHED. REPLACE WITH NEW CONDUIT AND
FEEDERS OF SAME SIZE.
FIRE ALARM DEVICES IN THIS SPACE ARE EXISTING TO REMAIN.
MACHINE ROOM LIGHTING IS EXISTING TO REMAIN. EXISTING LIGHTS MEET MINIMUM
FOOTCANDLE LEVEL CRITERIA.
ELEVATOR CONTROLLERS TO BE REPLACED. CONTROLLERS #3 AND #4 REPLACED
AND RELOCATED. PROVIDE NEW CONDUIT AND PULL NEW CONDUCTORS FOR ALL
CONTROLLERS.
CONTROLLER TO BE REPLACED WITH NEW, USE EXISTING CONDUIT AND
CONDUCTORS.
SHEET NOTES
(N) PANEL P1
(D) PANEL P1
10/28/25 DSA PLAN CHECK SUBMITTAL-
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
2/26/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-4219
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
FLS ACS
02-123762
03/12/2026
MAIN PASSENGER ELEVATORS
F100-DMV HEADQUARTERS -BUILDING EAST - 1St FLOOR ELEVATOR KEY
12 6
J
H
G
F
E
D
C
B
A
151413121110 9 8 7 6 5 4 3 2 1
1514131110 9 8 7 5 4 3 2 1
J
H
G
F
E
D
C
B
A
CAR #1
4,000 lbs
CAR #2
4,000 lbs
CAR #3
4,000 lbs
CAR #4
4,000 lbs
CAR #6
4,000 lbs
CAR #5
4,000 lbs
CAR #7
6,000 lbs.
CAR #8
6,000 lbs.
SVC/PASS.
ELEVATORS
FREIGHT
ELEVATORS
2415 1ST AVE.
SACRAMENTO, CA 95818
State of California
Department of General Services Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105 West Sacramento, California 95605
DMV HQ EAST ELEVATOR
MODERNIZATION
VT-0
16" = 1'
1ST FLOOR PLAN
RJN
06/03/25
10/28/251 100%
2280 GRASS VALLEY HWY. #281
AUBURN, CA 95603
JACK ARNS: (916) 300-3456
BOB NICHOLSON (206) 227-0417
architectural elevator consulting, llc
WWW.ARCHITECTURALELEVATOR.COM
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
2/26/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-4219
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
FLS ACS
02-123762
03/12/2026
VT-1
MACHINE ROOM PLAN CARS 1-4
#1 #2 #3 #4
#1 #2 #3 #4
#1 #2 #3 #4
#1 #2 #3 #4
CAR #1
4,000 lbs
CAR #2
4,000 lbs
CAR #3
4,000 lbs
CAR #4
4,000 lbs
VT-1
HOISTWAY PLAN CARS 1-4
L
6 th
L
M.R. FLOOR
VT-1
SECTION CARS 1-4
(N) MAINLINE DISCONNECTS
WITH SHUNT TRIP
$ = EXISTING LIGHT SWITCH
= NEW PIT STOP SWITCH
(N) = NEW
(E) = EXISTING TO REMAIN
DRAWING KEY:
= EXISTING SMOKE DETECTOR
= EXISTING HEAT DETECTORHD
= EXISTING SPRINKLER
SD
= NEW DUPLEX G.F.I. OUTLETS
= NEW GUARDED LIGHTS
(N) ELEVATOR
CONTROLLER WITH
VF DRIVE
#4 #3
(N) ELEVATOR
CONTROLLER WITH
VF DRIVE
(N) ELEVATOR CONTROLLER
WITH VF DRIVE
REMOVE CONTROLLERS FOR CARS 3 AND
4 FROM CONTROLLER ROOM AND INSTALL
IN MAIN MACHINE ROOM.
AT END OF PROJECT REMOVE HALL CALL
STATIONS on floors 1, 3, 5, and 6. Install new stainless steel plate with fire exit signs.
AT END OF PROJECT REMOVE HALL CALL
STATIONS on floors 1, 3, 5, and 6. Install new stainless steel plate with fire exit signs.
LEDGES AT BACK
WALL TO REMAIN.
(N) 110 v. CAB LIGHT
DISCONNECTS
HD
SD
HD
SD
HD
SD
HD
SD
HD
SD
HD
SD
HD
SD
HD
SD
HDSD HDSD
(N) REMOVE EXISTING DC MACHINES
AND REPLACE WITH NEW AC
GEARLESS MACHINES
VT-1
PIT PLAN CARS 1-4 AT END OF PROJECT REMOVE HALL CALL
STATIONS on floors 1, 3, 5, and 6. Install new stainless steel plate with fire exit signs.
AT END OF PROJECT REMOVE HALL CALL
STATIONS on floors 1, 3, 5, and 6.
This is the start of the file's text. The full file is on GovTribe.